Repair And Preventive Maint Of Transformer / Ht Panel Vcb Ht Cable At Af Station Bhowali Repair And Preventive Maint Of Transformer Ht Panel Vcb Ht Cable At Af Station Bhowali, Bhowali-Uttarakhand

Military Engineer Services-MES has published Repair And Preventive Maint Of Transformer / Ht Panel Vcb Ht Cable At Af Station Bhowali Repair And Preventive Maint Of Transformer Ht Panel Vcb Ht Cable At Af Station Bhowali. Submission Date for this Tender is 21-10-2021. Transformer Supply Tenders in Bhowali Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

29334628
Corrigendum : Repair And Preventive Maint Of Transformer / Ht Panel Vcb Ht Cable At Af Station Bhowali Repair And Preventive Maint Of Transformer Ht Panel Vcb Ht Cable At Af Station Bhowali
Open Tender
Indian
Uttarakhand
Bhowali
21-10-2021

Tender Details

Repair And Preventive Maint Of Transformer / Ht Panel Vcb Ht Cable At Af Station Bhowali Repair And Preventive Maint Of Transformer Ht Panel Vcb Ht Cable At Af Station Bhowali

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Oct-2021 Index Page revised Other 14-10-2021
2 14-Oct-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 21-10-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 20000.0 /-
Tender Value
INR 10 Lakhs /-

BOQ Items

Name of Work: REPAIR AND PREVENTIVE MAINT OF TRANSFORMER /HT PANEL ,VCB HT CABLE AT AF STATION BHOWALI
Sl. No. Item Description
1Servicing of HT panel, detection of defective components, replacement of worn out parts and servicing/ cleaning of mechanical components after drawout of VCB trolly andTestingfor smooth operation manual/ remote after caliberation of relaytrough OEM of VCB/Test wing of UPCLand resetting& generation of testing report by the primary injection set for 11 KV VCB for OC/EF ,parameter of relay setting for healthy system, complete all as specified and directed by Engr-in-Charge. Note: Worn outminor parts shall be deemed to included in quoted rate. Major parts shall be measured and paid separately
2Supply only spare parts for VCBof any make all as specified :-
3Trip Circuit Supervision Relay • Static Relay. • Monitors Trip Coil in Breaker ON & OFF condition • Site selectable Trip Coil Voltage20- 110 VAC/DC make :- C&S / L&T / ABB / ashida
4Spring Charging Motor of VCB110 V-230 Volt AC supply for the opening and closing of contacts complete all as required and directed at sitecomplete all as per sample. .
5Indicating lamp LED
6Space heater 100 watt 230 Volt AC supply with thermostat
7Digital multifunction meter 96x96 mm Range 0-300-150 /A Model type 3 phase 4W EN 8400class 1.0, aux supply 110Volt with RS 485 port
8DigitalVoltmeter (0 to 12 KVsize 96x96 mm class 0.5 ,PTR 11000/rt3/110/rt3
93 phase Over currentand earth faultrelay with High set and RS -485port, CT rating 1Aor 5A field selectable , IDMT & Definite time characteristics • Last 30 trip data recording with date and time complete ,operating voltage18-240 VAC/DCMake :-ABB/siemens/L&T MC61CnX
10Detection of pin point fault in HT cable 11 KV (burried in ground/under road/path up to depth of 1.5 m) by cable fault locating machine comprising impulse generator,acoustic fault locator and reflectometer (laptop based) complete all as specified and as directed by Engr-in-Charge. Notes-(1) Cable fault locating machine to be arranged at site with in 12 hrs after intimation(2) Earth work will be measured seperatly.(3) Cost of transpotation in unit rate is deemed to be included.
11Handling, transportation of transformers of any make, type and any capacity 200 KVA of any make, model & type including hoisting, taking down from pole (pole mounted) or plinth mounted by any means mechanically pulley/mechanical crane, transportation to workshop for repair/maint. Reinstallation of Transformer in position pole mounted/plinth mounted including disconnecting and connecting all cable, earth lead, clamps and channels etc as per site requirement all as directed by Engineer-in-Charge. Note : If any damage to transformer/OH line/cables occur duringhandling, transportation or during hoisting/lifting, the same will be rectifiedby the contractor without any extra cost to the department.
12M&L for changing of Old / Burnt Copper coil by new EC grade copper coils with complete including insulation materialoftransformerall as Specified
13Striping out of Insulation of LV Windings and reinsulation of Coil with insulating material of transformer for any type and capacity of transformers complete all as specified and directed by Engr-in-Charge..
14Labour only for opening of top cover and allied parts of transformer of cap up to 200 KVAlifting of Core for repair , preheating charges for copper coils, assy of core coil assy including assy of copper coils, Tapping connections , insulation on Tap leads with insulation paper ,star connection by new EC grade copper on HV & LV side ., Baking charges for transformer job for each proper IR value in vacuum Chamber ( Auto Clave ) , refitting ofHV / LV bushing and transformer accessories with top cover, M& Lfor painting of transformer tank having hot oilresistant paint inside all as specified
15M&L Transformer oil having di-electric strength of 60 KV as per IS complete for top up/ replacement all as specified and as directed by Engr-in-Charge. (Oil should be supplied in sealed barrel of Power/Transol brand) Note: oil shall be filled in the transformers/stabilizers to be repaired or installed at site at different locations.
16Dehydration/Filteration of transformer oil at site by means of centrifuging machine in order to improve dielectric strength of oil as per IS-355. Break down voltage should not be less than 50 KV complete all as specified and directed.
17Supply and fix LVporcelain bushing of transformer 1.1KV with metal partsbrass as per IS 3347 part iiiand 4 Nos hexagonal nuts, complete all as specified and directed.
18(a) 1.1KV /250 Amp
19(b)1.1KV /400 Amp
20Supply and fix HV porcelain bushing of transformer 12KV/250 Amp with metal partsbrass as per IS 3347 part iii and IS 2009, complete all as specified and directed.
21M&L for hammer tone spray painting of transformer 11 KV/433 volts indoor/outdoor type of following capacity, including cleaning, scraping of exposed surfaces with shade as approved including writing MES number and machine number with black paint, letters 15mm wide and 50mm height complete all as specified and directed.
22(a)Cap ofTransformer 125 KVA to 250 KVA
23Supply and Replacement of silica gel breather assembly for following capacity of transformer
24(a) for transformer capacity 63 KVA to 200 KVA
25Material and labour XLPE insulated, screened,PVC bedded ,galvanised steel strip or wire armoured,electric power cables( heavy duty ) with aluminium conductor, 11000 volts grade, laid in trenches/poles/walls all as specified and as directed by the Engineer-in-Charge of following sizes:- 95 sqmm 3 core
26M&Lcable jointing kit for 11 KV (E) grade cable for indoor end termination heat shrink type complete with jointing material and accessories suitable forXLPE armoured aluminium conductor cable of size 95 sqmm3 core complete all as specified and directed.
27M&Lcable jointing kit for 11 KV (E) grade cable for out door end termination heat shrink type complete with jointing material and accessories suitable forXLPE armoured aluminium conductor cable of size 95 sqmm3 core complete all as specified and directed.
28M&Lcable jointing kit for 11 KV (E) grade cable for straight throughheat shrink type complete with jointing material and accessories suitable forXLPE armoured aluminium conductor cable of size 95 sqmm3 core complete all as specified and directed.
29Material and labour for earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to copper earth strip 20x3mm size (upto 7.5 metre from ground electrode) by means of copper/brass bolts, nuts, check nuts and washers all as shown in electrical plate No.3 of MES Schedule Part-I,connected to earth test terminal block and testing on completion with and including 40mm bore light grade GI protection pipe for strip upto plingth protection, PCC pit in mix 1:3:6 type C1, with RCC 1:2:4type B-1, 40 mm thick cover, reinforced with 6 mm dia MS bars 3Nos. both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore medium grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work complete.
30M and L for Cleaning of the area with removing the green grass patches /Bushes/small ornamental plants/herbs from the complete area of 11 KV receiving station with suitable T&P and covering the area with suitable peables of suitable size dressing/cleaning the area complete and afterwards sparying the complete area with suitable herbicideto stop the growth of weeds and grass asdesired and directed byEngr-in-charge.( Note: the complete Job will be done only after taking proper shut down of 11 KV HT Line. Shut Down will provided by the Dept. with Liasion of SED.) Note: cleaning of area Quoted be done once in a three months.
31Supply and fixing dial type temperature gauge 110mm dia temperature range 0-100 degree Cin repair all as directed by Engr-in-Charge.
32Supply and fixing lightning arrestor of 09 KV metal oxide (Gap less type) heavy duty, self supporting station class having nominal discharge current 10 KA (peak), class II , insualationlevel 28/75KV suitable for 11 KV supply including necessary connections with complete all as specified and directed. Make : Raychem RPG , Oblum ,CG
33Taking out unserviceable/faulty cable of any size/type for repair/replacement from pole/wall/cable duct/underground trench etc for reuse or depositing to MES store yardcomplete all as specified and as directed by the Engineer-in-Charge.(Note:-Excavation and earth work shall be measured and paid separately)
34Material and labour XLPE insulated, screened,armoured electriccables with aluminium conductor, 1100 volts grade, laid in trenches/poles/walls all as specified and as directed by the Engineer-in-Charge of following sizes:-
35(a) 50 sqmm 3.5 core
36(b) 35 sqmm 3.5 core
37( c)35sqmm 4 core
38(d)25 sqmm 4 core
39Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation of pole or cable trenches etc and getting out in hard/dense soil complete all as specified and as directed by the Engineer-in-Charge.
40Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm in hard/dense soil complete all as specified and as directed by the Engineer-in-Charge.
41Removing excavated materials exc. 250M but not exc. 500M and depositing where directed all as specified and directed by the Engineer-in-Charge.
42Material and labour for laying ofsub Class ‘B’ bricks,common burnt clay building bricks,designation 75 complete all as specified and as directed by the Engineer-in-Charge.
43Material and labour for sand cushioning for protection of underground cable, consolidatedand compacted with clean dry sand all as specified and as directed by the Engineer-in-Charge.
44Material and labour for galvanized iron tubing 80 mm bore (medium grade) with all fittings for protection of cables, laid in trenches / fixed to wall or pole complete including providing fixing clamps, bolts and nuts of suitable size all as specified and as directed by the Engineer-in-Charge.
45All as per item No 26 above but galvanized iron tubing 50 mm bore (medium grade) all as specified and as directed by the Engineer-in-Charge.