Indian Institute Of Technology-IITB has published Supply Installation Testing And Commissioning Of 2 X 2 Tr Modular Floor Ceiling Mounted Fcu Ac And Associated Works At Main Lab Wl 210C. Submission Date for this Tender is 01-06-2022. Air Conditioner Tenders in kanpur Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | SITC of modular type Fan Coil Unit (floor/wall-mounted) , The unit shall be complete with grills, insulated enclosure, drain tray, comprising of blower, 2/3 speed motor with fan speed controller, 2/3 row copper coil section, washable filter section, 2 way motorized valve with actuator, andbrass flair fitting for copper pipe connection, i/c all necessary support /hangers, vibration isolators etc. complete as reqd. |
2 | 2.0 TR |
3 | Providing and fixing Digital type thermostat for FCUs/ AHUs i/c fixing elect PVC 4"x4" box,commissioning& dismantling old if anyetc. complete as reqd. |
4 | Supply, laying /fixing, testing and commissioning of MS Heavy "C" class pipe ( IS :1239 up 150mm & IS :3589 above 150mm ) of following sizes for chilled/ condenser water piping on surface / underground ( including fabrication of bends / elbows, tees, reducers, sockets, unions etc) with wooden / PUF block, masonry support / MS angle-clamp two coats primer/ enamel paint, vibration isolators and fittings as per standard specification complete as required. |
5 | 25 mm |
6 | 32 mm |
7 | 40 mm |
8 | Supplying & fixing insulation on existing MS "C" class pipe over exposed surface/underground of following sizes with 50 mm thick fire retardant thermocole ( polystyrene) molded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with500g polythene faced hessian cloth, wire mesh, sand-cement plaster &enamel painting two or more coat to give even shade after applying one coat of ordinary paint etc complete as required. |
9 | 25 mm |
10 | 32 mm |
11 | 40 mm |
12 | Supplying & fixing, insulation on existingpipe overhead/underground offollowing sizeswith 25 mm thick Aluminium faced nitrilel rubber / XLPE foam pipe section fixing with dentride and tightening of insulation sectionPVC tape to be wrapped all around the joints. of insulation etc complete as required |
13 | 25 mm |
14 | 32 mm |
15 | Providing & fixing ofThermal protecting layer(double coat ) painting over exposed MS/copper pipe insulation outer surface with approved make chemical, shade and glass cloth as per standard specification compete as required. |
16 | 20 mm |
17 | 25 mm |
18 | 32 mm |
19 | SITC of Butterfly valves CI body with SS DiscNitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water with hand lever operated including nut, bolt, flanges, gasket and insulation of valveas kind of existing pipe etc. complete as reqd. |
20 | 40 mm |
21 | Providing & fixing ofBrass Ball valve with Y-strainer of following sizewith compatible to proportioning Copper/MSpipei/c all necessary support /hangers & dismantling old if any complete as reqd. |
22 | 20 mm |
23 | Providing & fixing ofBrass ball valve of following sizewith compatible to proportioning Copper/MSpipei/c all necessary accessories, support /hangers, including old dismantling if any complete as reqd. |
24 | 20 mm |
25 | Providing & fixing ofSS ball valve of following sizewith compatible to proportioning Copper/MSpipei/c all necessary accessories, support /hangers, including old dismantling if any complete as reqd. |
26 | 20 mm |
27 | Providing & fixing ofBrass Air-Vent of following sizewith compatible Copper/MSpipei/c all necessary accessories & dismantling old if any complete as reqd. |
28 | 20 mm |
29 | Supply & fixing of copper piping 5/8" or 6/8" with 13/19 mm thick Class "O" Nitrile insulation on surface / recessed with flair nut, clamps etc.complete as reqd. |
30 | Providing and fixing of Single Phase Plug topISI Marked forAC (FCU) unitetc i/c dismantling old plug top if any complete as required. |
31 | 3 pin- 6 Amp. |
32 | Providing, laying & fixing of rain forced fiber flexible/softPVC pipe of size given below etc. complete as reqd. |
33 | 20 mm |
34 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
35 | 25 mm nominal outer dia Pipes |
36 | Providing, laying, testing, and commissioning of following sizeUn-armoured PVC insulated Copper conductor power/control cable of following size on surface/recessed complete as required. |
37 | 3 Core x 1.5 Sqmm,Un-armoured copper cable |
38 | 1 Core x 1 Sqmm,Un-armoured copper cable/wire |
39 | Supply and installation UPVC mini trunking (casing-capping) & flexible conduit of following size white-system with independent cover- without central part ion etc. as reqd |
40 | UPVC trunking 20mm x 12mm |
41 | Flexi Conduit 20 mm |
42 | Cutting & dismantling of damaged and defective insulation, removing the thermocole , nitrile, PUF insulation or cladding from chilled water MS pipe line of size mentioned belowincluding hessian cloth, wire mesh, sand, cement, plaster, cleaning of pipe and shiftingthe waste material outside the premises of I.I.T. K. campus or desired location as reqd.. |
43 | 20 mm to 100 mm dia. |
44 | Making wall opening upto 750 mm dia/Suitable in any type / thickof wall for pipe/duct etc and re-closing the opening with brick, sand, cementandplaster i/c re-painting as per existing desigine/shape complete as required. |
45 | Cutting & dismantling of condenser / chilled water pipe line with grinder/welding machine/gas cutter for drain out the water from supply and return pipe line and making good after leakage repairing i/c re-filling of water inpipe line size from 20 mm to 400 mm dia including isolation of defective pipeline, valve operation, testing & commissioning etc as required. |
46 | 20 mm to 100 mm dia. |
47 | Cutting road and making good the same /i/c supply of extra quantities of materials i.e agg., mooram screening, red bajri and labour reqd. |
48 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required,in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m |
49 | Pipes, cables, etc exceeding 80 mm dia.but not exceeding 300 mm dia |
50 | Providing and fixing double scaffolding system (cup lock type) on the exterior side of building/structure, upto 25 metre height, above ground level, including additional rows of scaffolding in stepped manner as per requirement of site, made with 40mm dia M.S. tube, placed 1.5 metre centre to centre, horizontal & vertical tubes joint with cup & lock system with M.S. Tubes, M.S. tube challis, M.S. clamps and staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for execution of work of cleaning and/ or pointing and/ or applying chemical and removing it thereafter. The scaffolding system shall be stiffened with bracings, runners, connecting with the building etc, wherever required, if feasible, for inspection of work at required locations with essential safety features for the workmen etc., complete as per directions and approval of Engineer-in-charge.Note:- (1) The elevational area of the scaffolding shall be measured for payment purpose.(2) The payment will be made once only for execution of all items for such works. |