Power Development Department has published Augmentation Of 1X6.3 Mva To 2X6.3 Mva Receiving Station Palhallan District Baramulla Under Winter Preparedness Scheme . Submission Date for this Tender is 10-08-2021. Electrical Maintenance Tenders in Palhallan Pattan Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | SITC of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) |
2 | SITC of 33 kV Isolator without Earthing Blade (36KV,1250A, Outdoor, 3 poles, 25 KA) |
3 | SITC of 33 kV Current Transformer (33 kV, 1F, Multi Ratio Multi Core, Outdoor) (1 No. per F) |
4 | SITC of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer) gap less |
5 | Supply of 33 kV C&R Panel along with O/C, E/F and differential relays(IEC61850), mimic diagram, voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5Amps, DLMS Compliant with RS-485 port |
6 | Instiallation testing and commissioning of 33 kV C&R Panel along with O/C, E/F and differential relays(IEC61850), mimic diagram, voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5Amps, DLMS Compliant with RS-485 port |
7 | SITC of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m |
8 | SITC of GI pipe nominal bore 200,5.9mm thick |
9 | SITC of Galvanised Steel Structures |
10 | SITC of Galvanised Nuts & Bolts |
11 | SITC of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
12 | SITC of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
13 | SITC of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
14 | SITC of Lugs, Ferrules etc. |
15 | SITC of ACSR Conductor Panther |
16 | SITC of T Clamps |
17 | Handling and carriage from Sub. Store / Divisional Store to siteandITC of 6.3 MVA 33/11KV, ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections. (job. include Dismentalling fixing of any accessory required during transit) |
18 | SITC of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
19 | SITC of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
20 | SITC of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
21 | Supply of11 kV VCB Panel Board (12 kV, 1250A, 25 KA, indoor) with O/C, E/F relays (IEC61850, mimic diagram, volt meter, ammeter, annunciation windows with annunciation relay, 3 phase triovecto meter-5Amp, Dlms compliant with RS-485 port(2Incommer ) |
22 | ITC of11 kV VCB Panel Board 2 no(12 kV, 1250A, 25 KA, indoor) with O/C, E/F relays (IEC61850, mimic diagram, volt meter, ammeter, annunciation windows with annunciation relay, 3 phase triovecto meter-5Amp, Dlms compliant with RS-485 portincluding supply of coupling bus chamber to match buses of existing VCB"s with new |
23 | SITC of 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) |
24 | SITC of 11 KV 400mm2single- Core XLPE cable (with one spare length) armoured, FRLS |
25 | SITC of 11 kV Indoor/outdoor Heat Shrinkable Cable Termination Kits |
26 | SITC of Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole |
27 | SITC of MCCB - 200 Amps with LED phase indicators enclosed in mettel coated box CRCA thickness not less than 2mm out door type |
28 | Cable Trench for laying of 11 kV XLPE / control Cables in the out door yard with cover plates of RCC or chequer plates (6mm Thick) (the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY) |
29 | 33/11 kV Power Transformer Foundation(the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY) |
30 | 33 kV Equipment Foundation & Gantry foundation(the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY) 1.REC/DDUGJY/33/11KV PSS/09for 33kv VCB & CT (individual layout to be adopted) 2.REC/DDUGJY/33/11KV/PSS/10 ( for ISO) 3. REC/DDUGJY/33KV/02 (for any other kindly refer Drawings attached) |
31 | Providing and Laying of Earthing Mat (GI Flat 50 mm x8 mm) ( design to be adopted as per REC statndard for the type of soilin that area )(Chemical earthing if required will be done by contractor withinquoted rateto get desired resistivity values required for rec stations ) |
32 | SITC of Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip. |
33 | Providing and Laying of 33 kV Yard Concreting and Metalling with crushed stone aggrigate of suitable dia required crushed out of Nalla boulder ) |
34 | SITC of Yard lights (LED lightsof 50Won 11 meter long octoganal galnanized GI poles) Incl. Glavinized holding arms for LED lights with RCC foundation and foundation bolts and MCB control on pole with under groundwiring using 6mm sq PVCcopper wire from inside control room distribution panel to the pole. with (pole and LED lights Should be of Bajaj / Philips / Havels make) as per REC Standard. |
35 | SITC of a). Battery Bank 36 V,180 AH , of 18 No. cells of 2 V each,sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame etardant. b). 36v,180 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . |