Repairs To Pump Sets, Motor Starters, Panels, Connected Items And Repair / Maint, Cleaning Of Stp And Connected Items Of Distribution System And ........ Foot Valve, Sluice Valve And Other Connected Items At Nagpur Under Ge Kamptee., kamptee-Maharashtra

Military Engineer Services-MES has published Repairs To Pump Sets, Motor Starters, Panels, Connected Items And Repair / Maint, Cleaning Of Stp And Connected Items Of Distribution System And ........ Foot Valve, Sluice Valve And Other Connected Items At Nagpur Under Ge Kamptee.. Submission Date for this Tender is 07-02-2022. Starter Tenders in kamptee Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

30748242
Corrigendum : Repairs To Pump Sets, Motor Starters, Panels, Connected Items And Repair / Maint, Cleaning Of Stp And Connected Items Of Distribution System And ........ Foot Valve, Sluice Valve And Other Connected Items At Nagpur Under Ge Kamptee.
Open Tender
Indian
Maharashtra
kamptee
07-02-2022

Tender Details

Repairs To Pump Sets, Motor Starters, Panels, Connected Items And Repair / Maint, Cleaning Of Stp And Connected Items Of Distribution System And ........ Foot Valve, Sluice Valve And Other Connected Items At Nagpur Under Ge Kamptee.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 31-Jan-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 07-02-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 68000.0 /-
Tender Value
INR 34 Lakhs /-

BOQ Items

Name of Work: REPAIRS TO PUMP SETS, MOTOR STARTERS, PANELS, CONNECTED ITEMS AND REPAIR/ MAINT, CLEANING OF STP AND CONNECTED ITEMS OF DISTRIBUTION SYSTEM AND CLEANING OF PVC TANK, OVERHEAD RESERVOIR, DISTRIBUTION PIPELINE WORK AND REP / REPLACEMENT OF EXT WATER SUPPLY DISTRIBUTION, CPVC / CI / GI PIPE LINE, FOOT VALVE, SLUICE VALVE AND OTHER CONNECTED ITEMS AT NAGPUR UNDER GE KAMPTEE.
Sl. No. Item Description
1Supply and installation LT electric control panel, cubical type, for indoor use floor mounted double door made out of CRCA sheet 2.00 mm thick for inner and outer shell mounted on angleiron legs of size 50mmx50mmx5mm with front openable shutters for eachhaving hinges on both side and locking knobs press type complete with fully enclosed bus bar chamber of capacity 100amps, having insulated bas bar made out of aluminium strips of size 20mmx10mm for 3 phase and neutral , 415 volts, 50Hz, 4 wire system, with cable entry provision complete, duly painted with two coats of stove anamelled powder coated paint over a coat of red oxide primer complete all as specified and equipped with the following items complete all as specified and directed:- (a) Star Delta starter with single phase preventer for motor rating AC-3 phase 415volts suitable for 20HP withMU-1 contactor with coil voltage 360V, overload, phase imbalance, phase reversal protection. (b) Aluminium busbar for 3 phase and neutral of capacity 100Amps (40mmx10mm). (c) MCB 4 poe 415volts of rating 63Amps :- 01 Nos as Incommer. (d) MCB 3 pole 415Volts of rating 32Anps -02 Nos for out going. (e) LED 3 phase multifunction meter to measure volts and Amp -02 Nos (f) Indicators / amp meter suitable for indication of three phases in red, yellow and blue colour-01 set of three.
2M&L for taking up vertical turbine pump set spilt casing type 75 HP/55KW electric driven water cooled 87(LBS) column pipe with shaft 40mtr heas from well after disconnection of electrical connection earthing lines and transportation to local workshop for repairs / overhaulling of pump including dismantling the assembly, cleaning all parts of pump assembly thoroughly and finding out the defects segregating the serviceable spare parts for reuse andincluding machine work, reassembling the pump set after successful repair and lowering to the existing position and refixing and testing complete all as specified and directed. Make: Jyoti Ltd. (Note:- Spares as required shall be measure & paid separately against the relevant items).
3S&F Impeller Holding Split ring complete all as specified and directed.
4S&F Ball bearing-Bronze complete all as specified and directed.
5S&F Top Bowl bearing-Bronze complete all as specified and directed.
6S&F Lantern ring complete all as specified and directed.
7S&F Impeller shaft packing ring-Bronze complete all as specified and directed.
8S&F Discharge case bearing-Bronze complete all as specified and directed.
9S&F Impeller shaft coupling-AISI410 complete all as specified and directed.
10S&F Line shaft bearing Bronze complete all as specified and directed.
11S&F Glide spider-CI complete all as specified and directed.
12S&F Rubber guide ring-STD complete all as specified and directed.
13S&F Rubber guide ring Circlip-STD complete all as specified and directed.
14S&F Gland packing-STD complete all as specified and directed.
15S&F Gland packing ring-Alu complete all as specified and directed.
16S&F Impeller seal ring Bronze complete all as specified and directed.
17Taking out of centrifugal horizontal split casing type pump set 40HP from pump foundation after disconnection from motor and transportation to workshop, dismantling the pump for repair/ overhauling incluiding cleaning of all parts of pump assembly throughly, including machine work of pump shaft inorder to obtain smooth finish including necessary polishing etc and installing back including heliumgasket sheet not less than 1mm thick complete uptoto the entire satisfaction of Engineer-in-charge all as specified and directed. Make:- Pump - Kirloskar, Motor Crompton at Swimming pool. (Note:- Spares as required shall be measure & paid separately against the relevant items).
18S&F Casing Wear Ring complete all as specified and directed.
19S&F shaft sleeve complete all as specified and directed.
20S&F Inter Stage Ring complete all as specified and directed.
21S&F Ball bearing SKF complete all as specified and directed.
22S&F suitable Ball bearing SKF complete all as specified and directed.
23S&F suitable Bearing cartridge DE complete all as specified and directed.
24S&F suitable Bearing cartridge NDE complete all as specified and directed.
25S&F shaft sleeve Nuts complete all as specified and directed.
26S&F Split Gland complete all as specified and directed.
27Disconnecting non clogging sewage monoblock pumps of 5.0 HP Capacity from the motor for complete over hauling of the pumpnecessary greasing replacing asbestors rope of the glands, grinding of shaft including necessary mechine work, assembling,including heliumgasket sheet not less than 1mm thick, testing and commissoning complete all as specified and directed. (Note:- Spares as required shall be measure & paid seperately against the relevant items).
28S&F Impeller key complete all as specified and directed.
29S&F Gland Bush Split type complete all as specified and directed.
30S&F Impeller Nut complete all as specified and directed.
31S&F Ball bearing SKF complete all as specified and directed.
32S&F shaft sleeve complete all as specified and directed.
33Taking out of centrifugal pump set 20HP from pump foundation after disconnection from motor and transportation to workshop , dismantling the pump for repair/ overhauling incluiding cleaning of all parts of pump assembly throughly, including machine work of pump shaft inorder to obtain smooth finish including necessary polishing etc and installing back including heliumgasket sheet not less than 1mm thick complete uptoto the entire satisfaction ofEngineer-in -charge all as specified and directed.at R line and NCC pump house (Note:- Sparesas required shall be measure & paid seperately against the relevant items).
34S&F Casing Wear Ring complete all as specified and directed.
35S&F shaft sleeve complete all as specified and directed.
36S&F Inter Stage Ring complete all as specified and directed.
37S&F suitable Ball bearing SKF complete all as specified and directed.
38S&F suitable Ball bearing SKF complete all as specified and directed.
39S&F suitable Bearing cartridge DE complete all as specified and directed.
40S&F suitableBearing cartridge NDE complete all as specified and directed.
41S&F shaft sleeve Nuts complete all as specified and directed.
42S&F Split Gland complete all as specified and directed.
43S&F Impeller made of brass complete as per existing size -1 Nos complete all as specified and directed.
44S&F suitable Ball bearing SKF complete all as specified and directed.
45S&F shaft sleeve complete all as specified and directed.
46Taking down old unserviceable three pole power contactors from the motor panel board sypply and fix three pole power contacor of seriesMNX 70 Cat No -CS 97076 with NO,NC and add on aux contact block, coils and the following sizes complete all as specified and as directed . Make L&T or equivalent.
47All as per item No 46 above but ofMNX 50Cat No -CS 97075 complete all as specified and directed.
48All as per item No 46 but ofMNX 40Cat No -CS 94190 complete all as specified and directed.
49All as per item No 46 but ofMNX 32 Cat No -CS 94111 complete all as specified and directed.
50All as per item No 46 but ofMNX 25 Cat No -CS 94110 complete all as specified and directed.
51All as per item No 46 but ofMNX 18 Cat No -CS 94101 complete all as specified and directed.
52Taking down unserviceable power contactor and S & F in repair Power contactor 3 pole with DC Coil of amp rating from 115A to 630A, AC-3Duty rating at 3 pole, 415V 50 Hz, type CH4 330T Cat Part No: IHPAB330400 UPTO TO 180KW complete all as specified and directed. Make:- Havells Cosmic star control gear, L&T, C&S, Havells, ABB, suitable for existing panel.
53Taking down unserviceable coil and M &L for Spare Coil of contactor of 115A to 630A, AC-3Duty rating at 3 pole, 415V 50 Hz, type CH4 330T, Cat Part No: IHPAB330400 UPTO TO 180KW complete all as specified and directed. Make:- Havells Cosmic star controlgear, L&T, C&S, Havells, ABB.
54Taking down unserviceable power contactor and S & F in repair Power Contactor model No -190Amps, 3 pole, 230/415V, 50 Hz suitable for 120 HP motors complete all as specified and directed. Make:- ABB, L&T, C&S.
55Disconnecting electrically and disengaging the AC Squirrel cage induction motor 3 phase 415 Vlots, 50 Cycles, and taking out to local workshop induction motor 75 HP for repair purpose including complete cleaning,varnishing ,reinsulation and greasing and including shifting back to location as directed, installing, testing and commissioning after repair complete all as specified and directed. (Note:- Rewinding will be measure & paid seperately under relavant item of sch.)
56Disconnecting electrically and disengaging the AC Squirrel cage induction motor 3 phase 415 Vlots, 50 Cycles, and taking out to local workshopinduction motor 20 HPfor repair purpose including complete cleaning,varnishing ,insulation and greasing andincluding shifting back to location as directed, installing, testing and commissioning after repair complete all as specified and directed. (Note:- Rewinding will be measure & paid seperately under relavant item of sch.)
57Disconnecting electrically and disengaging the AC induction motor 3 phase 415 Vlots, 50 Cycles, and taking out to local workshop induction motor 15 HPfor repair purpose including complete cleaning,varnishing ,insulation and greasing andincluding shifitng back to location as directed, installing, testing and commissioning after repair complete all as specified and directed. (Note:- Rewinding will be measure & paid seperately under relavant item of sch.)
58Disconnecting electrically and disengaging the AC Squirrel cage induction motor 3 phase 415 Vlots, 50 Cycles, 5/7.5HP,capacity motors from respective non clogging centrifugal pumps/open well submersible pumps, other rotating mechanism etc, removing from foundations, dismantling rotor and stator, bearings, cleaning the dust/dirt, overhauling thoroughly including complete varnishing and reinsulation,greasing, reassembling the motor, mounting on the foundations, coupling with non clogging centrifugal pumps/respective mechanism, making the electrical connections, testing and commissioning complete all as specified and directed. (Note:- Rewinding will be measure & paid seperately under relavant item of sch.)
59Disconnecting electrically and disengaging the AC Squirrel cage induction motor 3 phase 415 Vlots, 50 Cycles, 3HP, 2840 RPM capacity motors from respective non clogging centrifugal pumps/open well submersible pumps, other rotating mechanism etc, removing from foundations, dismantling rotor and stator, bearings, cleaning the dust/dirt, overhauling thoroughly including complete varnishing and reinsulation,greasing, reassembling the motor, mounting on the foundations, coupling with non clogging centrifugal pumps/respective mechanism, making the electrical connections, testing and commissioning complete all as specified and directed.(Note:- Rewinding will be measure & paid seperately under relavant item of sch.)
60M&L for Rewinding the motorof capacity 120hp, 75hp, 20hp, 15hp, 7.5hp, 5hp, & 3hp with super enamelled copper winding wire with appropriate same gauge of existingcoil with similar class of existing insulation as recommended by manufacturer with high quality nomenclatureinsulating paperapplying best quality insulating varnish on stator / rotor windings drying them completely, testing the insulations complete all as specified and directed.
61S&F including taking down voltmeter Class-1, digital pannal mounting type 96mmx96mm complete all as specified and directed. Make:- L&T or eq
62S&F including taking down ammeter Class-1,digital pannal mounting type 96mmx96mm complete all as specified and directed. Make: L&T cat no WDS101FCA00
63S&F including taking down SELECTOR SWITCH 10 AMPS for voltmeter/ammeter complete all as specified and directed.
64S&F including taking down CT 400/5 amps complete all as specified and directed.
65S&F including taking down CT 300/5 amps complete all as specified and directed.
66S&F including taking down CT 200/5 amps complete all as specified and directed.
67Taking down unservicable existing indicating lamp and S&F INDICATING LAMP led type complete all as specified and directed.
68S&F in repair pressure gauge dial type 0 to 20 Kg per cm2 including taking downcomplete all as specified and directed.
69Taking out unserviceable air break contactor fully automatic auto transformer starter installed in LT panel board of 120HP centrifugal pump at Independent pump house and supply and fix new air break contactor fully automatic auto transformer starter with air cooled having 50, 60 & 70% tappings installed in LT panel board of Independent pump house 120HP centrifugal pump as suitable to exising size, capacity complete all as specified and directed.
70Replacement of unservicable Motor protection circuit braker Auxilary contact Top, 1NO + 1NC complete all as specified and directed. Make:- L&T, ABB, Indo Asian.
71Replacement of unservicable Motor protection circuit braker Auxilary contact side frame-1) , 1NO + 1NC complete all as specified and directed. Make:- L&T, ABB, Indo Asian.
72Replacement of unservicable DOL starter with new DOL Starter suitable for 3HP motor installed at swimming pool complete all as specified and directed. Make :- L&T, C&S.
73Taking out old unserviceable rubber coupling of 20HP motor and supply and fix new rubber coupling of size 110/150mm complete all as specified and directed.
74Taking out unserviceable submerssible pump and motor 1.5HPfrom bore well with the help of chain pully carefully dismantling HDPE pipe and repair and maintenanance of pump and rewinding of motor as required and again droping in well after connecting HDPE pipe complete all as specified and directed.
75Taking out unserviceable Electro Chlorinator model No NC 600 capable to generate hypocloride solution from common salt powder pack unit from clorination tank and replacment of Electrolyser anode fin, element,recoating of electrochorinator anode, copper core and contact stud, cathode fin and other necessry repairs carried out and testing complete all as specified and directed.
76Taking out unserviceable CI foot valve, supply and fix in repair CI foot valve Ball type double end flanged/ drilled PN-0.2, ISI marked, IS-4038, with including necessary cutting of existing suction pipe line of any type and welding, jointing and jointing materials such nuts, bolts, washers, flangeand rubber gaskets etc for the pipe of 200 mm bore with reinforced rubber nitrile ball complete all as specified and directed. Make: Normex, Kirloskar.
77All as per item No 76 above but 150 mm bore complete all as specified and directed.
78All as per item No 76 above but 100 mm bore complete all as specified and directed.
79Replacement of worn out flat PVC insulated 3 core copper conductor of 2.5 Sqcm 1100V grade, 50 Hz for submersible complete all as specified and directed.
80Replacement of worn out / defective contactor of starter ML-3, 40 Amps, 415 V, 50 Hz, suitable for 120 HP star-delta starter complete all as specified and directed. Make : L&T (as per sample).
81Replacement of worn out / defective contactor of starter ML-2, 40 Amps, 415 V, 50 Hz, suitable for 120 HP star-delta starter complete all as specified and directed. Make: L&T (as per sample).
82Replacement of worn out / defective Electronic timer 800 SQ-A ,suitable for 120 HP star -delta starter complete all as specified and directed. Make : L&T (as per sample)
83Replacement of Unserviceable phase sequencerfor three phase centrifugle pump of capacity 120HP complete all as specified and directed. Make: C&S, L&T, Minilec.
84M&L for painting of different sizes of pumps,motors, connecting pipes and its related items at various installations as per colour code complete all as specified and directed.
85M&L for cleaning of Equalisation sewage tank for 400 KLD STP by cleaning entire internal surface by removing dirt, sludge etc with wire brush by applying bleaching power and fresh water and clean entire surface repeatedly with fresh water and draining out soiled water includingusing pressure jet pump and suction pump capacity of pool surface complete in all in as specified and directed.using acid and other suitable methods before filling as required atsite complete all as specified and directed. Note:- Quoted rates shall include for using fresh water for cleaning & sludge cutter pump for removing of sludge from tank the STP and de-watering as per the contractor arrangement.
86M&L for cleaning of MBBR REACTOR TANK, TUBE SETTLER TANK & sewage tank for 400 KLD STP by cleaning entire internal surface by removing dirt, sludge etc with wire brush by applying bleaching power and fresh water and clean entire surface repeatedly with fresh water and draining out soiled water includingusing pressure jet pump and suction pump capacity of poolsurface complete in all in as specified and directed.using acid and other suitable methods before filling as required at site complete all as specified and directed. Note:- Quoted rates shall include for using fresh water for cleaning & sludge cutter pump for removing of sludge from tank the stp and de-watering as per the contractor scope arrangement.
87M&L for cleaning of HYPO SOLUTION TANK, TREATED WATER TANK & SLUDGE HOLDING TANK for 400 KLD STP by cleaning entire internal surface by removing dirt, sludge etc with wire brush by applying bleaching power and fresh water and clean entire surface repeatedly with fresh water and draining out soiled water includingusing pressure jet pump and suction pump capacity of poolsurface complete in all in as specified and directed.using acid and other suitable methods before filling as required atsite complete all as specified and directed. Note:- Quoted rates shall include for using fresh water for cleaning & sludge cutter pump for removing of sludge from tank the stp and de-watering as per the contractor scope arrangement.
88Taking out use less filter media & refilling or Replacement of filter media (pabble) complete all as specified and directed. Note:- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clean the filter for STP 400 KLD size of DMF 1200 diax 1800 hos.
89Replacement of filter media (Gravel) complete all as specified and directed. Note:- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clean the filter for STP 400 KLD size of DMF 1200 diax1800 hos.
90Replacement of filter media (Core Sand) complete all as specified and directed. Note:- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clena the filter for STP 400 KLD size of DMF 1200 diax1800 hos.
91Replacement of filter media (fine Sand) complete all as specified and directed. Note:- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clena the filter for STP 400 KLD size of DMF 1200 diax1800 hos.
92Replacement of filter media (Antheracite) complete all as specified and directed. Note:- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clena the filter for STP 400 KLD size of DMF 1200 diax1800 hos.
93Replacement of Carbon for ACF media complete all as specified and directed. Note:- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clena the filter for size of ACF 1200 dia x1800 hos.
94Replacements of unserviceable nut bolts of any sizes complete all as specified and directed. Note- Quoted rates shall include for cleaning of vessel by using high jet pressure pump or using chemical to clen the filter for pool.
95Replacements of unserviceable media for MBBR Type of media fluidandom bio, cylindricalshaped, specific gravity 0-90 -0-95 gms/cm3, colour black for 400 kld stp complete all as specified and directed.
96Replacements of unserviceable media (PVC) for stting tank (tube settler media) for 400 kld stp complete all as specified and directed.
97Fabrication any type of MS pipe with flange, angle iron frame for valve chambers, cover made out of MS sheet of 5mm thickness and angle iron of 50 x 50 size with drilled hole and grouting in existing brick work with handles for opening of valves and with locking arrangement, making hole in valve chamber cover for insurtion of MS rod of 12 mm dia along with valve spindle cap properly welded to ms rod complete all as specified and directed.
98S&F in repair butterfly valve 50 mm dia including washers, nut bolts complete all as specified and directed. Make: kirloskar or equivalent
99M&L for unplasticised PVC pipes of pressure rating 6 kg/sqcm with all fittings and fixtures laid in trenches complete all as specified and directed for the following sizes 110 mm bore complete all as specified and directed. Make: Suprime, Plasto
100All as per item No 99 but of size 50 mm bore complete all as specified and directed.
101All as per item No 99 but of size 25 mm bore complete all as specified and directed.
102Replacement of worn out / defective contactor of starter ML-3, 40 Amps, 415 V, 50 Hz, suitable for 120 HP star-delta starter complete all as specified and directed. Make: L&T (as per sample).
103Replacement of worn out / defective contactor of starter ML-2, 40 Amps, 415 V, 50 Hz, suitable for 120 HP star-delta starter complete all as specified and directed. Make: L&T (as per sample).
104Taking out unserviceable spare coil of contactor and M&Lfor new contactor coil 240V,50Hz, for MNX 265-400 complete all as specified and directed. Make:- cat No CS94195B000 of L&T or eq in Havells/ ABB/ Legrand
105Fabrication, Supplying Installing, testing & Commissioning feeder pillar box weather / verminproof, Indoor type, factory made LT panel, CPRI approved manufacturer having dimensions of suitablesize with sufficient space required between MCCB cable connections place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands, thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter.The cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with Stainless Steellocking handle arrangement with Neoprene gasket, both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 450mm below the ground grouted in & including PCC 1:3:6 type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 200 Amps (20mm x 10mm) alumunium bus bar duly insulated. (b) Multifunctioning meter to measure Voltage, ampere, KWH,PF -1 Nos. (c) one set of pilot lamp. (d) On load Change over Switch 4 Pole 100 amps 415 voltscapacity. (d) Incoming MCCB 100 amps 4 Pole 415 volts 25 KA thermal magnetic setting type- 1 Nos. (e) Outgoing MCCB 63 amps 3 pole 415 volts 16 KA thermal magnetic setting - 2 Nos. (f) Outgoing Type MCB 32 amps 3 Pole 415 volts 10 KA thermal magnetic setting- 2 Nos. (g) Fully automatic star delta starter complete with contractors, over load relay, motor protection relay timer, Single phasing preventar etc suitable for pumping set of capacity 25 HP, in open execution in panel complete- 2 Nos. Make:- BCH/ Siemans/ L&T.
106M&L for cleaning of RCC over head reservoirs of 2.10 Lakh Gallons capacity, 40 Ft staging including arresting the leakages by brooming down all the side walls, bottom and top, removing fungus, scales dirt sludge etc. from inside and depositing the same at a distance not more than 100 mtrs after emptying the tank completely and washing the tank inside with water and chemicals such as bleaching powder, castic soda etc and applying one coat of white wash on internal surface of the tank and writing date of cleaning in white capital letters on black back ground, size of letters 80 x 10mm with sythetic enamel paint and marking the direction of flow and painting all inlets, outlets, washouts and overflow pipes with one coat of black bituminous paint completeincluding draining of excess water in tank by providing pump all as specified and as directed.
107All as per item No 106 above but 1.00 Lakh Gallons capacity, 40 Ft staging complete all as specified and directed.
108All as per item No 106 above but 0.80 Lakh Gallons capacity, 60 Ft staging complete all as specified and directed.
109All as per item No 106 above but 0.50 Lakh Gallons capacity, 60 Ft staging complete all as specified and directed.
110All as per item No 106 above but 0.30 Lakh Gallons capacity, 50 Ft staging complete all as specified and directed.
111All as per item No 106 above but 0.10 Lakh Gallons capacity, 50 Ft staging complete all as specified and directed.
112All as per item No 106 above but for UG sumps of 0.50 Lakh Gallons capacity complete all as specified and directed.
113All as per item No 112 above but 0.10 Lakh Gallons capacity complete all as specified and directed.
114All as per item No 112 above but 0.80 Lakh Gallons capacity complete all as specified and directed.
115All as per item No 112 above but 1.00 Lakh Gallon capacity complete all as specified and directed.
116Removal of sand /girth / gravel filter media from MS Pressure filter of filtration plant of swimming pool of size 6.5M long, 2.5M dia overall and 40675 gallons capacity and depositing the same at a distance not more than 100 Mtr after emptying the MS Pressure filter completly complete all as specified and directed.
117Removing existing nozzles from inside the pressure filter and keep in safe custody for reuse or disposal complete all as specified and directed.
118Removing rust and corrision from surface of pressure filter inner mentioned using wire brushes, scrappers and diluted acids for removing dust, scales accumulated organic materials and preperation of painting for the old surfaces complete all as specified and directed.
119M&L for painting of inner surface of pressure filter with two coats of epoxy paint over a coat of primer (Black bituminous paint), complete all as specified and directed.
120Returning filling spreading in layer of sand girth gravel (Filter Media) inside the pressure filter, removed vide serial item no 03 above here -in-before, in layers mentioned below and grades all as specified from top layers to bottom most layer in the same sequences specified below for each vessel:- (a) 100mm thick coarse sand size 1.5 to 3 mm (b) 75mm thick girth of size 3 to 6 mm (c) 75mm thick girth of size 6 to 12 mm (d) 75mm thick girth of size 12 to 25 mm (e) 100mm thick gravells of size 25 to 50 to 3 mm
121Supply fill and spread fine sand in top layer for pressure filter vessel of grades for 375mm thick (size of ferry sand 0.70 to 1.5mm) complete all as specified and as directed.
122Supply fill and spread coarse sand in layer for Pressure Filter Vessel of grades for 100mm thick (size of ferry sand 1.50 to 3.0mm) complete all as specified and as directed.
123Supply fill and spread gravel 3 to 6mm size in layer for Pressure Filter Vessel of grades for 75mm thick complete all as specified and as directed.
124All as per item no 123 above but with gravel of size 6 to 12 mm complete all as specified and directed.
125All as per item no 123 above but with gravel of size 12to 25 mm complete all as specified and directed.
126All as per item no 123 above but with gravel of size 25 to 50 mm complete all as specified and directed.
127Fixing only nozzles removed from item no 117 above after removing blockage servicing cleaning and testing for suitable pressure designed complete all as specified and directed.
128S&F 20mm dia nozzles of same quality existing one of gun metal brass against unserviceable item removed vide item no 04 above complete all as specified and directed. (a) Pressure Filter Vessel-02 Nos (capacity 40675 Gallons) (b) Inlet and outlet pipes of GI / CI/MS of anysize including washout pipe and back wash system at Swimming Pool
129Construction of valve chamber of size 1200 x 1200 x 1200 mm, with 15 Cm thick PCC foundation (1:4:8) type D2 (using 40 mm graded stone aggregate) and 15cm thick hard core 20cm PCC solid block grade D- 5 masonary work built in CM (1:6) 15mm thick internal & external plastering in CM (1:4), MS sheet cover 6 mm thick including 50 x 50 x 5 mm MS angle frame fixed in coping of PCC 1:2:4 type B-1 ( using 20 mm stone aggregate) making hole in valve chamber cover as per sluice valve location in side the valve chamber for insurtion of MS rod of 12 mm dia of 1.5m long along with valve spindle cap properly welded to ms rodwith locking arrangement & painting with one coat of red oxide & two coats of black bituminous paint & all as specified & directedincluding demolition ofUnsv Valve Chambers with chamber covers complete all specified and directed.
130All as per item No 129 above but valve chamber of size 1000 x 1000 x 1000 mm complete all as specified and directed.
131All as per item No 129 above but valve chamber of size 900 x 900 x 1000 mm complete all as specified and directed.
132M&L for pumping out water removing the sediments and mud, algae from the swimming pool, deep diving sump, lime tank and balancing tank (fresh water inflow tank), aeriation foundation, old used bleaching waste,etc by using electric/diesel driven pumpset to clean the walls, floors / ducts / channel and aerator complete including suface of glazed tiles, painted and cemented surfaces by using scrappers, brushes, and other mechanical equipments, replacing the broken/worn out tiles with the same matching colour tiles, washing the surfaces with clean water with applying acids and other detergents and drying in open,scrubbing the rusted part and removing the old paint completely and painting of suction and delivery pipes and pump motor including the base frame sluice valves angles frame stairs with esisting colour code, MS top of the clear water sump with black colour by applying one coat of primer and two coat of synthetic enamal paint, painting and numbering on the cubical pillars on either end of the pool in black colour letters on white back ground with synthetic enamel paint of existing size after scratching out the old painted surfaces complete all as specified and as directed. Note:- The tenderers are advised to visit the site to know the exact condition before quoting the rate.
133Taking down existing unserviceable ms laddar / step and M&L for laddar/ step of stainless steel pipe of 40mm dia for clorination tank in swimming pool as existing size complete all as specified and directed.
134M&L for painting of different sizes ofpipe inlet and outlet ,climbing lader , pumps, motors, pressure filterationplant, sluice valves , panel, trenc cover in swimming pool pump houseas per colour code with one coat of primer and two coat of synthetic enamelled black paint as existing colour complete all as specified and directed.
135S&F Glow sign board for Pump House Board size 500x80x40cm one side printed on a separate sheets of star flex imported sheet duly written in computerized digital letter on a sheet of size of not less than 5 inch for the first row and not less than 4 inch for the second row letter for illumination purpose.The frame work shall be made out of 1" Square MS pipe 18G for the sides and on all five sides with GI sheet of 22G duly painted with one coat of primer and two coats of black finishing paint and beading with 1" wide and 1mm thick aluminium strip with and. Rate quoted in respect of painting with two coats of black finishing paint over a coat of primer deemed to be inclusive in the unit rate quoted , The sign board shall be mounted and fixed to the wall/ roof top with necessary fixing arrangements such as nut, bolts complete all as specified and directed.
136Dismatling/taking out exsisting unserviceable water level indicator from over head reservoir/ UG sumps and supply and fixing new digital water level indicator consist of probe magnetic level sensor components within the probe tube stainless steel stem (SS-304) the length of the probe based on height of the tank upto 3meter height and microprocessor based digital ievel indicator digit size 100mm, monitoring in 10stages, wire andcable required from probe unit to display unit appx 60RM, of Over Head Tanks / under ground sump of any capacity complete all as specified and directed. Make:- Active Controls or eq
137M&L for swimming pool vacuum head of 14"" long and 6"" wide heavy dutyof watertech system or eq complete all as specified and directed.
138M&L for heavy duty in ground pool vaccum hose of size 40m dia as existing specification complete all as specified and directed.
139Taking out existing unserveciable suction sweeper water pump and M&L for swimming pool suction sweeper centrifugal water pump 1.5HP/1100w and 15 meter head, 24000LPH, single phase for swimming pool complete testing complete all as specified and directed.
140M&L for cleaning of PVC over head tank of capacity 500Ltrs by brooming down all the side walls, bottom and top, removing fungus, scales dirt sludge etc. from insideafter emptying the tank completely and washing the tank inside with water and chemicals such as bleaching powder, castic soda etc complete all as specified and directed.
141All as per item no 140 above but capacity of 1000Ltrs complete all as specified and directed.
142Taking out unserviceable sluice valve and S&F sluice valve, 200mm bore, flanged and drilled type PN-1.6, ISI marked with CI hand wheel and stainless steel spindleof IS:6603 bronze rings complete with jointing and jointing materials such as bolts, nuts, washers and rubber gaskets complete all as specified and directed. Make:- kirloskar Brothers Limited or equivalent.
143Taking up or down GI tubing and fitting, 80mm bore, from wall/ trenches and disconnecting from main distribution lines including necessary cutting of existing pipe line and threding the same and dewatering work as required and removing from site complete all as specified and directed.
144All as per item No 143 above but 50 mmbore complete all as specified and directed.
145All as per item No 143 above but 40 mmbore complete all as specified and directed.
146All as per item No 143 above but 25 mmbore complete all as specified and directed.
147All as per item No 143 above but 20 mmbore complete all as specified and directed.
148All as per item No 143 above but 15 mmbore complete all as specified and directed.
149Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc 10sqm on plan and not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed.
150Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25cm in soft/loose soil complete all as specified and directed.
151Removing excavated materials not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
152S&F 80mm bore GI tubing medium grade with all fittings laid in trenches and fixed complete to wall and ceilings or laid in floors as socket, bends/ elbow, union, tee etc complete all as specified and directed.
153All as per item No 152 above but 50 mm bore complete all as specified and directed.
154All as per item No 152 above but 40 mmbore complete all as specified and directed.
155All as per item No 152 above but 25 mmbore complete all as specified and directed.
156All as per item No 152 above but 20 mmbore complete all as specified and directed.
157All as per item No 152 above above but 15 mmbore complete all as specified and directed.
158S&F air release valve with sluice valve double ball type 50mm dia on rising main complete all as specified and directed.
159S&F sluice valve, 100mm bore, flanged and drilled type PN-1.0, ISI marked with CI hand wheel and stainless steel spindleof IS:6603 bronze rings complete with jointing and jointing materials such as bolts, nuts, washers and rubber gaskets complete all as specified and directed. Make: Kirloskar Brothers Limited.
160S&F sluice valve, 80mm bore, flanged and drilled type PN-1.0, ISI marked with CI hand wheel and stainless steel spindleof IS:6603 bronze rings complete with jointing and jointing materials such as bolts, nuts, washers and rubber gaskets complete all as specified and directed. Make: Kirloskar Brothers Limited.
161S&F PVC float valve (ball cock bady with epoxy coated aluminium rod & HD ball) of size 15mm dia including all fittings complete all as specified and directed.Make:- Prayag/ Hudson.
162All as per item No 161 but 20mm dia complete all as specified and directed.
163All as per item No 161 but 25mm dia complete all as specified and directed.
164M&L for unplasticised PVC pipes of pressure rating 10 kg/sqcm with all fittings and fixtures laid in trenches complete all as specified and directed for 110mm bore complete all as specified and directed.Make:- Suprime, Plasto.
165Taking out unserviceable CI Non-return valve, supply and fix in repair CI Non-return valve Ball type double end flanged/ drilled, PN-1.0 with including necessary cutting of existing delivery pipe line of any type and welding, jointing and jointing materials such nuts, bolts, washers, flangeand rubber gaskets etc for the pipe of 80 mm bore with reinforced rubber nitrile ball complete all as specified and directed. Make: Normex or equivalent.
166S&F in repair gun metal gate valve with iron wheel head, screwed both ends for iron pipe and fixed to 50mm bore including taking down / removing old unserviceable valve complete all as specified and directed.
167All as per item No 166 above but 40 mmbore complete all as specified and directed.
168All as per item No 166 above but 25 mmbore complete all as specified and directed.
169All as per item No 166 above but 20 mmbore complete all as specified and directed.
170All as per item No 166 above but 15 mmbore complete all as specified and directed.
171S&F in repair Ball valves high pressure, with polythene float and flynut complete, screwed for iron pipe and fixed complete of size 25mm dia complete all as specified and directed.Make:- Prayag or equivalent
172S&F in repair Ball valves high pressure, with polythene float and flynut complete, screwed for iron pipeand fixed complete of size 20 mm dia complete all as specified and directed.
173M&L for construction of brick masonry valve chamber of size 1050mm x 750mm x 1000mm (Internal dimension) with PCC (1:3:6) foundation 150 mm thick, brick work 23 cm thick built in CM (1:6), PCC (1:3:6) coping 50mm thick plastering 15 mm thick in CM (1:4) to all internal and exposed surfaces includingexcavation earth work in any type of soil, MS sheet cover 3.15mm thick fixed with angel iron frame 50x50x6mm with locking arrangement embedded in PCC and painting to MS cover with two coats of synthetic enamel paint over one coat of red oxide primer etc complete all as specified and directed.
174Fabrication, Supplying, Installing, testing & Commissioning feeder pillar box weather / verminproof, Indoor type, factory made LT panel, from any CPRI approved manufacturer having dimensions of suitablesize with sufficient space required between MCCB cable connections place and body of panel for easily working to workers including necessary incoming & outgoing cable connections, cable glands, thimbles of required sizes, made out of CRCA sheet 3.00 mm thick for outer shell and 2mm thick for inner shell duly powder coated paint with inner shutter.The cubical shall have a bottom channel of size 75x40x5mm duly coated with zinc metal coating with Stainless Steellocking handle arrangement with Neoprene gasket, both side openable fixed on 50 x 50 x 5 mm MS angle frame fixed 300mm above groud level & 450mm below the ground grouted in & including PCC (1:3:6) type C1 (using 20mm graded stone aggregate) complete all as specified, directed & comprising of following including refixing existing cables to new panels by proper lugging & cable gland as required. (a) Busbar chamebr for 3 phase & nuetral of capacity 200 Amps (20mm x 10mm) alumunium bus bar duly insulated. (b) Multifunctioning meter to measure Voltage, ampere, KWH,PF -1 Nos (c) Two set of pilot lamp. (R Y B) (d) On load Change over Switch 4 Pole 63 amps 415 voltscapacity. (d) Incoming MCCB 63 amps 4 Pole 415 volts 25 KA thermal magnetic setting type- 1 Nos (e) Outgoing MCB 32 amps 4 pole 415 volts 16 KA thermal magnetic setting - 2 Nos (g) Fully automatic star delta starter complete with contractors, over load relay, motor protection relay timer, Single phasing preventar etc suitable for pumping set of capacity 3 HP in open execution in panel complete- 1 Nos. Make:- BCH/ Siemans/ L&T. (h) Fully automatic star delta starter complete with contractors, over load relay,motor protection relay timer, Single phasing preventar etc suitable for pumping set of capacity 5 HP, in open execution in panel complete- 1 Nos. Make:- BCH/ Siemans/ L&T.
175M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized ironand connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 40mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 and all as specified. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,mediumgrade & copper lug etc. (f) 40mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
176NOTE:- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.1,00,610.00]