Municipal Corporation-MC has published Improvement Of Ei And Fans In Qtr No.E-71 Officer Flat Minto Road Under City Sp Zone. Submission Date for this Tender is 28-10-2021. Electrical Maintenance Tenders in CSPZ Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required |
3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
5 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
6 | Supplying and fixing brass batten/ angle holder including connections etc. as required. |
7 | S& F of 8/10 Watt Lamp as reqd. |
8 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
9 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
10 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. modular base & cover plate for modular switches in recess etc. as required. 3 Module (100mmX75mm) |
11 | 4 Module (125mmX75mm) |
12 | 6 Module (200mmX75mm) |
13 | 8 Module (125mmX125mm) |
14 | 12 Module (200mmX150mm) |
15 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 3 Module |
16 | 4 Module |
17 | 6 Module |
18 | 8 Module |
19 | 12 Module |
20 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessedPVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
21 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
22 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
23 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
24 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (A) 12 Way Double door |
25 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
26 | Supplying and fixing of following sizes of medium class Steel conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (A) 25 mm |
27 | Supplying and fixing 5amps,to 32 amps rating,240 volts, "C" curve miniature circuit breaker suitable for inductive load of following pole in the existing MCB DB complete with connection testing and commissioning etc, as required. (A) Single Pole |
28 | Supply and fixing following rating, double pole, 240 volt, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. (A) 63 Amp. |
29 | Supply and fixing following rating, Four pole, 240/415 volt, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. (A) 100 Amp. |
30 | S/I/T/CofLED tube type luminaire 20 watt rating complete with extruded aluminium batten prewired with high efficient LEDswith the following : Total system wattage 20 watt +/- 5 % Luminous efficacy lumens/watt >=95 Power factor >=0.95 |
31 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6amps switch |
32 | 15/16 amps switch |
33 | 3 pin 5/6 amps socket outlet |
34 | 6 pin 15/16 amps socket outlet |
35 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required |
36 | Supply of 15"(380mm)sweep 1400 rpm heavy duty Exaust Fan complete with ring, blade etc as required. ISI marked. |
37 | S.I.T.C. of 30 w LED Flood light fixture fitted with lense made of pressure die cast aluminium housing with high power LED and Toughened glass cover having top opening conrirming to IS -16103:2012 amended upto date with following specifaction as reqd. lumnaiar luminous >=5700 Total system wattage >30 watt +/- 10 % Lumnairer efficacy >= 95 luman/watt protection level IP-66 |
38 | Providing & Fixing of M.S. Fan Hook in the C.C. roof i/c dismentalling & repairing the roof for the same etc. as reqd. |