Provision Of Infrastructure For The Installation Of 400 Lpm Static Oxygen Generation Plant And Liquid Oxygen Storage Tank Of 6000 Litres And Related Paraphernalia Near Bldg No P 80 At Mh Ambala Under Ge (Utility) Ambala Cantt Provision Of Infrastructure F, Ambala Cantt-Haryana

Military Engineer Services-MES has published Provision Of Infrastructure For The Installation Of 400 Lpm Static Oxygen Generation Plant And Liquid Oxygen Storage Tank Of 6000 Litres And Related Paraphernalia Near Bldg No P 80 At Mh Ambala Under Ge (Utility) Ambala Cantt Provision Of Infrastructure F. Submission Date for this Tender is 20-09-2021. Tanks and Cylinders Tenders in Ambala Cantt Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

29221960
Provision Of Infrastructure For The Installation Of 400 Lpm Static Oxygen Generation Plant And Liquid Oxygen Storage Tank Of 6000 Litres And Related Paraphernalia Near Bldg No P 80 At Mh Ambala Under Ge (Utility) Ambala Cantt Provision Of Infrastructure F
Open Tender
Indian
Haryana
Ambala Cantt
20-09-2021

Tender Details

Provision Of Infrastructure For The Installation Of 400 Lpm Static Oxygen Generation Plant And Liquid Oxygen Storage Tank Of 6000 Litres And Related Paraphernalia Near Bldg No P 80 At Mh Ambala Under Ge (Utility) Ambala Cantt Provision Of Infrastructure For The Installation Of 400 Lpm Static Oxygen Generation Plant And Liquid Oxygen Storage Tank Of 6000 Litres And Related Paraphernalia Near Bldg No P 80 At Mh Ambala Under Ge (Utility) Ambala Cantt

Key Value

Document Fees
INR 1000 /-
EMD
INR 112000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: PROVISION OF INFRASTRUCTURE FOR THE INSTALLATION OF 400 LPM STATIC OXYGEN GENERATION PLANT AND LIQUID OXYGEN STORAGE TANK OF 6000 LITRES AND RELATED PARAPHERNALIA NEAR BLDG No P-80 AT MH AMBALA UNDER GE (UTILITY) AMBALA CANTT (Retender)
Sl. No. Item Description
1SCHEDULE A PART I (B/R WORKS) Excavation in trenches not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth for foundation of HT cables/pipes, foundation of poles,locatingfault of LT Cable and stay assembly etc or shaft, wells, cesspits, manholes, pier holes etc n.exc 10sqm on plan and n.exc 1.5mtr in depth and getting out in soft/loose soil complete all as specified and as directed.
2Material and labour for PCC (1:4:8) type D2 (using 40mm graded stone aggregates), as in foundation filling and mass concrete complete all as specified and as directed.
3Returning filling in foundation/trenches including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft loose soil complete all as specified and as directed.
4Removing surplus excavated soil/materials to a distance not exceeding 100 metre and depositing where directed at level not exceeding 1.5 metre from the starting point complete all as specified and as directed.
5Material and labour for brickwork, with subclass "B" bricks, straight or curved on plan to any radius, exceeding 6 metre mean radius built in cement mortar 1:6 complete all as specified and as directed.
6Material and labour for rendering 15 mm thick in cement mortar 1:4 with water proofing compound @2% by weight of cement including finished the surface even and smooth without using extra cement complete all as specified and as directed. Note: WPC shall be measured and paid separately as supply only.
7Material and labour for 15mm thick rendering in cement mortar (1:6)on surface of any description of brick or concrete and finished the surface even and smooth without using extra cement complete all as specified and directed.
8Supply only integral water proofing compound complete all as specified and as directed.
9Material and labour for preparation of new plastered surfaces of walls and applying three coats of white wash complete all as specified and directed.
10Material and labour for preperation of newly plastered surfaces of walls and applying two coats of cement base paint complete all as specified and as directed.
11Material and labour for preperation of old decorated brick/concrete, plastered or unplastered surfaces of walls, pillars, cornices, etc. by brooming down with steel wire brushing, scrapping, down smoke soot, moulds, moss, efflorescent salts, trading oil, greasy spots etc. and applying one coat of white wash complete all as specified and as directed.
12Material and labour for preperation of old decorated brick/concrete, plastered or unplastered surfaces of ceiling etc.by brooming down with steel wire brushing, scrapping, down smoke soot, moulds, moss, efflorescent salts, trading oil, greasy spots etc. and applying one coat of white wash complete all as specified and as directed.
13Taking down chowkats or frames with shutter, area exceeding 1.50 Square metre and not exceeding 4.00 Square metre (without taking off shutters from frame) and removing from site, including cutting holes in wall/concrete for taking out existing hold fasts and making good the disturbed portion of jambs and adjoining surfaces in CM (1:3) and finishing the surfaces to match with existing finish complete all as specified and directed.
14Supply and fixing of framed work such as in hung shutter, gates including pintle hinges, stops, hand made sliding door bolts, grills,gratings, etc. with ends of bars shouldered and/or riveted,or forged into spikes; framedguard bars; barred iron doors; ladders; framed balusters; walkways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and as directed.
15Supply and fixing of mild steel, plain, black sheet, 1.25mm thick, in covering to door shutters; covering to door chowkats (frames); chullah hoods; water tanks; water troughs; ducts; urinal troughs and funnels, etc. cut to size edges beaded if directed, holes punched; including round headed screws, clout nails or rivels and fixed to wood or steel members, etc., with plain 40 mm lap joints or welded/riveted seams including bending, turning up, mitred angles, stopped ends, outlets, etc. as required complete all as specified and as directed.
16Supply and fixing of steel window box type, using ERW hollow "P" section, factory made, comprising double frame for and including gauged and glazed skeleton shutter, 30mm thick, jointed internally with flat iron 25x3mm complete including hinges, handle, tower bolts, stops, lugs etc. all as shown on drawing No. TD-219sheet 1/3 to 3/3 of HQ CE Chandigarh Zone as applicable complete all as specified and as directed. Note: (i) For the purpose of measurementand payment double shutter both glazed and gauzed with frame shall be considered as one unit. (ii) Unit rate quoted against this item shall also include the iron mongery and grill 10 mm square bar irrespective of whatever shown on drawings and one shop coat of zinc chromate primer . The pattern of grill shall be all as shown on drawing (iii) Glazing, wire mesh and painting shall be measuredand paid for separately. (iv) The drawings may be referred from GE office or from this office during working hours.
17Preparing surfaces of wood and wood based materials, steel and iron work, new or old treating such as surfaces of hold fast, etc. area tarred n.exc 0.1sqm each, treated with tar or coal tar black paint complete all as specified and as directed.
18Material and labour for PCC (1:2:4) type B1 using 20mm graded stone aggregates as in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, fixing holdfasts, kneelers, apex stones, bed plates, water troughs and the like including use and waste of formwork including weathering, slightly rounded or chamfered angles and throating, as directed complete all as specified and as directed.
19Material and labour for bands, straps, hold fasts; clamps, supports or stays for rainwater, ventilating pipes, including bolts, if required: hooks (stay), heavy, for large gates; hook and pintle hinges: large hasps and staples;plate washers and similar small articles conforming to Fe-290 Gde-E-165 complete all as specified and as directed.
20S&F butt hinges 100mm size, heavy weight, cold rolled mild steel complete all as specified and as directed.
21Material and labour for hardcore of gauge not exceeding 63mm stone boulders, deposited, spread and levelled in layers not exceeding 15cm thick, watered and rammed to a true surface complete all as specified and as directed.
22Material and labour for 100 mm thick PCC (1:4:8) type D2 (using 40 mm graded stone aggregates) as in sub base of floors, finished rough and even to receive floor topping complete all as specified and as directed.
23Material and labour for 25 mm thick PCC (1:2:4) type B0 (using 12.5 mm graded stone aggregates) as in levelling course, laid and compacted in slope in floors, finished rough and even to receive floor topping complete all as specified and as directed.
24Material and labour for machine cut kota stone slab 16-18 mm thick ( size of each stonenot less than 55cm x 55cm), laid in flooring, over and including cement screed bed 15mm thick in cement mortar (1:4) base and jointed & pointed with grey cement slurry mixed with pigment to match shade of the slab including cutting, waste, rubbing and polishing (Granite finish) complete all as specified and directed.
25Material and labour for machine cut kota stone slab 16-18 mm thick ( size of each stoneshall match the floor slab), of hight as directed, laid in skirting or dado, over and including rendering 10mm thick in cement mortar (1:4) base and jointed & pointed with grey cement slurry mixed with pigment to match shade of the slab including cutting, waste, rubbing and polishing (Granite finish) complete all as specified and directed.
26Supply and fixing of pre-painted galvalume, aluminuim zinc coating, GI based corrugated steel sheet, 0.50mm thick, AZ-150 conforming to IS-15961, of red colour, having tensile strength of 550 MPa, as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed. Note- The sheets shall have super durable polyester quality paint of approved colour, 150 gm/sqm total on both sides, suitable for exterior application conforming to IS-15965.
27Material and labour for rolled mild steel sections such as joist, channel, angle, or tee sections, fixed independently, without connecting plates, etc. (cut to ordinary lengths i.e. within 20mm of the length indicated) including cutting to dead length where required, notching, drilling, fitting, riveting and/or welding or connecting with bolts and nuts (including rivets or bolts and nuts) etc. and similar work conforming to Fe-410-W Gde E-250 quality-A complete all as specified and directed.
28Material and labour for rolled mild steel sections as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for sliding doors; fixed with angle cleats or other connecting plates conforming to Fe 410-W (Gde-E- 250) quality-A complete all as specified and directed.
29Material and labour for rolled mild steel sections as in plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment conforming to Fe 410-W (Gde-E- 250) quality-A complete all as specified and directed.
30Excavating in post holes (or similar holes) each not exceeding 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface complete all as specified and directed.
31Material and labour for PCC (1:2:4) type B2 using 40mm graded stone aggregates as in foundations, filling and mass concrete complete all as specified and directed.
32Material and labour for rolled mild steel sections (channel, angle or tee sections) fixed independently, cut to length, as in hand rails, half round or other stock section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc. and similar work conforming to Fe-410 Gde E-250 complete all as specified and directed.
33Material and labour for mild steel round bars of 6 mm dia, as in reinforcement, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
34Material and labour for mild steel TMT bars of8 mm dia, as in reinforcement, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
35Material and labour for preparation of steel surfaces, of any description not otherwise described, over 10 cm width or girth and applyingtwo coats of approved colour synthetic enamel paint complete all as specified and as directed.
36Material and labour for preparation of steel surfaces, of any description not otherwise described, over 10 cm width or girth and applyingtwo coats of approved colour synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
37Supply and fixing of stainless steel wire cloth 0.36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire staples complete all as specified and as directed.
38Supply and fixing of sheet glass, 3mm thick, ordinary quality and glazing with oil putty in squares not exceeding 0.5 sqm in each pane complete all as specified and directed.
39Material and Labour for vibratory compacted, precast cement concrete, coloured (other than grey), rubber moulded , interlocking designer paver blocks( double glossy) in any and shape, confirming to IS-15658-2006 of 60mm thickness, M-35 grade in path, hard standing, etc. laid over and including 25 mm thick bedding layer of rammed sand complete, all as specified and as directed.
40Preparing surfaces of wood and wood based materials, steel and iron work, new or old treating such as surfaces of ends of posts, backs of chowkats, etc. area tarred exceeding 0.1sqm but not exceeding 0.50 Sqm each,treated with tar or coal tar black paint complete all as specified and as directed.
41All as per item No.40 above but on surfaces not exceeding 10 cm width or girth.
42Supply and fixing of chain link fencing of 4mm dia and mesh size 50mm x 50mm, weight not below 3 kg/sqm, including line wires, fixing to any type of standards, rails, straining bolts, etc. including provission of binding wire complete all as specified and as directed.Note: Line wires measured separately
43Supply and fixing of flat iron fillets (for securing chain link fencing, wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed.
44Material and labour for mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exceeding 5cm and not exceeding 10cm long with dia of neck 11 to 15mm complete all as specified and directed.
45Supply & fixing of PVC (SWR) pipe, 110mm size, single socketed, in any length, with rubber ring joints, laid in trenches or floor laid in trenches complete all as specified and directed.
46Supply & fixing of 20mm bore tubes, medium grade, galvanized, with all fittings such as sockets, bends, elbows, tees etc, laid in trenches complete all as specified and directed.
47Supply & fixing of 25mm bore tubes, medium grade, galvanized, with all fittings such as sockets, bends, elbows, tees etc, laid in trenches complete all as specified and directed.
48Supply and fixing of stop valves, 20mm bore, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified and as directed.
49Supply and fixing of water storage tank of 1000 litre capacity, HDPE triple layer, ISI marked, cylindrical vertical with closed top, fixed and hoisted in position on staging or roof complete with locking arrangement including over flow pipe, air lock pipe, ball brass valve 20 mm high pressure with polythene float and flynut, ISI marked, screwed andsuitable for iron pipe 20 mm bore complete all as specified and directed. Note:- Make of tank shall be engraved on the tank.
50SCHEDULE A PART II (MEDICAL GAS PIPELINE SUPPLY SYSTEM) (MGPS System): Refer PS Clauses hereinafter for notes, instructions and responsibility of bidder for design, supply, handling, installation, testing and commissioning of complete Medical Gas Pipeline Supply (MGPS) system including necessary accessories required in coordination with the GE and Users for this MGPS System work
51Supply, installation, commissioning and testing of Oxygen Manifold: Main confirming to ISO standards with Middle Frames 2 Banks x 6 Cylinder per Each bank Oxygen Manifold (without cylinders), suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 5/8” I.D. x 15swg as per BSEN 1057 with high pressure brass fittings made of high tensile brass equally spaced at 250mm fitted on powder coated MS frame and connections through non- return valves; 1.25 metre long high pressure copper tail pipes, made of high pressure copper pipe of size 5/16” I.D. x 16 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 300 bar and necessary test certificates accompany along with the supply.Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold. The middle frame shall be powder coated with cylinder holding chains for holding cylinders safely complete all as directed by Engineer-in-charge. Make: Oxicareengineers/Globalmedlife Solution/Lifeline Medisol/ Aktiv/ LMPL/ MK/ BSI/ MR Engg
52Supply , installation, commissioning and testing ofOxygen Manifold: Main confirming to ISO standards with Middle Frames 2 Banks x 2 Cylinder per Each bank Oxygen Manifold (without cylinders), suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 5/8” I.D. x 15swg as per BSEN 1057 with high pressure brass fittings made of high tensile brass equally spaced at 250mm fitted on powder coated MS frame and connections through non- return valves; 1.25 metre long high pressure copper tail pipes, made of high pressure copper pipe of size 5/16” I.D. x 16 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 300 bar and necessary test certificates accompany along with the supply. Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold. The middle frame shall be powder coated with cylinder holding chains for holding cylinders safelycomplete all as specified and directed by Engineer-in-charge. Make: Oxicareengineers/Globalmedlife Solution/Lifeline Medisol/Aktiv/LMPL/MK/BSI/MR Engg Notes for item No. 51 and 52 :The sizes of copper pipe mentioned are of minimum size and the quoted rate deemed to be inclusive of provn of higher sizes if any as per OEM requirement.
53Supply, installation, testing and commissioning of Fully Automatic Oxygen Control Panelwith automatic changeover cover made up of high quality Stainless steel, with built in LED display to indicate high normal and low line pressure, Capable to supply and distribution flow rate in excess of 1250 LPM. Panel cover fitted with lock to prevent unauthorized access and can be swung open for maintenance.The panel includes pressure gauge (63 mm) that indicates the gas pressure of each header and pipe line distribution pressure form Running Bank to Reserve Bank of Cylinder with timer complete all as directed by Engineer-in-charge.
54Notes: (a) Automatic control system consists two first stage regulators and consisting high pressure reducer panel, Alarm and control panel, left / right Ramp pressure sensors, pipeline pressure sensor, high pressure input valve, input filter, 315 Bar input gauge, high pressure reducer body, pressure set up screw, high pressure reducer drain, high pressure gauge, 2nd stage regulator, regulator set up, automatic change -over, automatic output pressure gauge in emergency outlet, back up system input, plant output regulators, plant output pressure gauges, plant output connectedpiping, control/power wiring and all necessary arrangement complete and should comply Indian Medical Standards and should comply standard : HTM 02-01/DIN/EN/ISO-7396-1 and should be CE certified.
55(b) 40 micron filter should be provided at the inlet of each high pressure regulators of the oxygen control panel.
56(c) The control panel will provide for two individual content contact pressure gauges to indicate the cylinder pressure in the two wings of the manifold and common pressure gauge to indicate the delivery / line pressure.
57(d) The control panel will have built in audio-visual signal lamp indications for bank Changeover.
58(e) The control panel will be covered with aesthetically suitable cover for safe operation indicating the respective services.
59(f) Control panel will have built in protection system to ensure safe operation by low voltage and all protections of surge, overload and earthfault. The Control panel shall include two pressure relief valves, one high pressure and one low pressure.
60(g) The panel should have the capacity to withstand maximum operating pressure of 220 bar for safety purposes.
61(h) The main control unit must be protected by amild steel with epoxy powder coated with a viewing window to monitor the digital display. Make: MEC Medical Equipment Co Ltd UK, Reanimed, CPX (UK), AKTIV, MPS
62Supply, Installation, testing and commissiong of Copper Piping of following dia (at ser no 54.03 to 54.05)and thickness with complete fittings/fixtures as per technical specification and BS: 13348 and as mentioned below all as directed by Engineer-in-charge:- (a) Installation of piping should be carried out as per approved medical standards with utmost cleanliness. (b) Only pipes, fittings and valves which have been degreased as per approved medical standards should be used . (c) Pipe fixing clamps for all diameter pipes. (d) Pipes should be non ferrous suitable for the diameter of the pipe and wherever required rigid metallic hanging or cemented supports to be used. (e) The main lines to the building to be taken overhead through heavy grade metallic poles or GI tubes with inspection pointsin metallic boxes wherever required . Adequate supports shall be provided while laying pipelines to ensure that the pipes do not sag. (f) All copper pipes and fittings should be made of phosphorous de-oxidized, non arsenic, and fully degreased.All pipes should be of Copper and copper alloys Seamless, solid drawn round copper tubes for Medical gases or vacuum. Suitable sleeves shall be provided wherever pipes cross through walls / slabs. All pipe clamps shall be non-reactive to copper.
63(g) All pipe joints should be made using inert gas fluxless brazing method. (h) All brazed joints in the piping shall be made up using brazing filler metals that bond with the base metals being brazed and that comply with Specification for Brazing Filler Metal, ANSI/AWS A5.8. Copper-to-copper joints shall be made using a copper-phosphorus brazing filler metal (BCuP series) without flux.Dissimilar metals such as copper and brass shall be joined using an appropriate flux with either a copper-phosphorus (BCuP series) or a silver (BAg series) brazing filler metal. Apply flux sparingly to the clean tube only and in a manner to avoid leaving any excess inside of completed joints. All joints should be of copper to copper and should be brazed brazing filler material without flux while being brazed joints shall be continuously purged with oil free dry nitrogen to prevent the formation of copper oxide on the inside surface of the joint. (j) All pipes should be installed without springing or forcing. (k)All pipes should be protected against mechanical injury in a manner satisfactory to authorities having jurisdiction. (l) Painting: All existing and proposed exposed pipes/should be painted with two coats of Synthetic enamel paint & color codification as per IS : 2379 of 1963. and approved medical standards. (m)All pipe clamp shall be non-reactive to copper.After erection the pipe should be flushed and then pressure tested with dry air at a pressure equal to 1.5 times of the working Pressure or 150 psig, whichever is higher for a period of not less than 24 hours in presence of medical authority/ MES authorities.
64(n) All copper pipes should be inspected and certified for medical use before dispatch and the pipe should be delivered plugged or capped at both ends. Notes: (i) The tenderer shall design & submit complete layout drawings with proper colour code, fittings, fixtures complete for approval of GE or rep of accepting Officer before placing order and the quoted rate includes for the same. (ii) The quoted rate inclusive of all mechanical protections with metallic pipes to pipe required. (ii)Contractor is required to visit the site prior to bidding Make: Mex flow/Janya/ Metal Gem / Cubex/Metalco
6542mm OD Copper pipe with fittings 1 mm thick
6628mm OD Copper pipe with fittings 1 mm thick
6722mm OD Copper pipe with fittings 1 mm thick
68Supply, Installation, testing and commissioning ofvalves, ball type, lockable in open and closed position and shouls fully meet and comply HMT 02-01 duly CE marked/NFPA 99 UL listed. The valves should be provided with PTEF seal, Brass body with nickel plating having quarter turn handle opening, sizes suitable for 12mm OD copper pipe to 22/28mm OD copper pipes with screwed ends. These shiould have brass adopter suitable for copper pipe and should be manufactured by an ISO 9001 certified company duly degreased for use with oxygenvalves used must given clear indication of the direction of closing. All valves should be pnuematically tested for twice the working pressure and degreased for medical gas service before supply. Each pressure gauge should be 2" dial with 1/8" BSP mate thread connection with 0 to 16 kg/cm2 dial reading and vaccum gauge should be similar but 0 to 760 mm/hg dial reading fitted along with isolation valves. All gauges should come with calibration certificate complete all as directed by Engineer-in-Charge. MAKE- CONEX/ RB/ AKTIV
6922 mm OD with brass NRV
7028 mm OD with brass NRV
71Material and labour for cable tray made up of MS angle of 50x50x6mm each and 150mm long welded/fixed with nut bolts to any steel frame or embedded in brick wall/concrete using PCC (1:2:4) typr B1 using 20mm graded aggregates complete allall as specified and directed.
72Notes for items in Sl Nos. 50 to 56: The quoted rate shall be inclusive for the following:- (a) The Contractor shall provide comprehensive on-site warranty (Including All Spares, Accessories and Labour) for a period of 3 years from the date of final acceptance of the complete system after successful and complete installation and commissioning with regular updation of newer technology as and when evolved. (b) The Contractor shall, depute trained manpower tomaintain manifold and medical gas pipeline system in case of any breakdowns within 24 Hrs. The technical maintenance personnel of the Contractor shall beresponsible for supervision and maintenance shall be available to reach the site(s) within 1 hour"s notice. (c)If the performance of any individual equipment or system is not satisfactory, the same shall be replaced by the contractor free of cost.
73(d) If it is found that to meet the performance criteria, any extra equipment is required the same will be provided free of cost by the contractor. (e) All faults appearing and their rectification shall be periodically advised to the hospital, the period being not more than a month. (f) Any lacuna or lacunae noticed in the functioning of the installation as a result of any design feature shall be rectified by thecontractorfree of cost. (g) The Contractor shall fully associate the engineers and technicians forMH Ambala during installation, testing, commissioning, operation and maintenance period. The testing of the entire system shall be carried out in the presence of GE / AGE and Officer rep (Min 02 Nos.) from Hospital authorities. (h) The Contractor shall train the staff of MH Ambala the operation of complete medical gas and oxygen plant system fopr a period of two weeks. (j) The Contractor shall submit MOU with authorised Medical Service engineer/ registered Bio medicalengineer services experienced in the relevant field for not less than 5 yearsimmediately before placing work order. (k) All electrical wiring/cables,cable tray, earthing, Control panels, connected electrical & pipeline distribution systemwith all connected accessories of complete medical gas system and oxygen plant system is deemed to be included in the quoted rates.
74(l) The MGPS system installation shall be deemed to have been completed only on satisfactory performance of the MGPS system and acceptance of the satisfactory test results by the representative detailed by the Accepting Officer. In case of any failure during the testing the contractor shall be responsible to carryout necessary rectification/replacement of defective items/system parts thereof as directed by the Garrison Engineer immediately next day at no extra cost to Government.The decision of the GE shall be final and binding in this regard. The installation shall be re-tested after rectification/ replacement of the defective components, the installation/ equipments shall be finally taken over after the contractor has given satisfactory test as certified by the GE.
75(m) The entire installation (after satisfactory completion of all tests and taking over) shall be deemed to be guaranteed by the contractor for efficient performance for thirty six months from the certified date of completion of work. In case of any fault arising during this period the contractor shall do the rectification/ replacement of defective parts, as the case may be, on his own expense. The defect liability period referred to in condition 46 of IAFW- 2249 (General condition of contracts) for the purpose of this contract, shall be deemed to be the period covered by the guarantee given by the contractor.
76SCHEDULE"A" PART-III (E/M WORKS) Material and labour for point wiring with 1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH, 1100 Volts grade with multi stranded copper conductor drawn through and including medium grade, ISI marked, PVC conduit not less than 25mm dia with accessories, concealed on wall/ ceiling and including1.50 Sqmm single core PVC insulated, unsheathed cable FRLSH, 1100 Volts grade stranded copper conductor green colour as earth continuity conductor and connected to common earth dolly with and including mild steel sunken box or pressed steel terminal boxes made out of 1.6 mm thick mild steel sheet metal confirming to IS-5139 (Pt-I) of 1969 and IS: 14772-2000 with earth dolly and coated with two coats of anti corrosive paint over a coat of red oxide primer both internally and externally including new 3mm thick plastic laminated sheet top cover extended up to 25mm over sunken box all around for housing the switches, socket outlet, fan regulator etc. with brass screws and brass washers and making good the disturbed surfaces as per existing for one light/ fan point controlled by one switch complete all as specified and directed. Notes :- (i) Switch, socket, lamp holder, ceiling rose and fan regulators to be measured and paid for separately.(ii) PVC Conduit shall conform to IS 9537 part I & III. (iii) All chases will be cut by chase cutter only.(iv) The concealed conduits and MS boxes shall be verified by Engineer-in-Charge before making good the surfaces by plastering and other finishes.
77Description all as per Srl item No.58.00 here in before but for one 3/5 pin socket outlet point, 5 Amp, on same board with other switches.
78Description all as per Srl item No.58.00 here in before but for one 3/5 pin socket outlet point, 5 Amp, on Independent board.
79Description all as per serial item No. 58.00 above, but for one socket point, 3/5 pin,15 Amps, on independent board, with 2.5 SqmmPVC, FRLS-H, unsheathed, multistranded cable, 1100 volts grade, ISI marked, including 2.5 Sq mm size, green colour, PVC insulated FRLS-H, continuous copper earth wire and connected to common earth dolly complete all as specified and as directed.
80Description all as per serial item No.58.00 above, but for one metal clad switch for AC, with 4.0 SqmmPVC, FRLS-H, unsheathed, multistranded cable, 1100 volts grade, ISI marked, including 4.0 Sq mm size, green colour, PVC insulated FRLS-H, continuous copper earth wire and connected to common earth dolly complete all as specified and as directed.
81Material and labour for sub main wiring with two single core, 6 sqmm, FRLS-H, 1100 volts grade, ISI marked, with multistranded, PVC insulatedunsheathed copper conductor cable, drawn in and including rigid non metallic PVC conduit, medium grade, not less than 25 mm dia, ISI marked for housing cables, concealed in wall or ceiling including necessary cutting, chasing with machine and making good disturbed surfaces as per existing, with accessories with and including one additional 6 sqmm, PVC insulated, stranded copper conductor, FRLS-H, green colour for earth continuity conductor connected to common earth dolly complete all as specified and as directed. Note- Three runs of cable and one run of concealed conduct shall be measured as one unit.
82Supply and fixing of switch piano, polycarbonate, 5 Amps, one way, flush type, single pole, 230 volt, ISI marked complete all as specified and directed.
83Supply and fixing of switch piano, polycarbonate, 15 Amps, one way, single pole, flush type, 230 volts, ISI marked complete all as specified and directed.
84Supply and fixing of socket outlet, polycarbonate, 2 in 1, 3 pin, 5 amps, flush type, 230 volts complete all as specified and directed.
85Supply and fixing of socket outlet, policarbonate, 2 in 1, 3 pin,5/15 Amps, flush type, 230 volts complete all as specified and directed.
86Supply and fixing of ceiling rose, surface bakelite, 65x50mm, three terminals along with back plates complete all as specified and as directed.
87Supply and fixing of angle lamp holder, PVC/Polycarbonate type, with back plate suitable for batten fittings complete all as specified and as directed.
88Supply and fixing of indoor decorative surface mounting LED tube light fitting, batten type, with poal diffuser, high efficient aluminium housing body in CRCA body suitable for LED tube, high efficient, AC 220-240 volts, 50 Hz with and including 18/20 watt LED tube rod luminaries (warm/cool as per site requirement), environment friendly, energy saving, high efficient PMMA diffuser, T8 with aluminium extrusion, heat sink and connecting with copper conductor flexible cable of size 0.50 Sqmm from ceiling rose to connector of the light fitting complete all as specified and as directed.
89Supply and fixing of exhaust fan , heavy duty, 380mm sweep, minimum 900 RPM, AC, single phase, 230 volts, metal body with louvers complete and connecting up from ceiling rose to fan by three core copper wire of suitable capacity, fixing exhaust fan and louvers with suitable size MS bolts and nuts in drilled holes of existing brick/PCC wall, suitable for mounting exhaust fan over and including supply and fixing of ply wood sheet/plastic sheet on brick/PCC wall surface for mounting of exhuast fan using fixing arrangement with anchor fastner/steel frame sheet etc and testing complete including making good the disturbed surfaces to match with existing by PCC/cement mortar work and finishing with white washing/colouring/distempering etc complete all as specified and directed.
90Supply and fixing of ceiling fans, AC, single phase, 230 volts, 1200mm sweep, with BLDC technology, maximum power input upto 26 watt, copper wire motor, with 5 star BEE rating along with canopy cover, down rod, U clamp, electronic regulator 2 module, socket type, 450 watt, and 3 core PVC flexible cable 1 sqmm for making the connection of fan including hanging fan in clamp and connecting to existing electric connections complete all as specified and as directed. NOTE: Contractor shall write MES No. with black colour synthetic enamel paint on ceiling fan as directed.
91Supply, installation, commissioning and testing of distibution board for MCBs, SPN, 4 way, made of CRCA sheet, dust and vermin proof, double door, IP 43, as per IS 8623, 240 volts, with and including 200 amps fully insulated copper bus bar fixed on wall duly grouted in solid block wall with and including copper lugs/thimbles duly crimped for connection complete all as specified and directed.
92Supply and fixing of MCB SP, 6 to 32 Amps, 240 volt, 10 kA, "C" curveIP-20, transperent label holder, fully insulated safety shutters, suitable for cable upto 35 Sqmm cross sectional area, ISI marked, connected with suitable lugs and testing complete all as specified and directed.
93Supply and fixing of MCB SPN, 40 Amps, 240 volt, 50 Hz, breaking capacity 10 kA, "C" curve conforming to IS-13947-3 and IEC-60947-3:2001, double pole complete all as specified and directed.
94Supply and fixing of sheet metal enclosures vertical load line TPN distribution board, 4 ways, double door powder coated alongwith 250 Amp rated busbar with and including MCCB 3 pole 160 Amp, 25kA adjustable type as incomer with suitable size of MS cabinet fabricated by 2mm thick MS sheet, 415 Volts, 10 KA and making all type of connections using proper size of gland for incomer cable complete loadline TPN concealed on wall surface & making good the disturbed surfaces as per existing complete all as specified and as directed.
95Supply and fixing of MCCB, 100 Amps, 4 pole, 16 KA, 415 volt, connected with suitable lugs and testing complete all as specified and directed.
96Supply and fixing of TPN DB-VTPN for independent mounting DRX3 160 MCCB enclosure, 4 way, IP-43, IK-09 with 250 Amp bus bar, 415 volts, 10 kA connected with suitable lugs and testing complete all as specified and directed.
97Material and labour for earthingwith galvanised earth plate electrode 600mm x 600mmx 6mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m belowground level with top edge of the earthplate not less than 1.5m belownormal groundlevel, connected to 4.00 mm GI wire earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire and thimbles protected by galvanized steel pipe 15mm dia (light grade) and connected to main switch or main control board all as shown in Electrical Plate No.3 of SSR Part-I & including necessary excavation and earth work in any type of strata, PCC (1:3:6) type C1 in pit, RCC cover slab 50mm thick in 1:2:4 type B-1 using 8mm dia TMT bars @10cm c/c both way with one 8mm dia bar as handle for lifting, 20mm dia GImedium grade watering pipe, funnel, wire wesh, charcoal or coke & salt in alternate layers, etc.all as indicated including testing on completion complete all as specified and directed.
98Supply and fixing in replacement of LED security light luminaire 45 watt, 240 volts, AC, 50 Hz, made up of die castaluminum housing with sealed toughened glass cover, top opening separate driver compartment with frame, safety input voltage range 160 to 270 Volts, IP66 protection, suitable for wall mounting, SMD led array with lense, cool white 6500K, LED efficacy>120 lm/W and system efficacy 90 lm/W, CRI>70%, power factor> 0.95, working temperature range -20 degree centigrade to 60 degree centigrade, built in surge protection of more than 5 kv with facility of power supply including service brackets of GI pipe 40mm bore, light grade, of length 0.90 metre, bent to required shape, fixed with MS clamps of size 40 x 6mm flat iron strip, 150mm long and 4 Nos.8mm dia stainless steel bolts andnuts and washers and suitable reducer for connecting to GI pipe as required at site and making all required electrical connections using 3 core copper flexible cable including cutting,drilling holes, welding etc complete all as specified and as directed.
99Supplying installing testing and commissioning diesel engine driven generating set 415 V, 3 phase, 4 wire as per BS 5514/IS-10002 complete with standard control panel, of capacity continuous rating 100 KVA/80 KW at NTP conditions with acoustic enclosure and canopy coverconsidering all derating factors and comprising of the following :- (a) ALTERNATOR : Self regulated with brushless self excitation 100 KVA 415 V, 3 phase, 4 wire, 50 HZ, 0.8 P.F.,1500 RPM, with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted, screen protected drip proof type with class "F" insulation, closed coupled single bearing alternator, with necessary controls as recommended by the manufacturers, conforming to BS-5000/IS-4772, capable of supplying unbalanced load. (b) Engine : Multi/cylinder,compression ignition, heavy duty,compact diesel engine liquid cooled with standard accessories, all as per BS-5514/ISO-3046,1500 RPM,control gauges, RPM/Hours meters etc; shaft H.P. suitable for generating application and capable of giving an output of 100 KVA/80 KW for coupled alternator under NTP conditions, complete with following:- (i) Flywheel housing with flywheel to suit closed coupled single bearing alternator.(ii) Air-cleaner dry type with vacuum indicator.(iii) Fuel pump and fuel piping 15mm M.S. pipe with bends, flanges etc.(iv) Fuel filter with water separator and filter element. (v) Lub-oil filter with filter element (vi) D.C. starter 12 volts. (vii) Storage Batteries of suitable voltage and ampere-hours as recommended by the manufacturers. (viii)Residential silencer as per CPCB norms (x)Supporting/fixing arrangement for muffler with celiling through antivibration pads. (xi) Engine overspeed stop/trip switch. (xii) Radiator with fan.(xiii) Dynamo for battery charging.(xiv) Corrosion inhibitor coolant.(xv) Engine control panel electronic digital display type consisting of battery voltage indicator, lub oil temp and pressure gauges coolant water temp gauge, RPM indicator cum hour meter etc.(xvi) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP).(xvii) Any other devices/accessories recommended/supplied by the manufacturers as standard eqpt.Engine.
100(c ) SKID : The engine and alternator will be coupled,aligned and mounted on a specially designed common base frame fabricated from M.S. channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads of required size and numbers as recommended by the manufacturers for mounting of 100 KVA/80 KW D.G. set. (d) AMF Panel : AMF panel shall be of suitable size factory made indoor cubical type front openable fabricated from CRCA steel sheet 1.6 mm thick complete as per manufacturer specification of Diesel Engine suitable for DG Set of capacity 100 KVA grouted in floor by providing PCC 1:2:4 type B-2 foundation of suitable size as per manufacturers recommendations complete in all respects and consisting of the following :- (i) Contactor ML of suitable capacity.Make:-L&T, C&S, ABB, Siemens (ii)Aluminium bus bar of capacity 200 Amps (04 Nos) for phase and neutral. (iii) Sensitivity relay set unit with auxiliary relay CT"s.(iv)Electronic latch circuit with tripping indication. (v)Instantneous tripping device suitable for complete panel over current 0.5 Amp. (vi) Reset facilities for complete protection of AMF Panel.(vii)Self squential starting relay unit 12 volts DC complete with alarm and power contactor. (viii) Electronic timer 220 Volts formain contactor with 1 No NC auxiliary contactor. (ix) Electronic timer 220 volts for fuel cut off operation for with 1 No NC auxiliary contactor. (x) Battery charging unit 12 volts 10 amp complete with digital volt metre & Amp metre. (xi)All as per item No ix here in before but for fuel cut off operation.(xii) Electrical starter 12/24 volts DC as per manufacturer"s design. (xiii)Digital volt meter 0-500 volts panel mounting type size 96square mm with digital selector switch.
101(xiv)3 Phase electronic energy meter for measuring meter for measuring generated units.(xv) Frequencymeter (Digital type) of suitable rating.(xvi)MCCB 200 Amps 4 Pole 25 kA & MCCB 200 Amp 4 Pole 25 kA breaking capacity with fixed thermal and magnetic release, for main supply & DG Supply adjustable over load and adjustable short circuit each 01 No (xvii) The AMF panel shall have manually by pass arrangement in case offailure of AMF Panel.(xviii) Other accessories, if any , as per manufacturer instructions.(e) Diesel tank of capacity for 8 hours continuous run on full load, with caliberated scale (fuel level indicator) dip stick, fuel inlet/outlet , Air vent, drain plug and inlet arrangement for direct filling, including suitable size gate valve in outlet, tank to be fitted at suitable height.(f)Sound proof enclosure with residential silencer (CPCB) approved) the sound less than 75 db at a distance of 1 meter from canopy in free field zone.(g) PCC/RCC foundation complete as per manufacturers own design/ Or as per directions of Engineer-in- charge.(h) Documents : Three sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty/test certificates, schematic diagrams of control panels.(j) other items : List of tools and two years normal maintenance spares as per manufacturers recommended lists, duly priced, item wise.Notes :(i) Contractor will satisfactorily conduct load test ofDG set for 12 hours including run on 10% overload for 1 hour.(ii) Testing equipment will be arranged by the contractor.(iii) Fuel/oil required for load test shall be arranged by the contractor and cost thereof is deemed to be included in the lump sum amount quoted by the contractor.(iv) AMF panel and DG set shall be procured from same OEM i.e make of both shall be same.
102Supply, install, test and commissioning of step down transformer, out door type complete with standard fittings and accessories, HT 11 KV, 3 Phase, LT 433 Volt, 3 Phase, 4 wire with off load tap changer on primary side to carry secondary voltage + 5% to-10% with tappings at every 2.5 % all as per IS 1180/2014 (Level-II) of capacity 100 KVA, copper wound, oil cooling with fins vector group : DYn 11, including initial oil filling complete all as specifiedand directed including the following accessories :- (a)Three Nos porcelain bushing HT 11 KV with brass bushing rods, nuts, bolts & washers etc inside cable end box. (b)One cable box LV side consisting of 4 Nos porcelain with brass bushing rods complete with nuts and washers suitable for runs of 3.5 core LT UG cable. (c)Oil conservator with filler type drain valve and oil level gauge. (d)Dehydrating breather with first fill of dehydrating agent.
103(e)Explosion vents. (f)Thermometer pocket on tank cover. (g)One No 100mm dia, dial type thermometer vapour pressure type having range 0 to 120 degree centigrade. (h)Rating plate and terminal marking plate. (j)Earthing arrangement. (k)Oil level gauge. (l)Oil drain filter valve. (m) Oil drain valve. (n)Lifting hook. (o)Oil conservator with filling hole and cap.
104(p)Air relief valve plug. (q)Four plate solid cast steel detachable rollers. (r)Earth bushing for neutral outside the cable box for providing independent earthing for neutral. (s)Necessary channel on foundation for fixing the transformer with joint and stopper. Note:-Necessary civil work like as foudation/ platform for the equipment of appropriate size as reccomended by OEM or as indicated/directed by the Engr-In-Chargefor the connected work is required deemed to be included in the unit quoted rate.
105Supply, install, testing and commissioning of Servo control voltage stabiliser,of capacity 100 KVA (conforming as per BIS : 9815: Part 1 : 1994 reaffirmed 2009), 3-phase, 50 Hz, naturally Oil Cooled, indoor/outdoor, Unbalanced Type, copper wounded, Digital Display Type, Relay Free smooth and silent, Operation with 1st filling of Transformer oil (IS 335:1993 reaffirmed 2005) having following specifications complete all as specified and directed:- (a)Input voltage 300V-480V or as per ground requirements. (b)Output voltage stablized at any designed/desired voltage 415v +/- 1% (Adjustable) (c)Rated frequency 50 hz (d)No distortion in wave form. (e)Response time not to exceed 10 mili seconds (f) Sensitivity /-) 1% (g)Rate of correction 8 volt/second for single phase and 20 volt/second for phase to phase (h)No load losses less than 0.5% (j) Full load losses less than 2.5% (k)Duty cycle - continuous 24 x 7 (l) Efficiency more than 95% (m) Type of load, 3 phase, unbalanced type (n)Digital display voltmeter/Ammeter (o)Capacity 100 KVA (p)Overload/Short circuit protection (q)High/Low voltage cut off (r)By pass arrangement in case of emergency (s)Single phase sequence change protection.
106Supply, Install, Testing & Commissioning of 11KV, 400 Amps, both side extensibleoutdoor[IP-54] protection, powder coated painted, light smoke gray colour, manually operated, SF-6 gas insulated RMU (Ring Main Unit), 3 way comprising of 3 Nos, 400 Amps vaccum circuit breaker of rupturing capacity 21 KA/3sec, inside SF-6 gas filled stainless steel (non ferride and non magnetic grade) tank having minimum thickness 2mm having IP-67 degree of protection and leak rate of SF-6 gas less than 0.1%. RMU should be provided withcopper Busbar, Scada compitable relayswith each incomming / outgoing,mechanism for interlocking arrangements for safety and operations, pad lock provisions, self powered & completewith all accessories RMU shall be type tested for internal arc testof 20 KA /3 Sec as per IEC : 62271-200. The unitshall include the following with all necessary standards fitting as required at site complete all as specified and directed. Note:-Necessary civil work like as foudation/ platform for the equipment of appropriate size as reccomended by OEM or as indicated/directed by the Engr-In-Chargefor the connected work is required deemed to be included in the unit quoted rate.
107Material and labour for earthing complete with copper plate, with 60cm x 60cm x 3.15mm thickelectrode, surrounded by charcoal and salt, buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level connected to GI strip of size 20x3mm as earthing lead with bolts, nuts, checknuts and washers of galvanised iron or steel, earth strip protected by galvanized iron pipe 32mm dia (medium grade) from earth pit to test point and connected to main switch or main control board all as shown in Electrical plate No. 3 connected to earthing test point all as specified including testing on completion including necessaryexcavation and earth work (in any strata) providing charcoal dust, salt mixed with fine sand in continuous layers, with CI frame with cover, PCC (1:3:6) type C1 in pit, RCC cover slab 50mm thick in 1:2:4 type B-1 using 8mm dia TMT bars @10cm c/c both way with one 8mm dia bar as handle for lifting, 20mm dia bore light grade GI watering pipe, PGI sheet funnel etc complete all as specified and directed.
108Material and labour for earthing complete with 60cm x 60cm x 6mm thick GI plate electrode surrounded by charcoal and salt, buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level connected to GI strip of size 32x6mm as earthing lead with bolts, nuts, checknuts and washers of galvanised iron or steel, earth strip protected by galvanized iron pipe 40mm dia (medium grade) from earth pit to test point and connected to main switch or main control board all as shown in Electrical plate No. 3 connected to earthing test point all as specified including testing on completion including necessaryexcavation and earth work (in any strata) providing charcoal dust, salt mixed with fine sand in continuous layers, with CI frame with cover, PCC (1:3:6) type C1 in pit, RCC cover slab 50mm thick in 1:2:4 type B-1 using 8mm dia TMT bars @10cm c/c both way with one 8mm dia bar as handle for lifting, 20mm dia bore light grade GI watering pipe, PGI sheet funnel etc complete all as specified and directed.
109Material and labour for chemical earthing complete with copper earth plate electrode 90cm x 60cm x 5mm thick surrounded from all sides by 20 cm thick salt (40 kg), charcoal dust (40 kg) and magnesium sulphate (50 kg) filling in each alternate layers upto 1.80m height, buried in ground vertically in pit of depth not less than 5.1mtrs deep below ground level with top edge of the plate not less than 3.75mtrs below ground level connected to copper earth strip of size 50x6mm as earthing lead with bolts, nuts, checknuts and washers, earth strip protected by galvanized iron pipe 40mm dia (medium grade) from earth pit to test point and connected to main switch or main control board all as shown in Electrical plate No. 3 connected to earthing test point all as specified including testing on completion including necessaryexcavation and earth work (in any strata) providing charcoal dust, salt mixed with fine sand in continuous layers, with CI frame with cover, PCC (1:3:6) type C1 in pit, RCC cover slab 50mm thick in 1:2:4 type B-1 using 8mm dia TMT bars @10cm c/c both way with one 8mm dia bar as handle for lifting, 20mm dia bore light grade GI watering pipe, PGI sheet funnel etc complete all as specified and directed.
110Material and labour for boring of holes under road, pavement, hard standing by trench less technology using ultra sound technique and necessary machine including providing HDPE pipe of 80mm dia suitable for 0.4 mpa working pressure complete all as specified and directed at site.
111Supply and laying of LT underground cable, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty), 1100 volts grade, with stranded aluminium conductor of size 3.5 core, 95 Sqmm and laying in trenches, floors, ducts, passing through pipe for road crossing etc, including connecting and testing of cable complete all as specified and as directed. Note:- Excavation, earth work, brick protection, sand cushioningand GI pipe etc shall be measured & paid for separately.
112Supply and laying of LT underground cable, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty), 1100 volts grade, with stranded aluminium conductor of size 4 core, 10 Sqmm and laying in trenches, floors, ducts, passing through pipe for road crossing etc, including connecting and testing of cable complete all as specified and as directed. Note:- Excavation, earth work, brick protection, sand cushioningand GI pipe etc shall be measured & paid for separately.
113Supply and laying of LT underground cable, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty), 1100 volts grade, with stranded aluminium conductor of size 3.5 core, 25 Sqmm and laying in trenches, floors, ducts, passing through pipe for road crossing etc, including connecting and testing of cable complete all as specified and as directed. Note:- Excavation, earth work, brick protection, sand cushioningand GI pipe etc shall be measured & paid for separately.
114Supplying and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95 Sqmm 3 core, suitable for 11 KV earthed system, in trenches, floors, ducts passing through pipe for road crossing etc, including connecting and testing of cable complete, all as specified and directed. Note : Excavation, earth work, brick protection, sand cushioningand GI pipe etc shall be measured & paid for separately.
115Material and labour for fine and dry sand, cushioning for underground cable, by providing a layers of sand 8cm deep before laying and 15cm deep after laying the cable including stretching the cable and punning sand cushioning complete all as specified and as directed. Note - Punned thickness 18cm of sand layer shall only be measured and paid to contractor.
116Supply and laying un-reinforced, precast concrete cable cover, class HV type 1, Flat, with peak, size 300 mm x180 mm x40 mm complete all as specified and as directed.
117Supply and laying burnt clay bricks, sub class "B", old size bricks, designation 75, laid in trenches, in transverse direction to cable, as protection to cables complete all as specified anddirected.
118Supply and fixing of GI tubing 80 mm bore light grade on poles, on walls, under floors, road crossing as required at site with and including clamps, nuts, bolts, saddles etc complete all as specified and directed.
119Supply and fixing of GI tubing 50 mm bore light grade on poles, on walls, under floors, road crossing as required at site with and including clamps, nuts, bolts, saddles etc complete all as specified and directed.
120Supply and fixing of GI tubing 40 mm bore light grade on poles, on walls, under floors, road crossing as required at site with and including clamps, nuts, bolts, saddles etc complete all as specified and directed.
121Material and labour for Cable jointing kit suitable for LT 1100 volts (Earthed) grade cable outdoor end termination, heat shrinkable type joint complete with jointing material and accessories suitable for 3.5 core LT XLPE armoured aluminium conductor cable of size 95 to 120 sq mm complete all as specified and as directed.
122Material and labour for Cable jointing kit suitable for HT 11 KV (Earthed) grade cable, outdoor end termination, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core HT XLPE armoured aluminium conductor cable of size 50 to 95 sq mm complete all as specified and as directed.
123Material and labour for Cable jointing kit suitable for HT 11 KV (Earthed) grade cable, indoor end termination, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core HT XLPE armoured aluminium conductor cable of size 50 to 95 sq mm complete all as specified and as directed.
124Supply, install, testing & commissioning of factory fabricated, out door type cubical panel board, of size 1.2 metre x 1.0 metre x 0.5 metre, outer shell made out of3.15 mm thick MS sheet including door and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm, mounted on PCC 1:2:4 type B-1 platform, 60 cm above and 45 cm below the ground level,frame factory fabricated with front & back openable, double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof, suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, tested at factory, approved from CPRI,having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :-
125a) TPN Copper bus bar, 300Amps, insulated with colour coded, heat shrinkable sleeve, heavy duty and shall be mounted on suitable size “F” class insulators not less than 1.0 mtr long. b) Incoming MCCB 200 Amps, 4 pole, 415 Volts, 36 KA, AC, Icu=100% Ics, having microprocessor based release for over current, short circuit & earth fault, front face isolation with positive break indication with double break contacts with spreader and phase barrier complete conforming to IS/IEC 60947-2.-01 No c) Outgoing MCCB 160Amps, 4 pole, 415 Volts, 36KA, AC, Icu=100%Ics, having microprocessor based release for over current, short circuit & earth fault with front face isolation with positive break indication with double break contacts with spreader and phase barrier complete conforming to IS/IEC 60947-2. Note:-one Nos as standby. -02 Nos (d)All as (c) above but MCCB 100 Amp36 KA - 1 No (f) Digital Ammeter 0-300 A of size 96sqmm with selector switch-01 No. (g) Digital Volt meter 0-500 V of size 96sqmm with selector switch-01 No (h) Indicator Lamp RYB 22.5mm dia LED type 240 volts AC with incoming includin back up protection by 2 Amp MCB RYB with holder-01 set of three. (j) On load change over 4 pole 415 volts 200 Amps in open execution -01 No (k) CT Coils of suitable ratio-01 Set.
126Note for 102 & 102.01:- (i)The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves,link spreater provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming toIS-694. (iii) Panel drawing shall be got approved before placing of orderfrom Engr-in-Charge/GE. (iv)The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (vi) The Panel shall be surrounded with 9 inch brick wall upto 0.5 mtr height all around the panel and blank portion between panel and wall shall be filled with PCC 1:2:4incl masonary work leaving ducts for cables complete all as directed.
127Supply and fixing of room window type air conditioner, electric driven (Single phase), cooling capacity 6000K Cal per hour (2 Ton), BEE5 star rating with remote complete all as specified and directed.
128Supply and fixing of voltage stabilizer for automatic operation, single phase, naturally air cooled, indoor type and designed for input variation between 170V to 260 V with output voltage stabilizer at 230 V with accuracy of + 2.5% and of capacity 4.0 KVA complete all as specified and directed.
129Supply and fixing of single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB SP 20 Amps, ISI marked complete all as specified and directed.
130Note:-Amount of credit ofRs. 1000.00 for retrieved materials is mentioned in Schedule of Credit Page No. 17 of tender documents in pdf form which will be deducted offline while acceptance of tender.