Ge / Khu-19 / 2021-2022 Ge / Khu-19 / 2021-2022 Repair / Replacemement To Unserviceable Lt Panels, Lt Cables, Switchgear, Lightening Conductors And Earthing In The Aor Of Age Br-Ii, Khaltsi Under Ge Khumbathang, GE KHUMBATHANG-Jammu And Kashmir

Military Engineer Services-MES has published Ge / Khu-19 / 2021-2022 Ge / Khu-19 / 2021-2022 Repair / Replacemement To Unserviceable Lt Panels, Lt Cables, Switchgear, Lightening Conductors And Earthing In The Aor Of Age Br-Ii, Khaltsi Under Ge Khumbathang. Submission Date for this Tender is 27-08-2021. Electrification Work Tenders in GE KHUMBATHANG Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

28695443
Corrigendum : Ge / Khu-19 / 2021-2022 Ge / Khu-19 / 2021-2022 Repair / Replacemement To Unserviceable Lt Panels, Lt Cables, Switchgear, Lightening Conductors And Earthing In The Aor Of Age Br-Ii, Khaltsi Under Ge Khumbathang
Open Tender
Indian
Jammu And Kashmir
GE KHUMBATHANG
27-08-2021

Tender Details

Ge / Khu-19 / 2021-2022 Ge / Khu-19 / 2021-2022 Repair / Replacemement To Unserviceable Lt Panels, Lt Cables, Switchgear, Lightening Conductors And Earthing In The Aor Of Age Br-Ii, Khaltsi Under Ge Khumbathang

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Aug-2021 GE/KHU-19/2021-2022 Date 20-08-2021
2 20-Aug-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 27-08-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 35980.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR/REPLACEMEMENT TOUNSERVICEABLE LT PANELS,LT CABLES,SWITCHGEAR,LIGHTENING CONDUCTORS AND EARTHINGIN THE AOR OF AGE BR-II,KHALTSIUNDER GE KHUMBATHANG
Sl. No. Item Description
1Excavation in trenches, getting out in hard/dense soil not exceeding 1.5m deep and not exc 1.5m wide for taking out the existing cable of poles etc any size at places complete all as specified and directed.
2Removing of surplus soil to a distance not exceeding 50 mtr complete all as specified and deposited where directed at a level not exceeding 1.5m above the starting point all as specified.
3Returning filling in including spreading, levelling, and well ramming, in layers not exceeding 25 cm each layer of any kind of soil complete all as specified and directed.
4M&LSandcushioningwith clean dry sandto cables with layer of sand 8cm before laying of cable and 15cm thick after laying of cablecomplete all as specified. Note : For payment purpose punned thickness of 18 cm shall be measured against spread thickness of 23cm as mentioned in para 19.75 of SSR part-I.
5M & L for providing PCC cable cover class LV type-I of size 250x150x40mm laid in perpendicular to the cable abutting each other all as specified and directed at site.
6M & L for Cement concrete 1:4:8 type D-2 using 40 mm graded crushedstoneaggregate in foundation filling & mass concrete for poles/struts/stays assembly including provision of necessary form work finishing the exposed surface even and smooth in cement mortar 1:3 complete all as specified and directed.
7M & L cement concrete 1:3:6, type C-1 using 40 mm graded crushedstone aggregate in coping padestal to poles including provision of necessary form work finishing the exposed surface even and smooth complete all as specified. .
8Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size16Sq mm 4 core complete in trenches/ ducts complete all as specified and directed.
9Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 25Sq mm 4 core complete in trenches/ ducts complete all as specified and directed.
10Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 35Sq mm 3.5 core complete in trenches/ ducts complete all as specified and directed.
11Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 50Sq mm 3.5 core complete in trenches/ ducts complete all as specified and directed.
12Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 70Sq mm 3.5 core complete in trenches/ ducts complete all as specified and directed.
13Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 95Sq mm 3.5 core complete in trenches/ ducts complete all as specified and directed.
14Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 120Sq mm 3.5 core complete in trenches/ ducts complete all as specified and directed.
15Supply and laying in replacement ofXLPE insulated screened PVC bedded galvanised steel strip armoured electric power cable heavy duty 1100 Volt grade with stranded aluminium conductor of size 185Sq mm 3.5 core complete in trenches/ ducts complete all as specified and directed.
16Supply & laying of 50 mm bore Mild steel galvanized steel tubing with screwed socket joints, Light grade, together with all fittings (such as bends, elbows, tees, short pieces, connectors, back nuts, diminishing pieces, caps, plugs and unions etc.) and laid in trenchesincluding , screwing and waste and for forged bends on piping as required , cutting through walls, floors and their making good to match with the existing specifications complete all as specified and directed.
17M & L in repair Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending (cold or hot), drilling holes for bolts, bent to any shape or size asdirected and inclusive of one primer coat of red oxide, one under coat of zinc oxide and one finishing coat of aluminium paint complete all as specified.
18M&L in repair pin type insulator, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two GI washers and one GI nut, 100mm height, 65mm dia for 1100 volts grade complete.
19M&L in repair for shackle type, porcelain, vitreous, white, brown or green insulator including galvanized mild steel straps, washers, insulator bolts, washers and nuts of size 75mm height and 90mm dia size of strap 31x3mm and dia of bolts 12mm for working pressure 1100 volts grade complete all as specified and as directed.
20M&L in repair for loop type insulator, vitreous porcelain white, brown or green large size with overall dimensions 90mmx140mm clearance of hole 25.5mm complete all as specified and as directed.
21M&L in repairfor stay assemby complete with accessories such as stay plate 230mmx230mmx6mm, stay rod 180cm long 16mm dia with nuts including GI bow, turn buckle etc. all as per electrical plate No. 01 of SSR Part-I 2009 complete all as specified and as directed.NOTE: Insulator, stay clamps, excavation earthwork and concrete shall be measured and paid for separately
22S&F in repair galvanized steel stranded wire size 7/3.15mm for stay assemblycomplete all as specified and as directed.
23M&L in repair for galvanized steel wire 3.15/4.0mm dia continuous earth wire/guard cradle horizontal/rectangular fabricated with 4mm dia galvanized mild steel binding wire complete all as specified and as directed.
24Material and labour for replacement ACSR conductor squirrelto Rabit (6/1/2.11 to 6/1/3.35)any sizedrawn straighthorizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag ,jointing jumpers,etc complete all as specified and directed
25S & F in repairs MCCB 63 Amp, 4 pole 16 KA with release adjustable thermal & fixed magnetic 240 volt ACIP 20 complete all as specified and directed by Engineer-in-Charge.
26S & F in repairs MCCB 100 Amp, 4 pole 25 KA with release adjustable thermal & fixed magnetic 415 volt AC supply IP 20 complete all as specified and directed by Engineer-in-Charge.
27S & F in repairs MCCB 160 Amp, 4 pole 36 KA with release adjustable thermal & fixed magnetic 415 volt AC supply IP 20 complete all as specified and directed by Engineer-in-Charge.
28S & F in repairs MCCB 200 Amp, 4 pole 36 KA with release adjustable thermal & fixed magnetic,415 volt AC supply IP 20 complete all as specified and directed by Engineer-in-Charge.
29S & F in repairs MCCB 400 Amp, 4 pole 36 KA with release adjustable thermal & fixed magnetic ,415 volt AC supplyIP 20 complete all as specified and directed by Engineer-in-Charge.
30S&F in replacement ofchangeover 4 pole 200 Amps front handle operated including minor additional/alternation as required at site for fixing and connecting up of changeover all as directed by Engr-in-Charge.
31S&F in replacement ofchangeover 4 pole 100 Amps front handle operated including minor additional/alternation as required at site for fixing and connecting up of changeover all as directed by Engr-in-Charge.
32Stretching only the ACSR conductor fixed on LT overhead line pole and tightening the ACSR, by taking down the conductor from insulator completely with auth sag and rewinding the insulator in proper position overhead line complete. Note: one span of Al conductor/GI wire from pole to pole will be measured as one unit/each run.
33M&L for scrapping of old paint from the steel tubular pole upto 9.0 mtr height with out removing accessories and preparation of surface for re-painting. Repainting the pole with one coat of alternative white and black straps of 30cm upto 1.5 mtr height using synthetic enamel paint starting with black strap. repainting the remaining pole and iron parts i.e. U clamps, channels, etc above 1.5mtr height by applying one coat of aluminium paint all as required at site or directed.
34Supply and fixing in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm, complete all as specified and directed
35Supply and fixing in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3½ / 4 core XLPE, armoured, Al conductor cable of size 70 to 120 sqmm, complete all as specified and directed
36M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed
37M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50mm to 95 sqmm complete all as specified and directed
38S & F in replacement ofAluminium strip 25 x 3.15mm complete with saddles and fixing screws etc. for roof conductors and down conductors above ground upto test points.
39M&L for earthing complete with galvanized cast iron earth plate electrode 600 x600x6.0mm buried directly in ground(earth pit not less than 2.25 mtrbelow normal ground level) with top edge of earth plate notless than 1.5 mtrs below normal ground level, connected to galvanized earth lead wire 4.0 mm diabymeans of bolts,nuts, andgalvanized iron or steel all as shown on electrical plate No.05 of SSR Part-1 connected to earthing test point all as specified or indicated including earth work in any type of soil, charcoal salt 15cm around the earth plant as shown inelectrical plate No. 3 of SSR Part-I, 20 mm dia watering pipe light grade 1.70 mtr long with plug at top, GI protection pipe light grade 15 mm dia from earth pit to main boad including testing after completioncomplete all as specified and directed. Note:- (i) Maximum length of GI wire, protection pipe with each earth shall not exceed 7.5 mtrs. (ii) The 20 mm dia watering pipe shall be 20 cm above the ground level and be provided with 20 mm dia GI plug at its top and no concrete watering pit/cover shall be provided.
40M&L in replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw.
41S& F in replacementofGI pipe Medium grade 40 mm dia galvanisedadded in pccblock for fixing air termination rod 12mm complete all as directed by Engineer-in-charge.
42Supply and fix in replacement ofsingle pointed Air termination aluminum rod ,12mm dia 300 mm long complete all as directed by Engineer-in-charge.
43Deduct Credit for Demolished/Dismantled material Rs (-) 26,250.00 (Minus) as listed in Schedule "A" Part-II (Credit Schedule) Note : Tenderers will not quote against this item being a tentative amount, to be considered to arrive at the "Contract Sum".