Providing Electrical Infrastructure For Cls Bitra .Sh: Ei& Fans - 1 Sub Head-I ( Wiring ) 2 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface , CTO Ernakulam-Kerala

Bharat Sanchar Nigam Limited-BSNL has published Providing Electrical Infrastructure For Cls Bitra .Sh: Ei& Fans - 1 Sub Head-I ( Wiring ) 2 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface . Submission Date for this Tender is 30-10-2021. Cutting Crimping and Punching Tools Tenders in CTO Ernakulam Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

29602660
Providing Electrical Infrastructure For Cls Bitra .Sh: Ei& Fans - 1 Sub Head-I ( Wiring ) 2 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface
Open Tender
Indian
Kerala
CTO Ernakulam
30-10-2021

Tender Details

Providing Electrical Infrastructure For Cls Bitra .Sh: Ei& Fans - 1 Sub Head-I ( Wiring ) 2 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Medium Class Pvc Conduit, With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvcinsulated Copper Conductor Single Core Cable Etc. As Required [ Group C ] 3 Wiring For Twin Control Light Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Medium Class Pvc Conduit, 2 Way Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. 4 Wiring For Light / Power Plug With 2X4 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Medium Class Pvc Conduit Alongwith 1 No. 4 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable For Loop Earthing As Required 5 Wiring For Light / Power Plug With 4X4 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Medium Class Pvc Conduit Alongwith 2 Nos. 4 Sq. Mm Frls Pvc Insulated Copper Conductor Single Core Cable For Loop Earthing As Required. 6 Wiring For Circuit / Submain Wiring Alongwith Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required 7 2X1.5 Sq.Mm + 1 X 1.5 Sq.Mm Earth Wire 8 4 X 6 Sq. Mm + 2 X 6 Sq. Mm Earth Wire 9 4 X 16 Sq. Mm + 2 X 6 Sq. Mm Earth Wire 10 2 X 6 Sq. Mm +1 X 6 Sq. Mm Earth Wire 11 Supplying And Drawing Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required. 12 3 X 1.5 Sq. Mm 13 6 X 1.5 Sq. Mm 14 2X 4 Sq. Mm 15 4 X 4 Sq. Mm 16 Supplying And Drawing Of 2Pair 0.5 Mm Dia Frls Pvc Insulated Annealed Copper Conductor, Unarmored Telephone Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required. 17 Supplying And Drawing Of One Run Of Utp 4 Pair Cat 6 Lan Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required. 18 Supplying And Fixing Following Sizes Ofmedium Class Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required. 19 A ) 20Mm 20 B ) 25Mm 21 Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required 22 5 / 6 A Switch 23 3 Pin 5 / 6 A Socket Outlet 24 15 / 16A Switch 25 6 Pin 15 / 16 A Socket Outlet 26 Telephone Socket Outlet 27 Supplying And Fixingtwo Module Stepped Type Electronic Fan Regulator On The Existing Modular Plate Switch Box Including Connections But Excluding Modular Plate Etc. As Required 28 Numbering Of Ceiling Fan / Exhaust Fan / Fluorescent Fittings As Required. 29 Supplying And Fixing The Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc As Required. 30 1 Or 2 Module ( 75Mmx75mm ) 31 3 Module ( 100Mmx75mm ) 32 4 Module ( 125Mmx75mm ) 33 Supplying And Fixing Suitable Size Gi Box With Modular Plate And Cover In Front On Surface Or In Recess, Including Providng And Fixing 2 Nos. 3 Pin 5 / 6 A Modular Socket Outlet And 2 Nos. 5 / 6 A Modular Switch, Connections Etc. As Required. ( For Light Plugs To Be Used In Non Residential Buildings ) . 34 Supplying And Fixing Pvc Batten / Angle Holder Including Connections Etc. As Required. 35 Supplying And Fixing Call Bell / Buzzer Suitable For Single Phase, 230 V, Complete As Required 36 Supplying And Fixing Modular Blanking Plate On The Existing Modular Plate & Switch Box Excluding Modular Plate As Required. 37 Supplying And Fixing Single Pole Blanking Plate In The Existing Mcb Db Complete Etc. As Required. 38 Sub Head-Ii ( Mcb & Db’S ) 39 Supplying And Fixing Following Way, Single Pole And Neutral, Sheet Steel, Mcb Distribution Board, 240 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator. 40 12 Way , Double Door 41 Supplying And Fixing Of Following Ways Surface / Recess Mounting, Vertical Type, 415 V, Tpn Mcb Distribution Board Of Sheet Steel, Dust Protected, Duly Powder Painted, Inclusive Of 200 A, Tinned Copper Bus Bar, Common Neutral Link, Earth Bar, Din Bar For Mounting Mcbs ( But Without Mcbs And Incomer ) As Required. ( Note : Vertical Type Mcb Tpdb Is Normally Used Where 3 Phaseoutlets Are Required. ) 42 8 Way ( 4 + 24 ) , Double Door 43 4 Way ( 4 + 12 ) , Double Door 44 Supplying And Fixing Of Following Ways Surface / Recess Mounting, Vertical Type, 415 V, Tpn Mcb Distribution Board Of Sheet Steel, Dust Protected, Duly Powder Painted, Inclusive Of 200 A, Tinned Copper Bus Bar, Common Neutral Link, Earth Bar, Din Bar For Mounting Mcbs ( But Without Mcbs And Incomer ) As Required. ( Note : Vertical Type Mcb Tpdb Is Normally Used Where 3 Phaseoutlets Are Required. ) 45 8 Way ( 4 + 24 ) , Double Door 46 Supplying And Fixing 5 Amps To 32 Amps Rating, 240 / 415 Volts, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 47 Single Pole 48 Triple Pole 49 Supplying And Fixing Of 100 Ampsfour Pole, 415 Volts, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required . 50 Supplying And Fixing Dp Sheet Steel Enclosure On Surface / Recess Along With 25 / 32Amps 240 Volts C Curve Dp Mcb Complete With Connections, Testing And Commissioning Etc. As Required 51 Supplying And Fixing Tp Sheet Steel Enclosure On Surface / Recess Along With 16 / 25 / 32 A, 415 V “C” Curve Tp Mcb Complete With Connections, Testing And Commissioning Etc. As Required 52 Supplying And Fixing 5 Amps To 32 Amps Rating, 240 / 415 Volts, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 53 For 14 Way, Double Door Spn Mcbdb 54 Supplying And Fixing Cable End Box ( Loose Wire Box ) ( Ip 43 ) Suitable For Following Triple Pole And Neutral, Sheet Steel, Mcb Distribution Board, 415 V, On Surface / Recess, Complete With Testing And Commissioning Etc. As Required 55 For 4 Way, Double Door Tpn Mcbdb 56 For 8 Way, Double Door Tpn Mcbdb 57 Supplying And Fixing Cable End Box ( Loose Wire Box ) Suitable For Triple Pole And Neutral, Sheet Steel, Vertical Mcb Distribution Board, 415 Volts, On Surface / Recess, Complete Withtesting And Commissioning Etc. As Required. 58 Supplying And Fixing Following Rating, Double Pole, 240 V, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required 59 63 A 60 Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 Volts, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current 30 Ma In The Existing Mcb Db Completewithconnections, Testingandcommissioning Etc. As Required 61 63 A 62 Sub Head-Iii Electrical Earthing / Cabling / Lightning Conductor 63 Providing And Fixing 25 Mm X 5 Mm Copper Strip In 40 Mm Dia G.I. Pipe From Earth Electrode Including Connection With Brass Nut, Bolt, Spring, Washer Excavation And Re-Filling Etc. As Required. 64 Providing And Fixing 25 Mm X 5 Mm Copper Strip On Surface Or In Recess For Connections Etc. As Required 65 Providing And Fixing Earth Bus Of 50 Mm X 5 Mm Copper Strip On Surface For Connections Etc. As Required. 66 Providing And Fixing 4.00 Mm Dia Copper Wire On Surface Or In Recess For Loop Earthing Along With Existing Surface / Recessed Conduit / Submain Wiring / Cable As Required. 67 Fixing Of Copper / G.I. Tape 20 Mm X 3 Mm Thick On Parapet Or Surface Of Wall For Lightning Conductor Complete As Required. ( For Horizontal Run ) 68 Laying Copper / G.I. Tape 32 Mm X 6 Mm From Earth Electrode Directly In Ground As Required. 69 Fixing Of Copper / G.I. Tape 20 Mm X 3 Mm Thick On Parapet Or Surface Of Wall For Lightning Conductor Complete As Required. ( For Vertical Run ) 70 Jointing Copper / G.I. Tape ( With Another Copper / G I Tape, Base Of The Finial Or Any Other Metallic Object ) By Riveting / Nut Bolting / Sweating And Soldering Etc As Required. 71 Supplying And Installing Following Size Of Perforated Hot Dipped Galvanisediron Cable Tray ( Galvanisation Thickness Not Less Than 50 Microns ) / Members With Perforation Not More Than 17.5%, In Convenient Sections, Joined With Connectors, Suspended From The Ceiling With G.I. Suspenders Including G.I.Bolts & Nuts, Etc. As Required. 72 Cable Tray With 300 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 73 Cable Tray Bend With 300 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 74 Cable Tray TeeWith 300 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 75 Cable Tray Cross Member With 300 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 76 Laying And Fixing Of One Number Pvc Insulated And Pvc Sheathed / Xlpe Power Cable Of 1.1 Kv Grade Of Following Size On Cable Tray As Required. 77 Upto 35 Sq. Mm ( Clamped With 1Mm Thick Saddle ) 78 Above 35 Sq. Mm And Upto 95 Sq. Mm ( Clamped With 25X3mm Ms Flat Clamp ) 79 Above 95 Sq. Mm And Upto 185 Sq. Mm ( Clamped With 25 / 40X3mm Ms Flat Clamp ) 80 Laying And Fixing Of One Number Pvc Insulated And Pvc Sheathed / Xlpe Power Cable Of 1.1 Kv Grade Of Following Size On Wall Surface As Required 81 Upto 35 Sq. Mm ( Clamped With 1Mm Thick Saddle ) 82 Above 35 Sq. Mm And Upto 95 Sq. Mm ( Clamped With 25X3mm Ms Flat Clamp ) 83 Above 95 Sq. Mm And Upto 185 Sq. Mm ( Clamped With 25 / 40X3mm Ms Flat Clamp ) 84 Laying And Fixing Of One Number Pvc Insulated And Pvc Sheathed / Xlpe Power Cable Of 1.1 Kv Grade Of Following Size On Wall Surface As Required 85 Upto 35 Sq. Mm ( Clamped With 1Mm Thick Saddle ) 86 Above 35 Sq. Mm And Upto 95 Sq. Mm ( Clamped With 25X3mm Ms Flat Clamp ) 87 Above 95 Sq. Mm And Upto 185 Sq. Mm ( Clamped With 25 / 40X3mm Ms Flat Clamp ) 88 Supplying And Making Indoor End Termination With Brass Compression Gland And Alluminium Lugs For Following Sizes Ofpvc Insulated And Pvc Sheathed / Xlpe Al. Conductor Cable Of 1.1 Kv Grade 89 3½ X 185 Sq. Mm ( 57Mm ) 90 3½ X 150 Sq. Mm ( 50Mm ) 91 3½ X 70 Sq. Mm ( 38Mm ) 92 4 X 25 Sq. Mm ( 28Mm ) 93 Providing And Fixing Extra Conduit Down Rod Of 20 Mm Dia, 2 X 10 Cm Length, Wiring With 2 X 1.5 Sq. Mm Frls Pvc Insulated, Copper Conductor, Single Core Cable Including Painting Etc. As Required. ( Note : More Than 5 Cm Length Shall Be Rounded To The Nearest 10 Cm And 5 Cm Or Less Shall Be Ignored ) 94 Supplying And Fixing Extra Conduit Down Rod Of 20 Cm Length G.I.Pipe 15 Mm Dia, Heavy Gauge Including Painting Etc. Asrequired. ( Note : More Than 5 Cm Length Shall Be Rounded To Thenearest 10 Cm And 5 Cm Or Less Shall Be Ignored ) 95 Supplying And Fixing 3 Pin, 5 A Ceiling Rose On The Existing Junction Box / Wooden Block Including Connections Etc. As Required. 96 Providing And Fixing M.V. Danger Notice Plate Of 200 Mm X 150Mm, Made Of Mild Steel, At Least 2 Mm Thick, And Vitreousenameled White On Both Sides, And With Inscription In Single Redcolour On Front Side As Required. 97 Supply, Installation, Testing And Commissioning Of 1200Mm Sweep, Bee 5 Star Rated, Ceiling Fan With Brush Lessdirect Current ( Bldc ) Motor, Class Of Insulation: B, 3 Nos.Blades, 30 Cm Long Down Rod, 2 Nos. Canopies, Shackle Kit, Safety Rope, Copper Winding, Power Factor Not Less Than0.9, Service Value ( Cmm / W ) Minimum 6.85, Air Deliveryminimum 215 Cmm, 350 Rpm ( Tolerance As Per Is : 374-2019 ) , Thd Less Than 10%, Remote Or Electronic Regulatorunit For Speed Control And All Remaining Accessories Including Safety Pin, Nut Bolts, Washers, Temperaturerise=75 Degree C ( Max. ) , Insulation Resistance More Than 2 Mega Ohm, Suitable For 230 V, 50 Hz, Single Phase Ac Supply, Earthing Etc. Complete As Required. 98 P / F Maintenance Free Earthing Comprises Of Molecularly Bonded Copperon Low Carbon Steel Of Min 3Mtr Having A Minimum Diameter Of 17.2Mm Dia With Copper Bonding Thickness Of 250 Microns , Earth Enhancing Compund Of Min 25Kg Is For Improving Soil Conductivity, Earth Electrode Inspection Chamber , Etc As Per Attached Specification. ( Cape Or Similar Superior Make ) 99 Supply And Fixing Of 4 Feet 1X 20 W Led Tubewith Batten Holderi / C Connections Etc As Reqd ( M / S Crompton Make Modeldijb12lt8-20 And Lt8-20-865- ( 2 ) Or Ss Make ) 100 Supply And Fixing Of Round Typefalse Ceiling Mountable15 Watt, Led Panel Lighting With Driver, Model : ( M / S Crompton Make Model: Cdr-205-15-57-Snwh Or Ss Make ) ( For Emergency Lighting ) 101 Supply And Fixing Of Recess Mounting 2X2 Size 24 Wattled Panel Lighting With Driver, In The Existing False Ceilling With Neccesssary Supporting Arrangement, Making Connection With 1.5 Sq Mm Pvc Insulated Copper Conductorsingle Core Cableetc As Reqd. Model : ( M / S Crompton Make Modellctlrne-24-Cdlor Ss Make ) 102 S / F Following Fancy Fitting On Wall I / C Providing E 27 Type 14W Led Lamp In The Fitting Etc As Reqd 103 A ) M / S Philips Model No: 30979 Or S / S Make 104 A ) M / S Philips Model No: 30978 Or S / S Make 105 Sitc Of Pre Wired Box Type Led Fitting With Powder Coated Crca Housingonball And Socket Arrangement With2 No.Suspended Down Rods Of 20 Mm Dia X 1.6 Mm Thick Steel Conduit Upto 30 Cm Length, Painting And Wiring The Down Rods And Connections With 1.5 Sq. Mm Frls Pvc Insulated, Copper Conductor, Single Core Cable And Earthing Etc., Andinstalling2 Nos T8 , 20W, Led Lampbuilt Driver With Metal Heat Sink Anddouble Sided Connection On The Box Type Fitting Etc As Reqd. ( Make : Box Type Fitting :Crompton Igp162lt8-16 And Led Tube Lt8-20-865-2 Or Ss Make ) 106 Sitc Of 12 Size Heavy Duty Exhaust Fan 1400 Rpm, With Metallic Bodyin The Existing Opening, Including Louver Shutter, Making The Hole To Suit The Size Of The Above Fan, Making Good The Damage, Connection, Testing Commissioning Etc As Required ( M / S Crompton / Almonard Or Similar Superior Make ) 107 Sitc Of 18 Size Heavy Duty Exhaust Fan 1400 Rpm, With Metallic Bodyin The Existing Opening, Including Louver Shutter, Making The Hole To Suit The Size Of The Above Fan, Making Good The Damage, Connection, Testing Commissioning Etc As Required ( M / S Crompton / Almonard Or Similar Superior Make ) 108 Providing & Fixing Of Fan Hook Fastner Of 16Mm Thick Ms Rod, With Bullet Type Anchor Bolt, Complete As Required. 109 Supplying And Fixing Rj-45 Jack With Cat- 6 On Thethe Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required 110 Supplying And Fixing Of 9 Watt Led Lamp In Thepvc Holder I / C Connection Etc Complete As Reqd. 111 S / F 25 A Dp Mcb Type Change Over Switch In Metallic Enclosure I / C Connections , Earthing Etc. 112 S / F 4 Pole32 A Mcb Typechange Over Switch In Metallic Enclosure I / C Connections , Earthing Etc. 113 Supply, Installation, Testing And Comissioning Of 450 Mm Sweep Wall Fan With Metal Leaf, Built In Speed Regulator And Oscillation Gear I / C Connection, Testing Commissioning Etc As Required ( M / S Almonard Mark Iior Similar Superior Make ) 114 S / F 230V, 50 Hz Led Type Mirror Lamp I / C Connections Etc As Reqd ( Philips Astraline 2 Ft 9W Led Tube Light Batten Or Ss Make ) 115 S / F 20 Mm Dia Metal Flexible Conduit As Reqd ( Fromceiling To Fitting ) 116 Providing, Laying And Fixing Following Dia G.I. Pipe ( Medium Class ) In Surface Or Recess I / C Making Good The Damages Etc As Reqd [ 80 Mm Dia ] 117 Providing, Laying And Fixing Following Dia G.I. Pipe ( Medium Class ) In Surface Or Recess I / C Making Good The Damages Etc As Reqd [ 40 Mm Dia ] 118 Providing And Fixing Testing Joint, Made Of 20 Mm X 3 Mm Thick Copper Strip, 125 Mm Long, With 4 Nos. Of Brass. Bolts, Nuts, Check Nuts And Spring Washers Etc. Complete As Required.. 119 Providing And Fixing Of Lightning Conductor Finial, Made Of 25 Mm Dia 300 Mm Long, Copper Tube, Having Single Prong At Top, With 85 Mm Dia 6 Mm Thick Copper Base Plate Including Holes Etc. Complete As Required 120 Supplying / Delivering At Site 20 X 3 Mmsize Copper Conductor Tape I / C Necessary Fixtures For Lightning Conductor Etc As Reqd 121 Supplying / Delivering At Site 32 X 6 Mmsize Copper Conductor Tape I / C Necessary Fixtures For Lightning Conductor From Test Joint To Earth Strip Etc As Reqd 122 Sh -Iv Main Lt Panel & Distribution Panels 123 Main Panel 124 Sitc Of Floor / Wall Mounting Cubicle Type Lt Panel Suitable For 415V, 3 Phase, 4 Wire, 50 Hz Ac Supply Systemfabricated In Compartmentalized Design From Crca Sheet Of 2 Mm Thick For Frame Work & Load Bearing Members And For Covers & Doors, 3 Mm Thick For Gland Plates, Powder Coated In Approved Shadeafter 7 Tank Process, Complete With Hinges And Earthed Front Door With Name Plate, Danger Notice Plate, Heavy Duty Rubber Gaskets And Having 300 Amps 3 1 / 2 Stripsaluminum Bus Bars Of High Conductivity With Heat Shrinkable Coloured Sleeves, Dmc / Smc Bus Bar Supports, , Bottom Base Channel Of Ms Section Not Less Than 100Mm X 50 Mm X 5Mm Thick ( In Case Of Floor Mounted ) , Entire Panel Shall Have A Common Copper Earth Bar Of Size 25Mm X 3 Mm At The Rear With 2 Numbers Earth Stud, Solid Connections From Main Bus Bars To Switch Gears With Requiredsize Al. Bus Bars And Control Wiring With 1.5Sq.Mm Pvc Insulated Copper Conductor Frlswires , Cable Alleys, Cable Gland Plates In Two Halves, I / C Providing Following Switch Gears And Providing Necessary Metal Angle Iron Supports Of Suitable Size Etc As Required. 125 Note: ( 1 ) The Panel Drawing Shall Be Got Approved By The Engineer In Charge Before Fabrication. ( All Items Make:- L&T, Siemens Or Ss Make ) ( 2 ) Aluminium Bus Bars Shall Be Of Sufficient Cross Section So That The Current Density Of 130 A / Sqcm Is Not Exceeded. 126 ( A ) Incomer 127 250 Amps4p Mccb, 36Ka, Thermal Magnetic Release - 2 Nos With 1 No: C / O And 1 No: Trip Alarm Contac ) ( Tac ) Aux Contacts And With Rotary Handle And Spreader Terminals. The Incomers Shall Be Mechanical Interlocked To Ensure Closing Of Only One Mccb At A Time. ( L&T Dsine Dn2 250D, Rr 200-250 Or Ss ) 128 ( B ) Outgoings: 129 A ] 160 Ampstpnsdf With 160 Amps Hrc Fuse - 2 Nos 130 B ] 100 Ampstpnsdf With 100 Amps Hrc Fuse - 2 Nos 131 C ] 63 Ampstpnsdf With 63 Amps Hrc Fuse - 3 Nos 132 Metering 133 A ) Digital Type Multifunction Meter With Lcd Display, Class 1 Accuracy, Withcts Of Suitable Rating For Measurement Of Voltage, Current, Frequency, Power Factor, Kva, Kw, Kwh With Rs 485 Port- 1 No. Make:L& T 4410 Series Or Similar Superior Make ) 134 B ) 3 Nos Led Indication Lamps ( Ryb ) With Mcb Control - 2 Sets 135 Complete As Above 136 S / F250a , 4 Pole On Load Change Over Switch With Suitable Metallic Enclosure I / C Connections, Testing Etc. As Reqd. ( M / Sl&T Model Co3-250 Co32500osoo Or Ss Make ) 137 Sub Lt Panel 138 Sitc Of Floor / Wall Mounting Cubicle Type Lt Panel Suitable For 415V, 3 Phase, 4 Wire, 50 Hz Ac Supply Systemfabricated In Compartmentalized Design From Crca Sheet Of 2 Mm Thick For Frame Work & Load Bearing Members And For Covers & Doors, 3 Mm Thick For Gland Plates, Powder Coated In Approved Shade After 7 Tank Process, Complete With Hinges And Earthed Front Door With Name Plate, Danger Notice Plate, Heavy Duty Rubber Gaskets And Having 300 Amps 3 1 / 2 Stripsaluminum Bus Bars Of High Conductivity With Heat Shrinkable Coloured Sleeves, Dmc / Smc Bus Bar Supports, , Bottom Base Channel Of Ms Section Not Less Than 100Mm X 50 Mm X 5Mm Thick ( In Case Of Floor Mounted ) , Entire Panel Shall Have A Common Copper Earth Bar Of Size 25Mm X 3 Mm At The Rear With 2 Numbers Earth Stud, Solid Connections From Main Bus Bars To Switch Gears With Requiredsize Al. Bus Bars And Control Wiring With 1.5Sq.Mm Pvc Insulated Copper Conductor Frlswires , Cable Alleys, Cable Gland Plates In Two Halves, I / C Providing Following Switch Gears And Providing Necessary Metal Angle Iron Supports Of Suitable Size Etc As Required. 139 Note: ( 1 ) The Panel Drawing Shall Be Got Approved By The Engineer In Charge Before Fabrication. ( All Items Make:- L&T, Siemens Or Ss Make ) ( 2 ) Aluminium Bus Bars Shall Be Of Sufficient Cross Section So That The Current Density Of 130 A / Sqcm Is Not Exceeded. 140 Incomer 141 250 Ampstpn Sdf With 250 A Hrc Fuse - 1 Nos 142 Out Goings 143 250 Ampstpn Sdf With 250 A Hrc Fuse - 3 Nos 144 Metering 145 A ) Digital Type Multifunction Meter With Lcd Display, Class 1 Accuracy, Withcts Of Suitable Rating For Measurement Of Voltage, Current, Frequency, Power Factor, Kva, Kw, Kwh With Rs 485 Port- 1 No. Make:L& T 4410 Series Or Similar Superior Make ) 146 B ) 3 Nos Led Indication Lamps ( Ryb ) With Mcb Control - 1 Set 147 Complete As Above 148 Power Plant ( Emergency ) Panel 149 Sitc Of Floor / Wall Mounting Cubicle Type Lt Panel Suitable For 415V, 3 Phase, 4 Wire, 50 Hz Ac Supply Systemfabricated In Compartmentalized Design From Crca Sheet Of 2 Mm Thick For Frame Work & Load Bearing Members And For Covers & Doors, 3 Mm Thick For Gland Plates, Powder Coated In Approved Shade After 7 Tank Process, Complete With Hinges And Earthed Front Door With Name Plate, Danger Notice Plate, Heavy Duty Rubber Gaskets And Having 2 Sets Of 250 Amps 3 1 / 2 Stripsaluminum Bus Bars Of High Conductivity With Heat Shrinkable Coloured Sleeves, Dmc / Smc Bus Bar Supports, , Bottom Base Channel Of Ms Section Not Less Than 100Mm X 50 Mm X 5Mm Thick ( In Case Of Floor Mounted ) , Entire Panel Shall Have A Common Copper Earth Bar Of Size 25Mm X 3 Mm At The Rear With 2 Numbers Earth Stud, Solid Connections From Main Bus Bars To Switch Gears With Requiredsize Al. Bus Bars And Control Wiring With 1.5Sq.Mm Pvc Insulated Copper Conductor Frlswires , Cable Alleys, Cable Gland Plates In Two Halves, I / C Providing Following Switch Gears And Providing Necessary Metal Angle Iron Supports Of Suitable Size Etc As Required. 150 Note: ( 1 ) The Panel Drawing Shall Be Got Approved By The Engineer In Charge Before Fabrication. ( All Items Make:- L&T, Siemens Or Ss Make ) ( 2 ) Aluminium Bus Bars Shall Be Of Sufficient Cross Section So That The Current Density Of 0.8A / Sqmm Is Conducted Safely 151 ( A ) Incomer 152 160 Amps4p Mccb, 36Ka, Thermal Magnetic Release - 2 Nos With Rotary Handle And Spreader Terminals. The Incomers And Bus Coupler Shall Be Mechanical Interlocked To Ensure Closing Of Only 2 Mccbs At A Time. ( L&T Dsine Dn2 250D, Rr 125-160 Or Ss ) 153 ( B ) Bus Coupler: 154 200 Amps4p Switch Disconnector Mccb Without Protection Release - 1 No With Rotary Handle And Spreader Terminals And With Mechanical Interlock ( L&T Dsine Dn2 250Sd Or Ss ) 155 ( C ) Outgoings: 156 A ] 100 Amps4p Mccb, 36Ka, Thermal Magnetic Release - 4 Nos With Spreader Terminals And Rotary Handle ( L&T Dsine Dn0 100D, Rr 80-100 Or Ss ) 157 B ] 63 Amps4p Mccb, 36Ka, Thermal Magnetic Release - 3 Nos With Spreader Terminals And Rotary Handle ( L&T Dsine Dn0 100D, Rr 50-63 Or Ss ) 158 C ] 32 Amps4p Mccb, 36Ka, Thermal Magnetic Release - 1 Nos With Spreader Terminals And Rotary Handle ( L&T Dsine Dn0 100D, Rr 25-32 Or Ss ) 159 ( D ) Instrument Panel: 160 A ) Digital Type Multifunction Meter With Lcd Display, Class 1 Accuracy, Withcts Of Suitable Rating For Measurement Of Voltage, Current, Frequency, Power Factor, Kva, Kw, Kwh With Rs 485 Port- 2 Nos. Make:L& T 4410 Series Or Similar Superior Make ) 161 B ) 3 Nos Led Indication Lamps ( Ryb ) With Mcb Control - 2 Sets 162 Complete As Above 163 Meter Board 164 Providing And Fixing Wall / Floor Mounting Cubicletype Energy Meter Board ( Ldeb ) Of Approx. Size 160Cm X 80Cm X 40Cm And Made Up Of 14 Gauge M.S Sheet, Powder Coated In Approved Shade After 7 Tank Process, Complete With Hinges And Earthed Front Door With Name Plate, Danger Notice Plate, Heavy Duty Rubber Gaskets.The Entire Meter Board Shall Be Weather Proof Double Door Type, Compartmentalised And With Locking Arrangement Suitable For Outdoor Installation And Shall Have Slanting M.S Sheet Roofs To Protect From Rain Water Entry, Locking Facility, View Glass, And Provision For Incoming And Outgoing Cables, Necessary Ventilation Arrangement, Danger Notice Plate And Suitable For Accommodating The Following Switchgears And Accessories And Having Front Door, Interconnections With Suitable Size Copper Conductor Wires Including Copper Sockets, Cable Gland Plates In Two Halves For Incoming Cables, Painting, Sign Writing Including Showing Eb Meter Panel, Con. No, Date Of Completion Etc, Including Mounting Arrangements On Wall / Or On Floor With Suitable Rcc / Brick Masonary / Ms Structure Foundation Arrangements Etc As Required. 165 A ) Separate Compartment For Ldeb Meter With Provision For Fixing 3 Phaseenergy Meterwith Separate Door And Sealing Facility And See Through Glass Windowfor Meter Reading. 166 B ) Supplying And Fixing Of 1 No. 250 Amps Tpn Sdf Suitable For Din Fuse With 250A Hrc Fuse ( Make: L & T / Siemens ) 167 C ) Supplying And Fixing 3 Nos. 300 A Porcelain Fuse Cutout & 200A Neutral Link, Etc. 168 D ) Supplying And Fixing 3 Nos Led Indication Lamp With Mcb. 169 E ) S / F 4 Nos. Suitable Class Ct Up To 250 / 5 As Per Electricity Board Requirement 170 F ) Digital Type Multifunction Meter With Lcd Display, Class 1 Accuracy, Withcts Of Suitable Rating For Measurement Of Voltage, Current, Frequency, Power Factor, Kva, Kw, Kwh With Rs 485 Port- 1 No. Make:L& T 4410 Series Or Similar Superior Make ) 171 G ) Provision For Mounting 4 P Rccb I / C Providing Suitable Din Rail / C Channel 172 Complete As Above 173 Sitc Of Double Sided 3W Green Led Exit Signage ( Sign Writing And / Or Artwork As Per Site Condition ) Of Standard / Suitable Size With Led Lamp, With 2 Hours Battery Back Up I / C Battery Charger, Accessoriesand Giving Connections Etc As Reqd ( The Sign Writing / Artwork Will Be Decided By The Engineer In Charge As Per Site Requirement ) 174 Compound Lighting 175 S / Fled Type Street Light Fitting On 25 Mm Size 1.2M Long Medium Class Gi Pipe Bend To Suitable Shape On Walli / C Brackets, Fixtures, Connections With 1.5 Sqmm Copper Conductor Unarmoured Cable From Control Box Etc As Reqd ( M / S Crompton Greaves Make , Model No: Lsts 25 Cdl Or Ss Make ) 176 S / Fled Type Post Top Street Light Fitting On 60 Mm Size Medium Class Gi Pipe Of Suitable Length On Gate Pillari / C Fixtures, Connections With 1.5 Sqmm Copper Conductor Unarmoured Cable From Control Box Etc As Reqd ( M / S Crompton Greaves Make , Model No: Lpto 40 Cdl M Or Ss Make ) 177 S / F Hot Tip Galvanised Street Light Post Of 5 Mtr Length With Bottom Dia 130Mm Top Dia 70Mm Having 3Mmthickness.The Sie Of The Base Plate Should Be 220Sq.Mm With 12Mm Thickness.Foundation Bolts Should Be Of 600Mm With M16 Size. 178 Single Arm With 1.5M Length 179 Double Arm With 1.5 M Length 180 Providing 1:2:4 Ratio Cc Foundation For Street Light Fitting I / C Excavation Including Refilling , Cement Plastering As Required, Fixing The Bolts Supplied With The Street Light Fitting Etc As Reqd 181 Supplying And Delivery Of Pvc Insulated And Sheathed Armoured 3 Core 1.5 Sq.Mm Copper Conductor 1.1 Kv Grade Cable As Reqd. ( Bsnl Approved Make ) . 182 Supplying And Making End Termination With Brass Compression Gland For Pvc Insulated And Sheathed Armoured Copper Conductor Cable Of 1.1 Kv Grade Of Size 3Core 1.5 Sq.Mm As Reqd. 183 S / F Of Smc Type Loop In And Loop Out Box / Control Box Of Size 140X140x95mm, I / C Pdg Sp Mcb Of 6A Rating B Series, Cable Terminals, Earthing Stud, Connection Complete As Reqd. 184 S / F Of Compound Light Control Unitconsisting Of One Analog Time Switch, 24 Hrs Mode With By-Pass Arrangement , Din / Base Mounting Type . Dp Mcb 6A, Within A Ncessary Smc Enclosurewiring For Interconnection, Complete As Reqd.L&T Fm / 1Qt Or Ss Make 185 Supplying And Delivery Of Following Size Of Pvc Insulated And Sheathed Aluminium Armoured Cable Of 1.1 Kv Grade As Reqd. ( Bsnl Approved Make ) . 186 31 / 2X150 Sq.Mm 187 31 / 2X70 Sq.Mm 188 4X 25 Sq.Mm 189 Sh-V Dc Cable & Allied Works 190 Supplying And Drawing Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable Onsurface / Recess Or In The Existing Cable Tray As Required. ( A ) 1X 150 Sq.Mm 191 Supplying And Making End Termination With 150 Sq.Mm Copper Lugs For Following Size Of Pvc Insulated And Pvc Sheathed Copper Conductor Cable Of 1.1 Kv Grade As Required ( A ) 1X 150 Sq.Mm 192 Supplying And Fixing 500A Rating Din Typehrc Fuseon 5Mm Thick Hylum Sheet With Fuse Adaptors For Terminating The Negative Terminal On The Vrla / Li-Ion Battery Assembly I / C Connections, Testing And Commissioning Etc. As Required. 193 Providing & Fixing On Wall Or In Existing Suitable Size Powder Coated 14 Gms Box With Sufficient Number Of Knock Outs For The Cables, 3 Nostinned Copper Bus Bar Of Section 50Mm X 6 Mm Thick, 0.30 Meters Long With Sufficient Number Of Holes For Termination Of Incoming And Out Going Cables, Brass Bolts, Nuts And Tinned Copper Washers On Suitable Epoxy Resin Cast Bus Bar Insulators As Required ( 2 Nos. For +Ve And 1 No. For Equipment Body Earth ) 194 Providing & Fixing On Wall Inthe Existing Ms Frame Work In Existing Suitable Size Powder Coated 14 G Ms Box With Door With Sufficient Number Of Knock Outs For The Cables, 2 Nostinned Copper Bus Bar Of Section 20Mm X 5 Mm Thick, 0.15 Meters Long On Bottom And 2 Nos40mm X 5 Mm Thick0.15 Meters On Top, With 2 Nos Din Channel For Mcbs With Sufficient Number Of Holes For Termination Of Incoming And Out Going Cables, Brass Bolts, Nuts And Tinned Copper Washers On Suitable Epoxy Resin Cast Bus Bar Insulators As Required ( For Termination Of Negative Terminal ) 195 Sh-Vi Ea Set Auxiliary Works , Display Sign Board & Pump Set 196 Providing And Fixing Braided Copper Equivalent To 25Mmx5mm Copper Strip I / C Crimping Etc As Reqd 197 S / F Wall Mounting Type Isi Marked Co2 Fire Extinguisher Of 4.5 Kg Capacity I / C Providing Necessary Hooks Etc As Required ( Bsnl Approved Make With Explosive Certificate ) 198 S / F Gi Bucket Each Set Comprising Of Two Nos Bucket Of 9 Ltr Capacity And Inscription Fire In Signal Red Colour On Each Bucket I / C P / F M.S.Brackets With Hooks For Hanging The Buckets Painting And Filling The Bucket Withsand Etc As Required. 199 Design, Composition , Supply And Installation Of 10 Mm Acrylic, Laser Cut Letter Pasting On 4 Mm Acp Sheet Box , Acrylic Layser Cut Letter Polyuratine Cotting ( Pu Cotted Or Vinyl Pasted In Colour Specified With Internally Lit Led , The Frame Shall Be Made Of Ms Tube Of 1.2 Mm Thick Rusted Treatment, Double Frame , 4 Inch Depth , Application Of Silicon Sealent On All Joints To Stop Water Sweepage , The Acp Brand .. Aludecor / Flexibond Cordd, Accrylic Letters Branding .. 3 Mm 3630 / 3050, Vinyl Acrylic Brand .. Atari / Marca Or Equialant Led Brand Lt / Goq / Hi Sign With Samsung Chip Water Proof , Ip 67 / 68 Grade 3 Years Warrentee With Drivers Complete As Required. ( Contents To Be Approved By Eic ) Offollowing Size. Size 8 Feet X 3 Feet 200 Steel Work Welded In Built Up Sections Or Framed Work Including Cutting Hoisting , Fixing In Positionand Applying A Priming Coat Of Approved Stell Primer Using Structural Steel , Paintingwith Synthatic Enamel Paint Two Or More Coats Etc As Required. ( For Glow Sign Board Support / Ea Exhaust Extenssion Etc ) . 201 Sitc Of1.0 Hp Capacity Single Phase Monoblock Pump Sethaving Suction And Delivery Pipe Of Size Of 50Mm X 40Mm , Discharge In Lps Of 1.5 At A Head Of 20Mtr As Required ( M / S Kirloskar Make, Model: Kds 128+ Or Ss Make ) 202 S / F 25A Rating Dpmcb With Enclosure For The Control Of Pumpset I / C Connections Etc As Reqd ( M / S Havells Make, Model:Dhmpcdpa032 Or Ss Make ) 203 S / F 50Mm Size Good Quality Flexible Green Hose With 3Mm Thickness I / C Ss Hose Clips At Both Ends Etc As Reqd 204 S / F 50 Mm Size Good Quality Pvc Foot Valvei / C Connections Etc As Reqd ( M / S Kirloskar Or Ss Make ) 205 S / F 40Mm Size Good Quality Pvc Pipe ( 6 Kg / Cm2 ) I / C Connections, Accessories Etc As Reqd ( M / S Finolex Or Ss Make ) 206 Supply And Installation Of 100 Mm Diaof Standard Welded Black Ms, Medium Pipe As Per Is:1239 ( I ) Cut To Required Lengths Including Long Bends, Flanges Etc And Installed In Existing Angle Iron Supports Through Following Way And Applying Heat Resistant Paint ( 600 Deg C ) Etc Complete As Required. ( Jindal India Ltd, Tata Make )

Key Value

Document Fees
INR 590 /-
EMD
Refer document
Tender Value
INR 41.08 Lakhs /-

BOQ Items

Name of Work:-Providing Electrical Infrastructurefor CLS Bitra .SH: EI& Fans
Sl. No. Item Description
1Sub Head-I (Wiring)
2Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable etc. as required [Group C]
3Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
4Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required
5Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
6Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
72x1.5 sq.mm + 1 x 1.5 sq.mm earth wire
84 X 6 sq. mm + 2 X 6 sq. mm earth wire
94 X 16 sq. mm + 2 X 6 sq. mm earth wire
102 X 6 sq. mm +1 X 6 sq. mm earth wire
11Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
123 x 1.5 sq. mm
136 x 1.5 sq. mm
142x 4 sq. mm
154 x 4 sq. mm
16Supplying and drawing of 2pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
17Supplying and drawing of one run of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
18Supplying and fixing following sizes ofmedium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
19a) 20mm
20b) 25mm
21Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
225/6 A switch
233 pin 5/6 A socket outlet
2415/16A switch
256 pin 15/16 A socket outlet
26Telephone socket outlet
27Supplying and fixingtwo module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required
28Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
29Supplying and fixing the following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.
301 or 2 Module (75mmX75mm)
313 Module (100mmX75mm)
324 Module (125mmX75mm)
33Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
34Supplying and fixing PVC batten/ angle holder including connections etc. as required.
35Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required
36Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
37Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
38Sub Head-II ( MCB & DB’S)
39Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator.
4012 way , Double door
41Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
428 way (4 + 24), double door
434 way (4 + 12), double door
44Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
458 way (4 + 24), Double door
46Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
47Single pole
48Triple pole
49Supplying and fixing of 100 Ampsfour pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required .
50Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required
51Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A, 415 V “C” curve TP MCB complete with connections, testing and commissioning etc. as required
52Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
53For 14 way, Double door SPN MCBDB
54Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required
55For 4 way, Double door TPN MCBDB
56For 8 way, Double door TPN MCBDB
57Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete withtesting and commissioning etc. as required.
58Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required
5963 A
60Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB completewithconnections,testingandcommissioning etc. as required
6163 A
62Sub Head-III Electrical Earthing /cabling/Lightning Conductor
63Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
64Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required
65Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
66Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit / submain wiring/ cable as required.
67Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
68Laying copper/ G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
69Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
70Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
71Supplying and installing following size of perforated Hot Dipped GalvanisedIron cable tray (Galvanisation thickness not less than 50 microns) / members with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I.bolts & nuts, etc. as required.
72Cable tray with 300 mm width X 50 mm depth X 1.6 mm thickness
73Cable tray " Bend" with 300 mm width X 50 mm depth X 1.6 mm thickness
74Cable tray " Tee"with 300 mm width X 50 mm depth X 1.6 mm thickness
75Cable tray "Cross Member " with 300 mm width X 50 mm depth X 1.6 mm thickness
76Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
77Upto 35 sq. mm (clamped with 1mm thick saddle)
78Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
79Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
80Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
81Upto 35 sq. mm (clamped with 1mm thick saddle)
82Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
83Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
84Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required
85Upto 35 sq. mm (clamped with 1mm thick saddle)
86Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
87Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
88Supplying and making indoor end termination with brass compression gland and Alluminium lugs for following sizes ofPVC insulated and PVC sheathed/XLPE Al. conductor cable of 1.1 KV grade
893½ X 185 sq. mm (57mm)
903½ X 150 sq. mm (50mm)
913½ X 70 sq. mm (38mm)
924 X 25 sq. mm (28mm)
93Providing and fixing extra conduit down rod of 20 mm dia, 2 X 10 cm length, wiring with 2 X 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
94Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
95Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
96Providing and fixing M.V. danger notice plate of 200 mm X 150mm, made of mild steel, at least 2 mm thick, and vitreousenameled white on both sides, and with inscription in single red colour on front side as required.
97Supply, Installation, Testing and Commissioning of 1200mm sweep, BEE 5 star rated, ceiling fan with Brush LessDirect Current (BLDC) Motor, class of insulation: B, 3 nos.blades, 30 cm long down rod, 2 nos. canopies, shackle kit,safety rope, copper winding, Power Factor not less than0.9, service Value (CMM/W) minimum 6.85, Air deliveryminimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulatorunit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
98P/F maintenance free earthing comprises of molecularly bonded copperon low carbon steel of min 3Mtr having a minimum diameter of 17.2mm dia with copper bonding thickness of 250 microns ,earth enhancing compund of min 25Kg is for improving soil conductivity, earth electrode inspection chamber ,etc as per attached specification. (Cape or Similar Superior make)
99Supply and fixing of 4 feet 1X 20 W LED tubewith batten holderi/c connections etc as reqd (M/s Crompton make ModelDIJB12LT8-20 and LT8-20-865-(2) or SS make)
100Supply and fixing of Round typeFalse ceiling mountable15 watt, LED panel lighting with driver, model :(M/s Crompton make Model: CDR-205-15-57-SNWH or SS make) ( for emergency lighting)
101Supply and fixing of Recess mounting 2"X2" size 24 wattLED panel lighting with driver,in the existing false ceilling with neccesssary supporting arrangement,making connection with 1.5 sq mm PVC insulated Copper conductorsingle core cableetc as reqd. model :(M/s Crompton make ModelLCTLRNE-24-CDLor SS make)
102S/f following fancy fitting on wall i/c providing E 27 type 14W LED lamp in the fitting etc as reqd
103a) M/s Philips Model No: 30979 or s/s make
104a) M/s Philips Model No: 30978 or s/s make
105SITC of pre wired Box type LED fitting with powder coated CRCA housingonball and socket arrangement with2 no.suspended down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.,andinstalling2 Nos T8 ,20W, LED lampbuilt driver with metal heat sink andDouble sided connection on the box type fitting etc as reqd. (Make : Box type fitting :Crompton IGP162Lt8-16 and LED tube LT8-20-865-2 or SS make)
106SITC of 12" size heavy duty exhaust fan 1400 rpm, with metallic bodyin the existing opening, including louver shutter, making the hole to suit the size of the above fan, making good the damage, connection, testing commissioning etc as required (M/s Crompton/Almonard or similar superior make)
107SITC of 18" size heavy duty exhaust fan 1400 rpm, with metallic bodyin the existing opening, including louver shutter, making the hole to suit the size of the above fan, making good the damage, connection, testing commissioning etc as required (M/s Crompton/Almonard or similar superior make)
108Providing & fixing of Fan Hook fastner of 16mm thick MS rod, with bullet type anchor bolt, complete as required.
109Supplying and fixing RJ-45 Jack with Cat- 6 on thethe existing modular plate & switch box including connections but excluding modular plate etc. as required
110Supplying and fixing of 9 watt LED lamp in thePVC holder i/c connection etc complete as reqd.
111S/F 25 A DP MCB type change over switch in metallic enclosure i/c connections , earthing etc.
112S/F 4 pole32 A MCB typechange over switch in metallic enclosure i/c connections , earthing etc.
113Supply, Installation, testing and comissioning of 450 mm sweep wall fan with metal leaf, built in speed regulator and oscillation gear i/c connection, testing commissioning etc as required (M/s Almonard mark IIor similar superior make)
114S/f 230V, 50 Hz LED type Mirror lamp i/c connections etc as reqd ( Philips Astraline 2 ft 9w LED tube light batten or ss make)
115S/f 20 mm dia Metal flexible conduit as reqd ( fromceiling to fitting)
116Providing, laying and fixing following dia G.I. pipe (medium class) in surface or recess i/c making good the damages etc as reqd [80 mm dia]
117Providing, laying and fixing following dia G.I. pipe (medium class) in surface or recess i/c making good the damages etc as reqd [40 mm dia]
118Providing and fixing testing joint, made of 20 mm X 3 mm thick Copper strip, 125 mm long, with 4 nos. of Brass. bolts, nuts, check nuts and spring washers etc. complete as required..
119Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, Copper tube, having single prong at top, with 85 mm dia 6 mm thick Copper base plate including holes etc. complete as required
120Supplying/ delivering at site 20 X 3 mmsize copper conductor tape i/c necessary fixtures for lightning conductor etc as reqd
121Supplying/ delivering at site 32 X 6 mmsize copper conductor tape i/c necessary fixtures for lightning conductor from test joint to earth strip etc as reqd
122SH -IV Main LT Panel & Distribution panels
123MAIN PANEL
124SITC of floor/ wall mounting cubicle type LT panel suitable for 415V, 3 phase, 4 wire, 50 Hz AC supply systemfabricated in compartmentalized design from CRCA sheet of 2 mm thick for frame work & load bearing members and for covers & doors, 3 mm thick for gland plates,powder coated in approved shadeafter 7 tank process,complete with hinges and earthed front door with name plate, danger notice plate, heavy duty rubber gaskets and having 300 Amps 3 1/2 stripsAluminum bus bars of high conductivity with heat shrinkable coloured sleeves,DMC/ SMC bus bar supports, , bottom base channel of MS section not less than 100mm x 50 mm x 5mm thick (in case of floor mounted), entire panel shall have a common copper earth bar of size 25mm x 3 mm at the rear with 2 numbers earth stud, solid connections from main bus bars to switch gears with requiredsize Al. bus bars and control wiring with 1.5sq.mm PVC insulated copper conductor FRLSwires , cable alleys, cable gland plates in two halves, i/c providing following switch gears and providing necessary metal angle iron supports of suitable size etc as required.
125Note:(1) The panel drawing shall be got approved by the Engineer in charge before fabrication.( All Items Make:- L&T, Siemens or SS make) (2) Aluminium Bus bars shall be of sufficient cross section so that the Current density of 130 A / sqcm is not exceeded.
126(A) Incomer
127250 Amps4P MCCB, 36KA, Thermal Magnetic release - 2 Nos with 1 No: C/O and 1 No: Trip Alarm Contac) (TAC)Aux contacts and with Rotary handle and spreader terminals. The Incomers shall be mechanical interlocked to ensure closing of only one MCCB at a time. (L&T Dsine DN2 250D, RR 200-250 or SS)
128(B) Outgoings:
129a] 160 AmpsTPNSDF with 160 Amps HRC Fuse - 2 nos
130b] 100 AmpsTPNSDF with 100 Amps HRC Fuse - 2 nos
131c] 63 AmpsTPNSDF with 63 Amps HRC Fuse - 3 nos
132Metering
133a) Digital type multifunction meter with LCD display, class 1 accuracy, withCTs of suitable rating for measurement of voltage, current, frequency, power factor, KVA, KW, KWH with RS 485 port- 1 No. Make:L& T 4410 series or similar superior make)
134b) 3 nos LED indication lamps (RYB) with MCB control - 2 Sets
135Complete as above
136S/F250A ,4 pole on load Change over switch with suitable metallic enclosure i/c connections, testing etc. as reqd.( M/sL&T model CO3-250 CO32500OSOO or SS make)
137Sub LT Panel
138SITC of floor/ wall mounting cubicle type LT panel suitable for 415V, 3 phase, 4 wire, 50 Hz AC supply systemfabricated in compartmentalized design from CRCA sheet of 2 mm thick for frame work & load bearing members and for covers & doors, 3 mm thick for gland plates,powder coated in approved shade after 7 tank process,complete with hinges and earthed front door with name plate, danger notice plate, heavy duty rubber gaskets and having 300 Amps 3 1/2 stripsAluminum bus bars of high conductivity with heat shrinkable coloured sleeves,DMC/ SMC bus bar supports, , bottom base channel of MS section not less than 100mm x 50 mm x 5mm thick (in case of floor mounted), entire panel shall have a common copper earth bar of size 25mm x 3 mm at the rear with 2 numbers earth stud, solid connections from main bus bars to switch gears with requiredsize Al. bus bars and control wiring with 1.5sq.mm PVC insulated copper conductor FRLSwires , cable alleys, cable gland plates in two halves, i/c providing following switch gears and providing necessary metal angle iron supports of suitable size etc as required.
139Note:(1) The panel drawing shall be got approved by the Engineer in charge before fabrication.( All Items Make:- L&T, Siemens or SS make) (2) Aluminium Bus bars shall be of sufficient cross section so that the Current density of 130 A / sqcm is not exceeded.
140Incomer
141250 AmpsTPN SDF with 250 A HRC Fuse - 1 Nos
142Out goings
143250 AmpsTPN SDF with 250 A HRC Fuse - 3 Nos
144Metering
145a) Digital type multifunction meter with LCD display, class 1 accuracy, withCTs of suitable rating for measurement of voltage, current, frequency, power factor, KVA, KW, KWH with RS 485 port- 1 No. Make:L& T 4410 series or similar superior make)
146b) 3 nos LED indication lamps (RYB) with MCB control - 1 Set
147Complete as above
148Power Plant (Emergency) panel
149SITC of floor/ wall mounting cubicle type LT panel suitable for 415V, 3 phase, 4 wire, 50 Hz AC supply systemfabricated in compartmentalized design from CRCA sheet of 2 mm thick for frame work & load bearing members and for covers & doors, 3 mm thick for gland plates,powder coated in approved shade after 7 tank process,complete with hinges and earthed front door with name plate, danger notice plate, heavy duty rubber gaskets and having 2 sets of 250 Amps 3 1/2 stripsAluminum bus bars of high conductivity with heat shrinkable coloured sleeves,DMC/ SMC bus bar supports, , bottom base channel of MS section not less than 100mm x 50 mm x 5mm thick (in case of floor mounted), entire panel shall have a common copper earth bar of size 25mm x 3 mm at the rear with 2 numbers earth stud, solid connections from main bus bars to switch gears with requiredsize Al. bus bars and control wiring with 1.5sq.mm PVC insulated copper conductor FRLSwires , cable alleys, cable gland plates in two halves, i/c providing following switch gears and providing necessary metal angle iron supports of suitable size etc as required.
150Note:(1) The panel drawing shall be got approved by the Engineer in charge before fabrication.( All Items Make:- L&T, Siemens or SS make) (2) Aluminium Bus bars shall be of sufficient cross section so that the Current density of 0.8A/Sqmm is conducted safely
151(A) Incomer
152160 Amps4P MCCB, 36KA, Thermal Magnetic release - 2 Nos with Rotary handle and spreader terminals. The Incomers and Bus coupler shall be mechanical interlocked to ensure closing of only 2 MCCBs at a time. (L&T Dsine DN2 250D, RR 125-160 or SS)
153(B) Bus Coupler:
154200 Amps4P Switch Disconnector MCCB without protection release - 1 No with Rotary handle and spreader terminals and with mechanical interlock (L&T Dsine DN2 250SD or SS)
155(C) Outgoings:
156a] 100 Amps4P MCCB, 36KA, Thermal Magnetic release - 4 Nos with Spreader terminals and Rotary handle (L&T Dsine DN0 100D, RR 80-100 or SS)
157b] 63 Amps4P MCCB, 36KA, Thermal Magnetic release - 3 Nos with Spreader terminals and Rotary handle (L&T Dsine DN0 100D, RR 50-63 or SS)
158c] 32 Amps4P MCCB, 36KA, Thermal Magnetic release - 1 Nos with Spreader terminals and Rotary handle (L&T Dsine DN0 100D, RR 25-32 or SS)
159(D) Instrument Panel:
160a) Digital type multifunction meter with LCD display, class 1 accuracy, withCTs of suitable rating for measurement of voltage, current, frequency, power factor, KVA, KW, KWH with RS 485 port- 2 Nos. Make:L& T 4410 series or similar superior make)
161b) 3 nos LED indication lamps (RYB) with MCB control - 2 Sets
162Complete as above
163Meter Board
164Providing and fixing wall / floor mounting cubicletype Energy meter board (LDEB) of approx. size 160cm x 80cm x 40cm and made up of 14 gauge M.S sheet, powder coated in approved shade after 7 tank process,complete with hinges and earthed front door with name plate, danger notice plate, heavy duty rubber gaskets.The entire meter board shall be weather proof Double door type, compartmentalised and with locking arrangement suitable for outdoor installation and shall have slanting M.S sheet roofs to protect from rain water entry, locking facility, view glass, and provision for incoming and outgoing cables, necessary ventilation arrangement, danger notice plate and suitable for accommodating the following switchgears and accessories and having front door, interconnections with suitable size copper conductor wires including copper sockets,cable gland plates in two halves for incoming cables, painting, sign writing including showing EB meter panel, Con. No, date of completion etc, including mounting arrangements on wall/ or on floor with suitable RCC/Brick masonary/MS structure foundation arrangements etc as required.
165a) Separate compartment for LDEB meter with provision for fixing 3 Phaseenergy meterwith separate door and sealing facility and see through glass windowfor meter reading.
166b) Supplying and fixing of 1 No. 250 Amps TPN SDF suitable for DIN fuse with 250A HRC fuse(Make: L & T/ Siemens)
167c) Supplying and fixing 3 Nos. 300 A Porcelain Fuse cutout & 200A neutral link, etc.
168d)Supplying and fixing 3 Nos LED indication lamp with MCB.
169e) S/F 4 nos. suitable class CT up to 250/5 as per Electricity Board requirement
170f) Digital type multifunction meter with LCD display, class 1 accuracy, withCTs of suitable rating for measurement of voltage, current, frequency, power factor, KVA, KW, KWH with RS 485 port- 1 No. Make:L& T 4410 series or similar superior make)
171g) Provision for mounting 4 P RCCB i/c providing suitable din rail/C channel
172Complete as above
173SITC of double sided 3W green LED exit signage(sign writing and /or artwork as per site condition) of standard/ suitable size with LED lamp, with 2 hours battery back up i/c battery charger, accessoriesand giving connections etc as reqd (The sign writing/ artwork will be decided by the engineer in charge as per site requirement)
174Compound lighting
175S/fLED type street light fitting on 25 mm size 1.2m long medium class GI pipe bend to suitable shape on walli/c brackets,fixtures, connections with 1.5 Sqmm copper conductor unarmoured cable from control box etc as reqd (M/s Crompton Greaves make , Model No: LSTS 25 CDL or SS make)
176S/fLED type POST TOP street light fitting on 60 mm size medium class GI pipe of suitable length on gate pillari/c fixtures, connections with 1.5 Sqmm copper conductor unarmoured cable from control box etc as reqd (M/s Crompton Greaves make , Model No: LPTO 40 CDL M or SS make)
177S/F Hot tip galvanised street light post of 5 Mtr length with bottom dia 130mm top dia 70mm having 3mmthickness.The sie of the base plate should be 220sq.mm with 12mm thickness.Foundation bolts should be of 600mm with M16 SIZE.
178Single arm with 1.5M length
179Double arm with 1.5 M length
180Providing 1:2:4 ratio CC foundation for street light fitting i/c Excavation including refilling ,Cement plastering as required, fixing the bolts supplied with the street light fitting etc as reqd
181Supplying and delivery of PVC insulated and sheathed armoured 3 core 1.5 sq.mm Copper conductor 1.1 KV grade cable as reqd.(BSNL approved make).
182Supplying and making end termination with brass compression gland for PVC insulated and sheathed armoured copper conductor cable of 1.1 KV grade of size 3core 1.5 sq.mm as reqd.
183S/F of SMC type loop in and loop out box / control box of size 140x140x95mm, i/c pdg SP MCB of 6A rating B series, cable terminals, earthing stud, connection complete as reqd.
184S/F of Compound Light control Unitconsisting of one analog Time switch, 24 Hrs mode with by-pass arrangement ,Din/base mounting type . DP MCB 6A,within a ncessary SMC enclosurewiring for interconnection, complete as reqd.L&T FM/1QT or ss make
185Supplying and delivery of following size of PVC insulated and sheathed Aluminium armoured cable of 1.1 KV grade as reqd.(BSNL approved make).
18631/2x150 sq.mm
18731/2x70 sq.mm
1884x 25 sq.mm
189SH-V DC cable & Allied works
190Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable onsurface/ recess or in the existing cable tray as required. (a) 1x 150 sq.mm
191Supplying and making end termination with 150 Sq.mm copper lugs for following size of PVC insulated and PVC sheathed copper conductor cable of 1.1 KV grade as required (a) 1x 150 sq.mm
192Supplying and fixing 500A rating DIN typeHRC fuseon 5mm thick hylum sheet with fuse adaptors for terminating the negative terminal on the VRLA / Li-Ion battery assembly i/c connections, testing and commissioning etc. as required.
193Providing & fixing on wall or in existing suitable size Powder coated 14 GMS Box with sufficient number of knock outs for the cables, 3 Nostinned copper bus bar of section 50mm x 6 mm thick, 0.30 meters long with sufficient number of holes for termination of incoming and out going cables, brass bolts, nuts and tinned copper washers on suitable epoxy resin cast bus bar insulators as required (2 Nos. for +ve and 1 No. for Equipment Body Earth)
194Providing & fixing on wall inthe existing MS frame work in existing suitable size Powder coated 14 G MS Box with door with sufficient number of knock outs for the cables, 2 Nostinned copper bus bar of section 20mm x 5 mm thick, 0.15 meters long on bottom and 2 Nos40mm x 5 mm thick0.15 meters on top,with 2 Nos DIN channel for MCBs with sufficient number of holes for termination of incoming and out going cables, brass bolts, nuts and tinned copper washers on suitable epoxy resin cast bus bar insulators as required (for termination of negative terminal)
195SH-VI EA set Auxiliary works , Display sign board & Pump set
196Providing and fixing braided copper equivalent to 25mmx5mm copper strip i/c crimping etc as reqd
197S/F wall mounting type ISI marked CO2 fire extinguisher of 4.5 KG capacity i/c providing necessary hooks etc as required (BSNL approved make with explosive certificate)
198S/F GI bucket each set comprising of two nos bucket of 9 ltr capacity and inscription " FIRE" in signal red colour on each bucket i/c p/f M.S.brackets with hooks for hanging the buckets painting and filling the bucket withsand etc as required.
199Design, composition , supply and installation of 10 mm Acrylic,laser cut letter pasting on 4 mm ACP sheet box , Acrylic layser cut letter polyuratine cotting (PU cotted or vinyl pasted in colour specified with internally lit LED , the frame shall be made of MS tube of 1.2 mm thick rusted treatment, double frame , 4 inch depth , application of silicon sealent on all joints to stop water sweepage , the ACP brand .. Aludecor/ flexibond cordd, accrylic letters branding .. 3 mm 3630 /3050, vinyl acrylic brand .. ATARI /MARCA or equialant LED brand LT / GOQ /HI sign with Samsung chip water proof , IP 67/68 grade 3 years warrentee with drivers complete as required.(contents to be approved by EIC) offollowing size. Size 8 feet x 3 feet
200Steel work welded in built up sections or framed work including cutting hoisting , fixing in positionand applying a priming coat of approved stell primer using structural steel , paintingwith synthatic enamel paint two or more coats etc as required.(for glow sign board support / EA exhaust extenssion etc ).
201SITC of1.0 HP capacity single phase monoblock pump sethaving suction and delivery pipe of size of 50mm X 40mm , discharge in LPS of 1.5 at a head of 20Mtr as required (M/s Kirloskar Make, Model: KDS 128+ or SS make)
202S/f 25A rating DPMCB with enclosure for the control of pumpset i/c connections etc as reqd( M/s Havells make, Model:DHMPCDPA032 or SS make)
203S/f 50mm size good quality flexible green hose with 3mm thickness i/c SS hose clips at both ends etc as reqd
204S/f 50 mm size good quality PVC foot valvei/c connections etc as reqd (M/s Kirloskar or SS make)
205S/f 40mm size good quality PVC pipe(6 Kg/cm2 ) i/c connections, accessories etc as reqd (M/s Finolex or SS make)
206Supply and installation of 100 mm diaof standard welded black MS, medium pipe as per IS:1239 (I) cut to required lengths including long bends, flanges etc and installed in existing angle iron supports through following way and applying heat resistant paint (600 deg C)etc complete as required. (Jindal India Ltd, TATA make)
Disclaimer :