Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun, GE DEHRADUN-Uttarakhand

Military Engineer Services-MES has published Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun. Submission Date for this Tender is 20-08-2021. Civil Work Tenders in GE DEHRADUN Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

28695559
Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun
Open Tender
Indian
Uttarakhand
GE DEHRADUN
20-08-2021

Tender Details

Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun Provn Of Mgps Manifold And Allied Works In Covid Ward At Mh (Spl Work) Under Ge Dehradun

Key Value

Document Fees
INR 500 /-
EMD
INR 88000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:-PROVN OF MGPS MANIFOLD AND ALLIED WORKS IN COVID WARDAT MH(SPL WORK) UNDER GE DEHRADUN
Sl. No. Item Description
1Excavation in trenches n exc. 1.5 m wide and n" exc. 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed.
2Returning, filling of excavated soil, including spreading leveling, watering and well ramming in layers, not exceeding 25cm complete all as specified and directed.
3Removing of surplus soil to a distance n exc 50 m and depositing where directed at a level n exc 1.5m above the starting point complete.
4Sand filling in trenches with clean dry unwashed sand free from sharp particles, gently punning around the cables complete.
5Supply & Laying well burnt bricks, sub class "B" brick laid breadth wise, along the cable in trenches after sand cushioning laid for protection of UG cable protection complete all as specified and directed.
6Cutting into existing bituminous carpet road/PCC hard standing to a depth of 30 CM and including excavation of remaining 30 CM soft /loose soil for laying of pipes/UG cables and making good the disturbed surfaces to match with the existing complete all as directed.
7S&F and lay GI Pipe galvanized, “light grade”, on wall/with pole/under PCC/under Road/ Under Pavments80 mmdia for cable protection all as specified and directed.
8S&F and lay GI Pipe galvanized, “light grade”, on wall/with pole/under PCC/under Road/ Under Pavments100 mmdia for cable protection all as specified and directed.
9M&L point wiring with PVC insulated 1.5 sqmm multi strandedFRLS copper conductor cable 1100 volts grade drawn into and surface nonmetallic PVC conduit medium grade not less than 20mm (ISI marked) with all conduit fitting and fixing accessories including sunk in cast iron/pressed steel terminal boxes (duly painted with two coats of anti corrosive paint out side and two coats of aluminium paint inside) with 2.8 mm thick HYLAM brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators, etc and 1.5 sqmm multi strand copper conductor cable as continuous earthwire complete for the following :-
10One light/fan point controlled by one switch.
11One 5 pin socket out let 5 amps on independent board complete.
12All as per item No 9 here in before but with cable 2.5 sqmm FRLS (nominal area) multi stranded copper wire unsheathed for one 5 pin socket out let 15 amps on independent board including continuous earth wire PVC insulated 1.5 sqmm copper multistranded conductor connecting to common earth and earth dolly complete all as specified and directed.
13S&F Switch piano flush button single pole one way 5 Amp complete all as specified and directed.
14S&F Switch socket combination , 5 Pin, 6 Amp2 in 1, flush type, universal complete.
15S&F Switch socket combination , 6 Pin, 5/ 16 Amp5 in 1, flush type, universal complete.
16S&F Ceiling rose 3 terminal/pvc/polycarbonate, isolated body.
17Supply and fixing LED lights fitting 1x 18W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose all as specified and directed.
18Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics, bend pipe and clamps, nut boltsetc complete with IP 65/66 protection all as specified and directed.
19S&F Sheet metal enclosure MCB DB, double door , 08 way SPN, 240 volts with 200 Amps rated bus bar with blanking plates wherever required and I.P. 20 degree protection all as specified and directed.
20S&F MCB single pole 240 volts, 6 to 32 Amps "B" Series all as specified and directed.
21S&F MCB single pole and neutral 240 volts, 25 to 40 Amps "B" Series all as specified and directed.
22S&F sheet metal enclosure, single pole and neutral with a two pin and earth plug and socket with and including one single pole MCB 20. Amps, 240 volts,10 KAcomplete all as specified and directed.
23M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) vertically, with top edge of plate not less than 1.5 metre below normal ground level connected to galvanised earth wire 4 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of MES Schedule Part-I connecting to earthing test point & to main switch board andtesting on completion with and including necessary excavation and earth work in any type soil, earth lead connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded BT stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, internal surface of concrete shall be given 10mm thick plaster in CM 1:4, pre cast RCC (1:2:4)type B-1 (using 20mm graded BTstone aggregate) 40mm thick cover, reinforced with 8mm dia deformed or TMT bars 3 Nos both way with 12mm dia round bar handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh and 15mm dia GI medium grade earth lead protection pipe etc complete all as specified and directed.
24M&L, sub main wiringwith two single core PVC insulated unsheathed FRLS multi stranded copper conductor (ISI marked with valid CML No), cable 1100 Volt grade, 4 sqmm size drawn in and includingnon metallic rigid PVC concealed conduit (ISI marked with valid CML No) not less than 25 mm dia with all fitting & fixing accessories including one run single core PVC insulated unsheathed 2.5 Sqmm FRLS copper conductor (ISI marked with valid CML No) colour code as a earth continuity and connected upto DB complete all as specified and directed. (NOTE: (i) Two run of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit and the quoted rates shall be deemed to be inclusive for cutting chasesin wall/pillars/columns etc. of any description for concealing the conduits to required depth & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with the existing surface.
25Supply and installing commissioning and testing ofHT 11 KV, 3 phase 50 Hz, indoor type,totally enclosed metal clad switchgear complete with Vacuum Circuit Breaker having rupturing capacity 250 MVA,overload and earth fault protection, ammeter, voltmeter and of rating upto 400 Amp, including necessary connection , PCC Platform complete all as specified and directed.
26Supply, installation, testing and commissioning of transformer 200 KVA, 11/0.433 KV, 3 phase50 Hz, Dyn11, out door ONAN type, copper wound, oil immersed naturally cooled,step down transformer with OFF circuit tap charging arrangement on HV side in steps of +5% to -10% in step of 2.5% each and having cable end box on HV & LV side. The cable box at LV/HV side shallbe suitable to house for proper size and capacity of out going aluminium cable and to be provided with gland and gland plate. The transformer shall be provided with all standard accessories and first filling of filtered dehydrated transformer oil of IS: 335 complete as per specification and confirming to IS: 1180:2014 energy efficiency having level-3(EEL3). The Transformer shall be having following standard accessoriescomplete all as specified and directed:- (a) Name rating & diagram plate - 01 Nos(b) Off circuit tap changing switch -01 Nos(c)Earthing Terminals -02 Nos(d)Lifting lugs -02 Nos (e) Oil level indicator (flush tube) -01 Nos (f)Oil drain valve with plug - 01 Nos(g)Oil temperature gauge-01 Nos(h) Aluminium body breather -01 Nos (j) Vent pipe - 01 Nos Note:- Cost of any other accessories as per manufacturers instructions/ IS provision shall be inclusive in the quoted rates.
27Supply and installing commissioning and testing of LT panel/ outdoor Kiosk type factory made weather and vermin proof fixed on and including ventilation and louvers arrangement, PCC (1:2:4) foundation of required/suitable size and as directed at site with angle iron frame of size and as directed at site with angle iron frame of size 40x40x6mm, 3 phase, 4 wire, 415 volts, 50 Hz, fabricated out of 3.15 mm thick MS sheet including two coats of synthetic enamel paint over a coat of primer red oxide paint and keeping adequate working space inside the box (outer width of the box not less than 45 cmand gap between bus bar not less than one inch) and double door be provided with proper hinged and sliding door handle including locking arrangement as directed and before manufacturing the panel and the same have the following electric controls :- (a) Insulation epoxy painted high conductivity Copper bus bar 400 Ampsfor 3 phase and neutral complete all as specified and directed. (b) Digital Voltmeter 0 to 500 Volts - 01 set (c) Digital Ampere meter 0 to 200 Amps capacity- 01 Set (d) Indicating lamps Neon type for RYB - 01 set Incoming (i)MCCB 4 Pole 415 volts 250 Amps, 16 KA as incoming - 01 Nos. Make :- ABB/L&T/Legrand. Outgoing (i)MCCB 4 Pole 415 volts 63 Amps, 16 KA as outgoing - 03 Nos Make :- ABB/L&T/Legrand. (ii)MCCB 4 Pole 415 volts 100 Amps, 16 KA as outgoing - 03 Nos Make :- ABB/L&T/Legrand.
28Supply,laying, testing & commissioning of XLPE insulated screened PVC bedded galvanised steel strip or wire armured electric power cable (Heavy duty ) with aluminium conductor 1100 volts grade, cross sectional area of following size :-
29185 Sqmm 3.5 Core
3070 Sqmm 3.5 Core
3110 Sqmm 4 Core
3210 Sqmm 2 Core
33Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sqmm complete all as specified and directed
34Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 70 to 120 sqmm complete all as specified and directed.
35M&L for earthing complete with GI or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI earth strip 32X6 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-Iand specified includingprovision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation andearth work & connecting the earthing to an earthing test point /transformer nuetral/body/ Lt panel etc. and testing on completion, complete all as specified & directed by Engr-in-Charge.
36Material and labour for earth continuity conductor or main earthing strip fixed to wall on batten or porcelain insulators or recess or chases or buried in ground or drawn inGI pipe 40 mm or fixed with poles or any other indicated sitution for loop earthing etc as required using galvanised iron strip of size 32 X 6 mm complete all as directed.NOTE :-(i)GI Pipe 40 mm shall be measured and paid separately
37Supplying, laying, testing and commissioning of XLPE insulated screened PVC bedded galvanised steel strip or wire armured electric power cable(Heavy duty ) with aluminium conductor 1100 volts grade, cross sectional area size 6 Sqmm 2 Core.
38S&F and lay GI Pipe galvanized, “light grade”, on wall/with pole/under PCC/under Road/ Under Pavments40 mmdia for cable protection all as specified and directed.
39S&F Sheet metal enclosure MCB DB, double door , 04 way SPN, 240 volts with 200 Amps rated bus bar with blanking plates wherever required and I.P. 20 degree protection complete.
40S&F MCB single pole and neutral 240 volts, 25 to 40 Amps "B" Series complete.
41S&F in repair steel medium grade tubing of 15 mm with all fittings laying in trenchesall as specified and directed by the Engr in Charge
42Supply & Fixing Bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed
43S&F self priming monobloc pump of 0.5 HP complete all as specified and directed by Engr - in - Charge.
44M & L for oxygen control panel with all accessoriescomplete all as specified and directed by Engr-in-Charge Note :- One for cylinder refilling and one for supplying of wards.
45Supply, installation, commissioning and testing of Oxygen Manifold : Main confirming to ISO standards with Middle Frams 2 Banks x 10 Cylinder each bank oxygen Manifold (without Cylinders) suitable to tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifol Top frame comprising of high pressure copper pipes of size 12 mm with high pressure brass fittings made of high tensile brass and connections thorugh non return valves high pressure copper tail pipes, made of high pressure copper pipe of size 12mm.the design middle and bottom frames should be provided fit both round and flat bottom cylinder safely.the manifold shall be tested (hydraucally) at 3500 psig and necessary test certificates of manufacturers be provided alongwith the supply.Only non Halogenated Polymer material are to be used in the Non Return Valves Supplied alongwith the manifold.
46Supply, installation, testing & commissioning of copper pipe of following sizes which shall be drawn half drawn half hard temp, solid drawn, seamless, phosphorous deoxidized, non-aresenic.The supplies of copper pipe would be accompanied with maufactureres test certificate for the physical properties of copper pipes and their chemical composition.
47Copper pipe & Tube (12 mm x 0.7mm Thick)
48Copper pipe & Tube (15 mm x 0.9mm Thick)
49Copper pipe & Tube (22 mm x 0.9mm Thick)
50Copper pipe & Tube (28 mm x 0.9mm Thick)
51Copper pipe & Tube (42 mm x 1.2 mm Thick)
52Copper pipe & Tube (54 mm x 1.2 mm Thick)
53S&F oxygen outlet point Amico type complete all as specified and directed
54S&F BPC flow meter with humidifier bottle typecompleteall as specified & directed
55S & F Isolation butterfly valve 12 mm with brass fittingscompleteall as specified and directed
56S & F copper elbow 15mmcompleteall as specified and directed
57S & F copper reducer Tee 15x12x15mmcompleteall as specified and directed
58S & F copper reducer Tee 22x12x22mm complete all as specified and directed
59S & F 15 mm seddlecompleteall as specified and directed
60S & F 22 mm seddlecompleteall as specified and directed
61S & F 15 mm copper socketcomplete all as specified and directed
62S & F 22 mm copper socketcomplete all as specified and directed
63S & F copper Tee 15mmcomplete all as specified and directed
64S & F 15mm main line gate valve with brass fittingcomplete all as specified and directed
65M&L for ABC type fire extinguisher 6 Kg hand held ISI marked complete all as specified.
66Supply and fixing alarm panel with guagecomplete all as specified and directed
67Supply installation testing and commissioning bed head panel with oxygen vaccum medical air and electrical switch provision complete all as specified.
68Supply installation, testing and commissioning of Master Alarm Panel which shall be LCD touch screen microprocessor controlled.The panel shall be 100 % digital and shall not require re-calibration.The panel shall be able to interface with building management systems.The alarm panel shall be enclosed in a steel box and shall be degined to accept an electrical input range 120-240 Volts Ac. (a) The source voltage shall be step down with a self-contained transformer.The panel shall contain audiable and visual alarm indicators.the audiable alarm may be silenced by pressing the alarm silence button,but the visual alarm indicator can only be cancelled by fault correction.the alarm shall detect and filter out transist signals ( liss than 0.6 seconds).The alarm shall be capable of displaying alarm history for all possible alarm conditions.
Disclaimer :