Public Works Department-PWD has published Retrofitting Of Jjm Scheme In North Tripura District During The Year 2021-22 Providing And Installation Of Clear Water V.T Pump For Clear Water Reservoir In The 0.65 Mgd Water Treatment Plant At Kanchanpur Under Dws Sub Division Kanchanpur. Submission Date for this Tender is 09-02-2022. VT Pump Tenders in kanchanpur Tripura. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Providing fitting fixing of 30000 GPH (135 m3/hr) capacity, 60.00 m head (total) Clear Water VT Pump (GRW / WPIL / Kirloskar / Jyotimake) with SS impeller along with suitable Verticle Hollo Shaft, Squirel Cage SPDP induction motor of capacity 37.00 KW/ 50 HP(minimum), 3Ph, 50 Hz, 415 V AC 1500 rpm(Kirlosker / Jyoti make)as per IS 12615 : 2011( with latest ammendment),surface discharge head assembly with flanged column and shaft assembly with basket strainer containing 6.00 Ft. of 150 mm dia flanged ERW Steel column pipe with 30 mm dia SS Shaft assembly complete with all accessories in/c installation and commissioning and testing as per specification and direction of the Engineer-in-Charge. (Excluding delivery pipe, Non Return Valve, Sluice Valve, Electrical Panel Board and other electrical accessories) |
2 | Providing and f itting f ixing of Fully Automatic Star Delta type Motor starter ( 3 ph. 50 Hz, 415V, in Steel Sheet Enclosures with Contractors and Timer etc. complete suitable for submersible Pump L & T, BCH, ABB make as per specif ication and direction ofthe Engineer-in-charge. i) 75 HP/ 55 kw Relay range within 45-75 + 10% |
3 | Providing and f itting f ixing steel sheet enclosed switch fuse unit (suitable for DIN fuses), triple pole with Neutral Link (TPN), 415/500 Volt, L & T / Havells / BCH make etc. completeas per specif ication and direction ofthe Engineer-incharge . i) 200 amps |
4 | Providing and f itting f ixing of Moulded Case Circuit Breaker (MCCB) of dif ferent Thermal release range , 415 + V, 50Hz (L & T, BCH, ABB make) as per specif ication and direction of the Engineer-in-charge. i) 128-160 Amps |
5 | Providing and f itting f ixing with PVC insulated single core multistrand Copper cable conforming to IS : 694 for inter connection with all electrical equipments of the pannel board as per specif ication and direction ofthe Engineer-in-charge. |
6 | i) 25 sqmm |
7 | ii) 50 sqmm |
8 | Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- i)1 X 4 sq mm |
9 | Providing and f itting f ixing of moving iron type, Range 0-500 V, 96 mm x 96 mm size AC Volt meter ( L & T / AE make) with selector switch as a electrical instrument of the pannel board as per specif ication and direction of the Engineer-incharge. |
10 | Providing and f itting f ixing of moving iron type, Range 0-100/0-200 amps, 96 mm x 96 mm size AC Amps meter direct reading type ( L & T / AE make) with selector switch and CT coil as a electrical instrument of the pannel board as per specif ication and direction ofthe Engineer-in-charge. |
11 | Providing and f itting f ixing 3 phase indicating lamp f iited with panel board with three dif ferent colour lamps with batten holder complete as per specif ication and direction of the Engineer-in-charge. |
12 | Suppying and installation of Bus bar chamber of the following ratings and sizes made of steel enclosure with all accessories including necessary connection etc. as required:- i) 200 amps 415 volts four strip Copper busbar chamber 6 ways of size (610mmx410mmx120mm):- |
13 | Supplying and fixing of copper terminal ends (LUGS)- long barrel of following sizes :- |
14 | i) 25 sqmm |
15 | i) 50 sqmm |
16 | Providing and fixing C.I. sluice valves ( with cap) complete with bolts, nuts, rubber insertions etc. (the tail pieces if required will be paid separately) as per CPWD specification and direction of the Engineer - in - charge i) 150 mm dia A) PN - 1.6 |
17 | Providing and fixing C.I. non-return valve of approved quality as per CPWD specification and direction of the Engineer - in - charge i) 150 mm nominal bore |