Repair And Maintenance To Internal Wiring To Certain Building At Af Stn Agra Under Ge ( Af ) Tech Area Agra, agra-Uttar Pradesh

Military Engineer Services-MES has published Repair And Maintenance To Internal Wiring To Certain Building At Af Stn Agra Under Ge ( Af ) Tech Area Agra. Submission Date for this Tender is 10-02-2022. Electrification Work Tenders in agra Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

30715335
Corrigendum : Repair And Maintenance To Internal Wiring To Certain Building At Af Stn Agra Under Ge ( Af ) Tech Area Agra
Open Tender
Indian
Uttar Pradesh
agra
10-02-2022

Tender Details

Repair And Maintenance To Internal Wiring To Certain Building At Af Stn Agra Under Ge ( Af ) Tech Area Agra

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Jan-2022 Corrigendum BOQ 03-02-2022
2 25-Jan-2022 Corrigendum Other 03-02-2022
3 03-Feb-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 10-02-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 39.85 Lakhs /-

BOQ Items

Name of Work: REPAIR & MAINT TO INTERNAL WIRING TO CERTAIN BUILDINGS AT AF STN AGRA UNDER GE (AF) TECH AREA,AGRA
Sl. No. Item Description
1Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc, including removal and making good disturbed surfaces of walls, ceilings etc complete all as specified & directed.
2Taking down main switches/DB"s (alongwith existing board, MCBs & isolators) including removing the same from site and making good disturbed surfaces complete all as specified & directed.
3Taking down existing old/unserviceable sub main wiring of any type and description, removal of teak wood batten/ PVC pipe/ PVC casing & caping and making good disturbed surfaces of walls, ceilings etc as per existing complete all as specified and directed.
4M&L for point wiring concealed type with 1.50 sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 1.5 sqmm FRLS PVC insulated unsheathed multi stranded copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20 mm dia with its accessories, pressed steel terminal box made of 1.2 mm thick MS sheet/anodised steel box, painted with one coat of red oxide primer including 3.0 mm thick ISI marked laminated sheet cover for fixing switches/ socket/ regulators etc & making good the disturbed surface by applying putty & matching with colour to the adjoining wall for one light/ fan/ exhaust fan point controlled by one no piano type switch 5 Amps single pole one way complete all as specified & directed.
5All as per srl item no. 4 above but for 3/5 pin socket outlet for 5 Amps on independent board with 1.5 sqmm PVC insulated, unsheathed single core multistranded copper conductor cable 1100 volts grade including 1.50 sqmm PVC insulated unsheathed multi-stranded copper conductor cable as earth continuity conductor complete all as specified & directed.
6All as per srl item no. 4 above but for 3/5 pin socket outlet for 15 Amps on independent board with 2.5 sqmm PVC insulated, unsheathed single core multistranded copper conductor cable 1100 volts grade including 2.50 sqmm PVC insulated unsheathed multi-stranded copper conductor cable as earth continuity conductor complete all as specified & directed.
7M&L for point wiring concealed type with 1.50 sqmm PVC insulated, unsheathed, single core, multistranded copper conductor cable 1100 volts grade including 1.5 sqmm FRLS PVC insulated unsheathed multi standard copper conductor cable as earth continuity conductor drawn through in and including rigid PVC conduit not less than 20 mm dia with its accessories, pressed steel terminal box made of 1.2 mm thick MS sheet/anodised steel box, painted with one coat of red oxide primer including 3.0 mm thick ISI marked laminated sheet cover for fixing switches/ socket/regulators etc & making good the disturbed surface by applying putty & matching with colour to the adjoining wall for one bell/ buzzer point controlled by one no bell push switch 5 Amps single pole one way complete all as specified & directed.
8Supply & fixswitch piano, flush type single pole, one way 5/6 Amps, 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
9Supply & fix bell push, single pole one way 5 Amps, 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
10Supply & fixsocket outlet 2 in 1, 3 pin 5/6Amps, flush universal type complete all as specified & directed. Make : Anchor / Havells / C&S
11Supply & fixswitch piano, flush type single pole, one way 15/ 16 Amps, 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
12Supply & fixsocket outlet 2 in 1, 3 pin 5 and 15 Amps, flush universal type complete all as specified & directed. Make : Anchor / Havells / C&S
13Supply & fixceiling rose, surface bakelite, 32.5x25mm surface type, two to three terminals, AC 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
14Supply & fixlamp holder, PVC/ polycarbonate type with back plate suitable for batten fittings complete all as specified & directed. Make : Anchor / Havells / C&S
15Supply & fixrotory stepped type electronic fan regulator mini flush type 120/ 280 Volts complete all as specified & directed. Make : Anchor / Havells / C&S
16Supply & fixswitch socket combination 2 in 1, 3 pin, 5/6 Amps shuttered flush type multipurpose controlled by one switch complete all as specified & directed. Make : Anchor / Havells / C&S
17Supply & fixswitch socket combination 2 in 1, 3 pins, 5 and 15/16 Amps flush universal type controlled by one switch complete all as specified & directed. Make : Anchor / Havells / C&S
18Supply & fixin repair switch piano, flush type single pole, one way 5/6 Amps, 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
19Supply & fix in repair bell push, single pole one way 5 Amps, 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
20Supply & fixin repair socket outlet 2 in 1, 3 pin 5/6Amps, flush universal type complete all as specified & directed. Make : Anchor / Havells / C&S
21Supply & fixin repair switch piano, flush type single pole, one way 15/ 16 Amps, 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
22Supply & fixin repairsocket outlet 2 in 1, 3 pin 5 and 15 Amps, flush universal type complete all as specified & directed. Make : Anchor / Havells / C&S
23Supply & fix in repair ceiling rose, surface bakelite, 32.5x25mm surface type, two to three terminals, AC 240 volts complete all as specified & directed. Make : Anchor / Havells / C&S
24Supply & fix in repair lamp holder, PVC/ polycarbonate type with back plate suitable for batten fittings complete all as specified & directed. Make : Anchor / Havells / C&S
25Supply & fix in repair rotory stepped type electronic fan regulator mini flush type 120/ 280 Volts complete all as specified & directed. Make : Anchor / Havells / C&S
26Supply & fix in repairs, switch socket combination 2 in 1, 3 pin, 5/6 Amps shuttered flush type multipurpose controlled by one switch complete all as specified & directed. Make : Anchor / Havells / C&S
27Supply & fix in repairs, switch socket combination 2 in 1, 3 pins, 5 and 15/16 Amps flush universal type controlled by one switch complete all as specified & directed. Make : Anchor / Havells / C&S
28M&L for provision of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, mutistranded copper conductor cable of size 4.0 sqmm drawn in and including PVC rigid conduit not less than 20mm dia with its accessories, surface type, including one run of single core FR PVC insulated, unsheathed, mutistranded copper conductor cable of size 4.0 sqmm as earth continuity and connected of common earth dolly complete all as specified & directed. Note:- Two runs of 4.0 sqmm cable & one run of 4.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length.
29M&L for provision of sub main wiring with two runs of single core FRLS PVC insulated, unsheathed, mutistranded copper conductor cable of size 6.0 sqmm drawn in and including PVC rigid conduit not less than 25mm dia with its accessories, surface type, including one run of single core FR PVC insulated, unsheathed, mutistranded copper conductor cable of size 6.0 sqmm as earth continuity and connected of common earth dolly complete all as specified & directed. Note:- Two runs of 6.0 sqmm cable & one run of 6.0 sqmm cable alongwith PVC conduit including its accessories shall be measured and paid one unit length.
30S&F in repairs 1.50 Mtr long house service bracket, made out of 32mm dia light grade GI pipe, bent to shape including MS hook & stay or guy and fixed to wall/ poles including all necessary nut/ bolts complete all as specified and directed.
31M&L for factory made sheet metal enclosure 240 volts, 8 ways with 200A rated bus bar, SPN, double door type suitable for housing MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
32M&L for factory made sheet metal enclosure 240 volts, 4 ways with 200A rated bus bar, SPN, double door type suitable for housing MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
33M&L for factory made sheet metal enclosure 240 volts, 2 ways without bus bar, SPN suitable for housing MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
34M&L for factory made sheet metal enclosure 415 volts, 4 ways with 200A rated bus bar, TPN, double door type suitable for housing MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
35M&L for factory made sheet metal enclosure IP 54, 415 volts, 8 ways with 200A rated bus bar, VTPN, double door type suitable for I/c as MCCB and outgoing as MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed. Make- Legrand / L&T/Havells/Schneider
36M&L for factory made sheet metal enclosure 415 volts, 4 ways with 200A rated bus bar, VTPN, double door type suitable forI/c as MCCB and outgoing as MCB/Isolators and fixed the same on & including mild steel hold fasts of suitable size & shape after grouting the hold fasts in the wall with and including PCC (1:2:4) type B1 using 20mm graded stone aggregate complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
37Supply & fixed in repairs AC box 240 Volt heavy duty with 25 Amp, plug top with live indicator and MCB 25 Amp "C" curve etc completecomplete all as specified & directed.Make : LEGRAND / L&T / SCHIENDER
38Supply and fixed in repairs junction/ sunken box of size 100x100x50mm of 1.60mm thick mild steel sheet with 1 to 4 way as per site requirement suitable for 20mm dia conduit with and including two coats of black bituminous painting on inner & outer surfaces of box and fixed on walls in CM 1:4 and making good the disturbed surfaces of walls as per existing complete all as specified and directed.
39Supply and fixed in repairs junction/ sunken box of size 175x100x50mm of 1.60mm thick mild steel sheet with 1 to 4 way as per site requirement suitable for 20mm dia conduit with and including two coats of black bituminous painting on inner & outer surfaces of box and fixed on walls in CM 1:4 and making good the disturbed surfaces of walls as per existing complete all as specified and directed.
40Supply and fixed in repairs junction/ sunken box of size 250x200x50mm of 1.60mm thick mild steel sheet with 1 to 4 way as per site requirement suitable for 20mm dia conduit with and including two coats of black bituminous painting on inner & outer surfaces of box and fixed on walls in CM 1:4 and making good the disturbed surfaces of walls as per existing complete all as specified and directed.
41Supply and fixed in repairs junction/ sunken box of size 275x225x50mm of 1.60mm thick mild steel sheet with 1 to 4 way as per site requirement suitable for 20mm dia conduit with and including two coats of black bituminous painting on inner & outer surfaces of box and fixed on walls in CM 1:4 and making good the disturbed surfaces of walls as per existing complete all as specified and directed.
42Supply & fix in repairs MCB, SP, AC, 240 volts of 06 to 32 Amps capacity "C" series and making connections complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
43Supply & fix in repair Isolator, SPN, AC, 240 volts of 10-32 Amps for inductive load connected through cable lugs of suitable size, complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
44Supply and fixed in repairs MCB SPN 40 to 63 Amp 240V, "C" series 10 KA, complete all as specified and directed.Make : LEGRAND / L&T / SCHIENDER
45Supply and fixed in repairsMCB TPN 63 Amps, 415 V, 50Hz,10 KA, "C" seriescomplete all as specified and directed. Make : LEGRAND / L&T / SCHIENDER
46Supply and fixed in repairs MCCB four pole with enclosure, 415 volts, 160 Amps with breaking capacity 16KA complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
47Supply and fixed in repairs MCCB four pole with enclosure, 415 volts, 125 Amps with breaking capacity 16 KA complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
48Supply and fixed in repairs MCCB four pole with enclosure, 415 volts, 100 Amps with breaking capacity 16kA complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
49Supply and fixed in repairs MCCB four pole with enclosure, 415 volts, 63 Amps with breaking capacity 16 KA complete all as specified & directed. Make : LEGRAND / L&T / SCHIENDER
50Supply & fixed in repair, 3.0mm thick ISI marked laminated bakalite sheet cover of size 125x125mm including making necessary provision for fixing/ mounting of existing switches/ socket/ regulators etc and fixing the existing switches/ socket/ regulators etc on board with existing screws and after making necessary connections fixing the board on existing position with and including new screws & GI covers with cup head washers complete all as specified and directed.
51Supply & fixed in repair, 3.0mm thick ISI marked laminated bakalite sheet cover of size 200x125mm including making necessary provision for fixing/ mounting of existing switches/ socket/ regulators etc and fixing the existing switches/ socket/ regulators etc on board with existing screws and after making necessary connections fixing the board on existing position with and including new screws & GI covers with cup head washers complete all as specified and directed.
52Supply & fixed in repair, 3.0mm thick ISI marked laminated bakalite sheet cover of size 275x225mm including making necessary provision for fixing/ mounting of existing switches/ socket/ regulators etc and fixing the existing switches/ socket/ regulators etc on board with existing screws and after making necessary connections fixing the board on existing position with and including new screws & GI covers with cup head washers complete all as specified and directed.
53Supply & fixed in repair, 3.0mm thick ISI marked laminated bakalite sheet cover of size 300x250mm including making necessary provision for fixing/ mounting of existing switches/ socket/ regulators etc and fixing the existing switches/ socket/ regulators etc on board with existing screws and after making necessary connections fixing the board on existing position with and including new screws & GI covers with cup head washers complete all as specified and directed.
54S&F in replacement surface/wall mountingLED batten, 20 watt LED lamp extruded aluminium housing provided for efficient heat dissipating with poly carbonate diffuser & intergrated industrial grade heavy duty electronic driver includinglamp.Make- Havells cat part ENDURALINEARNEOBS20WLED865SPCWH / Bajaj/Crompton or equivalent as approved by GE.
55S&F in repair LED wall bracket aesthetrical designedLED 8W flat panel for wall mounting which provides soft-light and glare free symmetrical illuminationincluding neccessary arrangement compelet all as specified and directed. Make : Halonix (Cat Part No HHW04808CFRF02)or equivalent in Bajaj / Crompton specified makes as approved by GE.
56S&F in repair LED Pluto panel (surface) aesthetrical designed 1x1 LED 15W flat panel for surface mounting which provides soft-light and glare free symmetrical illumination and fixutre sizein mm (LxWxH) 295X295X70 (1x1) including neccessary arrangement compelet all as specified and directed. Make : Havells (Cat Part No PLUTO1X1PLR15WLED857S)or equivalent in Bajaj / Crompton specified makes as approved by GE.
57S&F in repair Bulk LED light (surface) aesthetrical designed10W flat panel for surface mounting which provides soft-light and glare free symmetrical illuminationincluding neccessary arrangement compelet all as specified and directed. Make : Crompton (Cat Part No BULKHEAD10W)or equivalent in Bajaj / Havells specified makes as approved by GE.
58S&F in repair LED CromSqure/ Round Downlighter 18 Watt with aluminium housing including neccessary arrangement compelet all as specified and directed. Make : Havells (Cat Part No INTEGRAHEDLR18WLED857S) or equivalent in specified makes as approved by GE
59S&F in replacement ceilingrecessed mounting 2x2LED panel square type, slim, compact, LED edge lit panel fitting with high brightness and electronic driver complete of size 1*34/36 watt. Make- Havells-PLUTONEO2X2PLR34WLED857S/ Bajaj/Cromptonor equivalent as approved by GE
60S&F in repairs of LED Pluto panel (surface) aesthetrical designed 4x1 LED 36W flat panel for surface mounting which provides soft-light and glare free symmetrical illumination and fixutre sizein mm (LxWxH) 1200x300x70 (4x1) including neccessary arrangement compelet all as specified and directed. Make : Havells (Cat Part No PLUTONEO4X1PLR36WLED857S)or equivalent in Bajaj / Crompton specified makes as approved by GE.
61S&F in Pluto panel 2x2LEDsurface mounted panel on flat rooffitting with glare free symmetrical illumination ready to fit with complete fittings and fixture of size 34 watt. Make- Havells cat part PLUTOSURFACE2X2PLS34WLED840S/ Bajaj/Cromptonor equivalent as approved by GE
62M&L for earthing complete with galvaniseded steel earth plate electrode 600 x 600 x 6.0mm thick directly burried in the ground (Earth pit not less than 2.25 m deep below normal ground level) with top edge of earth plate not less than 1.50M below the normal ground level with and including provision of earth test point terminal block made out of gun metal or phosphorus bronze of size 75x75x25mm drilled and screwed with & including 3 Nos. 8mm dia 25mm long hexagonal head screw and necessary connections complete, connected to GI wire 4.0mm dia by means of bolts, nuts, check nuts andwashers of galvanised iron or steel, 15mm bore GI pipe medium grade including necessary fittings for protection of earthing wire, watering pipe 20mm bore GI medium grade, concrete chamber in PCC (1:4:8) type D-2 using 40 mm grade aggregate, coping shall be in PCC (1:3:6) type C-1 using 20 mm grade aggregate and internal surfaces of concrete chamber shall be given 12mm thick plaster in CM (1:4), funnel with wire gauge of 22 gauge (0.63 mm) 8 mesh per linear incl 50mm thick cover of RCC (1:2:4) type B-1 using 20mm grade stone aggregate reinforced with 8mm MS deformed bar @ 75 mm C/C both ways, char coal dust and common salt all as shown in electrical plate No. 3 of SSR Part-I (2009) includingall necessary excavation & earth work and removal of surplus soil to a distance n. exc 50M and providing connection points with MS bolts & washers as required and connection from earth test point to earth electrode with same GI wire alongwith protection pipe (upto max distance of 7.5 mtr is included in unit rate) and testing on completion including takingout old u/s broken galvanised steel earthing material such as plate, pipe etccomplete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail