Public Works Department-PWD has published Rmo Of Air Conditioning High And Low Side At 300 Bedded Janak Puri Super Specialty Hospital C-2B Janak Puri, New Delhi ( Sh Comprehensive Maintenance, Operation And Repair Work Of Blue Star Make Package Type And Ductable Type Air Conditioning Units ) . Submission Date for this Tender is 22-10-2021. Air Conditioner Tenders in Janak Puri Super Specialty Hospital Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Sub Head-I (Comprehensive Maintenance) Comprehensive Maintenance of following type and capacity Blue Star make Package Type/ Ductable Type Air Conditioner units including repair / replacement of all allied accessories/ parts like compressors, indoor/ outdoor units, repair of copper piping, controller, wiring, drain piping, gas charging (if required) etc. installed at Janak Puri Super Specialty Hospital, C-2B Janak Puri.(Note: The Servicing of all Units should be carried out on quarterly basis or as when required). |
2 | 22 TR Package Type Air Conditioning System (Model: DPA2642R1) - 07 Nos. |
3 | 8.5 TR Ductable Type Air Conditioning Units - 08 Nos. |
4 | 7.5 TR Ductable Type Air Conditioning Units - 01 No. |
5 | 5.5 TR Ductable Type Air Conditioning Units - 04 Nos. |
6 | Sub Head-II (Operation of PTAC & DTAC) Providing services for Operation of following type and capacity Blue Star make Package Type & Ductable Type Air Conditioner units installed at Janak Puri Super Specialty Hospital, C-2B Janak Puri including cleaning of filters, diffusers, indoor units, outdoor units, routine checking of electrical panels, mode of operation of indoor unit etc. for round the clock on monthly basis on all working days including Sundays & holidays as per terms & conditions and deploying a team of technically sound and capable staff as per terms & conditions attached. Details of equipments: 1. 22 TR Package Type Air Conditioning System (Model: DPA2642R1) - 07 Nos. 2. 8.5 TR Ductable Type Air Conditioning Units - 08 Nos. 3. 7.5 TR Ductable Type Air Conditioning Units - 05 Nos. 4. 5.5 TR Ductable Type Air Conditioning Units - 08 Nos. Staff to be deputed at site:- a). Operator - 3 Nos. (Round the Clock i.e. 6 AM to 2 PM, 2 PM to 10 PM and 10 PM to 6 AM) b). Khallasi - 1 No. (In General Shift) |
7 | Sub Head-III (Repairing Work of Blue Star Make PTAC) Supplying & Replacement offollowing capacity defective compressor with new one in existing Blue Star make package units including connection with suitable size of suction discharge copper pipe, copper strainer, capillary, nut bolts, anti-vibrating pads, connections, interconnections of the electrical wiring with thin cables, cleaning and leakage pressure testing with nitrogen gas for 24 hours, vacuumizing, charging with refrigerant gas complete including credit buyback of old material etc. as required |
8 | 11 TR Compressor |
9 | Supplying & charging of refrigerant gas in existing 22 TR capacity package type air conditioning unit complete including pressure testing of refrigerant circuits with nitrogen gas, vacuumizing the circuits & repairing / removing of any leakage in the system complete etc. as required. |
10 | Cleaning of Supply air duct through vacuumizing machines and motorize rolling brushes / scrubbers / compressed air jet nozzles and disposal of dust with all lead & lift for main block & additional block all floors and preparation of CD before & after cleaning with the help of robotic video camera and as per scope of works complete as reqd. (The measurements will be as per conditioned area only) |
11 | Supplying and replacement of PCB controller remote hand set unit in the existing Blue Star make 22 TR package type AC units including dismantling existing wornout PCB, connection, testing & buyback of the old etc. as required. |
12 | Supplying and replacement of outdoor unit motor in the existing Blue Star make 22 TR package type AC units including dismantling existing wornout motor, connection with providing thimbles, connectors, testing & buyback of the old etc. as required. |
13 | Servicing of existing Blue Star make 22 TR package type air conditioner units including cleaning the blowers and cooling coils with the help of pressure pump and chemical etc. complete as reqd. |
14 | Providing & Installation of refrigerant piping complete with copper pipe of size 11/8" & 5/8" with tube insulated including testing, commissioning and credit buyback of old materials etc. as required. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail