Supply Installation Testing Commissioning Of 33Kv Line Bay 33Kv Transformer Bay 33-11Kv Power Transformer Capacitor Bank 11Kv Indoor Switch Gears And Common Miscellaneous Civil ( Electrical Equipment Foundations ) And Electrical Works For Upcoming Rec, jagerpora Kupwara-Jammu And Kashmir

Power Development Department has published Supply Installation Testing Commissioning Of 33Kv Line Bay 33Kv Transformer Bay 33-11Kv Power Transformer Capacitor Bank 11Kv Indoor Switch Gears And Common Miscellaneous Civil ( Electrical Equipment Foundations ) And Electrical Works For Upcoming Rec. Submission Date for this Tender is 14-08-2021. Electrical Maintenance Tenders in jagerpora Kupwara Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

28464906
Corrigendum : Supply Installation Testing Commissioning Of 33Kv Line Bay 33Kv Transformer Bay 33-11Kv Power Transformer Capacitor Bank 11Kv Indoor Switch Gears And Common Miscellaneous Civil ( Electrical Equipment Foundations ) And Electrical Works For Upcoming Rec
Open Tender
Indian
Jammu And Kashmir
jagerpora Kupwara
14-08-2021

Tender Details

Supply Installation Testing Commissioning Of 33Kv Line Bay 33Kv Transformer Bay 33-11Kv Power Transformer Capacitor Bank 11Kv Indoor Switch Gears And Common Miscellaneous Civil ( Electrical Equipment Foundations ) And Electrical Works For Upcoming Receiving Station At Jagerpora Kupwara Sitc Of 33Kv Line Bay 33Kv Transformer Bay 33-11Kv Power Transformer Capacitor Bank 11Kv Indoor Switch Gears And Common Miscellaneous Civil ( Electrical Equipment Foundations ) And Electrical Works For Upcoming Receiving Station At Jagerpora Kupwara

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 16-Jul-2021 corrigundum Fee 26-07-2021
2 16-Jul-2021 CORRIGENDUM BOQ 26-07-2021
3 26-Jul-2021 Extension Notice Date 06-08-2021
4 06-Aug-2021 Extension 2 Date 14-08-2021

Key Value

Document Fees
INR 2000 /-
EMD
INR 226000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: SITC of 33KV Line Bay, 33KV transformer Bay, 33/11KV power transformer, Capacitor Bank, 11KV indoor Switch Gears and common miscellaneous civil ( electrical equipment foundations ) and electrical works for upcoming Receiving station at Jagerpora District Kupwara Under Capex Scheme.
S. No. Item Description Item Code / Make Quantity Units
1 1 SITC works for 33KV Line Bay of Single Bus Scheme BI01010001010000000000000515BI0100001141
2 1.01 SITC of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) BI01010001010000000000000515BI0100001142 1 No.
3 1.02 SITC of 33 kV Isolator with Earthing Blade (36KV,1250A, Outdoor, 3 poles, 25 KA) BI01010001010000000000000515BI0100001143 2 No.
4 1.03 SITC of 33 kV Isolator without Earthing Blade (36KV,1250A, Outdoor, 3 poles, 25 KA) BI01010001010000000000000515BI0100001144 1 No.
5 1.04 SITC of 33 kV Current Transformer (33 kV, 1F, Multi Ratio Multi Core, Outdoor) (1 No. per F) BI01010001010000000000000515BI0100001145 3 Nos.
6 1.05 33 kV Voltage Transformer (33 kV/110 V, 1F, Multi-Core, Outdoor), (1No. per F) BI01010001010000000000000515BI0100001146 3 Nos.
7 1.06 SITC of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer) gap less BI01010001010000000000000515BI0100001147 3 Set
8 1.07 Supply of 33kV C&R Panel along with O/C, E/F relays, mimic diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps with RS-485 port, DLMS Compliant with RS-485 port BI01010001010000000000000515BI0100001148 1 No
9 1.08 Instiallation testing and commissioning of 33kV C&R Panel along with O/C, E/F relays, mimic diagram,Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps with RS-485 port, DLMS Compliant with RS-485 port BI01010001010000000000000515BI0100001149 1 No
10 1.09 SITC of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m BI01010001010000000000000515BI0100001150 3 Nos.
11 1.1 SITC of GI pipe nominal bore 200,5.9mm thick / G.I Angle Iron Gaintaries BI01010001010000000000000515BI0100001151 2.8 MT
12 1.11 SITC of Galvanised Steel Structures BI01010001010000000000000515BI0100001152 1.9 MT
13 1.12 SITC of Galvanised Nuts & Bolts BI01010001010000000000000515BI0100001153 0.3 MT
14 1.13 SITC of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001154 120 M
15 1.14 SITC of 4 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001155 300 M
16 1.15 SITC of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001156 90 M
17 1.16 SITC of Lugs, Ferrules etc. BI01010001010000000000000515BI0100001157 1 Item /LS
18 1.17 SITC of 200 ACSR Conductor Panther BI01010001010000000000000515BI0100001158 100 M
19 1.18 SITC of T Clamps BI01010001010000000000000515BI0100001159 24 Nos.
20 1.19 SITC Single Tension Fittings BI01010001010000000000000515BI0100001160 9 Nos.
21 1.2 SITC Polymeric composite Disc Insulator 36KV, Lightening Impulse170kV Positive and 180kV Negative, creepage distance900mm,min failing load 70kN BI01010001010000000000000515BI0100001161 18 Nos.
22 1.21 SITC of Earth wire 7/4.00 mm sq. BI01010001010000000000000515BI0100001162 58 Kg
23 1.22 SITC of GI flat for earthing 50x6 mm BI01010001010000000000000515BI0100001163 225 Kg
24 2 SITC works for 33KV Transformer Bay of Single Bus Scheme BI01010001010000000000000515BI0100001164
25 2.01 SITC of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) BI01010001010000000000000515BI0100001165 1 No.
26 2.02 SITC of 33 kV Isolator without Earthing Blade (36KV,1250A, Outdoor, 3 poles, 25 KA) BI01010001010000000000000515BI0100001166 1 No.
27 2.03 SITC of 33 kV Current Transformer (33 kV, 1F, Multi Ratio Multi Core, Outdoor) (1 No. per F) BI01010001010000000000000515BI0100001167 3 Nos.
28 2.04 SITC of 30 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO,Polymer) gap less BI01010001010000000000000515BI0100001168 3 Set
29 2.05 Supply of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5Amps, DLMS Compliant with RS-485 port BI01010001010000000000000515BI0100001169 1 No
30 2.06 Instiallation testing and commissioning of 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5Amps, DLMS Compliant with RS-485 port BI01010001010000000000000515BI0100001170 1 No
31 2.07 SITC of 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m BI01010001010000000000000515BI0100001171 3 Nos.
32 2.08 SITC of GI pipe nominal bore 200,5.9mm thick / G.I Angle Iron Gaintaries BI01010001010000000000000515BI0100001172 2.85 MT
33 2.09 SITC of Galvanised Steel Structures BI01010001010000000000000515BI0100001173 1.9 MT
34 2.1 SITC of Galvanised Nuts & Bolts BI01010001010000000000000515BI0100001174 0.3 MT
35 2.11 SITC of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001175 120 M
36 2.12 SITC of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001176 300 M
37 2.13 SITC of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001177 90 M
38 2.14 SITC of Lugs, Ferrules etc. BI01010001010000000000000515BI0100001178 1 Item /LS
39 2.15 SITC of ACSR Conductor Panther BI01010001010000000000000515BI0100001179 100 M
40 2.16 SITC of T Clamps BI01010001010000000000000515BI0100001180 3 Nos.
41 3 Commissioning of 33/11KV Power transformer BI01010001010000000000000515BI0100001181
42 3.01 Handling and carriage from ECSD Pampora / Divisional Store to site and ITC of 6.3 MVA 33/11KV, ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections( within Receiving Sattion) BI01010001010000000000000515BI0100001182 1 No.
43 3.02 SITC of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001183 120 M
44 3.03 SITC of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001184 120 M
45 3.04 SITC of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. BI01010001010000000000000515BI0100001185 240 M
46 4 Capacitor Bank BI01010001010000000000000515BI0100001186
47 4.01 12 kV Capacitor Bank (3.6 MVAR) with VCB Panel with complete arrancement for conection with 11 kV incomer panel , Series Reactor, Isolator, RVT, Surge Arrestors, HT Cable with termination Kits, Control Cables, CRCA Cubicle Panel etc with structure, foundation & accessories. BI01010001010000000000000515BI0100001187 1 Set
48 5 SITC works for 11KV Switch Gear and yard works of 33/11KV Sub. Station. BI01010001010000000000000515BI0100001188
49 5.01 Supply of 11 kV VCB Panel Board (12 kV, 1250A, 25 KA, indoor) with O/C, E/F relays (IEC61850, mimic diagram, volt meter, ammeter, annunciation windows with annunciation relay, 3 phase triovecto meter-5Amp, Dlms compliant with RS-485 port (1+5) (1 Incommer and 5 outgoing) of make schnider / crompton / ABB / Eason Reyrole BI01010001010000000000000515BI0100001189 1 Set
50 5.02 ITC of 11 kV VCB Panel Board (12 kV, 1250A, 25 KA, indoor) with O/C, E/F relays (IEC61850, mimic diagram, volt meter, ammeter, annunciation windows with annunciation relay, 3 phase triovecto meter-5Amp, Dlms compliant with RS-485 port (1+5) (1 Incommer and 5 outgoing) of make schnider / crompton / ABB / Eason Reyrole BI01010001010000000000000515BI0100001190 1 Set
51 5.03 SITC of 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) BI01010001010000000000000515BI0100001191 5 Set
52 5.04 SITC of 11 KV 400mm2 single- Core XLPE cable (with one spare length) armoured, FRLS BI01010001010000000000000515BI0100001192 180 Mtr
53 5.05 SITC of 11 KV 3-Core XLPE 300 mm² armoured, FRLS BI01010001010000000000000515BI0100001193 280 Mtr
54 5.06 SITC of 11 kV Outdoor Heat Shrinkable Cable Termination Kits for single core incomming cable BI01010001010000000000000515BI0100001194 1 Set
55 5.07 SITC of 11 kV Indoor/outdoor Heat Shrinkable Cable Termination Kits (1 set means 1 set outdoor and 1 Setindoor) BI01010001010000000000000515BI0100001195 8 Set
56 5.08 SITC of 11 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch. BI01010001010000000000000515BI0100001196 5 Set
57 5.09 SITC of 9 Mtr. Long Pole(ST-410 SP33) BI01010001010000000000000515BI0100001197 8 Nos
58 5.1 SITC of Galvanised iron of sorts BI01010001010000000000000515BI0100001198 480 kg
59 5.11 SITC of 100 KVA,11/0.433KV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) BI01010001010000000000000515BI0100001199 1 No
60 5.12 SITC of 120 mm² PVC LT Cable 4 Core, armoured, FRLS BI01010001010000000000000515BI0100001200 40 Mtr
61 5.13 SITC of Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole BI01010001010000000000000515BI0100001201 8 Nos
62 5.14 SITC works for Earthing of 100 KVA substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. BI01010001010000000000000515BI0100001202 1 Nos
63 5.15 SITC works for Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip BI01010001010000000000000515BI0100001203 6 Nos
64 5.16 SITC of MCCB - 200 Amps with LED phase indicators enclosed in mettel coated box CRCA thickness not less than 2mm out door type BI01010001010000000000000515BI0100001204 1 No
65 6 Common MISCELLANEOUS works in 33/11 KV Sub. Station. BI01010001010000000000000515BI0100001205
66 6.01 Cable Trench for laying of 11 kV XLPE / control Cables in the out door yard with cover plates of RCC or chequer plates (6mm Thick) (the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY) BI01010001010000000000000515BI0100001206 45 RM
67 6.02 33/11 kV Power Transformer Foundation (the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY) BI01010001010000000000000515BI0100001207 1 Full Job
68 6.03 33 kV Equipment Foundation & Gantry foundation (the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY)\n1. REC/DDUGJY/33/11KV PSS/09 for 33kv VCB & CT (individual layout to be adopted)\n2.REC/DDUGJY/33/11KV/PSS/10 ( for ISO)\n3. REC/DDUGJY/33KV/02\n(for any other kindly refer Drawings attached) BI01010001010000000000000515BI0100001208 1 Full Job
69 6.04 11 kV Equipment Foundation & Gantry foundation (the Design / drawing / rainforcement / concrete mix will be as per standards adopted by deptt under REC / PMDP/DDUGJY)\n(for reference Check Drawings attached) BI01010001010000000000000515BI0100001209 1 Full Job
70 6.05 Supply and fixing of tar steel (16mm, 12mm, 10mm, 8mm) for Rainforcement concrete BI01010001010000000000000515BI0100001210 10 Qtl
71 6.06 Providing and Laying of Earthing Mat (GI Flat 50 mm x8 mm) ( design to be adopted as per REC statndard for the type of soil in that area )(Chemical earthing if required will be done by contractor within quoted rate to get desired resistivity values required for rec stations ) BI01010001010000000000000515BI0100001211 35 Qtl
72 6.07 SITC of Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip. BI01010001010000000000000515BI0100001212 50 No.
73 6.08 Providing and Laying of 33 kV Yard Concreting and Metalling with crushed stone aggrigate of suitable dia required crushed out of Nalla boulder ) BI01010001010000000000000515BI0100001213 1 Item
74 6.09 Providing and Laying of 11 kV Yard Concreting and Metalling with crushed stone aggrigate of suitable dia required crushed out of Nalla boulder ) BI01010001010000000000000515BI0100001214 1 Item
75 6.1 SITC of Yard lights (LED lights of 50W on 11 meter long octoganal galnanized GI poles) Incl. Glavinized holding arms for LED lights with RCC foundation and foundation bolts and MCB control on pole with under ground wiring using 6mm sq PVC copper wire from inside control room distribution panel to the pole. with (pole and LED lights Should be of Bajaj / Philips / Havels make) as per REC Standard. BI01010001010000000000000515BI0100001215 4 No
76 6.11 2KV dry type voltage stablizer(Copper Wound) for LED lights to be supplied and installed on AC Distribution board with volt meter input put out put slector switch , 16mm male female socket and 2mtr lead. BI01010001010000000000000515BI0100001216 1 No
77 7 Common MISCELLANEOUS equipments for 33/11 KV Sub. Station. BI01010001010000000000000515BI0100001217
78 7.01 SITC of \na). Battery Bank 36 V,180 AH , of 18 No. cells of 2 V each,sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame etardant.\nb). 36v,180 AH , Float-Cum-Boost Charger With Full wave\nrectification for 220 V, 1Phase, 50 HZ AC Input Supply . BI01010001010000000000000515BI0100001218 1 No.
79 7.02 Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories BI01010001010000000000000515BI0100001219 1 No.
80 7.03 Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories BI01010001010000000000000515BI0100001220 1 No.
81 7.04 Supply of Fire Extingiusher Co2 Type of 4.5 kg capacity for control room BI01010001010000000000000515BI0100001221 6 No.
82 7.05 Supply of 3 Sand Bucket Fire Extingiusher BI01010001010000000000000515BI0100001222 1 set
83 7.06 Supply of Helmet (motercycle Type with wind glass) BI01010001010000000000000515BI0100001223 4 No.
84 7.07 Supply of Rubber Gloves for 33 kV level BI01010001010000000000000515BI0100001224 2 set
85 7.08 Supply of Rubber Gloves for 11kV level BI01010001010000000000000515BI0100001225 2 set
86 7.09 Supply of Safety Belt BI01010001010000000000000515BI0100001226 4 No.
87 7.1 Supply of Safety Shoes heavy dutty rubber sole BI01010001010000000000000515BI0100001227 4 No.
88 7.11 Supply of HV Detectors all voltages (50 hV with teloscopic rod of 5 Mtr detachable) BI01010001010000000000000515BI0100001228 1 No.
89 7.12 Supply of Earthing rod (set of 3 rods) (with telescopic rod of 5 Mtr detachable) BI01010001010000000000000515BI0100001229 1 set
90 7.13 Supply of HV Detectors all voltages (50 hV with telescopic rod of 5 Mtr detachable) BI01010001010000000000000515BI0100001230 1 No.
91 7.14 Supply of Dell 3 in 1 Intel® Core™ i5-9500 (6 Cores/9MB/6T/3.0GHz to 4.4GHz/65W),Windows 10 Pro (64bit) English\n(Dell recommends Windows 10 Pro for business),Intel® Integrated Graphics, 8GB 1X8GB 2666MHz DDR4 Memory, 2.5 inch 1TB 7200rpm SATA Hard Disk Drive, Ports & Slots with wireless Key board , mouse and double battery UPS ( to be delivered at Divisional Store) BI01010001010000000000000515BI0100001231 1 No.
92 7.15 Chain saw petrol 18 inch ( Bosh/Honda) ( to be delivered at Divisional Store) BI01010001010000000000000515BI0100001232 1 No
93 7.16 Pulling and lifting machine 5 ton with Steel cabble of 10 Mtr long. ( to be delivered at Divisional Store) BI01010001010000000000000515BI0100001233 1 No
94 7.17 2000 watt with wire G-coil hot plate indection cooking stove with ON OFF Switch (220volt, wire length 1.5 Mtr with 3Pin top) BI01010001010000000000000515BI0100001234 1 No
95 7.18 SITC of Bore well with control Pannel of Specification outer casing 5'' Steel Iron Pipe with 1HP submersible Pump with 1inch Gi pipes and fittings upto storage tank with 1out let point in yard complete job with a digging range of 150 ft to 180 ft BI01010001010000000000000515BI0100001235 1 Job