Indian Institute Of Technology-IITB has published Providing Power Points, Light Points In Environmental Engg. Lab And Atmospheric Chemistry And Climate Change Lab At A-17 Ground Floor, North Campus Of Iit Mandi. Providing Power Points, Light Points In Environmental Engg. Lab And Atmospheric Chemist. Submission Date for this Tender is 13-12-2021. LED Light Tenders in North campus of IIT Mandi Himachal Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
2 | Supplying and drawing 3x2.5sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
3 | Supplying and drawing 3x4 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
4 | Supplying and drawing 6x4 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
5 | Supplying and fixing 5/6 A switch modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
6 | Supplying and fixing 15/16 A switch modular switchon the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
7 | Supplying and fixing 3 pin 5/6 Asocket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
8 | Supplying and fixing 6 pin 15/16 Asocket outlet modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
9 | Supplying and fixing 3 Module Modular base & cover plate on existing modular metal/PVC boxes etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
10 | Installation of exhaust fan up to 300 mm sweep in the existing opening, including making good the damage, connection, testing, commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
11 | Supplying and fixing 8 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
12 | Supplying and fixing 12 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
13 | Supplying and fixing single pole 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of Single pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
14 | Supplying and fixing 40 A rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
15 | Supplying and fixing 63 A rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
16 | Supplying and installing 150 mm width X 50 mm depth X 1.6 mm thickness size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
17 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of up to 35sq mm size on cable tray (clamped with 1mm thick saddle) as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
18 | Supplying and making end termination with brass compression gland and aluminium lugs for 3 X 10 sq. mmsize of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
19 | Supplying and fixing 3 Module PVC box in open surface/wall asrequired as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
20 | Supplying of 3 Core x 10 Sq. mm XLPE insulated armoured copper cable as per IS7098 (Part 1) 1988 as requiredas per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
21 | Supplying and fixing of 25 mm size of medium class PVC Casing-Capping along with accessories in surface as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
22 | Supplying of 300 mm sweep metal body exhaust fanas per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy