Repair / Maint Of Dg Sets, Voltage Stabilisers, Washing Machine, Air Compressor, Security / Street Light, Sewage Installation / Pump House, Fans, Geysers, Internal Wiring Etc At Mil Stn Aurangabad Under Ge ( S ) Ahmednagar Repair / Maint Of Dg S, aurangabad-Maharashtra

Military Engineer Services-MES has published Repair / Maint Of Dg Sets, Voltage Stabilisers, Washing Machine, Air Compressor, Security / Street Light, Sewage Installation / Pump House, Fans, Geysers, Internal Wiring Etc At Mil Stn Aurangabad Under Ge ( S ) Ahmednagar Repair / Maint Of Dg S. Submission Date for this Tender is 16-02-2022. Electrification Work Tenders in aurangabad Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

30702591
Corrigendum : Repair / Maint Of Dg Sets, Voltage Stabilisers, Washing Machine, Air Compressor, Security / Street Light, Sewage Installation / Pump House, Fans, Geysers, Internal Wiring Etc At Mil Stn Aurangabad Under Ge ( S ) Ahmednagar Repair / Maint Of Dg S
Open Tender
Indian
Maharashtra
aurangabad
16-02-2022

Tender Details

Repair / Maint Of Dg Sets, Voltage Stabilisers, Washing Machine, Air Compressor, Security / Street Light, Sewage Installation / Pump House, Fans, Geysers, Internal Wiring Etc At Mil Stn Aurangabad Under Ge ( S ) Ahmednagar Repair / Maint Of Dg Sets, Voltage Stabilisers, Washing Machine, Air Compressor, Security / Street Light, Sewage Installation / Pump House, Fans, Geysers, Internal Wiring Etc At Mil Stn Aurangabad Under Ge ( S ) Ahmednagar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Jan-2022 Dateamended8848 Date 09-02-2022
2 25-Jan-2022 8848BOQrevised BOQ 09-02-2022
3 09-Feb-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-02-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work : REPAIR/MAINT OF DG SETS, VOLTAGE STABILISERS, WASHING MACHINE, AIR COMPRESSOR, SECURITY/STREET LIGHT, SEWAGE INSTALLATION/PUMP HOUSE, FANS, GEYSERS, INTERNAL WIRING ETC AT MIL STN AURANGABAD UNDER GE (S) AHMEDNAGAR
Sl. No. Item Description
1Dismantling from site andtransportingto authorised workshop, 100 KVA double cylinder DG set engine for complete overhauling, drilling the bore,servicing of piston head, piston rod, piston rings, head gasket,piston bearing, tapit valve and covers, pressure oil pipes, fuel injection pump, Alternator, machining of crank shalft at lathe machine replacement of fuel filter and oil filter complete with "O" rings, dry air filter, airInlet andexhaust outlet manifolds and refixing the same after repair and cleaning with diesel and removing all dirt/oil deposted on body of engine andtesting commission complete all as specified and as directed.Note:- All necessary spares parts/ items shallbe measured saperately.
2S&FV belt for fan/water pump assy etc for 100 KVA DG set including taking down existing V belt all as specified and as directed.
3S&F gasket for Exhaust manifold for 100 KVA DG sets including taking down existing gasket all as specified and as directed.
4S&F Air hose setwith all necessary fitting for 100 KVA DG set including taking down existing air hose set with fitting all as specified and as directed.
5S&F water hose set with all necessary fitting for 100 KVA DG set including taking down existing water hose set with fitting all as specified and as directed.
6S&F in repairs, fuel pipe for 100 KVAall as specified and as directed.
7S&F in repairs, radiator cap for 100 KVA all as specified and as directed.
8S&F in repairs, outer glass and gasket as required at site for 100 KVAall as specified and as directed.
9S&Fin repairs, solenoid switchfor 100 KVA DG setsall as specified and as directed.
10M&L for draining out from the fuel tank of DG set of capacity 100 KVA and keeping it in a separate container, cleaning the fuel tank all lnternally & externally by removing all the accumulated sediments, leak testing the tank and welding/brazing including one coat of black synthetic enamelpaint over a coat of red oxide primer and refixing the tank to its original position & refilling the fuel back into the tank all as specified and as directed.
11S&F self starter for 100 KVA DG set, suitable for 12/24 Volt DC operationincluding disconnecting and taking down the existing unserviceable self starter & depositing to MES store yard all as specified and as directed. Make - Lucas
12S&F piston Assembly (one piston with ring) for 100 KVA DG set including taking down existing piston assembly all as specified and as directed.
13Dismantling from site andtransportingto authorised workshop, 40 KVA,double cylinder DG set enginefor complete overhauling, drilling the bore,servicing of piston head, piston rod, piston rings, head gasket,piston bearing, tapit valve and covers, pressure oil pipes, fuel injection pump, Alternator, machining of crank shalft at lathe machine, replacement of fuel filter and oil filter complete with "O" rings, dry air filter, airInlet andexhaust outlet manifolds and refixing the same after repair and cleaning with diesel and removing all dirt/oil deposted on body of engine andtesting commission complete all as specified and as directed.Note:- All necessary spares parts/ items shallbe measured separately.
14S&FV belt for fan/water pump assy etc for 40 KVA DG set including taking down existing V belt all as specified and as directed.
15S&F gasket for Exhaust manifold for 40 KVA DG sets including taking down existing gasket all as specified and as directed.
16S&F Air hose set with all necessary fitting for 40 KVA DG set including taking down existing air hose all as specified and as directed.
17S&F water hose set with all necessary fitting for 40 KVA DG set including taking down existing water hose set all as specified and as directed.
18S&F in repairs, fuel pipe for 40 KVAall as specified and as directed.
19S&F in repairs,radiator cap for 40 KVAradiator cap all as specified and as directed.
20S&F in repairs, outer glass and gasket as required at site for 40 KVA outer glass and gasket all as specified and as directed.
21S&F solenoid switchfor 40 KVA DG sets including taking down existing solenoid switchall as specified and as directed.
22M&L for draining out from the fuel tank of DG set of capacity 40 KVA and keeping it in a separate container, cleaning the fuel tank all lnternally & externally by removing all the accumulated sediments, leak testing the tank and welding/brazing including one coat of black synthetic enameledpaint over a coat of red oxide primer and reflxing the tank to its original position & refilling the fuel back into the tankall as specified and as directed.
23S&F self starter for 40 KVA DG set, suitable for 12/24 Volt DC operationincluding disconnecting and taking down the existing unserviceable self starter & depositing to MES store yard all as specified and as directed.Make - Lucas
24S&F piston Assembly (one piston with ring) for 40 KVA DG set including taking down existing piston assembly all as specified and as directed.
25M&L for painting of DG Set Canopy with two coats of powder coated paint as per existing colour by scrapping the old surface of canopy and applying one coat of red oxide on the surface and makinggoodcomplete all as specified and as directed
26M&L for painting of DG Set Exhaust with two coats of synthetic enamel aluminium paint silver colour paint including scrapping the old surface of exhaust and applying one coat of red oxide on the surface and makinggood.complete all as specified and as directed
27S&F in repairs, automatic battery charger input voltage 170V to 300V Ac and output voltage 12V/24V DC, with features Automatic Selection of FLOAT and BOOST modeall as specified and as directed
28S&F in repairs, power contactors of AC1 upto 210 Amps 3 Pole 415 voltsall as specified and as directed.
29S&F in repairs, power contactors of AC3 upto 210 Amps 3 Pole 415 voltsall as specified and as directed.
30M&L for complete wiring to LT panel of pump and motorof all connected items and replacement ofVoltmeter, ammeter with digital display, MCB TPN 63 Amp -01, Contactor, single phase prevantor, LED type indicator lamp set of threeincluding CT PT for 3 phase amperemeterupto capacity of 60 Amp, Volt including taking down old unserviceable items complete all as specified and as directed.
31S&F in repairs, water meter gaugeall as specified and as directed.
32M&L for denting, welding/fixing of hinges, replacement of damaged door (made up of 3.15mm thick steel sheet) of indoor/outdoor panel door of various capacity, preparation of old/new surfaces of panel box and applying two coats ofsynthetic enamel paintall as specified and as directed.
33Taking LT shutdown, dismantling and removing Sq cage induction motor upto 5.5 HP, 3 phase alongwith star delta connection from existing foundation / position, shifting to authorized workshop forrepair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials, Varnishing, Heating, Drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it"s original position, aligning, testing and commissioning on full load for 8 hrs continuous runningcomplete all as specified & as directed.
34Half yearly Inspection, maintenance and servicing ofDG set any Make and any type including alternator, Electric panelboard, Connection from DG set etc by thorough check (B check) along with routine A check for smooth functioning and carrying out complete maint as per OEM instructions comprising of following all as specified and as directed. (a) Replacing lubricant oil. (b) Replacing lubricating oil filter element with sealing "O’ ring. (c) Replacing fuel filter element (Pre + Micro) with sealing "O’ ring. (d) Replacing coolant. (e) Replacing Governor oil. Note :- Spares, Oil, Lubricants, Coolant etc will be measured & paid under relevant item.
35S&F in repairs, fuel filter element pre+micro with "O" ring for DG set 100 KVA of Make Kirloskar or as per existing make at site, fixed complete all as directed.
36S&F in repairs, fuel filter element pre+micro with "O" ring for DG set 40 KVA of Make Kirloskar or as per existing make at site, fixed complete all as directed.
37S&F in repairs, fuel filter element pre+micro with "O" ring for DG set 15 KVA of Make Kirloskar or as per existing make at site, fixed complete all as directed.
38S&F in repairs, oil filter element with "O" ring for DG set 100 KVA of Make Kirloskar or as per existing make at site, fixed complete all as directed.
39S&F in repairs, oil filter element with "O" ring for DG set 40 KVA of Make Kirloskar or as per existing make at site, fixed complete all as directed.
40S&F in repairs, oil filter element with "O" ring for DG set 15 KVA of Make Kirloskar or as per existing make at site, fixed complete all as directed.
41Supply and filling engine oil 10W30 of Make: Shell /Servoall as specified and as directed.
42Supply and filling coolent of Make: Indian oil / TVS,all as specified and as directed.
43Taking out old unserviceableoil fired incinator pump and transporting to authorised workshop of Denfoss for repairing and replacement of unserviceable parts such as firing nozzle, control valve, relay and communication wires, control switch , serving/replacement of fuel pump , cleaning of diesel tank and fuel pipes andrefixing the same in position and testing commisioning at site all as directed. Note : S&F in repairs of spare parts are deemed to be included in the quoted rate.
44Repairing of oil fired incinator chimney, 20 mtr high and refixing the lightening arrestor, air termination rod and aluminium strip on saddle/ wooden gutties and connecting upto the earthing pit complete all as directed by Engr-in-Charge at site. Note :- Work shall be carried out at a height of 20 mtr and rate quoted shall be deemed to be included for any expediture for provn of crane etc.
45S&F in repairs, wall mounting type pre wired DOL starter, suitable for 1.5 HP motor with overload protection and suitable relay and making connection complete all as specified and directed.
46Servicing of washing machine of capacity 45 kg/hr of Make -Shine and carry out testing after repair/replacement of following spares (if required) :- Note :- (i) Servicing/repair will be carried out by Service Engineer of company and any charges on account of his visit will be paid by the contractor (ii) Spare parts shall be measured and paid separately
47S&F in repairs, heating element of 10 KW suitable for washing machine of Shine make of capacity 45 kg/hr all as specified and as directed.
48S&F in repairs, timer switch with rotating motor, suitablefor washing machine of Shine make of capacity 45 kg/hr all as specified and as directed.
49S&F in repairs, relay for washing machine of Shine make of capacity 45 kg/hr all as specified and as directed.
50S&F in repairs, rotor motor of any capacity/any parts of door cover of washing machine all as specified and as directed.
51S&F in repairs, drier motor of capacity 0.5 HP, 2800 rpm including break shoe/wash out valve suitablefor washing machine of Shine make of capacity 45 kg/hr all as specified and as directed.
52Taking out old unserviceable submersible sewage pump setfrom sewage underground sump by means of chain pully and transporting to authorised workshop for repair and rewindingthemotorwith super enamelled insulated copper wire of existing gauge including insulated packing, liquidcompound, differential oil-4.5 ltrs, repalcement of oil seal and motor/pump bearing, replacement/repair of motor and pump shaft made out of high quality Stainless steel andreassembling and installing back at it"s original position, aligning, testing and commissioning on full load for 8 hrs continuous running for upto 40HP, 3 phase electric motor all as specified & as directed.
53Disconnect the electric supply, dismantle coupling and remove compressor upto 40 HP,shifting to local workshop for repair / servicing, opening up the compressor unit, dismantle and remove damaged twin lobo air compressor, piston, piston connecting rod, rings etcand replace with new one, reconditioning / welding / filling / grinding / lathework to shaft of the compressor unit, supply & replace suitable size bearing of make : SKF - 2Nos, drain out the out dated compressor oil, cleaning the oil chamber thoroughly by removing the sludges from the oil sump, replace with new compressor oil of specified gravity - 4 Litres, supply & replace air filters of suitable size - 2Nos, reassembling with new gasket set, transporting back to the original location, coupling, aligning, supply and replace worn out V - belts ( B-72) of make : Fenner - 3Nos, and reinstalling at sie, connecting, testing& commissioning complete all as specified & as directed.
54Taking LT shutdown, dismantling and removing the 10 HP, 3 phase electric motor from existing foundation / position, shifting to authorized workshop forrepair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials, varnishing, heating, drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it"s original position, aligning, testing and commissioning on full load for 8 hrs continuous runningcomplete all as specified & as directed.
55Taking LT shutdown, dismantling and removing the 7.5 HP, 3 phase electric motor from existing foundation / position, shifting to authorized workshop forrepair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials, Varnishing, Heating, Drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it"s original position, aligning, testing and commissioning on full load for 8 hrs continuous runningcomplete all as specified & as directed.
56Taking LT shutdown, dismantling and removing the upto 5.5 HP, 3 phase electric motor from existing foundation / position, shifting to authorized workshop forrepair work, removing the burnt winding, cleaning rotor / stator slots, re-winding the motor with super enamelled copper wire of the size equivalent to the original winding including insulated packing materials, varnishing, heating, drying etc, replacing the bearings, reassembling the motor, transporting to site of work and reinstalling back at it"s original position, aligning, testing and commissioning on full load for 8 hrs continuous runningcomplete all as specified & as directed.
57Disconnecting, taking out and transporting to workshopold unserviceable pump of capacity 40 HP for repair/replacement of worn out parts & reassembling aftersatisfactorycompletion of repair work (the repair work shall includesreplacement of both end pumpbearings, gland packing, oil seal, including machining of shaft at lathe machine, greasing complete) transporting back to site of work, reconnecting and testing for smooth running at pump house complete all as specified and directed. Note - Any nut/bolts/ studs and packing required shall deemed to be included in the rates quoted by the contractor.
58Disconnecting, taking out and transporting to workshopold unserviceable pump of capacity 25 HP for repair/replacement of worn out parts & reassembling aftersatisfactorycompletion of repair work (the repair work shall includesreplacement of both end pumpbearings, gland packing, oil seal, including machining of shaft at lathe machine, greasing complete) transporting back to site of work, reconnecting and testing for smooth running at pump house complete all as specified and directed. Note - Any nut/bolts/ studs and packing required shall deemed to be included in the rates quoted by the contractor.
59Disconnecting, taking out and transporting to workshopold unserviceable pump of capacity 15 HP for repair/replacement of worn out parts & reassembling aftersatisfactorycompletion of repair work (the repair work shall includesreplacement of both end pumpbearings, gland packing, oil seal, including machining of shaft at lathe machine, greasing complete) transporting back to site of work, reconnecting and testing for smooth running at pump house complete all as specified and directed. Note - Any nut/bolts/ studs and packing required shall deemed to be included in the rates quoted by the contractor.
60M&L for scrapping the old painting and removing the grease, oil, dirt etc, filling the cavities of exposed surfaces of pump, motor,sand filter,ladder, gate and pipe line and spray painting with two coats of super enameled anti corrosive paint of approved colour (according to colour codeat STP area ), over a coat of primer after taking proper shutdown of LT pannel and restoring of supply after completion of the work all as specified and as directed.directed.
61M&L for cleaning vegetation/grass and bushes with roots in the water supply installation and STP area, removing the garbage and depositedat distance not exceeding 100m as directed by Engr-in-Charge.
62Taking down old unserviceable street light/metal halliedfittings fromstreet light poles of any type/gun shedfor repairs and refixing including testing the same in existing position after repair complete all as directed. Note-Parts/Items as required for repairs and replacement shall be measured and paid for separately under respectiveitems of BOQ
63S&F in repairs, electronic ignitor suitable for 70 to 400 wattHPSV/HPMV street light fittings all as specified and as directed.
64S&F in repairs, ballast, heavy duty, copper wound,SP 230 Volts, 50 Hz suitable for HPSV/MH 250 Watt all as specified and as directed.
65S&F in repairs, ballast, heavy duty, copper wound,SP 230 Volts, 50 Hz suitable for HPSV/MH 150 Watt all as specified and as directed.
66S&F in repairs, High Pressure Sodium Vapour lamp/metal halide lamp, tubular type of capacity 250 watt, all as specified and as directed.
67S&F in repairs, High Pressure Sodium Vapour lamp/metal halide lamp, tubular type of capacity 150 watt, all as specified and as directed.
68S&F in repairs, capacitor of size 10/20 mfd 220 Volt, all as specified and as directed.
69S&F in repairs, capacitor of size 33 mfd 220 Volt, all as specified and as directed.
70S&F in repairs, bracket for street light, made out of GI pipe, medium grade of suitable size (40 mm dia and 1.2 mtr long), bent to shape, fixed with and including necessary heavy duty clamps of suitable size including painting the clamps with two coats of synthetic enamel paint over a coat of primer all as specified and as directed.
71Taking down old unserviceable street light/metal halliedfittings fromstreet light poles of any type/gun shed& fixing only street/flood light fittings of any capacity/type including connection from junction box/OH line to fittings and testing complete all as specified and as directed. Note-Street lights/flood lights will be issued under Sch"B" "FREE FOR FIXING only"
72S&F in repairs, astronomical street light timer switch electronic type with digital display suitable for Indian region longitude/latitudewith 24 Hours operation settings including single phasecontactor suitable for 10 KW complete with all accessories and prewired suitable for and including panel/pole moutingbox made out of 3mm thick CRCA sheet apoxy painted and powder coatingsingle door, outdoor typewith mounting arrangements complete all as specified and as directed.
73M&L for complete wiring to LT panel of DG Set of all connected items and replacement ofvoltmeter, ammeter,RPM & HRS meter with digital display,oil pressure gauge, oil temperature gauge, solenoid switch,LED type indicator lamp set of threeincluding CT PT for 3 phase amperemeterupto capacity of 60 Amp including taking down old wiring and voltmeter, ammeter,RPM & HRS meter with digital display,oil pressure gauge, oil temperature gauge, solenoid switch,LED type indicator lamp set of threecomplete all as specified and directed.
74M&L for 1100 volts grade, heavy duty, multi stranded aluminium conductor cable, PVC insulated, served with inner sheathing of PVC tape and overall PVC sheathed in service connection flat/circular cable of sizes 4 Sqmm 2 core laid and jointed in position including taking out existing service cableall as specified and directed.
75M&L for 1100 volts grade, heavy duty, multi stranded aluminium conductor cable, PVC insulated, served with inner sheathing of PVC tape and overall PVC sheathed in service connection flat/circular cable of sizes 6 Sqmm 2 core laid and jointed in position including taking out existing service cableall as specified and directed.
76Disconnecting electric and water supply connection of centrifugal pump of any capacity for repairs such as cleaning, servicing, repair of leakage/ unserviceable parts any type and reconnecting all electric and water supply connections and testing complete all as specified and directed.Note : Cost of repair, servicing and spare parts shall be included in the quoted rate.
77M&L for filter media plastic round pieces which is use in fabrication tank to settled down bacteria in itcomplete all as specified and as directed.
78Cleaning, checking and servicing of Aerobic tank open well of size 5 mtrdia and 12 mtr depth, disposal of wastage away from STP area andnecessary connected works for proper working system complete all as specified and as directed.
79Cleaning, checking and servicing of collection sump of size 5 mtrdia and 12 mtr depth, disposal of wastage away from STP area andnecessary connected works for proper working system complete all as specified and as directed.
80Cleaning, checking and servicing of equilization tank of size 13 mtrdia and 3 mtr height, disposal of wastage away from STP area andnecessary connected works for proper working system complete all as specified and as directed.
81Cleaning, checking and servicing of chamber and Fab - Itank of size 5 mtrdia and 6 mtr height, disposal of wastage away from STP area andoutgoing pipe net and to stop flow of filter media from fabrication tank to tube settler tank complete all as specified and as directed.
82Cleaning, checking and servicing of chamber and Fab - IItank of size 5 mtrdia and 6 mtr height, disposal of wastage away from STP area andoutgoing pipe net and to stop flow of filter media from fabrication tank to tube settler tank complete all as specified and as directed.
83Cleaning, checking and servicing of sludge tank of size 2mtr x 2mtr x 5mtr depth, disposal of wastage away from STP area andoutgoing pipe net and necessary connected works for proper working system complete all as specified and as directed.
84Cleaning, checking and servicing of sludge sump, tube settler tank and resetelling the tube setter tank of size 6.5mtr dia and 5 mtr height, disposal of wastage away from STP area andoutgoing pipe net and necessary connected works for proper working system complete all as specified and as directed.
85Cleaning, checking and servicing of Primary, secondary & Filter tank of size 10mtr x 6mtr x 3mtr height, disposal of wastage away from STP area andoutgoing pipe net and necessary connected works for proper working system complete all as specified and as directed.
86Taking down sludge motor of 40 HP from existing location to workshop for windingand servicing of sludge pump and after repair testingand fixing the motor at the existing location and connect to sludge line after checking of servicibility, checking of valve, any type leakageand servicing of centrifugal machine all as specified and as directed.
87Thorough checking and servicing of pressure sand filter and pressure activated carbon filter complete all as specified and as directed.
88M&L for hand trolley of mild steel single hand wheel barrow rectangular shape, rust proof, two wheel contrationall as specified and as directed.
89S&F in repairs, PVC flexible hose pipe 100 mm bore all as specified and as directed.
90M&L for removal of blockage and leakage of pipe line, checking and servicing from sludge sump to sludge tank to centrifugal pump set, taking down and refixing of pipe line after clearing the blockage of pipe line in STP area andnecessary connected works for proper working systemall as specified and as directed.
91Repair/servicing of pressure pump any type and capacity completeall as specified and as directed.
92S&F in repairs, Exide Xpress, 200AHBattery, 12 voltsall as specified and as directed Make : Exide Model FXPO-XP2000 or equivalent model in Amco/Nicco/Amaron
93Taking down from site or collectingfrom E/M yard, unserviceable (burnt) ceiling fan, 1200 mm sweep, any make, with blades, transporting to local workshop, opening, cutting and taking out complete copper winding, cleaning with kerosene oil /diesel/ terpentine oil and dried out, rewindingwith new super enamelled copper wire of suitable size and gauge and number of turns as recommended by the respective manufactures, varnishing and heating the winding including providing paper insulation (cuff/strip type) replacing unserviceable providing paper insulation (cuff / strip type) replacing unserviceable / missing spare (bush, bearing, capacity shackle insulator, canopy, nuts, bolts, earthing, screw, upper, socket, CI block , quarter /split pin (top & bottom) , lock nut etc) fixing the stator in rotor properly aligned and resembling ensuring right DOR, speedy and noiseless running and depositing in E/M yard and hanging at site in position complete all as directed by Engr-in- charge. Note : Bush, bearing, capacitor, and canopy, shackle insulator with nuts, bolts and sockets shall be measured and paid for separately as supply only but fixing in repairs/replacement is included in this items
94All as per serial item No 93, but ceiling fan 1400 mm sweep
95All as per serial item No 93, but exhaust fan 300 mm sweep
96All as per serial item No 93, but exhaust fan 450 mm sweep
97All as per serial item No 93, but Wall mounted fan/table fan/cabin fan /Padestal fan
98All as per serial item No 93, but air circulating wall mounted fan above 450 mm upto 600 mm sweep
99Taking down from siteor collecting unserviceable ceiling fan of any sweep and make from E/M yard, transporting to local wksp, cleaning external portionwith washing soda for removing oily stain, opening and cleaning internal portion with kerosene oil, drying it out, oiling / greasing properly, replacing unserviceable bearing / bush / rubber bush for arm with nuts & clamp / flexible wire and reassembling ensuring speedy and noiseless run and hanging the same at site complete all as directed. Note :- (i) Spares if required shall be measured and paid separately under respective items as supply only, however fixing in repairs/replacement is deemed to be included in this item.(ii) Repairs to winding is not included in this item.
100Taking down from siteor collecting unserviceable exhaust fan of any sweep and make from E/M yard, transporting to local wksp, cleaning external portionwith washing soda for removing oily stain, opening and cleaning internal portion with kerosene oil, drying it out, oiling / greasing properly, replacing unserviceable bearing / bush / rubber bush for arm with nuts & clamp / flexible wire and reassembling ensuring speedy and noiseless run and hanging the same at site complete all as directed. Note :- (i) Spares if required shall be measured and paid separately under respective items as supply only, however fixing in repairs/replacement is deemed to be included in this item.(ii) Repairs to winding is not included in this item.
101Supply only bush, suitable forceiling fan /exhaust fan of any sweep complete all as specified and as directed.
102Supply only ball bearing (No 6201,6202,6203 or 6204) suitable for 1200 / 1400 mm sweep ceiling fan complete all as specified and as directed.
103Supply onlyball bearing (No 6201,6202,6203 or 6204)suitable for 300 / 400/ 450 mm sweep exhaust fan complete all as specified and as directed.
104Supply only ball bearing (No 6201,6202,6203 or 6204) suitable for 400 / 450 / 600 mm sweep wall mounted/cabin/table fan complete all as specified and as directed.
105Supply only capacitor 2.50 mfd to 3.15 mfd complete all as specified and as directed.
106Supply only capacitor 4 mfd, for exhaust fan/wall mounted fans etc of 300mm/450mm/600 mm sweep complete all as specified and as directed.
107Supply only canopy for ceiling fan (top and bottom), any size & make complete all as specified and as directed.
108Supply only MS fan rod andclamps with rubber real including nuts and bolts, split pin, suitable for ceiling fan 1200 / 1400 mm sweep complete all as specified and as directed.
109Supply only ceilingfan blade set of 3 piece of aluminium sheetsuitable for 1200 mm sweep, matching with the existing colour brown / white etc. complete all as specified and as directed.
110Supply only ceiling fan blade set of 3 piecemild steel sheet, suitable for 1400 mm sweep matching with the existing colour brown / white etc. complete all as specified and as directed.
111M&L for preparation of surfaces and spray painting to ceiling fans (in situ) ofany type , size and make, with super enamelled heat resistant synthetic white paint duly filling the cavities with filler and re-writing the MES number in black paint in appropriate size and shape all as specified and as directed.
112M&L for preparation of surfaces and spray painting to exhaust fans (in situ) ofany type , size and make, with super enamelled heat resistant synthetic white paint duly filling the cavities with filler and re-writing the MES number in black paint in appropriate size and shape all as specified and as directed.
113M&L for preparation of surfaces and spray painting to wall mounted fans/air circulating fans, pedestal fans etc (in situ) ofany type , size and make of with super enamelled heat resistant synthetic white paint duly filling the cavities with filler and re-writing the MES number in black paint in appropriate size and shape all as specified and as directed.
114Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fittings such as switches, ceiling roses, pendants, regulators, sockets etc but excluding DBs, light fittings etc andmaking good disturbed surfaces of walls, floors etc. and matching with existing surface all as specified and as directed.
115M&L for point wiring complete with 1.5 Sqmm single core, multistranded, copper conductor, fire retardant, PVC insluated and unsheathed cable 650/1100 volts grade,conforming to IS-694 1990,drawn through and including casing capping 25mm/32 mm width with all accessories as specified with modular cover plate with frame and modular metal fluxboxes, blank platefor mounting fittings & fixing like switches sockets and fan regulators etc. including copper earth continuity wire for PVC insulated of size 1.5 Sqmm for one light/fan point controlled by oneway switchcomplete all as specifed and as directed.
116All as per serial item No. 115 above but for one 3 pin socket outlet, 5 Amps on same board with other switches
117All as per serial item No. 115 above but for one 3 pin socket outlet, 5 Amps on independent board but below the switch board of light points in the same vertical plane, with cables, 1.5 sq. mm size
118All as per serial item No. 115 above but for one lightpoint controled by two, two way switch
119All as per serial item No. 115 above but for one bell point controlled by one bell push
120All as per serial item No. 115 above butwith 4.0 Sqmm copper conductor cable for socket outlet 15 Amps
121S&F modular switch, piano type, 5 Amp, single pole, one way, flush type, white or ivory, ISI marked all as specified and as directed.
122S&F modular switch, piano type, 15 Amp, single pole, one way, flush type, white or ivory, ISI marked all as specified and as directed.
123S&F modular switch, piano type, 5 Amp, single pole, two way, flush type, white or ivory, ISI marked all as specified and as directed.
124S&F modular bell push, piano flush type, one way, ISI marked all as specified and as directed
125S&F modular socket outlet, 3 pin, 5 Amps, flush type, ISI marked all as specified and as directed
126S&F modular socket outlet, 6 or 5 pin & 15 Amps, flush type, ISI marked all as specified and as directed
127S&F electric door bell, 230 V, multi music type, ISI marked all as specified and as directed
128S&F ceiling rose, surface bakelite, 65 x 20 mm, two to three terminals all as specified and as directed
129S&F modular fan regulator, electronic step type, humming free, ISI marked all as specified and as directed.
130S&F in repairs, LED security light for buildings with single piece new generation energy saving and environmental friendly long life LED, 35 W made up of pressure die cast aluminium housing with acrylic covers as diffuser with IP66 protection and impact resistance of IK07 andall acessoriesincluding one bracket made of light gradeGI Pipe 32 mm dia, 1.5 mtr long fixed to wall/ pole with two clamps made out of mild steel flat iron40 mm x 5 mm and connected to nearest electric supply with and including three core 1.5 sqmm aluminium conductor cable of suitable lengthcomplete all as specified and as directed.Make of LED: Havells Professional luminaries Cat Part No ENDURACITYLITEPLATPLUSSL35WLED757SASYBOPCequivalent model of make Philips / GE/ Crompton/ Century LED/Halonix
131S&F in repairs, ultra slim, edge-lit LED ceiling panel light, 22 W, 220 V AC, white, powder coated aluminium housing, recess/surface mountingall as specified and as directed. Make : Havells Cat Part No LHEBGAP71Z1W022 or equivalent model of make Philips /GE/ Crompton/ Luker/ Halonix/Century LED ltd/SYSKA .
132S&F in repairs, LED tube light fitting withsingle LED tube 1x20 W, 230V, four feet long, energy efficient, direct surface mounted, decorative with aluminium extrusion with PC diffuserincluding connecting up with twin core PVC insulated copper conductor cable of suitable size all as specified and as directed. Make : Havells Professional luminaries Cat Part No LUMILINEPLUSBS20WLED865SPCS or equivalent model of make Philips /GE/ Crompton/ Luker/ Halonix/Century LED ltd/SYSKA .
133S&F in repairs, bathroom/mirror light LED tube light fitting withsingle LED tube 1x10 W, 230V, energy efficient, direct surface mounted, decorative with aluminium extrusion with PC diffuserincluding connecting up with twin core PVC insulated copper conductor cable of suitable size, all as specified and as directed.Make : Havells Professional luminaries Cat Part No LUMILINEPLUSBS10WLED865SPCSS or equivalent model of make Philips /GE/ Crompton/ Luker/ Halonix/Century LED ltd.
134S&F in repairs, surface mounted, decorative round plastic bulk head LED luminaire comprising of high brightness LED"s, IP54 protection, 10 watt, 6000K complete fitting with LED lamp, driver and all other fixing accessories including electric connection connecting with using flexible copper wire twin core upto ceilling rose/connector all as specified and as directed.Make : SYSKA Cat Part No SSK-BHP-1201 or equivalent model of make Philips /GE/ Crompton/ Luker/ Halonix/Century LED ltd/Havells
135S&F in repairs, standard PVC batten/angle holder including LED bulb of 10 watts all as specified and as directed.
136S&F in repairs, sheet metal enclosure (Factory made), double door shutter type for distribution board (when MCBs are to be used) single pole and neutral 240 volts, 12 way,protection class IP-42, suitable for fixing MCBs,Isolators etc,confirming As per IEC 61439-3,suitable for flush mounting and surface mounting,with 200 Amps rated copperbusbar,withNeutral bar,Earthbar and cable lies for cable managment,fully shrouded,Neutral bars,prefittes masking sheet complete all as specified and as directed.
137All as per serial item No 136 butsingle pole and neutral 240 volts,8 way.
138All as per serial item No 136 butsingle pole and neutral 240 volts,6 way.
139All as per serial item No 136 buttriple pole and neutral 240 volts,4 way.
140S&F in repairs, sheet metal enclosure, single pole and neutralwith 2 pinand earth plug and socket complete with and including single pole, 20 Amps MCB, 240V (for AC/Geyser) all as specified and as directed.
141M&L for sub main wiring with 2 runs of 4 sqmm, single core, PVC insulated & unsheathed cable, conforming to IS-694, 1100 volts with copper conductor, multi stranded, drawn in and including suitable size casing / caping (ISI marked) with all accessories such as Tees, Elbows, junction box etc as requied alongwith one run of 4 sqmm single core PVC insulated & unsheathed copper conductor as continuous earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and any type of casing/caping, complete all as specified and as directed.Note : Three runs of 4 Sqmm cable and one run of PVC casing/caping will be measured as one Rm unit.
142All as per serial item No 141 but 2 runs of 6 sqmm cable and 1 run of 6 sqmm continuous earth wire
143All as per serial item No 141 but 2 runs of 10 sqmm cable and 1 run of 10 sqmm continuous earth wire
144S&F in repairs, MCBs, SP 6 to 32 Amps, 10 KA, IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed.
145S&F in repairs, MCB, SPN 40 to 63 Amps, 10 KA,"C" curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and directed.
146S&F in repairs, MCB, TPN 63 Amps, 415 volts, 10 KA,"C" curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed.
147M&L in repairs/replacement for earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6.3 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting to the GI wire 4 mm dia , by means of nut bolts, check nuts and washer of the GI . Earth wire connected upto main earth point/DBs alongwith 15mm dia GI pipe, medium grade,including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4)cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh andearth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion.
148S&F in repairs/replacement, tamper proof electronic energy meter tamper proof digital LED display, single phase, 220v, suitable for 60A current rating capacity with FRP box with locking arrangement all as specified and as directed.
149S&F in repairs/replacement,tamper proof electronic energy meter, tamper proof digital LED display, three phase, 415v, suitable for 0-100A current rating capacity with suitable raing CTs and FRP box with locking arrangement all as specified and as directed.
150S&F in repairs, top plug, 3 Pin, 5 Amps all as specified and as directed.
151S&F in repairs, top plug, 3 Pin, 15 Amps all as specified and as directed.
152S&F in repairs, PVC copper conductor wire of size 1.5 sqmm, multi-stranded, unsheathed all as specified and as directed.
153S&F wall mounting fan, 450 mm sweep with all accessoriescomplete & testing at site including taking down old wall mounted ceiling fan and depositing in MES storeyard all as all as specified and as directed.
154Taking down electirc water heater (geyser) of any type/capactiy for repairs, dismantling the accessories carefully after disconnecting the water/electirc connection and transporting to workshop(if required) for repairs and refixing the same inoriginal position after repairs and connecting up the water/electric connections including testing complete all as specified and as directed.Note : Replacement of unserviceable parts shall be measured and paid seperately.
155S&F in repairs, heating element, triangular or square type, 1500watts, 230 volts, suitable for geyser and as per approved sample all as specified and as directed.
156S&F in repairs, heating element, triangular or square type, 2000watts, 230 volts, suitable for geyser and as per approved sample all as specified and as directed.
157S&F in repairs, heating element triangular/ square headed with inbuilt thermocut switch/ thermostat of1.5/2.0 KW, suitable for 25/50 litre capacity geyser existing at site all as specified and as directed.
158S&F in repairs, thermostat, auto cut with thermal setting upto 80 degree centigrade, 230 Volts, suitable for existing geysor(25/35/50 lit) of various capacitiesall as specified and as directed.
159S&F in repairs, inner copper, water storage tank of25 ltr capacity geyser existing at site all as specified and as directed.
160S&F in repairs, inner copper, water storage tank of50 ltr capacity geyser existing at site all as specified and as directed.
161S&F in repairs, psyphon assembly suitable for 25 ltr capacity geyser existing at site all as specified and as directed.
162S&F in repairs, psyphon assembly suitable for 50 ltr capacity geyser existing at site all as specified and as directed.
163S&F in repairs, aperture plate assembly complete suitable for 25 Ltrs capacity geyers existing at site all as specified and as directed.
164S&F in repairs, aperture plate assembly complete suitable for 50 Ltrs capacity geyers existing at site all as specified and as directed.
165S&F in repairs,15mm bore dia, non return valve, cast copper alloy suitable for geyser all as specified and as directed.
166S&F in repairs, 15mm bore dia, pressure release valve, cast copper alloysuitable for geyser all as specified and as directed.
167S&F glass wool in geyser of 25/50 litre capacity all as specified and as directed.
168S&F indicator, pamp red/green for geyser all as specified and as directed.
169S&F drain plug for 25/50 litre capacity geyser all as specified and as directed.
170S&F in repairs, 15mm bore dia, stop valve,fancy type, cast copper alloy, chromium plated, screwedfor iron pipe and fixed all as specified and as directed.
171M& L for mild steel hold fast/fasteners fixing to wall, suitablefor hanging of geyser of any capacity including making good surface with cement mortar 1:4 complete all as specified and as directed.
172S&F in repairs, heat resistant, PVC, flexible connection pipe, 450 mm long, suitable for 15 mm dia pipe with brass creamed nipple and nuts, heavy duty pressure grade 6 Kg/cm2 all as specified and as directed.
173Taking out the old thermostat/heating element and refixing the same after descaling/ cleaning and making electrical connection andcalibrating/adjusting to a temperature rating as per manufacturer recommendation all as specified and as directed..
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail