Addn Altn And Repair Of Various Type Of Ups Against Be At Army Hosp Rr Under Ge Rr Hosp Delhi Cantt 10, delhi-Delhi

Military Engineer Services-MES has published Addn Altn And Repair Of Various Type Of Ups Against Be At Army Hosp Rr Under Ge Rr Hosp Delhi Cantt 10. Submission Date for this Tender is 24-03-2022. UPS Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

30760021
Corrigendum : Addn Altn And Repair Of Various Type Of Ups Against Be At Army Hosp Rr Under Ge Rr Hosp Delhi Cantt 10
Open Tender
Indian
Delhi
delhi
24-03-2022

Tender Details

Addn Altn And Repair Of Various Type Of Ups Against Be At Army Hosp Rr Under Ge Rr Hosp Delhi Cantt 10

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Feb-2022 Amendment No. 1 Date 22-02-2022
2 14-Feb-2022 Amendment No 2 Date 01-03-2022
3 21-Feb-2022 Amendment No 3 Date 09-03-2022
4 28-Feb-2022 Amendment No 4 Date 17-03-2022
5 07-Mar-2022 Amendment No 5 BOQ 17-03-2022
6 17-Mar-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 24-03-2022

Key Value

Document Fees
INR 2000 /-
EMD
INR 352000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work :ADDN/ALTN AND REPAIR OF VARIOUS TYPE OF UPS AGANIST BER AT ARMY HOSPITAL (R & R) UNDER GE (R&R HOSP) DELHI CANTT
Sl. No. Item Description
1Supply, Installation,testing and commissioning of5 KVA UPS (unitrupted Power Supply),Inbuilt isolation transformer Microprocessor, solid state type, Online Double conversion technology, Low harmonic,distortionbest regulation, excellent transient response and high stabilit.LCD Display Pannel (AC input & output Load level temporater, AC Mode , Battery Mode , Bypass Mode & Faults Etc )Cold Start Audible Alarm Serial Port RS-485Certified With ISO-9001 & ISO-14000, with SMF batteries including suitable size of steel battery rackincluding inter cable connecting completeall as specified and directed by Engineer-in-Charge .he following consisting of :- (a)INPUT: Single phase AC input Threewire system, Voltage 160 to 260 volts and + 15% (User selectable), frequency-50 Hz, current distortion max 5% THD at full load.(b) OUTPUT : Voltage -230 V + 1% (User selectabale), Frequncy-50Hz, PF-0.8 lagging, Harmonic-2%THD for leaner full Load and 5% THD for Non-leaner full load, over load capacity is 120%, Inverter effeiency 90% at full load, RH<95%,(c) Nos & type of Battery which is part of the system Reputer Make and World class only will be provided for 30 Minutes power back up supply.(d) Providing continous quality computer grade sonusoidle wave form power for electronic equipment load .(e) The system has monitoring with various type of fault alarms and metering functions including out put voltage and current out put frequency etc. (f)The battery charger is provision of monitering battery temp. battery charger can be adjusted accordingly to enhance the battery life(g)The system is Provision for protection for input under voltage, inpur over voltage, ,output over voltage. output Over load, Output short circuit , battery under voltage, Over temperature, DC Over Current etc, (h) the system has contrrol as input circuit breacker, baypass circuit breacker, Battery circuit breacker, maintenance Baypass Switch, Inverter ON/OFF Switch, By Pass transfer Switch, etc.(k)Load crest factoreis 3:1,(m) Acoustical Noises :- <60DB typical, Measured at 1.5 Mtr Distance.(Make- Labotek, Emerson, Luminous and their equivalent.
2Supply, Installation,testing and commissioning of10 KVA UPS (unitrupted Power Supply), Inbuilt isolation transformer Microprocessor, solid state type, Online Double conversion technology, Low harmonic,distortionbest regulation, excellent transient response and high stabilit.LCD Display Pannel (AC input & output Load level temporater, AC Mode , Battery Mode , Bypass Mode & Faults Etc ) Cold Start Audible Alarm Serial Port RS- 485 Certified With ISO-9001 & ISO-14000 with SMF batteries including suitable size of steel battery rack including inter cable connecting cablecomplete withand inter connecting cable. all as specified and directed by Engineer-in-Charge .he following consisting of :- (a)INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts and + 15% (User selectable), frequency-50 Hz, current distortion max 5% THD at full load. (b) OUTPUT : Voltage -230 V + 1% (User selectabale), Frequncy-50Hz, PF-0.8 lagging, Harmonic-2%THD for leaner full Load and 5% THD for Non-leaner full load, over load capacity is 120%, Inverter effeiency 92% at full load, RH<90%,(c) Qty of SMF Battery , AH,Volt as per site requirement ,Steel rack for suitabiles battery capacity and size for .30 Minutes power back up supply. (d) Providing continous quality computer grade sonusoidle wave form power for electronic equipment load .(e) The system has monitoring with various type of fault alarms and metering functions including out put voltage and current out put frequency etc. (f)The battery charger is provision of monitering battery temp. battery charger can be adjusted accordingly to enhance the battery life(g)The system is Provision for protection for input under voltage, inpur over voltage, ,output over voltage. output Over load, Output short circuit , battery under voltage, Over temperature, DC Over Current etc, (h) the system has contrrol as input circuit breacker, baypass circuit breacker, Battery circuit breacker, maintenance Baypass Switch, Inverter ON/OFF Switch, By Pass transfer Switch, etc.(k)Load crest factoreis 3:1,(m) Acoustical Noises :- <60DB typical, Measured at 1.5 Mtr Distance.Make- Labotek, Emerson, Luminous and their equivalent.
3All as per item no 02 ButCapacity 15 KVA UPS,INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -230 Vfor .30 Minutes power back up supply.
4All as per item no 02 ButCapacity 20 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -230 Vfor 60 Minutes power back up supply..
5All as per item no 02 ButCapacity 20 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -230 Vfor 60 Minutes power back up supply.
6All as per item no 02 ButCapacity 20 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -415Vfor 120 Minutes power back up supply.
7All as per item no 02 ButCapacity 20 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -230 Vfor 30 Minutes power back up supply.
8All as per item no 02 ButCapacity 30 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -230 Vfor 60 Minutes power back up supply.
9All as per item no 02 ButCapacity 30 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -415 Vfor 120 Minutes power back up supply.
10All as per item no 02 ButCapacity 30 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -415 Vfor 60 Minutes power back up supply.
11All as per item no 02 ButCapacity 160 KVA UPS, INPUT: Three phase AC input Four wire system, Voltage 300 to 450 volts andOUTPUT : Voltage -415 Vfor 30 Minutes power back up supply.
12Note for item no 01 to 11 : the contractor shall 02 years wattenty of each ups & 04 ( four) years replacement warrenty of each Battery and period shall be counted from the next day of actual date of competion of work. 2. an approprite sum equal to the amount of security depositre calculated as per scale laid down for individual securities deposite on the quoted amount for this Items, shall be related out of the final Bill amount as securities deposite against the 02 years replacement of UPS and 04 Years replacement of Battery and same shall be relaesed only after expired of guriantee period. the contractor may also funished fixed deposite recipt/BGB in liue of the sum to be retained as securities
13Material and labour in replacement of Sub main wiring with 4 run of 16 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable ISI marked, drawn in and including cutting and chasing,and also PVC conduit suitable dia as per SSR part-I with medium grade including 2.5 Sqmm (nominal area) FRLS, PVC insulated, unsheathed and stranded copper conductor cable ISI marked as earth wire, connected with thimble from main DB to sub main DB complete all as directed. Note : 1. The two run of 4 Sqmm wire, one run of 16 Sqmm wire and 1 run of PVC conduit will be measured as one unit.
14All as per srl item no. 13 here-in-before but with 2 run of 16.0 sq mm FRLS copper wire with 10.0 Sqmm FRLS copper cable as earth wire.
15All as per srl item no. 13 here-in-before but with 4 run of 10.0 sq mm FRLS copper wire with 10.0 Sqmm FRLS copper cable as earth wire.
16All as per srl item no. 11 here-in-before but with 2 run of 10.0 sq mm FRLS copper wire with 10.0 Sqmm FRLS copper cable as earth wire.
17S&F in replacement Distribution Boarddouble Doormade out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, flushed mounting, SPN 4 way, 240 volts with bus bar rating 100 Amps dust and vermin proof suitable for incorporation of MCB’s and isolators etc and making all necessary connections, incl cutting & chasing and making good the surface as per existing complete all as directed. ote: MCBs shall be measured and paid seperately.Make - Legrand,L&T,ABB.
18Supply and fixingof MCB "C" curve type, 10 kA, 20-63 Amp, TPN, 10 KA with over load and short circuit protection complete all as directed. Make - Legrand,L&T, ABB
19All As slr Item No 18 here- in -before but UptoSPN 63 Amp.
20All As slr Item No 18 here- in -before butUpto TPN 100 Amp MCCB bracking Capacity 16 ka
21All As slr Item No 18 here- in -before butUpto TPN 160 Amp MCCB bracking Capacity 36 ka
22S&F in replacement MCCB Incomer distribution board double door vertical type made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating, TPN 6 way, 415 volts with copper bus bar rating 250 Amps for each phase, dust and vermin proof and IP 43, IK-09 protection for provision of MCCB, MCBsas required at siteincluding necessary cutting chasing and making good the disturbed surfaces complete all as directed.Make - Legrand,L&T,ABB
23M&L for Disconnecting all cable connections, from Unservicable UPS and Battery Bank, taking out the completecable connections from terminal box/ by removing all nuts/bolts/gasket etc. ofany size and capacity of UPS and deposite to MES store/ Yard from site complete UPS withBattery Bank all as per directed by Eng- In - Charge.Note: All site avaiablle around 500 Mtr radius from site.
24Taking down carefully unserviceable sub maincomplete wiring including conduit/casing N Capping etc complete.
25Taking down unserviceable DBs any type / size carefully disconnecting and making good disturbed surfaces complete all as directed.