Military Engineer Services-MES has published Repair And Maintenance Of Internal Electrification To Certain Md And Otm Accn At 2 Afsb Mysore Repair And Maintenance Of Internal Electrification To Certain Md And Otm Accn At 2 Afsb Mysore. Submission Date for this Tender is 24-12-2021. Electrification Work Tenders in AGE I AF CHIMNEY HILLS BANGALORE Karnataka. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Taking down carefully aluminium point wiring light, fan, sockets or power complete from surface wiring or from concealed wiring without disturbing concealed conduit including fittings such as ceiling rose, light fittings of any type, fan regulators etc and making good to the disturbed surfaces wall ceiling floors to match existing surfaces. |
2 | M&L for Point wiring with 1.5 sqmm, single core ,PVC insulated, unsheathedFRLS cable, 1100 volts grade, IS -694marked, with multi stranded copper conductor and earthcontinuity copper conductor cable of same size as in phase/neutral and connected to common earth dolly drawn through and including PVC casing and caping of suitable size alongwith fittings and accessories, fixed /laid on wall/beam/coloumn and also incl steel terminal box embedded in wall suitable for mounting of switches sockets regulators etc complete for one light point, controlled by one switch 5 amps one way one fan point controlled by one switch and regulator or one socket outlet point three pin 5 amps. |
3 | All as per item No.2 above but with 2.5 sqmm cable for socket outlet 3 pin 15 Amps on independent board incl 2.5 sqmm PVC insulated copper conductor cable as earth continuity conductor |
4 | All as per item No.2 above but one staircase light control by 2 Nos two way switch |
5 | S & F in repair switch piano 5 Amps one way flush type |
6 | S & F in repair switch piano 5 Amps two way flush type |
7 | S & F in repair switch piano 16 Amps one way flush type |
8 | S&F in repair socket, 2 in 1, 3 pin 5 Amps flush type |
9 | S&F in repair socket 2 in l, 3 pin 6 Amps and 3 pin 15 Amps flush type. |
10 | S&F in repair Call bell (Ding Dong Type), AC 230 VoIt, single pole 230V |
11 | Supply and fix in repair bell push 5 Amps single pole |
12 | Supply and fix in repair electronic fan regulator, AC230 V, dimmer type |
13 | Supply and fix in repair fan regulator AC230 V electronic step type |
14 | Supply and fix in repair ceiling rose 3 terminals |
15 | S&F in replacement regal battten T8 1X22 watt complete with all accessories prewired suitable for LED tube Make:HavellsModel No REGALBATTENT8UPTO1X22WSSBSWH or equivalent in Philips/Crompton/Bajaj |
16 | S&F in replacement crystal glass LED tubelight (double side connection) with high efficacy suited for installation in existing T8 fiiting with G13 lamp holders Make:HavellsModel No CRYSTAL1213T8DSTL20WLED865SGLASS or equivalent in Philips or Bajaj |
17 | S&F in replacement surace and wall mounted LED batten with aluminium housing & integrated electronic driver of 10 watt (2 ft)Make:Havells Model No LIMELINEPLUSBS10WLED865SPCSS or equivalent in Crompton & Philips |
18 | S&F in replacement Surface mounted LED downlight with white powder coated polycarbonate housing and pressure die-cast heat sink having high efficacy of 10 watt Make:HavellsModel No INTEGRANEOSURFACEDLS10WLED830S or equivalent in Philips/Crompton/Bajaj |
19 | S&F in replacement LED luminaire glare free symmetrical illumination suitable for Amstrong/Grid ceiling of 24 watt (2 ft X 2ft) Make:HavellsModel No VENUSNEOHE2X2PLR18-42WLED865MOD & LEDDRIVER36V24WS or equivalent in Philips/Crompton/Bajaj |
20 | S & F MCB SP 6 to 32 Amps10 KA, "B" Series, 240V, 50HZ, ISI Marked . |
21 | S & F MCB SPN 6 to 32 Amps10 KA, "C" Series, 240V, 50HZ, ISI Marked . |
22 | All as per item No. 21 above but MCB SPN 40 Amps |
23 | All as per item No. 21 above but MCB SPN 63 Amps |
24 | S & F MCB TP 40 Amps 10 KA,"C" Series, 415V, 50HZ, ISI Marked |
25 | S & F MCB TP 63 Amps 10 KA, "C" Series, 415V, 50HZ, ISI Marked |
26 | Taking down existing Ceiling fan/Wall Mounting fan from its location and Rewinding of fan motor with super enameled copper winding wire of similar gauge and weight of the original winding insulating with class B, varnishing, drying etc complete, including taking down from its location and refixing the same after carrying out the repair for the following: 1200 mm sweep ceiling fan/450 mm sweep wall mounting fan |
27 | All as per item No. 26 above but for exhaust fan 300 mm sweep |
28 | Taking down geyser assembly 25/35/50 ltrs capacity of any type and detecting and rectifying leakage of inner tank by copper bracing and testing for leakage, assembly and refixing back incIudng reconnecting Inlet outlet water connections.Note: a) Soldering and minor spares are included in the quoted rate.b) Heating element and thermostat are measured and paid seperatly |
29 | S & F in repair heating element 2 KW of any type suitable for Geyser |
30 | S & F in repair thermostat assembly stud type suitable to adjust the temp upto 70 Degree Celsius |
31 | S & F in replacement fan condenser 2.5 MFD suitable for AC 240 V 50 HZ |
32 | S & F in repair MCB distribution board SPN 4 way single door 240V powder coated with 200 Amps rated bus bar neutral link etc. |
33 | All as per item No. 32 above but SPN 8 ways |
34 | All as per item No. 32 above but TPN 4 ways |
35 | All as per item No. 32 above but TPN 6 ways |
36 | M&L spray painting of ceiling fan, Exhaust fan, Wall Mounting, Pedastal fan of any sweep including diconnecting, taking down, scrapping the old paint, filling cavities and spray painting with one coat of synthetic enameled white paint, numbering with black enamel paint, refixing in position connecting testing complete all asspecified and as directed. |
37 | M&L in replacement submain wiring with PVC insulated, single core, multi stranded, 1100 volts grade unsheathed copper conductor cable in and including PVC Conduit/Casing capping with accessories fixed on wall /ceiling with GI screws complete with 2 runs of 2.5 sq mm and one run of 2.5 sqmm for earth continuity conductor all as directed. |
38 | All as per item No. 37 above but 3 runs of 4 sqmm |
39 | All as per item No. 37 above but 3 runs of 6 sqmm |
40 | Supply and fix Modular switch 1 way 6A,1 module complete all as specified and as directed. |
41 | Supply and fix Modular switch 1 way 16A,1 module complete all as specified and as directed. |
42 | Supply and fixModular switch 2 way 6A,1 module complete all as specified and as directed. |
43 | Supply and fix Modular Bell push 6A 1 moduler |
44 | Supply and fix Modular socket 6A 2 /3 pin combined 2 module |
45 | Supply and fixModular socket 16A 2 /3 pin combined 2 module complete all as specified and as directed. |