E / 631 / 2021 Supply, Installation, Testing And Commissioning Of Ventilation System For Dry Area Of Pfff Module-2, Nfc- Kota, Rawatbhata, Rajasthan-Rajasthan

Bhabha Atomic Research Centre-BARC has published E / 631 / 2021 Supply, Installation, Testing And Commissioning Of Ventilation System For Dry Area Of Pfff Module-2, Nfc- Kota. Submission Date for this Tender is 10-12-2021. Ventilation Dampers Tenders in Rawatbhata, Rajasthan Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

29758154
Corrigendum : E / 631 / 2021 Supply, Installation, Testing And Commissioning Of Ventilation System For Dry Area Of Pfff Module-2, Nfc- Kota
Open Tender
Indian
Rajasthan
Rawatbhata, Rajasthan
10-12-2021

Tender Details

E / 631 / 2021 Supply, Installation, Testing And Commissioning Of Ventilation System For Dry Area Of Pfff Module-2, Nfc- Kota

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Nov-2021 Pre Bid Clarification Other 10-12-2021
2 25-Nov-2021 Corrigendum for Submission of Declarations Other 10-12-2021
3 08-Dec-2021 PreBid Electrical Additional Specification Other 10-12-2021

Key Value

Document Fees
Refer document
EMD
Refer document
Tender Value
INR 12.50 Crore /-

BOQ Items

Name of Work:"Supply, Installation, Testing & commissioning of Ventilation system for Dry Area of PFFF Module-2, NFC- Kota"
Sl. No. Item Description
1Masonry Spray type Air Washer system (AWS)of air flow capacities mentioned below having a saturation efficiency of 85-90%.The AWS shall consist the following major components-(Note: Civil works not included.). Pl refer drg No. C-CED/EP(AC&V)NFC(K)-149
2Supply air Fans : DIDW type, backward curved, belt driven. Temperature to be considered is 50deg C. The scope also includes accessories like flexible connections at fan outlet,common base frame, vibration isolators, V-belt, guard,electrical actuator controlled volume control damper at the outlet. Entire construction shall be epoxy painted. Capacity: 192500 CFM Static Pressure 150 mmWC MOC: Mild Steel Drive Arrangement Suitable with VFD (Note: VFD is covered in electrical schedule )
3Supply
4Installation
5Centrifugal pumps: Water recirculation centrifugal pumps suitable to handle water for above mentioned air flow rate. Accessories:Flexible coupling, mounting frame, etc., MOC: Cast Iron casing with SS impeller Drive Arrangement Suitable with VFD (Note: VFD is covered in electrical schedule)
6Supply
7Installation
8Plumbing between Spray chamber and Pumps Pipingfrom spray chamber to/from the pumps. Associated pump accessories : Isolation valves at inlet & outlet, flow regulation valves, NRV/check valve, strainer, etc. Piping from battery limit is also covered in this scope . Necessary fittings : Elbows, tees, couplings, reducersfasteners, clamps.etc, MOC : GI Class B Dwg: "C-CED/EP(AC&V)NFC(K)-147" for reference.
9Supply
10Installation
11Spray Chamber internals: Supply InstallationTesting & Commissioning of three bankwater spraying system with header, distributers, HDPV nozzles, marine light, pipe fittings, quick fill make up water line along with float and valve, drain pipe with gate valve, etc. MOC : GI Class-B
12Supply
13Installation
14Fresh Air Filter Capacity : 2000 CFM Grade : G4 Efficiency : 90% down to 10 micron Filter Media : HDPE Size :610x610 mm Casing : Aluminium Face guard : Wire mesh type (Note: Necessary support structure is covered in another item)
15Supply
16Installation
17PVC Air distributer (Note: Necessary MS support structure is covered in another item).
18Supply
19Installation
20Chevron type PVC Mist eliminator (Note: Necessary MS support structure is covered in another item).
21Supply
22Installation
23Exhaust air Fans : SISW type, backward curved, belt driven. Temperature to be considered is 50deg C. The scope also includes accessories like flexible connections at fan outlet,common base frame, vibration isolators, V-belt, guard,electrical actuator controlled volume control damper at the outlet. MS construction shall be epoxy painted. Static Pressure: 350 mm WC Drive Arrangement Suitable with VFD (Note: VFD is covered in electrical schedule )
24Capacity: 95300 CFM (MOC:Air Stream Components i.e. Casing and Impeller to be made of SS304 and the rest of the fan will be MS)
25Supply
26Installation
27Capacity: 19000 CFM (MOC:Air Stream Components i.e. Casing and Impeller to be made of SS304 and the rest of the fan will be MS)
28Supply
29Installation
30GI DUCTING: Duct shall be complying to IS: 277, Class IV, Grade 275 GSM. Accessories included: Supply/Exhaust air collars, vanes, splitters, necessary MS structural members (viz. angle flanges for duct joining, lateral& longitudinal reinforcement, internal tie rods,fasteners), gaskets, sealent, etc. Duct construction shall be as per IS-655/SMACNA standrad. (Note: Necessary duct supporting/hanging structural material (MS) is covered under item)
3118 gauge ducting , Rectangular
32Supply
33Installation
3422 gauge ducting , Rectangular
35Supply
36Installation
3718 gauge ducting, Circular
38Supply
39Installation
4022 gauge ducting, Circular
41Supply
42Installation
4316 Gauge for Plenum
44Supply
45Installation
46Manually operated Volume Control Dampers Thickness: 16 G Thick Dimensions: As per Requirement Measurement: Cross Sectional Flow Area including flanges
47Rectangular, MOC: GI
48Supply
49Installation
50Circular, MOC: GI
51Supply
52Installation
53Electrically operated Volume Control Dampers for ducting with one of the dimensions 1.0 mtr and above Thickness: 16 G Thick Dimensions: As per Requirement Measurement: Cross Sectional Flow Area including flanges
54Rectangular, MOC: GI
55Supply
56Installation
57Circular, MOC: GI
58Supply
59Installation
60Actuators for electrically operated Volume Control Dampers
61Supply
62Installation
63Non Return damper MOC: SS 304 Thickness: 16 G Thick Dimensions: As per Requirement Measurement: Cross Sectional Flow Area including flanges
64Supply
65Installation
66Fusible link type Fire dampers MOC: GI Thickness: 16 G Thick Dimensions: As per Requirement Note: Dampers shall be CBRI tested & certified for minimum 90 minutes rating as per UL 555 Measurement: Cross Sectional Flow Area including flanges
67Supply
68Installation
69Supply Air Grills: Type : Double deflection grills/Four Way Diffusers as per layout MOC: Extruded Aluminium Powder Coated Frame Thickness : 16 G Accessories : Volume control Dampers
70Supply
71Installation
72Return Air diffusers MOC: Extruded Aluminium Powder Coated Frame Thickness : 16 G
73Supply
74Installation
75MS. Structure (For General purpose): Painting : Epoxy painting with primer Scope: Duct supports, Yard Trustels for carrying ducts, supporting stand.
76Supply
77Installation
78MS. Structure(For retainer frames): Painting : Epoxy painting with primer Scope: HEPA filter/ Pre Filter/ Fresh Air filter/Air Distributer/ Mist Eliminator etc
79Supply
80Installation
81HEPA Filters Grade : H-14 Size: 610x 610x300 mm (Approx.) Flow Rate: 2000 CFM Efficiency : 99.97% down to 0.3 micron Initial Pressure Drop: 40 mmWC maximum in clean condition Casing : 1.2 mm thickAluminium Media : Borosilicate Microfibre
82Supply
83Installation
84Pre-Filters Grade : G4 Size: 610x 610 mm Flow Rate: 2000 CFM Efficiency : 95% down to 10 micron Initial Pressure Drop: 12 mmWC maximum in clean condition Casing : 1.2 mm thick Aluminium Media : Non woven Synthetic media sandwiched between 2 layers of HDPE Mesh
85Supply
86Installation
87MS Leak tight doors Size : 2.215 x1.115 m Note: For masonary type HEPA/Pre-filter chambers Refer : Drawing no C-CED/EP(AC&V)-142
88Supply
89Installation
901)DevelopingCAD drgs pertaining to GA, duct layout drawings as per specifications. 2)Simulation of Air flow pattern byCFD analysis using ANSYS or equivalent software. 3) Developing P&ID drgs of all ventilation systems as per schemes given 4) Assessing TAG numbers to all ventilation equipment 5)Validating of total sytem by smoke test.
91Supply
92Installation
93Design, Engineering, fabrication, transportation, supply, Safe handling, site storage, Installation, Testing & Commissioning of Motor Control Centre for air blowers and pumps as per tender specifications
94Dry Section ventilation PDP 4P, 800A EDO type ACB I/C-2Nos. 4P, 800A EDO type ACB B/C-1No. 3P+NL, 400A MCCBs --- 2 Nos. 3P+NL, 250A MCCBs --- 3 Nos. 3P+NL, 63A MCCBs --- 3 Nos.
95Supply
96Installation
97Damper Control Panel 4P, 63 A MCCB I/C-1Nos. 1 KW DOL starter(3Phase) - 8 Nos 1 KW DOL starter(1 Phase) - 9 Nos 3P+NL, 32A MCCB --- 1 Nos.
98Supply
99Installation
100Design, Engineering, fabrication, transportation, supply, Safe handling, site storage, Installation, Testing & Commissioning ofVFD Motor Control Centre for air blowers and pumps as per tender specifications: Dry Area Supply Air MCC panel (Non-drawout type) 4P, 800A EDO type ACB I/C-1No. 250kW VFDs --- 1 No. 90kW VFDs --- 1No. 3P+NL, 63A MCCBs --- 1 Nos.
101Supply
102Installation
103Design, Engineering, fabrication, transportation, Safe handling, site storage, Installation, Testing & Commissioning of Variable Frequency Drives for air blowers and pumps as per tender specifications
104250kW VFD panel
105Supply
106Installation
107220kW VFD panel
108Supply
109Installation
11055kW VFD panel
111Supply
112Installation
113Supply, installation, testing and commissioning of 1100 V grade, Aluminium Conductor, XLPE insulated and armoured FRLS cables of following sizes as per data sheet, specifications of this tender and directions of Engineer-in-Charge. including transport, all labourand materials, complete in all respects.
1143.5Cx 185 sqmm
115Supply
116Installation
1173.5Cx120sqmm
118Supply
119Installation
1204Cx16sqmm
121Supply
122Installation
123Supply, installation, testing and commissioning of 1100 V grade, Copper Conductor, XLPE insulated and armoured, FRLS cables of following sizes as per data sheets, specifications of this tender and directions of Engineer-in-Charge.including transport, all labourand materials, complete in all respects.
1243Cx185sqmm
125Supply
126Installation
1273Cx120sqmm
128Supply
129Installation
1304Cx2.5sqmm
131Supply
132Installation
133Termination of XLPE insulated armoured Aluminium/Copper power cables (up to 1100 V grade) and connection of leads including the supply of single compression cable glands and heavy duty copper lugs, drilling of suitable holes in equipments for fixing purposes, including fixing of cable glands, supply and fixing of PVC shrouds, cutting and stripping of cable insulation, crimping the lug on to the conductor, clamping of the cable-cores, marking with wire number, ferrules etc., including all labour and materials, as per approved drawings, specifications of this tender and directions of Engineer-in-Charge.
1343.5Cx 185 sqmm
135Supply
136Installation
1373Cx185sqmm
138Supply
139Installation
1403.5Cx120sqmm
141Supply
142Installation
1433Cx120sqmm
144Supply
145Installation
1464Cx16sqmm
147Supply
148Installation
1494Cx2.5sqmm
150Supply
151Installation
152CABLE – TRAYS : Supply and installation of prefabricated hot dip galvanised steel cable trays, fabricated out of hot rolled sheet steel with rigid welded construction ladder type with a rung as per std. tender drawing of approved makeandcable tray fittings, including all labour and materials, as per approved drawings, specifications of this tender anddirections of Engineer-in-Charge.
153150 mm wide Straight run cable tray
154Supply
155Installation
156450 mm wide Straight run cable tray
157Supply
158Installation
159Supply and installation of 100 mm wide galvanised slotted channel trays of 2 mm thickness and50 mm high for supporting cables, including all labour andmaterials, as per approved drawings, specifications of this tender and directions of Engineer- in-Charge.
160Supply
161Installation
162Supply, fabrication andinstallation of 0.91 mm (20 gauge) GI sheet covers for all sizes cable trays, including necessary hardware, including all labour andmaterials, as per approved drawings, specifications of this tender and directions of Engineer- in-Charge.
163Supply
164Installation