Dismantling of Bus Coupler Bay, Erection of new AIS Bay, 01 No Bus Coupler & 01 no Hybrid Bay and replacement of Conductor of 220 KV Main Bus from Twin Zebra to Twin Moose for RRTS Project of M/S NCRTC at 220 KV Sub-Station Shatabdinagar under ETD Meerut., meerut-Uttar Pradesh

Uttar Pradesh Power Transmission Corporation Limited-UPPTCL has published Dismantling of Bus Coupler Bay, Erection of new AIS Bay, 01 No Bus Coupler & 01 no Hybrid Bay and replacement of Conductor of 220 KV Main Bus from Twin Zebra to Twin Moose for RRTS Project of M/S NCRTC at 220 KV Sub-Station Shatabdinagar under ETD Meerut.. Submission Date for this Tender is 09-02-2022. Couplers Tenders in meerut Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

30864601
Dismantling of Bus Coupler Bay, Erection of new AIS Bay, 01 No Bus Coupler & 01 no Hybrid Bay and replacement of Conductor of 220 KV Main Bus from Twin Zebra to Twin Moose for RRTS Project of M/S NCRTC at 220 KV Sub-Station Shatabdinagar under ETD Meerut.
Open Tender
Indian
Uttar Pradesh
meerut
09-02-2022

Tender Details

Dismantling of Bus Coupler Bay, Erection of new AIS Bay, 01 No Bus Coupler & 01 no Hybrid Bay and replacement of Conductor of 220 KV Main Bus from Twin Zebra to Twin Moose for RRTS Project of M/S NCRTC at 220 KV Sub-Station Shatabdinagar under ETD Meerut.

Key Value

Document Fees
INR 3540 /-
EMD
INR 35000.0 /-
Tender Value
INR 34.77 Lakhs /-

BOQ Items

Name of Work: Dismantling of Bus Coupler Bay, Erection of new AIS Bay, 01 No Bus Coupler & 01 no Hybrid Bay and replacement of Conductor of 220 KV Main Bus from Twin Zebra to Twin Moose for RRTS Project of M/S NCRTC at 220 KV Sub-Station Shatabdinagar under ETD Meerut.
Sl. No. Item Description
1PART-A (Work)
2Following work is to be carried out for erection of new AIS Bay, Bus Coupler Bay and Hybrid Bay at 220 KV S/S Shatabdinagar
3Dismantling of 220 KV Equipment , Structure and Jumper form Existing 220 KV TBC Bay
4Dismantling of 220 KV Jumpers betweenMain Bus to Transfer Bus
5Dismantling of Circuit Breaker & opening of Cable Terminations form Circuit Breaker & its Control Panel & shifting from site to store.
6Dismantling of Bus Isolators and their Auxiliary structures & shifting from site to store.
7Erection of 220 KV Structure /Equipments
8Sorting and stacking of structures
9Erection of Main & Auxiliary structure lattice type ETM, BXM, BCT, ALP etc. consisting of column, beam, peak, mast etc. and auxiliary structure for installation of CTs, PTs, LAs, etc. The job consistof shifting of all material from store to site of erection, erection of structure as perdrawing with the help of GI nut & bolt, flat & spring washer, matching the hole, cutting & matching of member if required including cost of all men and T & P excluding GI structure Nut & bolt to complete the work. Erection of Main & Auxiliary structure lattice type BCT, ALP etc. upon foundation and its proper tightening.
10Erection of 245 KV SF-6 Circuit Breaker.
11Erection of 245 KV Bus / Line Isolator (Motorized )
12Erection of 245 KV Tandem Isolator (Motorized)
13Erection and mounting of245KV CT.
14Erection and mounting of 245KV CT Junction Box.
15Erection and mounting of 245KV CVT.
16Erection and mounting of 245KV CVT Junction Box.
17Erection of 245 KV Post Insulator for support.
18Erection of 198 KV Lighting Arrestors.
19Erection of 220 KV Control Panel & Relay Panel of Line Bay as per technical specification.
20Erection of 245 KV SF6 Gas Insulated Hybrid Switchgear-Line bay module comprising of circuit breaker, current transformer, per phase isolator and local control cubical. Work also includes shifting and unpacking of hybrid switchgear and its accessories.
21Delta earthing of 198 KV LAs of 220 KV linesby40mm dia. 150 mm long conical shape its placing inside the ground in rectangular shape and connecting all 6 Nos. electrodes with 75x10 mm MS flat laid on its edge and then this rectangle/triangle shape be connected to main earth mat at two place in opposite direction strictly as per drawing (MS Rod & MS Flat will be provided by the department).
22198 KV LA (Rectangle shape by 06 electrodes) with 40mm dia. round bar.
23Earthing of equipments by cutting straightening, bending, laying 700 mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure and equipments structure including welding with main earthmat and with object to be earthed. Excavation of trenches, its back filling, painting and all other associated work as required to complete the work.
24Laying of MS Flat of size 75x10 mm
25Laying of MS Flat of size 50x6 mm
26Laying of MS Flat of size 25x6 mm
27Complete cleaning of disc insulators for all phases by suitable liquid cleaner, testing of IR value by insulation tester, making series connection & ready for hoisting with all cost of men, T & P to complete the work.
28Cleaning of disc insulator of 220 KV string
29Stringing of various Single Phase Jack Bus of 220 KV with different type conductor and different length of span as mentioned below. The work includes cutting & bending of conductor, fixing of single /double bolted type tension fitting/ suspension. Hoisting of disc insulator and shifting of material from store site to erection site and all other associated work to complete the work satisfactorily as per drawing and technical specification.
30220 KV Jack Bus of Twin Zebra / Moose conductor.
31Hoisting of 220 KV string under Beam to pass the jumper including hanging of disc insulator and suspension fitting complete with all work.
32Jumpering, interconnection of equipment with specified conductor of various 220 KV equipments with main/Transfer/Jack Bus Bar of Twin ACSR Moose/Zebra conductor. The work includes cutting of conductor, bending in proper shape, clamping with the help of clamps and all other associated work to complete the work.
33220 KV Line Bay/ Bus coupler bay
34Laying& Termination of following size control cable in trench/ cable trays from different control room equipments to 220KV CB, CT, PT and their junction boxes, isolators boxes and other outdoor equipments installed in 220KV switch yard as per cable schedule including carriage of cable drum from storeand all other associated work.
352 core x 2.5 mm2
364 core x 2.5 mm2
376 core x 2.5 mm2
3810 core x 2.5 mm2
39Termination of control cable
40Laying of power cable of following size 500mm below ground level including excavation of trench and laying of cable putting of brick and filling of Ganga sand over the cables then filling of earth with all cost of men, material and T & P for the completion of job
413.5 Core x 300 sq. mm
42Termination of above power cable by providing suitable size aluminum dowel make lugs its crimping and connecting with equipment including cost of lugs and all other associated work to complete the job.
433.5 Core x 300 sq. mm
44Switch yard lighting
45Providing and fixing of new generation energy saving and environment friendly long life versatile pressure die casting aluminum out door high beam flood light with high power 120 watt LED as light source and exclusively designed polycarbonate cover along with electronic driver complete fitting suitable for 220V input supply, ISI mark, make CGL /HAVELLS/ SURYA /PHILIPS /BAJAJ etc. or equivalent, including electrical connections also to be done by the contractor.
46Providing and Fixing of Junction box on Gantry Structureof size 200x200x150mm made of MS Sheet of 16 gauge duly power coated, in side fixing 1 no 6 amp MCB , 1no TB of 04 Nos. Terminal and 1no. kit -kat 16 amp fuse fixed up on MICA sheet and back side a half round MS Clamp and along with PVC pipe fixing on junction box as per technical specification.
47Providing and fixing of half round GI pipe OD 50mm for mounting the 120 watt LED light upon gantry mounting of 02nos bracket upon gentry and fixing GI pipe complete with GI nuts bolts and washer as per technical specification
48Following work is to be carried out for 220 KV Main Bus Bar Replacement.
49Opening / cutting of R, Y & B phase Twin jumper of 220 KV existing Main Bus Made of Twin Zebra between Bus sections below gantries, step by step during bus bar replacement work includes dismantling of all types of associated clamps & fittings.
50Dismantling of existing jumper of ACSR Twin Zebra conductor of ICT-I, II & III and bus coupler & feeder bay from main bus bar by opening of all associated clamps, step by step during bus bar replacement.
51Dismantling of 220 KV oldmain bus bar, R,Y & B phase bus sectionof Twin Zebra conductor and lowering down of conductor from Sub-Station gantry to complete dismantling works including dismantling of all associated tension clamps fitting & disc insulator etc.
52Fixing of quadruple Moose suspension fitting under bus section of main bus below gantries with suitable hardware such as hoisting of disc insulators etc. to complete the work in all respect satisfactorily.
53Stringing and proper sagging of new 220 KV main bus bar (R,Y & B ph) by Twin Moose conductor the work includes fitting of tension clamps, hoisting of 120 KN disc insulators, tension fitting, spacers PG-clamps etc. and cutting of conductor as required.
54Re-connecting of R, Y & B phase of 220 KV main bus bar of Twin Moose conductor between bus sections below gantries, step by step during bus bar replacement work including jointing of Zebra conductor below the gantries with the help of suitable PG-clamps through the quadruple suspension fitting & spacers etc. and cutting of conductor as required.
55Re-connecting new jumpers of ACSR Twin Zebra conductor of ICT-I,II & III and bus coupler bays & feeder bays after fixing spacers, clamps as required.
56Replacement of damaged jumper of Twin Zebra of different bays in the 220 KV switchyard after opening of damage jumper & re-fixing of fresh jumper with the help of suitable PG clamp etc. and cutting of conductor as required.
57Erection of ALP structure under 220 KV Main Bus to pass the R-phase jumper.
58Erection of 245 KV polyclone insulators upon ALP structure.
59PART-B (Supply)
60Supply of 220 KV bolted type single tension fitting for Twin Moose conductor 1x16 No disc insulator with turn buckle complete with hardware fitting d-shackle, d-socket, Ball hook, yoke plate, d-clip, tension clamp etc. as per technical specification.
61Supply of 220 KV bolted type tension fitting for Twin Moose conductor 1x16 No disc insulator without turn buckle complete with hardware fitting d-shackle, d-socket, Ball hook, yoke plate, d-clip, tension clamp etc. as per technical specification.
62Supply of 220 KV bolted type Suspension fitting for Quadruple Twin Moose conductor 1x16 No disc insulator complete with hardware fitting as per technical specification.
63Supply of 220 KV bolted type Suspension fitting for Twin Zebra conductor 1x16 No disc insulator complete with hardware fitting as per technical specification.
64Spacers for Twin Zebra conductor 250 mm spacing as per technical specification.
65Spacers for Twin Moose conductor 250 mm spacing as per technical specification.
66Spacers for Twin Zebra conductor 100 mm spacing as per technical specification.
67Spacers for Twin Moose conductor 100 mm spacing as per technical specification.
684 Bolted Type PG clamp suitable for Zebra to Zebra/Moose to Moose Conductor Complete with HDG nut bolt & washer as per technical specification.
694 Bolted Type PG clamp suitable for Moose to Moose Conductor Complete with HDG nut bolt & washer as per technical specification.
704 Bolted Type PG clamp suitable for Zebra to Moose Conductor Complete with HDG nut bolt & washer as per technical specification.
71Bimetallic 220 KV Tandem Isolator clamp made of aluminum alloy LM-6 for Twin Zebra/Moose conductor with HDG nuts & bolts and washer as per technical specification.
72Bimetallic 220 KV Bus Isolator clamp made of aluminum alloy LM-6 for Twin Zebra/Moose conductor with HDG nuts & bolts and washer as per technical specification.
73Bimetallic 220 KV Breakerclamp made of aluminum alloy LM-6 for Twin Zebra/Moose conductor with HDG nuts & bolts and washer as per technical specification
74Bimetallic 220 KV CT clamp made of aluminum alloy LM-6 for Twin Zebra/Moose conductor with HDG nut & bolts and washer as per Technical specification.
75Bimetallic 220 KV CVT clamp suitable for Twin Zebra/Moose conductor complete nut, bolts and washer. As per technical specification.
76Bimetallic 220 KV LA clamp made of aluminum alloy LM-6 for Zebra/Moose conductor with HDG nut & bolts and washer as per Technical specification.
77220 KV Bus Post clamp suitable for Twin Zebra/Moose conductor complete with hot dip galvanized nut, bolts & washer as per technical specification.
78220 KV CT/CVT Junction box of size 600x450x300 mm made of 16 SWG sheet complete with 16 Amp link type TB 60 No and cable gland 06 No duly painted with one coat of red oxide & two coat of grey paint as per technical specification.
79Supply of Power receptacles with canopy for outdoor installation rating 415 V, 400 Amp. 3 Phase and neutral of size 1550x800x500 mm with MS Sheet thickness 14 SWG duly powder coated of good quality. The receptacles shell be provided incorporating a manually operated TPN on load change over selector switch of Havell’s/ C&S/Standard make rated for 400 Amp-1 No. with 08 Nos. Aluminum insulated bus bar suitable for 3.5 x 400 sq.mm PVC armored cables-1 No. on incoming side and on outgoing side 04 Nos. aluminum insulated bus bar with section window/door & 1 No. side window/door gland plate with 02 Nos. cable gland suitable for 3.5 x 400 sq.mm PVC armored cable, provision of visual indication of incoming supply & indoor light fitting 16 W CFL. Power receptacles shall be weather, dust and vermin proof with proper locking arrangement with base for centrifuging work of transformer as per technical specification.
80Supply of power supply cubical Transformer, isolator & breaker with canopy for outdoor installation rating 415V, 200 Amp 3 phase of size 1800x600x500 mm with MS sheet 14 SWG duly powder incorporating a manually operated TPN on load change over selector switch of Havell’s/C&S/Standard make rated for 200 AMP-1 No. with 08 Nos. aluminum insulated bus bar suitable for 3.5 x 70 sq.mm PVC armored cables -02 Nos. on incoming side and on outgoing side 32 Amp. 3 Pole MCB-04 Nos. 16 Amp. 3 Pole MCB-04 Nos. 6 Amp. Single Pole MCB -04 Nos. of Havell’s /Legrand make. Power supply cubical with double door (01 No. Fr. Door and 02 Nos. inside door) (One for bus bar section for incoming supply & second for MCB section for outgoing supply.) Provision of gland plate with 02 Nos. cable glands suitable for 3x70/95 sq. mm PVC armored cable. Complete proper wiring from 200 Amp. TPN to MCB with copper wire & lugs along with 40 Nos. TB suitable size. Provision of visual indication of incoming supply & indoor light fitting 16 W CFL Power receptacles shall be weather, dust and vermin proof with proper locking arrangement with base as per technical specification.
81Supply of cable gland of different sizes
82i- 2C x 2.5 mm (16mm)
83ii- 4C x 2.5 mm (19mm)
84iii-6C x 2.5 mm (22mm)
85iv- 10C x 2.5 mm (25mm)
86Supply of copper lug of different types.
87i- Ring type of size 2.5 mm
88ii- Pin type of size 2.5 mm