Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar, Amritsar-Punjab

Military Engineer Services-MES has published Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar. Submission Date for this Tender is 12-10-2021. HVAC Tenders in Amritsar Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

29204733
Corrigendum : Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar
Open Tender
Indian
Punjab
Amritsar
12-10-2021

Tender Details

Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar Provn Of Central Ac Plant In Icu Against Ber Including Extention For Covid Icu At Mh Amritsar Under Ge Amritsar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 15-Sep-2021 Corrg01ofCWE25of2122 Other 04-10-2021
2 15-Sep-2021 BOQofCWE25of2122 BOQ 04-10-2021
3 25-Sep-2021 CORRIGENDUM NO 02 Date 11-10-2021
4 28-Sep-2021 CORRIGENDUM NO 03 DRAWING Other 11-10-2021
5 28-Sep-2021 CORRIGENDUM NO 03 BOQ BOQ 11-10-2021
6 28-Sep-2021 CORRIGENDUM NO 03 Other 11-10-2021
7 11-Oct-2021 CORRIGENDUM NO 04 Date 12-10-2021
8 11-Oct-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 18-10-2021

Key Value

Document Fees
INR 1000 /-
EMD
INR 170500.0 /-
Tender Value
INR 97 Lakhs /-

BOQ Items

Name of Work:PROVN OF CENTRAL AC PLANT IN ICU AGAINST BER INCLUDING EXTENTION FOR COVID ICU AT MH AMRITSAR UNDER GE AMRITSAR.
Sl. No. Item Description
1Demolition of Cement Concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all as specified and directed.
2Dismantaling of brickwork, built in cement mortar including all quoins, arches, pillars, etc. complete all as specified and directed
3Demolition Roofs, floors (other than ground floors), beams, staircases, landing, chajjas and similar suspended work complete all as specified and directed.
4M & L for PCC 1:3:6 type C2 (using 40mm graded stone aggregate) in foundations, filling and mass concrete complete all as specified and directed.
5M&L RCC M-25 (Design Mix) using 20 mm graded stone aggregates as in column footings, plinth beams complete all as specified and directed.
6M&L RCC M-25 (Design Mix) using 20 mm graded stone aggregatesas in columns complete all as specified and directed.
7M&L RCC M-25 (Design Mix) using 20 mm graded stone aggregatesas in beams complete all as specified and directed.
8M&L RCC M-25 (Design Mix) using 20 mm graded stone aggregatesas in Slabs supported on walls, beams and columns in floors, roofs, landings,balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.
9M&L for Mild steel TMT bars 10 mm dia., and over cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia. and securing with clips complete all as specified and directed.
10M&L for Mild steel TMT bars 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
11M&L for Formwork to sides of fair finished flat surfaces of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter complete all as specified and directed.
12M&L for Fair finished Square, rectangular or polygonal Form work to sides of pillars, posts, struts, columns and stanchions complete all as specified and directed.
13M&L for Fair finished flat Form work to sides and soffits of floor or roof beams, lintels, cantilevers, shelves including supports etc complete all as specified and directed.
14M&L for Fair finished flat form works to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping) complete all as specified and directed.
15M & L Brick work builtin CM 1:6 subclass B brick strength curved or plan exc 6m mean radius complete all as specified and directed.
16M & LBrickwork with subclass ‘B’ bricks, straight or curved on plan to any radius inhalf brick thick walls builtin CM 1:4complete all as specified and directed.
17M&L for Cutting out bricks, forming toothing for, and bonding new into old work in cement mortar CM 1:6 including value of new materials entering old walls and jointing and pointing (measured on vertical face in contact with old wall only) complete all as specified and directed.
18M&L for 15mm rendering in cement mortar CM (1:4) on brick/concrete surfaces finished the surface even and smooth without using extra cement complete all as specified and directed.
19M & L for 15mm rendering in cement mortar CM (1:6) on brick/concrete surfaces finished the surface even and smooth without using extra cement complete all as specified and directed.
20M&L for rendering 10 mm thick on fair faces of brick work or concrete surfaces on ceiling in CM 1:3finishing even and smooth without using extracement complete all as specified and directed
21M&L for Preparation of Newly Plastered surfaces of Wall and applying Two coats of Oil Bound Distemper over a 3mm thick wall care putty all as specified and directed.
22M&L for preparation of newly plastered wall surface and applying two coats of cement Base paint complete all as specified and directed by Engr-in-Charge.
23M&L for applying two coats of white wash on ceiling surface and complete all as specified and directed by Engr-in-Charge.
24M & L for hardcore of gauge not exceeding 63 mm of broken stones or boulders, deposited, spread and levelled in layers not exceeding15 cm thick watered and rammed to a true surface in broken boulder complete all as specified and as directed.
25M&L for machine cut kota stone slab flooring 18-20 mm thick over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab as in floors including rubbing and pollishing completeincluding 15 mm thick screed bed in CM 1:6 complete all as specified and directed.
26All as per Item No.25 here-in-before but as skirting/dado over rendering 15mm thick in CM 1:4.
27S & F 110 mm bore PVC (SWR) pipes single socketed in any length with rubber ring joints fixed to walls complete all as specified and directed.
28S & F 110 mm bore PVC (SWR) bends of any radius complete all as specified and directed.
29S&F framed work as door, chowkhats, andGrill gates of angle frame work fixed with Nut & bolt to wall or other section complete drilling or fixing welding be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittingsand hanging also festering and fixing complete all as specified and directed.
30M&L for PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) in bed blocks for hold fast & similar work etc complete all as specified and directed
31S&F factory made 35 mm thick flush shutters solid core construction with block board core and plywood face panels complete all as specified and directed.
32S&F extruded aluminium alloy handles, fabricated type, anodised all as specified ofsize 150mm long.
33S&F Aluminium, anodised, barrel tower bolts of extruded section complete all as specified of size 75mm long.
34S&F 300mm long aluminum alloy anodized sliding door bolt with hasp and staple(bolt type)and fixing clips of sheet cast or extruded sec and fixing bolts and sliding bolts of extruded sec or cast aluminum alloy and fixed all as spd and directed.
35S&F butt hinges medium weight cold rolled mild steel complete size 100mm.
36Preparation of New or previously untreated steel surfaces of any description, not otherwise described, over 10 cm width or girth and applying two coats of Synthetic enamel paint (Ordinary tint) over a coat of red/zinc oxide primer.
37M&L two coats of synthetic enamel paint over a coat of pink primer over woodensurfaces including preparation of surfaces complete all as specified.
38M&L 12mm thick perforated particle board/ tiles for insulation and accoustic purpose of size 60cmx60cm placed in ceiling including aluminium anodised snap grid frame 605mm x 605 mm for false ceiling including hanging arrangements complete all as specified in clause 10.38.1 of MES Schedule Part-I complete all as specified and directed by Engr-in-Charge.
39Dismantling Brick tiles or terracing tiles, single layer on roofs complete all as specified and directed.
40M & L for applying evenly a tack coat of industrial bitumen 85/25 grade @ 1.2 Kg/Sqm at 180 degree temperaturein each layer ( first layer below APP membrane and second layer above APP membrane) on 0.40 kg/sqm bitumen primer surfaces including cleaning surfaces etc complete all as specified and directed
41M & L for APP based polymeric membrane minimum weighing 3kg/sqm and minimum 3mm thick reinforced with polyester non woven fabric(wt not less than 150 gms/sqm) laid on bitumen surfaces by forced application complete all as specified.
42M&L 40mm thick brick tiles laid on cement mortar and jointed grouted, flush pointing in Cement Mortar (1:3) mixed with 5% crude oil by weight of cement on flat roof over andincluding 20mm thick screed bed in cement mortar 1:6 complete all as specified and directed
43Ditto all as per item No 42 here-in-before but except brick tile.
44Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for foundation etc. or for laying of pipes and fittings, cables, HT / LT poles, stay assembly etc including forming bottom surfaces to required level and slope and getting out in hard / dense soil complete all as specified and directed.
45Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick in each layer as in hard / dense soil complete all as specified and directed.
46Removing surplus excavated material (SOIL) to distance not exc. 50 m and depositing where directed at a level not exc. 1.50 m above the starting point complete all as specified and directed.
47Supplying, fixing, connecting & testing of GI tubing 40mm bore medium grade, ISI marked including all fittings laid in trenches, under floors, fixed to walls etc, complete all as specified and directed by Engineer-in-charge. Make: JINDAL/TATA/PRAKASH and all other equivalent makes specified inAppendix"B". Note: (a) Excavation and earth work will be meaured and paid separately. (b) Cost of GI bends, sockets, unions and connected items will be deemed to be included in the unit rate quoted by the contractor.
48Supplying, fixing, connecting & testing of GI tubing 25mm bore medium grade, ISI marked including all fittings laid in trenches, under floors, fixed to walls etc, complete all as specified and directed by Engineer-in-charge. Make: JINDAL/TATA/PRAKASH and all other equivalent makes specified inAppendix"B" Note: (a) Excavation and earth work will be meaured and paid separately. (b) Cost of GI bends, sockets, unions and connected items will be deemed to be included in the unit rate quoted by the contractor.
49Supplying, fixing, connecting & testing of GI tubing 20mm bore medium grade, ISI marked including all fittings laid in trenches, under floors, fixed to walls etc, complete all as specified and directed by Engineer-in-charge. Make: JINDAL/TATA/PRAKASH and all other equivalent makes specified inAppendix"B" Note: (a) Excavation and earth work will be meaured and paid separately. (b) Cost of GI bends, sockets, unions and connected items will be deemed to be included in the unit rate quoted by the contractor.
50Supply and fixing in replacement of Gun metal globe or Gate valveswith iron wheel head,screwed both ends for iron pipe of 40 mmbore including taking out unserviceable valve complete all as specified and directed . Make -BIR/Leader/Zoloto and all other equivalent makes specified inAppendix"B"
51Supply and fixing in replacement of Gun metal globe or Gate valveswith iron wheel head,screwed both ends for iron pipe of 25 mm bore including taking out unserviceable valve complete all as specified and directed . Make -BIR/Leader/Zoloto and all other equivalent makes specified inAppendix"B"
52Supply and fixing in replacement of Gun metal globe or Gate valveswith ironwheel head,screwed both ends for iron pipe of 20 mm bore including taking out unserviceable valve complete all as specified and directed. Make -BIR/Leader/Zoloto and all other equivalent makes specified inAppendix"B"
53Material & labour for sand filling in trenches for cable protection including necessary punning and consolidation as required complete all as specified and directed. NOTE:- Punned thickness only will be considering for payment.
54Supply and laying burnt brick sub class "B" modular size, for cable protection laid length wise perpendicular to the axis of cable complete all as specified and directed.
55Supplying, laying, jointing & testing 150 Sqmm 3½ core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade complete including taking down old unserviceable cable any type and size all as specified and directed. Make :- Polycab/Havells/RR Kabel and all other equivalent makes specified inAppendix"B"
56Supplying, laying, jointing & testing 95 Sqmm 3½ core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade complete including taking down old unserviceable cable any type and size all as specified and directed. Make :- Polycab/Havells/RR Kabel and all other equivalent makes specified inAppendix"B"
57Supplying, laying, jointing & testing 50 Sqmm 3½ core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade complete including taking down old unserviceable cable any type and size all as specified and directed. Make :- Polycab/Havells/RR Kabel and all other equivalent makes specified inAppendix"B"
58Supplying, laying, jointing & testing 6 Sqmm 3 core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade complete including taking down old unserviceable cable any type and size all as specified and directed. Make :- Polycab/Havells/RR Kabel and all other equivalent makes specified inAppendix"B"
59Supplying, laying, jointing & testing 25 Sqmm 4 core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade complete including taking down old unserviceable cable any type and size all as specified and directed. Make :- Polycab/Havells/RR Kabel and all other equivalent makes specified inAppendix"B"
60Material & labour for earthing complete with galvanised earth plate electrode 600 X 600 X 6 mm thick burried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.5 m below normal ground level, connected to galvanised earth strip 25x4 mm dia by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2009, Part – I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, 50 mm thick RCC cover in PCC 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate), duly reinforced with 6 mm dia mild steel round bars @ 150 mm both ways center to center with suitable lifting handle to cover, earth pit of PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate), GI protection pipe light grade 15 mm bore up to 7.5 m length from earth electrode & engraving of earth marking on nearby building with CM 1:4 plate size 200 X 150 X 15 mm & painting of earth result etc. including testing on complete all as specified and directed.
61Material and labour for earth continutity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etch as required 4mm galvanised iron wire complete all as specified and directed by Engineer-in-Charge
62Material & labour for cable tray of Galvanised iron steel sheet 2mm thick 30cm width x 5 cm height with manufactures holes for water drainage fixed in duct/wall by angle, nut, bolts as per site requirement and cables covered with wire mesh superior quality for protection from any mechenical damages as per sample including binding / cutting / welding work complete all as specified and directed.
63Same as item No 62 above but of width 20 cm .
64Same as item No 62 above but of width 15 cm.
65Same as item No 62 above but of width 10 cm.
66Same as item No 62 above but of width 5 cm.
67Design, supply, installation, testing and commissioning of scroll type Chiller Central Air Conditioning Plant, water cooled with multi-compressors, comprising of Semi-Hermetic / Hermetic, DX Evaporator, Shell and tubecondenser, suitable expansion device, suitable for operation with minimum nominal operational capacity of 78 TR including 50% as standby (2x39TR chiller units as working + 1x39 TR chiller unit as standby) for the space to be air-conditioned as given in drawing enclosed, to achieve the desired parameters of temparature of 23°C ± 2°C, RH of 55% ± 5%, The AC plant is deemed to be comprising of the following equipments which are not exhaustive but for indication only. Any other equipment / accessories as required at site for the complete operation to achieve the desired results are to be provided as per the latest trends and the rates quoted is deemed to be inclusive of of all. Make:-Bluestar/Carrier/ Daikin/Voltas or equivalent makes specified inAppendix"B" CHILLER PACKAGE UNIT:- Micro Processor controlled Scroll Chiller unit complete, factory assembled, factory tested, of minimum cap 39 TR Each, 3 Nos (02 Nos working and 01 number as standby), suitable for plant of minimum nominal capacity of 78 TR , working on latest eco friendly (with no greenhouse effect) refrigerant R407c/410a (Green gas) comprising of scroll compressor suitable for 415V, 50 HZ, 3 phase, including pipes, controls & accessories, starters & microprocessor controlled panels with all required safetys as per OEM, refrigerant, oil charged mounted on common base frame with anti-vibration pads complete as per recommendation by OEM: 03 Nos (2 Nos working at a time and 01 Standby). Notes :- (i)Efficiency of scroll type chiller package shall comply with latest ECBC norms. (ii) RCC foundation as per manufacturers standards shall be deemed to be included in the rates quoted. (iii) The job consists of design, supply, installation,testing and commissioning of 3x39TR chiller units, where two units shall be working and one unit shall be used as standby as elucidated above.
68Supply and fixing CONDENSER WATER CIRCULATION SYSTEM:-Comprising of the followings:- FRP induced draft cooling tower Round bottle type , with minimum Cap of 50 TR x 3 Nos., complete with spray section, honey comb fill, basin, CT fan, TEFC Motor with IP65 protection, intake bird screen and other accessories with out cut off arrangmements at the time of low ambient conditions (Technical Specifications as per OEM Recommendations) Make:- Delta/ Advance/ Pharpur and all other equivalent makes specified inAppendix"B" Note:- Necessary water supply lines and masonry valve pits for tapping water from the existing pipe line/tank shall be deemed to be included in the quoted rates.(2 Nos working at a time and 01 Standby)
69Supply and fixing of HDPE/PVC make up water tank of 5000 LTRS capacityinstalled on PCC/ brick staging upto suitable height as per manufacturer specifications for make up water requirement including brass float valve with ployethylene ball, over flow and drain arrangement, including cutting of existing pipe line and tapping of branch connections, laying of suitable bore GI pipe , medium grade as incomer all as directed by Engineer-in-Charge. Make of tank:- Sintex/ Polycab/Rotex and all other equivalent makes specified inAppendix"B"
70Supply and fixing of Energy efficient mono block type, 3 phase electric driven pump sets, working on 415V, 50 Hz AC,class F insulation with TEFC Squirrel cage induction motor and bronze imepller with mechanical seal for recirculation of condenser water, 9.5 LPS AT 18-20 M Head (not less than 5HP rating) for operation on 50% plant capacity - 03 Nos (02 Nos working and 1No standby) including rubber vibration isolation pads, mounted on ISMC frame (painted with anti-corrosive primer & paint) on PCC foundation complete all as specified and as recommended by OEM. Make of pump:- Kirloskar/ Beacon/ Jyoti. and all other equivalent makes specified inAppendix"B"
71Supply and fixing of Non-chemical type Online Scale Preventer of required size as per the capacity of the condenser water pumping system including piping and control valve of dia 100mm complete all as specified and as recommended. Make:- Scale X / Scale Off and all other equivalent makes specified inAppendix"B"
72Supply and fixing of Condenser water piping made of MS Pipes, Class "C" Heavy grade (ISI marked), of suitable size, connected/jointed by Electric Arc Continuous Welding including two coats of anti-corrosive paint over a coat of primer for interconnecting the cooling tower with condensers & pumps, make up water tanks, drain pipes, complete with Y-stainer, NRV, pressure gauges and butterfly valves as mentioned below complete all as specified and as recommended. Make of pipe:-Jindal/ TATA/ Parkash Surya and all other equivalent makes specified inAppendix"B". Size of pipe of dia 125mm including necessary steel supporting structure.
73Same as item No 72 above but pipe of size of dia 100mm.
74Same as item No 72 above but pipe of size of dia 65mm.
75Same as item No 72 above but pipe of size of dia 50mm.
76Supply and fixing of CI Butterfly valve of pressure rating PN 1.6 of size of dia 100 mm. Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B"
77Same as item No 76 above but pipe of size of dia 125mm.
78Same as item No 76 above but pipe of size of dia 50mm.
79Supply and fixing of CI NRVof pressure rating PN 1.6 of size 100mm dia. Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B"
80Supply and fixing of CI Balancing valve of pressure rating PN 1.6 of size 100mm dia Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B"
81Supply and fixing of CI Y Strainer of pressure rating PN 1.6 of size 100mm dia. Make:- Emerald/ sant/ Rapid Strain and all other equivalent makes specified inAppendix"B"
82Supply and fixing of Pressure gauge of 100mm dia. Make:- Febig/ H Guru and all other equivalent makes specified inAppendix"B"
83Supply and fixing of Stem type thermometer (Brass). Make:-Febig/ H Guru and all other equivalent makes specified inAppendix"B"
84Supply and fixing of Water flow switch. Make:- Rapid cool/ Anergy/ Honeywell and all other equivalent makes specified inAppendix"B"
85Supply and fixing of POT Strainer of PN 1.6 . Make:-Emerald/ sant/ Rapid Strain and all other equivalent makes specified inAppendix"B". Size of valve 125 MM
86CHILLED WATER CIRCULATION SYSTEM:- Comprising of the following:- Supply and fixing of Energy efficient, mono block type, 3 phase electric driven pump sets working on 415V, 50 Hz AC class F insulation with TEFC Squirrel cage induction motor and bronze impeller with mechanical seal for recirculation of chilled water , 7.8 LPS 24 M HEAD (not less than 5 HP rating) for 50% plant capacity - 03 Nos (02 Nos working and 1 No. standby) including vibration isolation pads, mounted on ISMC frame (painted with anti-corrosive primer & paint) on PCC foundation including all connections complete all as specified. Make of pump:- Kirloskar/ Beacon/ Jyoti and all other equivalent makes specified inAppendix"B"
87Supply and fixing of Chilled water piping with MS, Heavy Grade(class C) ERW pipes of suitable diameter, including all weldable fittings, butterfly valves, NRVs & "Y" strainers for interconnection between water chiller, chilled water pumps with AHUs and cooling coil units. Chilled water piping shall be insulated with 50mm thick EPS pipe section TF quality, cladded with Aluminium sheet 26 SWG of dia 100mm including necessary steel supporting structure complete all as specified and as recommended. Make of pipe :-Jindal/ TATA/ Parkash Surya and all other equivalent makes specified inAppendix"B"
88Same as item No 87 above but of size of dia 80mm.
89Same as item No 87 above but of size of dia 50mm.
90Same as item No 87 above but of size of dia 25mm.
91Supply and fixing ofButterfly valve of PN 1.6 Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B"Size of valve of dia 80mm.
92Supply and fixing of NRVof PN 1.6 Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B". Size of valve of dia 80mm.
93Supply and fixing of Y Strainer of PN 1.6 Make:- Emerald/ sant/ Rapid Strain and all other equivalent makes specified inAppendix"B". Size of valve of dia 80mm
94Same as item No 93 above but of size of dia 50mm.
95Supply and fixing of Balancing valve of PN 1.6 Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B". Size of valve of dia 80mm.
96Same as item No 95 above but of size of dia 50mm.
97Supply and fixing of Auto air vent of size 15 mm. Make:- Rapid cool/ Anergy/ Honeywell and all other equivalent makes specified inAppendix"B"
98Supply and fixing of PVC / HDPE Expansion tank of Min 500 ltrs capacity, including insulation with 50mm thick fibre glass/ thermo coal of density 24kg/Cum, finished with cement plaster. Including all necessary civil works, painting with 3 coats of cement based paint, GI medium grade pipes including their connections, necessary piping control valves on inlet, outlet and wash out, including float valve etc complete all as specified and as directed.
99AIR TREATMENT SYSTEM :- Comprising of the following: Supply and fixing of Double skin construction Air Handling Unit of 4500 CFM with 85mm SP Thermal break profile for MED ward suitable for chilled water system made out of extruded aluminium structural frame / aluminium corners and intermediate connecting pieces and panels of galvanised steel sheet of appropriate thickness as recommended by OEM on both sides with 25mm thick pressure injected PUF of appropriate density using CFC free blowing agent, the panels having scratch free plastisol coating on outer side. The fan section should be mounted on anti-vibration spring isolators free from main structure. The fan should be backward curved centrifugal fan with air discharge upblast, belt driven with TEFC induction motor of suitable capacity. The coil section consist of 8/6 row deep coil and 2 row deep heating coil with min 12 fins/inch duly coated. The filter section consist of prefilter with 10 micron, 90% efficiency & microve Fine filters 5 micron, 95% efficiency. The other accessories to be included are view port, limit switch, stainless steel (SS3) drain pan. AHU shall be provided with UVC emitters & fixtures in sufficient quantity so as to provide equal distribution of UVC energy on the coil and in the drain pan fcomplete all as specified or as recommended by OEM. Make of AHU:- Edgetech/ Zeco/ LLoyd and all other equivalent makes specified inAppendix"B"
100All as per srl item No.99 here in before but Unit of 4000 CFM with 85mm SP Thermal break profile for MED Ward.
101All as per srl item No. 99 here in before but Unit of 8000 CFM with 85mm SP Thermal break profile for general Ward.
102Supply and fixing of Fancoil unit of cap. 3 TR having three speed complete with thermostat, 3 way valve with necessary fitting such as ball valve & ball valve with strainer.
103Hot Water Generators : - Supply, installation and commissioning of electrical hot water generator equipped with sufficient no. of flanges and electric immersion heaters. The pressure vessel shall be constructed as per ASME standards and insulated on all sides with 2 layers of 50 mm thick fiberglass with 28 guage aluminium cladding as per specifications. The hot water generator shall be equipped with all automatic and safety controls such as manual reset, high temperature water outlet, step controller and recycling relay, on/off switch type thermostat, pilot light, low water cut off and other controls as per manufacturers recommendations. All basic control and terminals shall be located in an integral controlabinet factory wired and tested. The hot water generator shall be suitable for 415+/- 10% volts/50 cycles, 3 phase power supply. The entire hot water generator shall be factor assembled and testedof cap 120 KW water in -110 Deg F Water out -120 Deg F. Make:- Rapid Cool/ KEPL/ Thermax and all other equivalent makes specified inAppendix"B"
104Supply and fixing of Energy efficient mono block type, 3 phase electric driven pump sets, working on 415V, 50 Hz AC class F insulation with TEFC Squirrel cage induction motor and bronze imepller with mechanical sealfor recirculation of hot water, 5.6 LPS AT 18-20m HEAD (not less than 3 HP) for operation on 100% capacity of HWG - 02 Nos (01 Nos working and 1No standby) includingrubber vibration isolation pads, mounted on ISMC frame (painted with anti-corrosive primer & paint) on PCC foundation complete all as specified or as recommended by OEM. Make of pump:- Kirloskar/ Beacon/ Jyoti and all other equivalent makes specified inAppendix"B"
105Supply and fixing of Hot water piping with MS, Heavy Grade (C class) pipes of suitable diameter, including all weldable fittings, butterfly valves, NRVs & "Y" strainers for interconnection between water chiller, chilled water pumps with AHUs and cooling coil units. Chilled water piping shall be insulated with 50mm thick EPS pipe section TF quality, cladded with Aluminium sheet 26 SWG of size of dia 65mmincluding necessary steel supporting structure Make of pipe:-Jindal/ TATA/ PArkash Surya and all other equivalent makes specified inAppendix"B"
106Same as item No 105 above but of size of dia 50mm.
107Same as item No 105 above but of size of dia 32mm.
108Supply and fixing of CI Butterfly valve of pressure rating PN 1.6. Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B" Size of valve 65mm.
109Same as item No 108 above but of size 32mm.
110Supply and fixing of CI NRVof pressure rating PN 1.6. Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B" Size of valve 65mm.
111Supply and fixing of CI Y Strainer of PN 1.6. Make:- Emerald/ sant/ Rapid Strain and all other equivalent makes specified inAppendix"B" Size of valve 65mm.
112Supply and fixing of CI Balancing valve of PN 1.6. Make:- Deepak/ Sant/ Kartar/ Advance/ Castle and all other equivalent makes specified inAppendix"B" Size of valve 50mm.
113Same as item No 112 above but of size 32mm.
114Supply and fixing of Spray type humidification system with connected items PVC tank of 100 Ltrs, circulation pump, G.I. pipe fitting & PVC/ Brass spray nozzles with humidistat & control wiring to control the humidity automatically.
115Supply and fixing of Humidistats and Thermostats are to be provided in AHU room. Note:-The control wiring of suitable rate shall be included in the quoted rate.
116Supply and fixing of Three way Mixing valve of required size with motorised actuator and modulatingcontrol for AHU including control wiring of suitable size as per OEM. Make of valve:- Rapid control/ Honeywell/ Belimo and all other equivalent makes specified inAppendix"B" of size 80mm.
117Same as item No 116 above but of size 50mm.
118Same as item No 116 above but of size 32mm.
119AIR DISTRUBUTION SYSTEM :- Comprising of the following:- Supply and fixing of Air Ducting and return Air Ducting both made out of commercial grade GI sheet of thickness 24 Gauge confirming to IS:277 with Zinc coating of not less than120 grade, site fabricated as per SMACNA-1995 standards and as per IS:655. Make : Sail/ Tata /Jindal and all other equivalent makes specified inAppendix"B"
120Same as item No 119 above but of size 22 Gauge.
121Supply and fixing of thermal insulation of external duct exposed to sky with Nitrile sheet class "O" (FR) of size 19mm and covered with glasscloth and finished with starbond. Make of insulation:- K Flex/ A flex/ Amrmacell and all other equivalent makes specified inAppendix"B"
122Supply and fixing of thermal insulation of internal duct with Nitrile sheet class "O" (FR) of size 9mm and covered with glasscloth and finished with starbond. Make of insulation K Flex/ A flex/ Armacell and all other equivalent makes specified inAppendix"B"
123Supply and fixing of Aluminium powder coated double deflection adjustable type Supply Air Grills/ Diffusers with GI/MS volume control dampers and aluminium powder coated fixed bar return Air Grills/ Diffusers without volume control damper for return air. Make:- Caryaire/ Mapro/ Ravi star and all other equivalent makes specified inAppendix"B"
124Supply and fixing MotorisedFire Dampers automatic type complete with actuator motor, control panel,smoke & fire sensor made out of 16 SWG GI sheet andlimit switches, to be provided in each main supplyair ductin AHU room for each AHU and interlocked with AHU motor to cut off circulation of air in case of fire. Make:- Caryaire/ Mapro/ Ravi star and all other equivalent makes specified inAppendix"B"
125Supply and fixing of Acoustic Insulation with 10mm thick open cell NITRILE SHEET upto 5 Mtr from outlet of the air plenum including air plenum for all AHUs all as specified and directed. Make of insulation:- K Flex/ A flex/ Armacell and all other equivalent makes specified inAppendix"B"
126ELECTRICAL WORK :- Comprising of the followings: (i)Main Electrical panel Board:-Supply and fixing of Cubical type floor mounted, vermin proof, dust proof,powder coated switch board panel indoor type made out of CRCA sheet not less than 2.0 mm thick, suitable for operation on 415Volts, 50Hz, AC supply, internally wired with FRLS copperconductor wire of suitable size for control wiring, comprising of the following:- (a)Air insulated Aluminium bus bar of minimum rating 300A Main Incoming:- (i)MCCB 4P 250 Amps 35KA (Adjustable type) 415 Volts (incoming)-1No. Outgoing :- (i) MCCB 4P 100 A 25 KA 415 Volts -03 No(for chiller) (ii) MCCB 4P 120A 25 KA 415 Volts -01 Nos.(for HWG) (iii) MCCB 4P 32 A 25 KA 415 Volts -03 Nos (for sub panel of AHU) (iv) DOL Starter for condenser water pumps of rating as above-03 Nos. (v) DOL Starter for chilled water pumps of rating as above-03 Nos. (vi) DOL Starter for hot water pumps of rating as above-02 Nos. (vii) DOL Starter for cooling tower Fan motor-01 Nos. Incoming Accessories:- (i) Digital ammeter with inbuilt selector switch0 to 300 Amps (ii) Digital voltmeter with built in selector switch 3 phase (iii) CT coils 250/5A-03 Nos (iv) LED pilot lamps single module 16mm of RYB colours -03Nos (v) One electronic energy meter 3 phase, 415V of suitable capacity at main incoming. Out going Accessories:- (i) Digital ammeter with inbuilt selector switch required for each outgoing items (ii) Connected CT coils Makes of switchgear: L&T/Schneider/Legrand and all other equivalent makes specified inAppendix"B"
127Sub Electrical Panel for AHUs:- Cubical type floor / wall mounted indoor type, verminproof, dust proof, powder coated switch board panel made out of CRCA sheet not less than 2.0mm thick suitable for operation on 415volts 50HZ AC supply, internally wired with FRLS copper conductor wire for control wiringalongwith Air insulated Aluminium bus bar of minimum rating 100A. Main Incoming:- (i)MCCB 4P 100 Amps 35KA (Adjustable type) 415 Volts (incoming)-1No. Outgoing :- (i) Star delta Starter for AHU motor -01 Nos. Incoming Accessories:- (i) Digital ammeter with inbuilt selector switch0 to 300 Amps. (ii) Digital voltmeter with built in selector switch 3 phase. (iii) CT coils 250/5A-03 Nos. (iv) LED pilot lamps single module 16mm of RYB colours -03 Nos. Out going Accessories:- (i) Digital ammeter with inbuilt selector switch required for each outgoing items. (ii) Connected CT coils. Makes:L&T/Schneider/Legrand and all other equivalent makes specified inAppendix"B"
128Material and Labour for any Civil Work comprising of Masonry/PCC foundation for, pumping sets, cooling tower, make up water tank and AHUs etc. as per OEM, making opening in the brick wall, making good for ducts, pipes, cables and fresh air intake complete all as seocified and directed. Note:-This AC plant system is being installed in existing building which is being used for operation. This involves alteration / modification in the building. All these modification will be deemed to be included in the quoted rates. The tenderer is advised to visit the site prior to quote the rates. The tenderer will submit a detailed structural drawing for necessary support structure for supporting the duct, from AC plant room to the building for the apporval of accepting officer. The cost of this support structure is deemed to be included in the quoted rates.
129Dismantalling of existing central AC Plant complete with all respect such as package type AC 3 units of 16.5TR capacity , cooling towers, ducting, water circulation pumps including dismantling of related water pipe line, disconnection of power and control connections, dismantling of electric panel and including demolishing of existing foundation and shifting/transporting the AC material to the MES store Yard safely.
130Supply and fixing of GI "B" class drain pipe of dia 32 mm for AHU & FCU with nitrile insulation of thickness 9mm complete all as specified and directed by Engineer-in-Charge.
131Supply and fixing of GI "B" class drain pipe of dia 25 mm for AHU & FCU with nitrile insulation of thickness 9mm complete all as specified and directed by Engineer-in-Charge.
132NOTE:- (i)The quoted rates are inclusive of Phase-I test for the period of 24 HRS and seasonal test summer in month of april/ May, Monsoon test in month of July/ Aug and winter test in month of Dec/ January for 72 Hrs in the presence of GE as per engineering practices and laid down procedures. The test results will be signed by the contractor, Engineer in charge, GE and rep of OEM. (ii) Provisional completion will be issued after successful completion of Phase-I test. The plant is to be tested during Summer,Monsoon andWinterseason before issue of final completion, which will be termed as Phase-II tests.The Defect liability period will start after completion of Phase I test. (iii) The contractor will provide training to MES staff for duration of 01 (one) Month after Provisional completion of work for satisfactory operation of AC plant. (iv)Details of items/ tonnage of AC plant as given above are only indicative/ tentative, vendor shall ensure proper design of AC plant duly approved by OEM as per latest engineer practice based on buildings drawings (showing air conditioned space) and include all accessories essentially required. (v) Design of AC plant with complete heat load calculation/ ducting/ AHU/ other details duly approved by OEM shall be submitted for approval of GE not later than one month of acceptance of contract. (vi)The Specifications given above are for broad reference purpose only. The contractor shall design the air conditioning as per best/latest engineering practice/ conforming to latest relevant IS. (vii) The contractor shall get the work executed from authorized vendor of the OEM of chiller units. The MoU in respect of the authorized vendor shall be submitted to the dept for approval of GE.
133Taking down carefully copper / aluminium point wiring (light, fan, socket or power) complete with fittings such as switches, ceiling roses, pendants, sockets, lamp holders, brackets, bulk head fittings, tube light fittings etc. and making good disturbed surfaces of walls etc. as per existing finishes by plastering, repairs and white / colour wash etc. complete all as specified and directed.
134S & F point wiring for one light point / fan point / bell point , controlled by one, one way switch with 1.50 sqmm size PVC insulated unsheathed 1100 volts grade single core (multi-stranded) copper conductor cable (FR) drawn into and including medium grade PVC conduit concealed (not less than 20 mm dia) all necessary fittings and accessories fixed concealed (including chase cutting in brick/stone masonery wall for fixing conduit and plastering the external surfaces and matching the same with existing suface)and sunk cast ironor pressed steel terminal boxes for mounting fittinglike switches, sockets, lamp holders, sketch fittings and covered with 3 mm thick plastic laminated bakelite sheet cover fixed with brass screws and cup washers including one continuous run of PVC insulated 1.50 sqmm sizecopper conductor cable as in earth wire and connected to common earth dolly complete all as specified and directed. Make:- of FR wire RR Kabel/Polycab/Havells and all other equivalent makes specified inAppendix"B" (a)One light/one fan/one bell point controlled by one, one way switch.
135All as per item No 133 but one socket outlet 5 pin 5 Amp controlled by one, one way switch on same board.
136All as per item No 133 but one socket outlet 5 pin 5 Amp controlled by one, one way switch on independentboard.
137All as per item No. 133 hereinbefore but wiring with using cable 2.50 sqmm size copper wire (FR) and earth wire of FR PVC insulated (Green colour) 2.50 Sqmm sizecopperwire for one 6 pin socket outlet, 16 Amperes on independent board.
138Supply and fixing of switch piano flush button single pole one-way 5 Ampere complete all as specified and directed. Make:- Anchor/Plaza/SSK and all other equivalent makes specified inAppendix"B"
139Supply and fixing of socket outlet 5 Ampere, 2 and 3 pins (TOTAL 05 PINS), flush type 250 volts AC complete all as specified and directed. Make:- Anchor/Plaza/SSK and all other equivalent makes specified inAppendix"B"
140Supply and fixing of switch piano flush button single pole one-way 15 Ampere complete all as specified and directed. Make:- Anchor/Plaza/SSK and all other equivalent makes specified inAppendix"B"
141Supply and fixing of socket outlet two-in-one, 3 pin each suitable for 5 and 15 Amperes flush type, 250 volts AC complete all as specified and directed. Make:- Anchor/Plaza/SSK and all other equivalent makes specified inAppendix"B"
142Supply and Fixing Ceiling rose, surfacebakelite 3 terminal, 240 volts, 5 Amps with back plate of 3 mm thickbakelite, laminated hylem sheet of appropriate size complete all as specified. Make:- Anchor/Plaza/SSK and all other equivalent makes specified inAppendix"B"
143S & F lamp holder, PVC / polycarbonate type insulated body with back plate suitable for batten / angle fittings complete all as specified and directed. Make:- Anchor/Plaza/SSK and all other equivalent makes specified inAppendix"B"
144S & F MCB single pole with magnetic characteristics, 240 volts, 6 to 32 Ampere, rupturing capacity 10 KA, ‘C’ curve type complete all as specified and directed. Make:- Legrand/Schneider/Siemens and all other equivalent makes specified inAppendix"B"
145S & F MCB double pole with magnetic characteristics, 240 volts, 40 to 63 Ampere, rupturing capacity 10 KA, ‘C’ curve type complete all as specified and directed. Make:- Legrand/Schneider/Siemens and all other equivalent makes specified inAppendix"B"
146S & F sheet metal enclosure for DB’s (Double door type) when MCB’s to be used, single pole and neutral, 8 ways with 200 ampere rated bus bar, 240 volts fixed sunk / flush to the wallwith IP-43 and IK-09 protection complete all as specified and directed. Make:-Legrand/Siemens/Schneider and all other equivalent makes specified inAppendix"B"
147S&F MCCB Incomer distribution board double door vertical type made out of CRCA MS sheet surface with insulated material like polyester or with epoxy powder coating surface mounting TPN 4 way, 415 volts with copper bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCCB and IP 43 - IK 09protection with and incl 100 amp 16 kA 4 pole MCCB with thermal - magnetic setting and Icu = Ics = 100% including blank plateincluding taking down old distribution board complete all as specified and directed. Note :- The cost of removing old wooden/steel box etc and making good of surface as original by brick work, plastering, whitewash/colour/distemper etc is included in quated rate Make:-Legrand/Siemens/Schneider and all other equivalent makes specified inAppendix"B"
148M & L for sub main wiring with 1100 volt grade two single core FR Wire PVC insulated and unsheathed cable with stranded copper conductor 6 sqmm drawn into and including electrical grade PVC conduit not less than 25 mm dia with IS 9537 (Part-III) 1983 mark, or relevant ISI mark with all accessories fixed concealed including chase cutting in brick/ stone masonry for fixing conduit and making good the disturb surfaces of wall as per existing including 6 sqmm multi - stranded copper conductor as earth wire in green colour complete all as specified and directed. Including taking down old unserviceable sub main wiring Make of wire:- Polycab/RR Kabel/Havells and all other equivalent makes specified inAppendix"B" NOTE: -3 single core 6 sqmm and PVC conduit shall be measured as one RM. Make:- RR Kabel/Polycab/Havells and all other equivalent makes specified inAppendix"B"
149S & F wall /ceiling mounting LED 18 Watt pride plus/smart line tube light fitting complete withall acessories 1x18 Watt LED , with CCT of 6000k suitable for domestic application, 240 Volts, 50 Hz,and internally pre-wired with 1.5 sqmm twin twisted flexible cable copper conductor and connection complete all as specified and directed. Make:- Havells/Philips/Wipro and all other equivalent makes specified inAppendix"B"