}

138We / L-74 / 2021-22 Special Repair To Electrical Fittings And Fixtures In Bldg No P-114 Offrs Mess Of 153 Gh Special Repair For Conversion Of Existing Single Phase Power Supply To Three Phase Power Supply For 146 Ew Coy Under Ge 865 Ews At Leh, GE 865 EWS-Jammu And Kashmir

Military Engineer Services-MES has published 138We / L-74 / 2021-22 Special Repair To Electrical Fittings And Fixtures In Bldg No P-114 Offrs Mess Of 153 Gh Special Repair For Conversion Of Existing Single Phase Power Supply To Three Phase Power Supply For 146 Ew Coy Under Ge 865 Ews At Leh. Submission Date for this Tender is 12-11-2021. Electrical Maintenance Tenders in GE 865 EWS Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

29568517
Corrigendum : 138We / L-74 / 2021-22 Special Repair To Electrical Fittings And Fixtures In Bldg No P-114 Offrs Mess Of 153 Gh Special Repair For Conversion Of Existing Single Phase Power Supply To Three Phase Power Supply For 146 Ew Coy Under Ge 865 Ews At Leh
Open Tender
Indian
Jammu And Kashmir
GE 865 EWS
12-11-2021

Tender Details

138We / L-74 / 2021-22 Special Repair To Electrical Fittings And Fixtures In Bldg No P-114 Offrs Mess Of 153 Gh Special Repair For Conversion Of Existing Single Phase Power Supply To Three Phase Power Supply For 146 Ew Coy Under Ge 865 Ews At Leh

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Nov-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 12-11-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 48600.0 /-
Tender Value
INR 24.27 Lakhs /-

BOQ Items

Name of Work: Special Repair to electrical fittings and fixtures in Bldg No P-114(offrs Mess) of 153 GH and Special Repair for conversion of Existing Single phase Power Supply to Three Phase Power Supply for 146 EW coy under GE 865 EWS At Leh
Sl. No. Item Description
1Taking down carefully copper/aluminium point wiring (light, fan, socket and power point) complete fittings such as switches, ceiling rose, regulators, socket etc and removing material from site withand making good disturbed surfaces of walls, floors/ceiling to match the existing surface, complete all as specified and as directed by Engr-in-charge.
2M&l for Point wiring complete with 1.5 Sqmm nominal area forOne light/exhaust fan point controlled by one way switch of copper conductor multi stranded PVC insulated and unsheathed 1100 volts cable drawn through & including PVC casing & caping with standard accessories such as elbows, tees, junctions etc. And PVC moulded terminal box with top cover of including PVC insulated unsheathed solid 1.5 Sqmm copper conductor cable as continuous earth lead all as specified and directed by Engr-in-charge.
3All as per above item No 2 but One switch socket outlet 5 Amps, 230 volts point on same board with 1.5 Sqmm cable all as specified and directed by engineer in charge
4All as per above item No 2 but One switch socket outlet 5 Apms, 230 volts point on independent board with 1.5 Sqmm cable all as specified and directed by engineer in charge
5All as per above item No 2 but One bell point controlled by one bell push with 1.5 Sqmm cable all as specified and directed by engineer in charge
6All as per above item No 2 above but for power point 3 Pin Switch socket 15 Amp with PVC copper Conductor Cable Multistrand Unsheathed 2.5 Sqmm on Independent Board incl One Run 1.5 Sqmm Multistrand PVC copper conductor Cable For Earth Continuity in and including PVC casing fixed on Wall incl PVC Box/Wooden Board complete all as specified and as directed by engineer incharge
7Supply and fix in replacement of Modular switch SP one way 6 Amps 230 volts, 1 Module complete all as specified and directed by Engr-in-charge.
8Supply and fix in replacement of Modular switch SP one way 16 Amps 230 volts, 1 Module complete all as specified and directed by Engr-in-charge.
9Supply and fix in replacement of Modular switch socket combination out let 2/3 pin combined 6 Amps 230 volts 2 Module complete all as specified and directed by Engr-in-charge.
10Supply and fix in replacement of Modular switch socket combination out let 2/3 pin combined 6/16 Amps 230 volts 2 Module complete all as specified and directed by Engr-in-charge.
11S&F Metal flush Box 8 Module Complete All as specified and directed by engineer in charge
12S&F Metal flush Box 6 Module Complete All as specified and directed by engineer in charge
13S&F Metal flush Box 4 Module Complete All as specified and directed by engineer in charge
14S&F Metal flush Box 3 Module Complete All as specified and directed by engineer in charge
15S&F White cover Plate with frame (inner Plate) 8 Module Complete all as specified and Directed by engineer in charge
16S&F White cover Plate with frame (inner Plate) 6 Module Complete all as specified and Directed by engineer in charge
17S&F White cover Plate with frame (inner Plate) 4 Module Complete all as specified and Directed by engineer in charge
18S&F White cover Plate with frame (inner Plate) 3 Module Complete all as specified and Directed by engineer in charge
19Supply and replacement of ceiling rose, surface bakelite 65X50mm two to three terminals complete all as specified and directed by Engr-in-charge.
20S&F Lamp holder PVC/Polycarbonate type withy back plate suitable for batten fittingscomplete all as specifiedand directed by Engr-in-charge.
21S&F Old U/S Lamp LED 7 Watt, 230 Volts 50 Hz AC complete all as specifiedand directed by Engr-in-charge.
22Supply and fix in replacement of electrical bell push (Multi music type)modular type 6 Amp single pole 230 volt complete all as specified and directed by Engr-in-charge.
23Supply and fix in replacement of electrical bell push modular type 6 Amp single pole 230 volt complete all as specified and directed by Engr-in-charge.
24S&F in replacement Decorative Ultra Slim round Profile LED lighting Fixture with Extruded polycarbonate, enviromently friendly, energy efficient LED tube light 4 feet long of capacity 18 Watt 6000K (batten fitting) connecting up with three core flexible copper conductor cable of suitable size from celing rose complete all as specified and directed by engineer in charge
25S&F in replacement Decorative Ultra Slim round Profile LED lighting Fixture with Extruded polycarbonate, enviromently friendly, energy efficient LED tube light of capacity 5/4 Watt 6500Kconnecting up with three core flexible copper conductor cable of suitable size from celing rose complete all as specified and directed by engineer in charge
26Supply and fixing of LED Luminaire 600X600mm, 36 Watt, 220 V AC recessed surface mounted Type with high efficiency white powder coated CRCA housing with LED"s seamless front frame with white coloured flat acrylic cover including connecting up the driver three core flexible copper conductor of suitable size complete all as specified and directed by engineer in charge
27Supply and fixing of LED Luminaire 300X300mm, 18 Watt, 220 V AC recessed surface mounted Type with high efficiency white powder coated CRCA housing with LED"s seamless front frame with white coloured flat acrylic cover including connecting up the driver three core flexible copper conductor of suitable size complete all as specified and directed by engineer in charge
28S&F LED Post top made in cast aluminium spigot housing with decorative opal polycarbonate diffser and IP 65 protection of capacity 70 Watt LED white colour including suitable size of GI Pipe for fixing of light on post and electrical connection complete all as specified and directed by engineer in charge
29S&f LED garden light bamboo type new generation energy saving, enviromental friendly long life aesthtically designed aluminiumlandscape luminaire for diffused lighting with high power LED as light source of capacity 9 Watt LED 6000K including suitable size of GI pipe and PCC block for fixing of light around the garden and electrical connection complete all as specified and directed by Engineer in charge
30S&F in replacement of decorative wall mounting chrome finish fixture suitable for 40 Watt Mini GLS Lamp ELEGANT Type complete all as specified and directed by Engineer in charge
31S&F surface mounted round shaped LED downlighter with durable housing with AI heat Sink with diffuser to give glare free light with removable driver of capacity 18 Watt LED 6000K including electrical connection complete all as specified and directed by engineer in charge
32S&F LED Bldg Mounted security light fittings 45 Watts, having pressure die cast housing with IP 66 Efficient, protection with heat resistant toughned glass with individual LED lenses Complete with GI pipe of suitable size, GI bracket, Nuts, Bolts washers etc for mounted on bldg wall including making connection with ceiling rose of light point PVC insulated and seathed single core multi stranded copper conductor cable of size 1.5 Sqmm Complete all as specified and directed by engineer in charge
33S&F energy saving new generation bulkhead luminaire with opal diffuser of capacity 13.5Watt LED 6000K including electrical connnection complete all as specified and directed by engineer in charge
34S&F LED flood light luminaire with secondary optics Made in pressure die cast housing and heat sink in aluminium extrusion and IP66 protection Turbo Type of capacity 120Wattincluding electrical connnection complete all as specified and directed by engineer in charge
35Supply andreplacement of sheet metal enclosures with 20 Amp 240V socket plug top and MCBs single pole and neutral enclosure with three pin and earth plug and socket with one single pole 20 Amp MCB complete all as specified and directed by Engr-in-charge.
36S&F in replacement of any size and provided new sheet metal distribution board iron clad VTPN, double door with IP-54 iK-09, 08 ways protection suitable for MCCB as incomer and MCB as outgoing 415 Volts 3 Phase 50 C/S 4 Way, Complete with suitable size copper bus bar and netural link conforming complete with one MCCB 4 Pole 415 Volts 250 Amps rating, thermal magnetic with rapturing vap 35 kA of the same make as distribution board & including cutting chase to wall for fixing DB and Making good the disturbed wall surface all as required at site including testing complete all as specified and directed by Engr-in-charge.
37S&F in replacement of Old U/S sheet metal enclosure TPN 04 Way 415 Volts with blank plate Double door complete all as specified and directed by Engr-in-charge.
38Supply and fix in replacement of sheet metal enclosures for DBs double door when MCB"s to be used single pole & neutral 200 Amps bus bar of 12 ways, 240 volts, with blank plate complete all as specified and directed by Engr-in-charge.
39Supply and fix in replacement of sheet metal enclosures for DBs double door when MCB"s to be used single pole & neutral 200 Amps bus bar of 08 ways, 240 volts, with blank plate complete all as specified and directed by Engr-in-charge.
40Supply and fix in replacement of sheet metal enclosures for DBs double door when MCB"s to be used single pole & neutral 200 Amps bus bar of 04 ways, 240 volts, with blank plate complete all as specified and directed by Engr-in-charge.
41S&F in replacement of MCB SP 6 to 32 Amps240 Volts "C" curve complete all specified and directed by Engr-in-charge.
42S&F in replacement of MCB SPN 40 Amps, 10kA, 230 Volts, "C" curve complete all specified and directed by Engr-in-charge.
43S&F in replacement of MCB TPN 100 Amps, 10kA, 415 Volts, "C" curve complete all specified and directed by Engr-in-charge.
44M&L in replacement for Sub Main wiring with 2 runs of FR PVC insulated multistrand copper conductor cable of size 6.0 Sqmm along with one run of 6.0 Sqmm PVC insulated cable 1100 Volts multistranded copper conductor as earth wire in and including PVC casing & capping complete all as specified and directed by engineer in charge
45M&L in replacement for Sub Main wiring with 2 runs of FR PVC insulated multistrand copper conductor cable of size 4.0 Sqmm along with one run of 4.0 Sqmm PVC insulated cable 1100 Volts multistranded copper conductor as earth wire in and including PVC casing & capping complete all as specified and directed by engineer in charge
46M&L in replacement for Sub Main wiring with 2 runs of FR PVC insulated multistrand copper conductor cable of size 2.5 Sqmm along with one run of 2.5 Sqmm PVC insulated cable 1100 Volts multistranded copper conductor as earth wire in and including PVC casing & capping complete all as specified and directed by engineer in charge
47Supply laying & testing of XLPE cable insulated screened PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade, earthed system of size 3.5 core 70 sqmm complete all as specified and directed by Engr-in-charge.
48Supply laying & testing of XLPE cable insulated screened PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade, earthed system of size 2.0 core 10 sqmm complete all as specified and directed by Engr-in-charge.
49Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.5 mtr in depth and getting out, hard/dense soil, complete all as specified and directed
50Excavation in trenches, not exceeding 1.5 mtr wide and exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and exceeding 1.5 mtr in depth and getting out, hard/dense soil, complete all as specified and directed
51Returing, filling in (soil) including spreading, leveling, watering and well ramming in layers not exc, 25cm, complete all as specified and as directed by Engr-in-charge.
52Removing excavated material n. exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified and as directed by Engr-in-charge.
53M&L Sand cushioning to protection of underground cables, laid 8 Cmbelow the cable before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified in clause 19.75 ofSSR PART-1 and directed Note: Punned thickness shall be measured.
54Supplying and laying un-reinforced precast concrete cable cover, Class LV Type-I, flat, size 250mm x 150mm x 40mm, complete all as specified and directed
55Supply and Laying XLPE Insulated, Screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables, heavyduty with aluminium conductor, 1100 Volts (Earthed) grade cross sectional area 120 Sqmm 3.5 Core complete all as specified and as directed.
56Supply and Laying XLPE Insulated, Screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables, heavyduty with aluminium conductor, 1100 Volts (Earthed) grade cross sectional area 50 Sqmm 3.5 Core complete all as specified and as directed.
57Dismantling of ACSR conductors complete of any size and type from exisiting site all as directed by Engr -in- Charge.
58Taking down old insulator of any type shape and size type complete all as specified and directed by Engr -in- Charge.
59Supply and erection steel tubular swaged poles complete with cast iron base plate, finial taper plug, botls, nuts and screws as specified, type-410, SP-31 (09.00 meters long), including one coat of red oxide zinc chrome primer and two coats of aluminium paint on surface exposed to view and making 30cm wide strips (total 5 Nos) paint internally including writing pole number in white letters on black background complete and externally for portion embended in PCC complete all as specified and directed by engineer in charge Note : Excavation, earth work and cement concrete shall be measured and paid under relevant items of schedule.
60M&L for ACSR conductor any sizedrawn straighthorizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag, jointing jumpers,etc complete all as specified.
61M&L for galvanised steel wire 4mm dia for continuous earthing on HT poles or for fabrication of cradles hexagonal/ rectangular guards etc complete all as specified and directed .
62Supply, fabrication & fixingof cross arms, any type bracings, supports, clamps and back plates fabricated from structural steel sections made out of Fe-0-310/Fe-0-410 includingnuts, bolts, washers welding, bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed complete and duly painted with one coat of PRIMERand two coats of aluminium paintcomplete all as specified.
63M&L for Pin insulator porcelain white, brown or green 50 mm height, 65 mm dia for 1100 volts grade complete all as specified.
64S&F Shackale typeInsulator, porcelain, vitreous white, brown or green insulator incl galvanized mild steel straps, spindle,galvanised iron washers, nuts working pressure 11000 volts and size of 75X90 CMISI marked complete all as specified and directed by engineer in charge
65Material and labour for stay assembly with stay plate blow ,stay rod 20 mm dia180 cm long complete with accessories as shown in electrical plate No 1 including galvanized iron stay wire strand of size 7/4 mm and asscessories as shown in electrical plate No 1 of SSR Part 1(loop type insulator, stay clamp, excavation and concrete shall be measured and paid forseparately). Complete all as specified and directed by Engr-in-Charge
66Material and labour for PCC 1:3:6 type C–2 (using 40 mm crushed graded stone aggregate)as in foundation of poles studs including formwork etc complete all as specified and as directed by engineer in charge
67Material and labour for PCC 1:3:6 type C–1 (using 20 mm crushed graded stone aggregate)as in coping of poles studs including formwork etc complete all as specified and as directed by engineer in charge
68Supply and replacement of ON load change over switch 415 Volts in sheet metal enclosure four pole of capacity 200Amps with connecting acessories complete all as specified and directed by engineer in charge
69Supply and replacement of ON load change over switch 415 Volts in sheet metal enclosure four pole of capacity 320/315Amps with connecting acessories complete all as specified and directed by engineer in charge
70Supply installation, commissioning in replacement of factorey made cubical outdoor LT panel pedestal mounting type conforming to IP-54, CPRI Approved fabricated from 3.15mm thick CRCA sheet powder coated copper bus bar 400Amps rating capacity. THree Phase and 400 Amps for netural with Minimum clearence 75 mm all as per IS shall be avaliable inside for easy access and working condition Markings shoud be made to identify incoming and outgoing circuits and earthing bolts at two points inside panel for housing the following accessories:- (a)Copper Bus bar (RYB & N)-01 Set (b) Phase Indicating Lamp (RYB)-01 Set (c) MCCB 315/320 Amps50kA, 4 Pole 415 Volts 50Hz AC - 01 No (Incoming) (d) MCCB 100 Amp 35/36 kA 4 pole 415 Volts - 04 Nos(outgoing) (e)MCCB 100 Amp 35/36 kA 4 pole 415 Volts - 01 No (Spare) (f)MCB SPN 32 Amp - 01 No (g) MCB SP 32 Amp - 01 No (h) Digital Multifunctional meter voltmeter Ampmeter ferquency power factor with LED/LCD display Electronic type Note :- (i) The rates deemed to be inclusive of suitable size copper wiring / copper strips from Main I/CMCCB to change over switch, change over switch to Main Bus bar and Bus Bar to outgoing MCCB complete all as specified and directed. (ii) The design of panel, make of complete accessories and drawing of the LT panel should be submitted by the contractor for pre-approval from the Engineer-in-charge before order and execution at site.
71M&L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. Belowground level connecting to galvanised iron strip32x6mm as earth lead by means of bolts, check nuts and washers of GI or steel complete with 40 mm dia GI light grade protection pipe, 20mm dia medium grade watering pipe with funnel including charcoal dust salt PCC M-15, Type B_1 in pit with precast RCC M-15 1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0kg per Sqm, test point etc all as shown in electrical plate No-3 of SSR Part-I (2009) complete with necessary earthwork in any type of soil, removal to distance not exceeding 50mtr including testing on completeion complete all as specified and as directed by engineer in charge Note:- Earth pit chamber and RCC pit Cover shall be painted with two coats of red synthetic enamel paint over one coat of primer includingpreparing of surface
72M&L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. Belowground level connecting to GI wire 4mm by means of bolts, check nuts and washers of GI or steel complete with 15 mm dia GI light grade and connected to main distribution board/earthing test points all as shown in electrical plate No-5 of SSR part 1 and all as specified including testing on completeion Note:- The unit rate also including for excavation, earth work in any type of strata plain cement concrete 1:3:6 mix Type C1 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bars @ 150mm C/C bothways GI funnel with watering pipe, wire mesh protection pipe for earth lead Upto 7.50m long complete in addition to item above premable (notes) under sub heading earthing specified in SSR Part II earth Strip beyond 7.5m Shall be measured and paid seperately
73M&L for synthetic insulating Mat for electrical instrument of size 2mX1mX10mm complete all as specified and directed by engineer in charge
74Supply and laying GI pipe light grade 50 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail