Border Security Force-BSF has published Shifting Of 315 Kva Transformer From Ftr Hq Gujrat To Dantiwada Campus Alongwith Installation , Testing And Commissioning At Bsf Campus Dantiwada 109Bn ( Now 123 Bn ) Bsf Under Shq Bsf Gandhinagar Shifting Of Transformer And Installation , Testing And. Submission Date for this Tender is 08-12-2021. Transformer Supply Tenders in At BSF CAMPUS DANTIWADA Gujarat. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
2 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
3 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
4 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required |
5 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
6 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
7 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. A) 3½ X 240 sq. mm (62mm) |
8 | Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
9 | Providing and laying in position cement concrete 1:3:6 (1 cement : 2 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc including form work etc as required. |
10 | Providing 12 mm thick cement plaster of mix 1:6 (1 cement : 6 fine sand) at all levels |
11 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundations and plinth in : A) Cement mortar 1:3 (1 cement : 3 coarse sand) |
12 | Supplying & Laying of one number PVC insulated and PVC sheathed /XLPE insulated (Heavy duty), armoured aluminium conductor cable of 1.1 KV grade size of 3.5 x 240 sqmm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Make Havells/ Polycabe/ KEI/ Finolex/Gloster |
13 | Supplying & layingof one number PVC insulated and PVC sheathed /insulated (Heavy duty), armoured aluminium conductor cable of 1.1 KV gradesize 3.5x 240 sqmm. in the existng RCC / HUME / METAL pipeas required. Make Havells/ Polycabe/ KEI/ Finolex/Gloster |
14 | Supplying & Laying of one number PVC insulated and PVC sheathed /insulated (Heavy duty), armoured aluminium conductor cable of 1.1 KV grade of size 3.5 x 240 sqmmin the existing masonry open duct as required. Make Havells/ Polycabe/ KEI/ Finolex/Gloster |
15 | Supplying & Laying of one number PVC insulated and PVC sheathed /XLPE insulated (Heavy duty), Galvanised steel flate strip armoured aluminium conductorof Grade 11KV(E) grade size of 3 (core) x 185 sqmm cable direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Make Havells/ Polycabe/ KEI/ Finolex/Gloster |
16 | Supplying &Laying of one number PVC insulated and PVC sheathed /XLPE insulated (Heavy duty), Galvanised steel flate strip armoured aluminium conductorof Grade 11KV(E) grade size of 3 (core) x 185 sqmm cable in the existng RCC / HUME / METAL pipeas required. |
17 | Supplying & Laying of one number PVC insulated and PVC sheathed /XLPE insulated (Heavy duty), Galvanised steel flate strip armoured aluminium conductorof Grade 11KV(E) grade size of 3 (core) x 185sqmm cable in the existing masonry open duct as required. |
18 | supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required A) 185sqmm |
19 | Loading & transportation of 315 KVA ONAN transformer from Gen Room BSF campus Gandhinagar to109 BN BSF Damtiwada andunloading the same in DG panel room as per direction of site engineer. |
20 | Supplying and filling the new transformer oil |
21 | Transformer oil filtering i/c empty & refilling etc as required |
22 | Providing of Electric Shock Proof Rubber mats of size 2.5mm x1000mm x 2000mmHigh Di-Electric Strength up to 45 kV, Grade 11 kV etc as required |
23 | Providing of 3mm thick MS sheet over trench/drain etc as required |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail