Tender For Item Rate Contract For Repair / Maint Of Lt Distribution System And Allied Works In North And South Area Under Age E / M Elect Supply At Ge ( U ) E / M Meerut Cantt Tender For Item Rate Contract For Repair / Maint Of Lt Distribution Syste, Meerut Cantt-Uttar Pradesh

Military Engineer Services-MES has published Tender For Item Rate Contract For Repair / Maint Of Lt Distribution System And Allied Works In North And South Area Under Age E / M Elect Supply At Ge ( U ) E / M Meerut Cantt Tender For Item Rate Contract For Repair / Maint Of Lt Distribution Syste. Submission Date for this Tender is 28-12-2021. Electrical Maintenance Tenders in Meerut Cantt Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

30132149
Corrigendum : Tender For Item Rate Contract For Repair / Maint Of Lt Distribution System And Allied Works In North And South Area Under Age E / M Elect Supply At Ge ( U ) E / M Meerut Cantt Tender For Item Rate Contract For Repair / Maint Of Lt Distribution Syste
Open Tender
Indian
Uttar Pradesh
Meerut Cantt
28-12-2021

Tender Details

Tender For Item Rate Contract For Repair / Maint Of Lt Distribution System And Allied Works In North And South Area Under Age E / M Elect Supply At Ge ( U ) E / M Meerut Cantt Tender For Item Rate Contract For Repair / Maint Of Lt Distribution System And Allied Works In North And South Area Under Age E / M Elect Supply At Ge ( U ) E / M Meerut Cantt

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-Dec-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-12-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 40 Lakhs /-

BOQ Items

TENDER FOR ITEM RATE CONTRACT FOR REPAIR/MAINT OF LT SWITCHGEARS ANDALLIED WORKS IN NORTH AND SOUTH AREA UNDER AGE E/M ELECT SUPPLY AT GE (U) E/M MEERUT CANTT
Sl. No. Item Description
1Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundations etc. or for shafts, well cess pits, manholes,pier holes, laying of pipe and cables etc. but not exceeding 10 sqm on plan including dressing/trimming sides and levelling/grading & ramming bottom of excavation and getting out in soft/loose soil complete all as specified.
2Returning ,filling in , including spreading , levelling , watering and well ramming in layer not exceeding 25 cm thick insoft/loose soil complete all as specified.
3Removing excavated material ( soils) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
4M&L fly ashold sizebricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection all as specified.
5Material and labour for river sand, unwashed and screened dry ) for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete as specified and directed . (Note:Punned thickness shall be measured for the purpose of payment)
6Taking down old existing LT cable of any size and finding out fault in cable and reparing the cable by providing cable Joints and making the cable line functional and relaying in the cable in its original locations by providing retrived bricks and sand including necessary earthworkcomplete all as specified and directed. Note:- Cable joints required shall be paid seoarately unde relevant item as supplied only.
7Taking out unserviceable cable and Supplying, laying or fixing, jointing and testing LT under ground electric power cableCrossed linked polyethylene ( XLPE Cable)insulated, galvanised steel strip or wire armoured,ISI-7098 marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of240 sqmm3 1/2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc.( Excavation, earth work, sand cushioning, protection bricks/ tiles/ block,clamps, nuts , bolts, washers andpipe shall be measured and paid separately under appropriate items ).
8Taking out unserviceable cable and Supplying, laying or fixing, jointing and testing LT under ground electric power cableCrossed linked polyethylene ( XLPE Cable)insulated, galvanised steel strip or wire armoured,ISI-7098 marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of150 sqmm3 1/2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc.( Excavation, earth work, sand cushioning, protection bricks/ tiles/ block,clamps, nuts , bolts, washers andpipe shall be measured and paid separately under appropriate items ).
9Taking out unserviceable cable and Supplying, laying or fixing, jointing and testing LT under ground electric power cableCrossed linked polyethylene ( XLPE Cable)insulated, galvanised steel strip or wire armoured,ISI-7098 marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of120 sqmm3 1/2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc.( Excavation, earth work, sand cushioning, protection bricks/ tiles/ block,clamps, nuts , bolts, washers andpipe shall be measured and paid separately under appropriate items ).
10Taking down existing unserviceable pipe and M&L 80mm nominal bore mild steel galvanised water tubing, light grade with all fittings like bends, elbows, Tee, reducers, sockets, unions etc laid in trenches/ fixed to walls / poles / laid in floorsfor protection of GI earth strip/ under ground cablecomplete all as specfied and directed. Note: Excavation, RF&R, removal of surplus soil and mild steel clamps with nuts and bolts shall be measured separately)
11M&L for auguring of hole suitable for passing 80mmbore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified. Note: Pipe shall be measured and paid separately under appropriate items and any damage to existing cables of anytype shall be made good by the Bidder without any extra cost to department.
12Supplying, installing, commissioing and testing of factory made ,CPRI approved ,LT switchgear panel board of size 1200mmx1000mmx500mm (min) , IP-54 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) ,1000 Amps aluminiumbus bars 4 pole , duly insulated with heat shrinkable sleeves as per colour code supported on epoxy insulators , having independent compartment for insulated bus bar, incoming feeder and each out going feeder i.e cubical type, made out of 3.15mm thick CRCAsheet, rigid mild steel angle iron frame of 50mmx50mmx6mm with 600mm long extended legs grouting in PCC 1:3:6 type C2block ofsize 300mmX200mmx300mm, duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front and back openable doors with proper locking arrangements for dust and vermin proof ,complete including suitable size cable alley,lugs , cable glands,common earth bus bar of GI strip 32x6mm at bottomand making connections with MCCB spreaders,/ wiring with suitable size SC PVC insulated copper conductor cable, locking arrangements 65mm size and lock with keys, earthwork and excavationcomprising of the followings and specified hereafter:-
13Incoming:-
14FP, MCCB,Adjustable thermalmagnetic release , 50 KA, 630 Amps, 415V ,-01 No.
15Aluminium busbars suitable for 1000 Amps, 3 Phase, 4 wire system,fixed on insulators -01 Set
16Digital ampere meterwith CT ( for each Phase) square type with selector switch -01 No.
17Digital Volt meter square type with selector switch-01 No.
18LED type indication lamps ( R-Y-B) with holder panel mounting type complete all as specified. -01 No.
19Outgoing:-
20FP, MCCB, Adjustable thermalmagnetic release , 16 KA, 400 Amps, 415V ,-02 Nos.
21FP, MCCB, Adjustable thermal magnetic release, 16 KA, 250 Amps, 415V ,-02 Nos. Note- Plateform shall be made as per Sketch "A" enclosed. Drawings shall be got appoved before procurement
22Supplying, installing, commissioing and testing of factory made ,CPRI approved ,LT switchgear panel board of size 1000mmx800mmx400mm (min) , IP-54 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) ,600 Amps aluminiumbus bars 4 pole , duly insulated with heat shrinkable sleeves as per colour code supported on epoxy insulators , having independent compartment for insulated bus bar, incoming feeder and each out going feeder i.e cubical type, made out of 3.15mm thick CRCAsheet, rigid mild steel angle iron frame of 50mmx50mmx6mm with 600mm long extended legs grouting in PCC 1:3:6 type C2block ofsize 300mmX200mmx300mm, duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front and back openable doors with proper locking arrangements for dust and vermin proof ,complete including suitable size cable alley,lugs , cable glands,common earth bus bar of GI strip 32x6mm at bottomand making connections with MCCB spreaders,/ wiring with suitable size SC PVC insulated copper conductor cable, locking arrangements 65mm size and lock with keys, earthwork and excavationcomprising of the followings and specified hereafter:-
23Incoming:-
24FP, MCCB, Adjustable thermalmagnetic release , 36 KA, 400 Amps, 415V ,-01 No.
25Aluminium busbars suitable for 600 Amps, 3 Phase, 4 wire system, 01 Set
26Digital ampere meterwith CT ( for each Phase) square type with selector switch -01 No.
27Digital Volt meter square type with selector switch-01 No.
28LED type indication lamps ( R-Y-B) with holder panel mounting type complete all as specified. -01 No.
29Outgoing:-
30FP, MCCB, Adjustable thermalmagnetic release setting , 35 KA, 250 Amps, 415V ,-02 Nos.
31FP, MCCB, Adjustablemagnetic release setting , 36 KA, 160 Amps, 415V ,-02 Nos. Note- Plateform shall be made as per Sketch "A" enclosed. Drawings shall be got appoved before procurement
32Supplying, installing, commissioing and testing of factory made ,CPRI approved ,LT switchgear panel board of size 1000mmx800mmx400mm (min) , IP-54 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) ,400 Amps aluminiumbus bars 4 pole , duly insulated with heat shrinkable sleeves as per colour code supported on epoxy insulators , having independent compartment for insulated bus bar, incoming feeder and each out going feeder i.e cubical type, made out of 3.15mm thick CRCAsheet, rigid mild steel angle iron frame of 50mmx50mmx6mm with 600mm long extended legs grouting in PCC 1:3:6 type C2block ofsize 300mmX200mmx300mm, duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front and back openable doors with proper locking arrangements for dust and vermin proof ,complete including suitable size cable alley,lugs , cable glands,common earth bus bar of GI strip 32x6mm at bottomand making connections with MCCB spreaders,/ wiring with suitable size SC PVC insulated copper conductor cable, locking arrangements 65mm size and lock with keys, earthwork and excavationcomprising of the followings and specified hereafter:-
33Incoming:-
34FP, MCCB, Adjustable thermalmagnetic release , 36 KA, 250 Amps, 415V ,-01 No.
35Aluminium busbars suitable for 400 Amps, 3 Phase, 4 wire system, 01 Set
36Digital ampere meterwith CT ( for each Phase) square type with selector switch -01 No.
37Digital Volt meter square type with selector switch-01 No.
38LED type indication lamps ( R-Y-B) with holder panel mounting type complete all as specified. -01 No.
39Outgoing:-
40FP, MCCB, Adjustable thermalmagnetic release setting , 16 KA, 100 Amps, 415V ,-02 Nos.
41FP, MCCB, Adjustablemagnetic release setting , 16 KA, 63 Amps, 415V ,-02 Nos. Note- Plateform shall be made as per Sketch "A" enclosed. Drawings shall be got appoved before procurement
42Supplying, installing, commissioing and testing of LT switchgear panel board ( Kiosk) of size not less than 600mmx450mmx300mm,IP-55 (outdoor type) , 415 Volts, 50 Hz, AC supply, three phase and neutral ( 4 wire) ,200 Amps coloured horizontal tinned Aluminium bus bars , factory made out of 3.15mm thick MS sheetstructure mounted onrigid mild steel angle iron frame of 50mmx50mmx6mm with 400mm long extended legs grouting in PCC 1:2:4 type B1 of size 150mmx150mmx250mm , duly epoxy powder coated internally and externally with approved shade, rubber gasketted, hinged front double doorand back openable doors with proper locking arrangements for dust and vermin proof ,complete including adjustable thermal and fixed magnetic release MCCB 4 pole, 100 Amps, 415V, 36 KA,50 hz-01 No (incoming),suitable size cable allay,lugs , glands and making connections/ wiring with suitable size SC PVC insulated copper conductor cableall as specified.
43S&F in repairMCCB, 4 pole, 50 Hz,630 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
44S&F in repairMCCB, 4 pole, 50 Hz, 500 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
45S&F in repairMCCB, 4 pole, 50 Hz, 400 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
46S&F in repairMCCB, 4 pole, 50 Hz, 250 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
47S&F in repairMCCB, 4 pole, 50 Hz, 200 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
48S&F in repairMCCB, 4 pole, 50 Hz, 160 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
49S&F in repairMCCB, 4 pole, 50 Hz, 100 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
50S&F in repairMCCB, 3 pole, 50 Hz, 400 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
51S&F in repairMCCB, 3 pole, 50 Hz, 250 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
52S&F in repairMCCB, 3 pole, 50 Hz, 200 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
53S&F in repairMCCB, 3 pole, 50 Hz, 160 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
54S&F in repairMCCB, 3 pole, 50 Hz, 100 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
55S&F in repairMCCB, 3 pole, 50 Hz, 63 Amps, 36/27KA, rupturing capacity thermal adjustable type duly connected with copper spreader links and proper size lugs, nuts, bolts and washers for proper connections, all as specified and directed.
56Supply and fixing digital Amp Meter square flush type , 0-300 Amp with suitable CT and selector switch on existing LT feeder pillar box complete all as specified and directed.
57Supply and fixing digital Amp Meter square flush type , 0-800 Amp with suitable CT and selector switch on existing LT feeder pillar box complete all as specified and directed.
58Supply and fixing digital Volt Meter square flush type , 0-500 Volt withselector switch on existing LT feeder pillar box complete all as specified and directed.
59Supply and fixing in replacement selector switch suitable for 415 volt , 50 Hzcomplete all as specified and directed.
60Taking down unserviceable indicatorand S&F indicator LED type (R, Y, B) suitable for220 volt, 50Hz complete all as specified and directed.
61Supply and fixing in reair aluminium thimble size 25 Sqmm to 50 Sqmm complete all as specified and directed.
62Supply and fixing in reair aluminium thimble size 70 Sqmm to 120 Sqmm complete all as specified and directed.
63Supply and fixing in reair aluminium thimble size 150 Sqmm to 185 Sqmm complete all as specified and directed.
64Supply and fixing in reair aluminium thimble size 240 Sqmm to 400 Sqmm complete all as specified and directed.
65Cutting of wornout / burnt aluminium cable terminal lugs from the HT/LT cable , crimping of new aluminium cable core and fixing with transformer, Panel MCCB terminal stud including cutting/ dressing of cable,disconnecting under ground cable from over head conductor , cutting down wornout portion under ground cables of any type and size for repairs including taking out under ground cable loop from ground and making connections of restoration of electric supply complete all as specified. Note:- Excavation, earth work , taking out cable protection covers, and sand cushion and relaying the same shall be deemed included in the unit rate quoted by Contractor)
66M&L for taking down defective portion of LT panel board and refixing the same afterrepair including welding of door hinges, locking arrangement etc including complete rewiring of LT panel booard, painting two coats of synthetic enamel paintby spray painting after scrapping old painting and preparation of surface including all necessary spares like lugs, insulation tape etcand making functional voltmeter, ameter, selector switch, indicating lamps etc and writing on panel board indicating area feeding complete all as specified and directed.
67Supplying and fixing STRAIGHT THROUGH cable jointing Kit for 1100 V grade cable forcomplete with jointing material ( heat shrink type) and accessories suitable for 95 sqmm to 150sqmm 3.5 core XLPE armoured aluminkium conductor cable and testing aftre jointing complete all as specified and directed.
68Supplying and fixing STRAIGHT THROUGH cable jointing Kit for 1100 V grade cable forcomplete with jointing material ( heat shrink type) and accessories suitable for 185 sqmm to 400sqmm 3.5 core XLPE armoured aluminkium conductor cable and testing aftre jointing complete all as specified and directed.
69M&Lfor preparation of old treated steel surfaces ofLT feeder pillar box/APFC panel out door/ indoor type and applyimg one coat of synthetic enamel paint by spray complete all as specified and directed.
70Supply and fixing in repair worn out aluminium bus bar of capacity 100 Amp to 800 Amp as per existing in LT panel board fixed with nut bolt and washer, making connection with existing MCCBs, CTs etccomplete all as specfied and directed.
71M&LEarthing complete with galvanised mild steel earth plate electrode 600x600x6mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32x6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected at another end, GI earth strip encased inand including 40 mm dia GI "light grade" pipe from upper end of earth plate upto equipments,20 dia bore GI pipe "medium grade" as water pipe from earth chamber to upper edge of earth plate,GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 40mm thick precast RCC 1:2:4 type B-1, duly reinforced with 8mm dia TMT bars @ 150mm C/c and 6mm dia bars in lifting handles amd MS angle frame of angle iron 40x40x5 mm thick, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate number 3 of SSR Part I completeall as specified and directed and testing on completion. Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
72Finding out faultin any size of cable, 1100V grade to 33000V with the help of FaultTesting Vanby disconnecting of cable from both sides and making connection after fault finding and repairs upto a length of 500m complete all as specified. Note:- All the equipments, tackle, T&P, Fault finding/ testing Van etc shall be arranged by contractor at hos own cost. The rate quoted by contractor shall deem to be included and nothing extra shall be allowed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail