Supply, Erection And Commission Of Ahu Unit With Duct System In Clean Room Of Ethno Building At Veterinary College And Research Institute, Orathanadu. ( Re-Tender ) As Per Boq, VCRI-Orathanadu-Tamil Nadu

Tamil Nadu Veterinary And Animal Sciences University-TANUVAS has published Supply, Erection And Commission Of Ahu Unit With Duct System In Clean Room Of Ethno Building At Veterinary College And Research Institute, Orathanadu. ( Re-Tender ) As Per Boq. Submission Date for this Tender is 12-08-2021. Air Handling Unit Tenders in VCRI-Orathanadu Tamil Nadu. Bidders can get complete Tender details and download the document.




Tender Notice

28728621
Corrigendum : Supply, Erection And Commission Of Ahu Unit With Duct System In Clean Room Of Ethno Building At Veterinary College And Research Institute, Orathanadu. ( Re-Tender ) As Per Boq
Open Tender
Indian
Tamil Nadu
VCRI-Orathanadu
12-08-2021

Tender Details

Supply, Erection And Commission Of Ahu Unit With Duct System In Clean Room Of Ethno Building At Veterinary College And Research Institute, Orathanadu. ( Re-Tender ) As Per Boq

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Aug-2021 Tender Document Condition Technical Bid 12-08-2021

Key Value

Document Fees
Refer document
EMD
INR 40200.0 /-
Tender Value
INR 60.29 Lakhs /-

BOQ Items

Name of Work: Supply, erection and commission of AHU Unit with Duct System in clean room of ETHNO Building at Veterinary College and Research Institute, Orathanadu.(Re-Tender)
Sl. No. Item Description
1AHU Facilities
2FLOOR MOUNTED AIR HANDLING UNITS : (ALL OTHER ROOM) Supply of 22 TR-7608CFM Factory assembled Double Skin AHU with 50 mm 40 kg/cum PUF Insulated detachable panels, Base frame made of galvanised steel with die cast aluminium joints having lifting holes , AMCA tested DIDW backward curved centrifugal fan with EFF1 rating motor compatible ,vibration isolators out of heavy duty rubberised mounts, prefilters with 3 ply HDPE flanged type 100 mm thick filters having an efficiency of 90%-10 Mic, 6 row deep high delta T DX copper cooling coil, aluminium fins at 12 FPI, velocity across coil not exceeding 475 FPM, condensate coil trough with SS-304-20G insulated with13 mm thick RPUF ,Fine filters double stage 5Micron Filters, Mixing Box For Fresh air & Return air Provision for fresh air damper & Return air damper. CLASS 100000 HEPA filters have to placed in AHU. The panel for outer and inner will be 0.8mm.Accessories include access doors with hinges, handles and door knobs, Polycarbonate View Glass, Pressure Ports, DOP Ports Limit Switch, Emergency Light, Guard for Inspection Door, dampers of aerofoil blades & PVC gears and flexible fire retardant canvass complete with galvanised hardware to mention 60% RH, Totally internal & External 70MM of STATIC OF WG
3Supply, Installation Testing Commissioning and handling over of Air cooled self contained ductable 11TR Ductable condensing unit with connection complete.
4FLOOR MOUNTED AIR HANDLING UNITS : (AUTOMATIC FILLING ROOM) Supply of 5.5 TR-5500CFM Factory assembled Double Skin AHU with 50 mm 40 kg/cum PUF Insulated detachable panels, Base frame made of galvanised steel with die cast aluminium joints having lifting holes , AMCA tested DIDW backward curved centrifugal fan with EFF1 rating motor compatible, vibration isolators out of heavy duty rubberised mounts, prefilters with 3 ply HDPE flanged type 100 mm thick filters having an efficiency of 90%-10 Mic, 6 row deep high delta T DX copper cooling coil, aluminium fins at 12 FPI, velocity across coil not exceeding 475 FPM, condensate coil trough with SS-304-20G insulated with13 mm thick RPUF ,Fine filters double stage 5Micron Filters, Mixing Box For Fresh air & Return air Provision for fresh air damper & Return air damper. CLASS 10000 HEPA FILTERS have to placed in AHU The panel for outer and inner will be 0.8mm.Accessories include access doors with hinges, handles and door knobs, Polycarbonate View Glass, Pressure Ports, DOP Ports , Limit Switch, Emergency Light, Guard for Inspection Door, dampers of aerofoil blades & PVC gears and flexible fire retardant canvass complete with galvanised hardware to mention 60% RH, Totally internal & External
5Supply, Installation Testing Commissioning and handling over of Air cooled self contained ductable 5.5TR Ductable condensing unit with connection complete.
6FLOOR MOUNTED AIR HANDLING UNITS : (BLISTERING ROOM) Supply of 3 TR-1200CFM Factory assembled Double Skin AHU with 50 mm 40 kg/cum PUF Insulated detachable panels, Base frame made of galvanised steel with die cast aluminium joints having lifting holes , AMCA tested DIDW backward curved centrifugal fan with EFF1 rating motor compatible, vibration isolators out of heavy duty rubberised mounts, prefilters with 3 ply HDPE flanged type 100 mm thick filters having an efficiency of 90%-10 Mic, 6 row deep high delta T DX copper cooling coil, aluminium fins at 12 FPI, velocity across coil not exceeding 475 FPM, condensate coil trough with SS-304-20G insulated with13 mm thick RPUF ,Fine filters double stage 5Micron Filters, Mixing Box For Fresh air & Return air Provision for fresh air damper & Return air damper. CLASS 10000 HEPA FILTERS have to placed in AHU The panel for outer and inner will be 0.8mm.Accessories include access doors with hinges, handles and door knobs, Polycarbonate View Glass, Pressure Ports, DOP Ports , Limit Switch, Emergency Light, Guard for Inspection Door, dampers of aerofoil blades & PVC gears and flexible fire retardant canvass complete with galvanised hardware to mention 60% RH, Totally internal & External 60MM of STATIC OF WG.
7Supply, Installation Testing Commissioning and handling over of Air cooled self contained ductable 3 TR Ductable condensing unit with connection complete.
8Supply and Installation of Pass box which is made up of IS 304 Stainless steel. The working dimension is (W24"xD24"xH24") and overall dimension is ( W 675 x D 675 x H 675 mm). Pass box we consider as static pass box
9Supplying and fixing of GI Single Door:45 mm thick single door made of 0.8 mm thick GI powder coated on both sides with infill of PUF 40 kg/m3 with all hardware, toughened double glazing, and all accessories are Dorset 1200x2100 including cost of material etc., complete (1.20x2.40)
10Supplying and fixing of GI Single Door:45 mm thick Double door made of 0.8 mm thick GI powder coated on both sides with infill of PUF 40 kg/m3 with all hardware, toughened double glazing, and all accessories are Dorset including cost of material etc., complete (1.50x2.10)
11Supply and Installation of 50mm PUF panel which is 0.47mm thick Preprinted Off White off white colour50 mm thick Polyurethane Of Density 40Kg/M3(+ or - 2kg) 0.47mm thick Prepainted off white colourincluding cost of materials and labour charges etc., complete.
12Supply and fixing of Star delta Starter and Direct on line starter Control panel for AC unit with suitable electrical connection complete. 22TR AHU
135.5TR AHU
143.0TR AHU
15Supply, Installation & Testing of Refrigerant copper piping between AHU & outdoor units with 19 mm thick Nitrile Rubber insulation for Gas pipe and 13mm thick Nitrile Rubber insulation for Liquid pipe 1-1/8"
167/8"
173/4"
185/8"
193/8"
20Supply & laying of PVC drain pipe with 9mm thick Nitrile Rubber insulation 32mm dia
21Supply & laying of 4C x 2.5 sq.mm Copper control cabling between panel to outdoor unit with connection complete.
22Supply & laying of 4C x 4 sq.mm Copper control cabling between panel to indoor unit with connection complete.
23Supply and Charging of Additional R410a Gas
24Installation, Testing and handing over of the entire unit 22TR AHU
255.5TR AHU
263.0TR AHU
27Supply and Installation of Relative Humidity controller and Temperature controller and all accessories
28Supply and Installation of factory fabricated Aluminium sheet rectangular ducting 1 mm thick (20G)
29Supply and Installation of factory fabricated Aluminium sheet metal rectangular ducting 0.8 mm thick (22G)
30Acoustic insulation of ducts with 10 MM Nitrile Rubber Insulation With Addssive.
31Supply and erection of thermal insulation for supply air duct with closed cell XLPE, 13mm thick with aluminium foil.
32Supply and Installation of Al Diffuser 450x450mm Collar size 600x600mm Neck size
33Supply and Installation of GI volume control duct damper
34Supply and Installation of Canvass Connection for Duct
35Supply and Installation of 5/8" Drier & Expansion value for the Outdoor Units
36Supply and Installation of N2 pressure testing and Vaccumssing
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail