Ca No Ge / H-07 / 2021-22 Repair / Maint Of Water Supply Distribution System Including Pipe Line Network Control System Valve Pit Repair Work Fire Fighting Wet Riser Including Sprinkler System At Ahrr Under Ge E / M R And R Hosp Delhi Cantt-10 Ca No Ge , GE EM RR HOSPITAL-Delhi

Military Engineer Services-MES has published Ca No Ge / H-07 / 2021-22 Repair / Maint Of Water Supply Distribution System Including Pipe Line Network Control System Valve Pit Repair Work Fire Fighting Wet Riser Including Sprinkler System At Ahrr Under Ge E / M R And R Hosp Delhi Cantt-10 Ca No Ge . Submission Date for this Tender is 08-10-2021. Irrigation System Tenders in GE EM RR HOSPITAL Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

29261283
Corrigendum : Ca No Ge / H-07 / 2021-22 Repair / Maint Of Water Supply Distribution System Including Pipe Line Network Control System Valve Pit Repair Work Fire Fighting Wet Riser Including Sprinkler System At Ahrr Under Ge E / M R And R Hosp Delhi Cantt-10 Ca No Ge
Open Tender
Indian
Delhi
GE EM RR HOSPITAL
08-10-2021

Tender Details

Ca No Ge / H-07 / 2021-22 Repair / Maint Of Water Supply Distribution System Including Pipe Line Network Control System Valve Pit Repair Work Fire Fighting Wet Riser Including Sprinkler System At Ahrr Under Ge E / M R And R Hosp Delhi Cantt-10 Ca No Ge / H-07 / 2021-22 Repair / Maint Of Water Supply Distribution System Including Pipe Line Network Control System Valve Pit Repair Work Fire Fighting Wet Riser Including Sprinkler System At Ahrr Under Ge E / M R And R Hosp Delhi Cantt-10

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Oct-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-10-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 44300.0 /-
Tender Value
INR 22.14 Lakhs /-

BOQ Items

Name of work:Repair/Maint of water supply distribution system including pipe line network, control system, valve pit repair work, fire fighting wet riser including sprinkler system at AHRR under GE E/M R&R Hosp, Delhi Cantt-10
Sl. No. Item Description
1Excavation in trenches in soft/loose soil not exceeding 1.5 metre deep and not exceeding 1.5 metre wide for laying of pipes in trenches and getting out, complete all as specified & directed by Engr-in-Charge.
2All as per item No 1 above but in hard/dense soil.
3Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each, after laying of pipeline complete all as specified & directed by Engr-in-Charge.
4Removing excavated surplus material to a distance not exceeding 50 metres and depositing where directed, at a level not exceeding 1.5 metre above the starting point, complete all as specified & directed by Engr-in-Charge.
5Taking up cast iron water mains (including all fittings) for the sizesof bore 300 mm with spigot and socket ends and lead joints including burning out joints and recovering lead complete all as specified & directed by Engr-in-Charge.
6All as per item No 5 .but dia 150 mm bore.
7All as per item No 5 .but dia 100 mm bore.
8M&L CI fittings upto 300 mm dia such as bends, tee, tail piece, collars, caps and plugs (any types) complete all as specified & directed by Engr-in-Charge.
9M&L CI pipes for the sizesof bore 300 mm with spigot and socket ends centrifugally cast, class A in any length laid in trenches complete all as specified & directed by Engr-in-Charge.
10All as per item No.9 but dia 150 mm bore.
11All as per item No.9 but dia 100 mm bore.
12M&L run lead joints to spigot and socketed DI/Cast Iron pipes of 300 mmbore all as specified in SSR Part-I (2009 ), complete all as specified & directed by Engr-in-Charge.
13All as per item No.12 but dia 150 mm bore.
14All as per item No.12 but dia 100 mm bore.
15Taking out old MS ERW pipe 200 mmbore, laid in trenches, under the roads or fixed on walls, with and including all old fittings and connections, complete all as specified & directed by Engr-in-Charge.
16All as per item No 15 here-in-before but for pipe of size 150 mmbore.
17All as per item No 15 here-in-before but for pipe of size100 mm bore.
18All as per item No 15here-in-before but for pipe of size 80 mm bore.
19M&L for laying the MS ERW pipe200 mm boreand of wall thickness 6.00mm with all fitting i.e. includingtee, elbow, reducer, union, nipple, socket etc. in new or old position, floors, walls, ceiling complete all as specified & directed by Engr-in-Charge.
20All as per item No 19 here-in-before but for pipe of size 150 mmbore.
21All as per item No 19 here-in-before but for pipe of size 100mmbore.
22All as per item No 19here-in-before but for pipe of size 80mmbore.
23Taking out GI Tubing 150 mmbore, laid in trenches/, under the roads or fixed on roof and wall with and including all old fittings and connections, complete all as specified & directed by Engr-in-Charge.
24All as per item No 23here-in-before but for pipe of size 100 mmbore.
25All as per item No 23here-in-before but for pipe of size 80 mm bore.
26All as per item No 23here-in-before but for pipe of size 50/40 mm bore.
27All as per item No 23here-in-before but for pipe of size 25 mmbore.
28All as per item No 23 here-in-before but for pipe of size 20 mmbore.
29M&LGI tubing 150 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc. in new or old position laid in trenches complete all as specified & directed by Engr-in-Charge.
30M&L GI tubing 150 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
31M&LGI tubing 100 mmbore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc. in new or old position laid in trenches complete all as specified & directed by Engr-in-Charge.
32M&LGI tubing 100 mmbore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
33M&LGI tubing 80 mmbore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position laid in trenches complete all as specified & directed by Engr-in-Charge.
34M&LGI tubing 80 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
35M&LGI tubing 50 mmbore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position laid in trenches complete all as specified & directed by Engr-in-Charge.
36M&L tubing 50 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
37M&LGI tubing 40 mmbore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position laid in trenches complete all as specified & directed by Engr-in-Charge.
38M&L GI tubing 40 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
39M&L GI tubing 25 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
40M&L GI tubing 20 mm bore, medium grade, ISI marked with and including all fittings i.e. tee, elbow, reducer, union, nipple, socket etc, in new or old position fixed complete to walls & ceiling or laid in floors complete all as specified & directed by Engr-in-Charge.
41Cutting existing GI pipes of 150 mm bore including taking down for alteration or addition including screwing existing pipe wherever required all as specified & directed by Engr-in-Charge. (Each cut measured).
42Cutting existing GI pipes of 100 mm bore including taking down for alteration or addition including screwing existing pipe wherever required all as specified & directed by Engr-in-Charge. (Each cut measured).
43Cutting existing GI pipes of 80 mm bore including taking down for alteration or addition including screwing existing pipe wherever required all as specified & directed by Engr-in-Charge. (Each cut measured).
44Cutting existing GI pipes of 50 or 40 mm bore including taking down for alteration or addition including screwing existing pipe wherever required all as specified & directed by Engr-in-Charge. (Each cut measured).
45S&F in repairstop valves , cast copper alloy, screwed down , high pressure,with crutch or butterfly handle,screwed both ends for iron pipe or for unions and fixed suitable for 50mm borecomplete all as specified & directed by Engr-in-Charge.
46All as per item No 45here-in-before but for 40 mm bore size.
47All as per item No 45 here-in-before but for 25 mm bore size.
48All as per item No 45 here-in-before but for 20 mm bore size.
49S&F, in repair float valve high pressure of PTMT with epoxy coated aluminium rod and high density plastic valve screwed for iron pipe of 50 mm bore including taking out old unserviceable valve, complete all as specified & directed by Engr-in-Charge.
50All as per item No 49 here-in-before but for 40 mm bore size.
51All as per item No 49here-in-before but for 25 mm bore size.
52All as per item No 49 here-in-before but for 20 mm bore size.
53Taking down old unserviceable Non Return Valve & supply and fix new cast iron non return valve of 150mm bore as per IS5312 part 1 PN 1.6 including nuts, boltscomplete all as specified & directed by Engr-in-Charge.
54Taking down old unserviceable Non Return Valve & supply and fix new cast iron non return valve as per IS W532 part-I of 100mm bore including nuts, bolts complete all as specified & directed by Engr-in-Charge.
55All as per item No 54here-in-before but of size 80 mm bore.
56S&F, in repair foot valves, without bypass arrangement, vertical installation, flanged type for iron pipe of 150 mmbore as per IS 4038 including taking out old unserviceable valve complete all as specified & directed by Engr-in-Charge.
57All as per item No 56 here-in-before but for 100 mm bore size.
58All as per item No 56 here-in-before but for 80 mm bore size.
59All as per item No 56here-in-before but for 50 mm bore size.
60M&L for fixingthe CI Sluice valve of 150 mm PN 1.6 as per IS;14846including CI flange with gaskit of matching holetofix easily to the existing systemof the 150mm bore in replacement after taking out the existing unserviceable CI Sluice Valvecomplete all as specified & directed by Engr-in-Charge.
61All as per srl item No 60 here-in-before but of size 100 mmbore.
62All as per srl item No 60 here-in-before but of size 80 mm bore.
63S&F in repair MS nut bolt with washer of any size all as specified & directed by Engr-in-Charge.
64M&L PCC 1:4:8 type D-2, using 40 mm graded stone aggregateincluding demolishing the existing damaged foundation,provision of necessary form work where required andfinishing fairto the exposed surfaces, complete all as specified & directed by Engr-in-Charge.
65M&L construction of valve pit chamber of internal size 1200x1200x1500mm including necessary excavation, returning filling in, & removal of surplus soil to a distance not less than 250M, 100mm thick PCC (1:4:8) type D2 (using 40mm graded stone aggregate ) in foundation,230mm thick brick work in CM (1:4), PCC (1:2:4) type B1 (using 20mm graded stone aggegate) for coping inclduing necesary form work, 15mm thick plastering in CM (1:4) including3mm thick M S Sheet cover fixed on MS angle iron 50x50x6mm,painting with two coats of synthetic enamel paint over a coat of red oxide primer on all steel/iron surfaces and provision of suitable locking arrangement complete all as specified & directed by Engr-in-Charge.
66M&Lconstruction of valve pit chamber of internal size 900x900x1200mm including necessary excavation, returning filling in, & removal of surplus soil to a distance not less than 250M and levelliing evenly, 100mm thick PCC(1:4:8) type D2 (using 40mm graded stone aggregate ) in foundation,23 cm thick brick work in CM (1:4), PCC (1:2:4) type B1 (using 20mm graded stone aggegate) for coping inclduing necesary form work, 15mm thick plastering in CM (1:4) including5mm thick M S Sheet cover fixed on MS angle iron 50x50x6mm,painting with two coats of synthetic enamel paint over a coat of red oxide primer on all steel/iron surfaces and provision of suitable locking arrangement complete all as specified & directed by Engr-in-Charge.
67M&L cleaning of under ground sump reservoir of 3,50,000 gallon capacity including scrapping of scales, flushing out of silt and muddy water, washing with anti bacterial solution etccomplete all as specified & directed by Engr-in-Charge.
68All as per item No 67 here-in-before but for under ground sump reservoir of 1,65,000 gallon capacity.
69All as per item No 67 here-in-before but for under ground sump reservoir of 50,000 gallon capacity.
70All as per item No 67 here-in-before but for Overhead reservoir of 20,000 gallon capacity.
71S&F in replacement rotational mouled polyethylene water storage tanks of triple layers. (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I of capacity 500 ltr complete all as specified & directed by Engr-in-Charge.
72S&F in replacement rotational mouled polyethylene water storage tanks of tripple layers (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I of capacity 1000 ltr complete all as specified & directed by Engr-in-Charge.
73S&F in replacementrotational mouled polyethylene water storage tanks of tripple layers (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I of capacity 5000 ltr complete all as specified & directed by Engr-in-Charge.
74M&L writing " Date of cleaning and capacity of Under Ground / over head reservoir" in neat & clean words on water reservoir of any capacity and height quite front to entry gate of installation with white synthetic enamel paint in English letters of 20 cm high and clearly visible with naked eyes, over black colour synthetic enamel painted surface, complete all as specified & directed by Engr-in-Charge.
75Cleaning and removing all scale and dirt, etc, from tanks and from mouths circulating pipes exceeding 500 and not exceeding 1000 ltr capacity complete all as specified & directed by Engr-in-Charge.
76S&F in replacementgun metal gate valve of 50 mm bore dia ISI marked to IS:778-1984 Class-I screwed in bonnet, non rising stem screwed ferrule ends as per IS-554 complete of the following sizes complete all as specified & directed by Engr-in-Charge.
77All as per Item No.76 but40mm bore
78All as per Item No.76 but25mm bore
79All as per Item No.76 but20mm bore
80S&F in replacement pressure gauge, bourdon type, 100 mm dial size, pressure range 0-14 Kg with syphon pipe and control valve complete all as specified & directed by Engr-in-Charge.
81M&Lpainting ofexisting MS/GIPipeline with one coat of primer and two coat ofBlack/Blue colour synthetic enamelled paint including preparation of surfaces complete all as specified & directed by Engr-in-Charge.
82S&F in replacement of hose real drum 30m complete along with brass adopter for fixing in hydrant valve complete all as specified & directed by Engr-in-Charge.
83S&F in replacement of fire brigade inlet connection 2 way complete all as specified & directed by Engr-in-Charge.
84all as above per item No.83but 4 way
85Supply, installation, testing and commissioning, in repacement, of oblique type hydrant valve made of stainless steel, ISI marked, 75mm NB flange inlet, single way outlet type with hose coupling adaptor of 63 mm size, instantaneous spring lock arrangement and blank cap with chain, conforming to IS 5290, type "A", suitable for hydraulic pressure of 21 kgf/cm2, complete all as specified & directed by Engr-in-Charge.
86S&F in replacement of 3 ply rubber hose reel pipe, ISI marked, of length 30 M, 20 mm nominal bore size, with nozzle with valve conforming to IS 12585, suitable for working pressure 25 kg/cm2, complete all as specified & directed by Engr-in-Charge.
87S&F, in replacement, of Reinforced rubber lined fire hose pipe as per IS 636, type "A", ISI marked, 63 mm nominal internal dia, 15 M long each, duly fitted with stainless steel coupling of 63 mm size, ISI marked with multi serrated tail and double instantaneous spring lock arrangement comprising of male half at one end and female half at other end complete with rubber cup washer and conforming to IS 903, suitable for hydraulic pressure of 21 kgf/cm2, complete all as specified & directed by Engr-in-Charge.
88S&F in replacement of short branch pipe, made of gun metal, ISI marked, instantaneous pattern type to suit fire hose delivery coupling of 63 mm size complete with stainless steel nozzle of 15 mm nominal size conforming to IS 903, suitable for hydraulic pressure of 21 kgf/cm2, complete all as specified & directed by Engr-in-Charge.
89Dismantling of unserviceable Fire Hose cabinet / housing placed in main bldg and making good the disturbed surface of wall / floor/ ceiling etc to match with original existing i.e. brick work, plastering, white washing, OBDGlass replacement etc and refixing it properly etc complete as specified & directed by Engr-in-Charge.
90M&L in repair for fixingthe hose box made of 18 gauge MS sheet 800mmx600mmx250mm with double door in front with 4mm thick glass and door frame made of 16 gauge MS sheet painted fire red outside and brilliant white insideafter taking out the existing unserviceable hose boxcomplete all as specified & directed by Engr-in-Charge.
91M&L for writing 250mm high letters "Fire" and "??" by means of self adhesive PVC reflectivetap of red colour on glass surfaces, complete all as specified & directed by Engr-in-Charge. Note :- The pair of words "Fire" and "??" shall be measured & paid for as one Job.
92Supply and fix in repair of air cushion tank with a min height of 2 mtr anddia of tank as per existing at site with relief valve 200mm or all as per site requirement complete all as specified & directed by Engr-in-Charge.
93Supply and fix in repair sprinkler quick/early response type as per IS 105/TAC guidelines 68 degree temp rating pendant type.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail