Border Security Force-BSF has published Sitc Of High Mast In Dark Patches Sensitive Area Of 88 Bn Bsf Shq Bsf Asr Pb Sitc Of High Mast In Dark Patches Sensitive Area Of 88 Bn Bsf Shq Bsf Asr Pb. Submission Date for this Tender is 08-10-2021. High Mast Tenders in DIG SHQ BSF ASR Punjab. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 25-Sep-2021 | BOQ | Other | 08-10-2021 |
Sl. No. | Item Description |
1 | PITC of 16 Mtr high mast shaft (as per Additional specification in NIT page No-40)in two sections suitable for 50 m/sec wind speed, with head frame , winch mounting bracket, luminaries carrige suitable to install 16 nos luminaries in symmetrical arrangement.Make-Philips, Bajaj ,Crompton/valmount |
2 | PITC of raising lowering system comprising double drum winch, 5 mm diameter SS wire rope, trailing cable , connector , intrgral power tool motor, manual handle, junction box, lightening finial. (wiring material from JB to individual luminaire & MCB in base compartment are not included and are the part of installation) |
3 | PITC of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template. |
4 | PITC 150 Watt LED Flood light fitting exclusive aluminum die cast IP 66 flood light source with PMMA lens for individual led suitable for specially design for border flood lights with suitable clamp nuts and bolts on existing BFL poles having following technical specification, Crompton make-model-LFLN-150-CDL-90X10-BFL or equivalent Phillips-xiiLM 79-Report from NABL accredited laboratory mandatoryBVP410 LED 172 CWHENBFG (150) or Bajaj. 3000k |
5 | Power Consumption-150 Watt(+ / - 5%) |
6 | Voltage range -100-300 VAC and with Stand up of 320 V upto 48 HRS, 350 V AC Driver will work for 02 HRS |
7 | Surge Protection- 5kv Internal |
8 | Surge protection (External)-10 Kv external |
9 | LED EFFICIENCY >130 lm/watt |
10 | LED Life>1 lacs Hours |
11 | Total Harmonic distortion< 10% |
12 | Power factor of fitting>0.95 |
13 | Beam angle- 90X 10 degree |
14 | Driver- Driver Should be IP 67 Potted type anti vibrationDriver efficiency > 87% |
15 | Name of LED-Crompton/Phillips |
16 | LM 79-Report from NABL accredited Laboratory mandatory |
17 | LM80- Mandatory |
18 | Warranty-02 Year from the date of installation |
19 | Qty |
20 | PITCof outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic swictching of luminaries, power tool control with 2 nos 9A contactors and raise lower push button, incoming 35 sq mm and outgoing as per reequirment. |
21 | Foundation |
22 | Earth work in excavation by mechanicallymeans(Hydraulicexcavator)/manual means over areas(exceeding 30 cm in depth,1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed. All kinds of soil.(3 mx 3 mx2.5m) |
23 | Centering& shuttering i/c sturring, propping etc and removal of form work for foundations & footings for Foundations, footings, bases of columns, etc. for mass concrete. 2.7x .3x4+.3x3x4=3.24+3.6=6.84 for 03 Nos |
24 | Providing and laying in position specified grade of reinforcedcement concerte, excludilng the cost of centering ,shuttering, finishing and reinforcement-all work up to plinth level:1:1.5:3 ( 1 cement: 1.5 coarse sand: 3 graded stone aggregate 20 mm nominal size) (.9x.9x2.7m)+ .3x3x3=(2.187+2.700=4.887) for 03 =14.661 |
25 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC Sheathed/XLPE aluminium coductor cable of 1.1 KV grade as required i) 3-1/2 X 35 sqmm |
26 | Steel reinforcement for R.C.C. work including straightening , cutting, bending, placing in position and binding all complete above plinth level.(Thermo Mechanically Treated bars)(20nos-12 mm Vertical bar lenght of 1.995 mtr ,9-nos-8mm stirrupusbar each-3.392mtr) 44 nos Cross bars of 10 mm length of 2.6 mtr |
27 | Earthing |
28 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required |
29 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required |
30 | Supplying and laying 6 SWG G.l. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with Gl thimble etc. as required.Details of cost for 30 Metre |
31 | Service conection |
32 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
33 | Upto 35 sq. Mm |
34 | Above 35 sq. mm and upto 95 sq. Mm |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy