Military Engineer Services-MES has published Special Repairs And Replacement Of Ber Declared Lt Panel At Sub Station F And Provision Of Stabilizer Work Stattion Minor Work At Arakkonam. Submission Date for this Tender is 01-07-2021. Electrical Panel Tenders in Arakkonam Tamil Nadu. Bidders can get complete Tender details and download the document.




Tender Notice

28290138
Corrigendum : Special Repairs And Replacement Of Ber Declared Lt Panel At Sub Station F And Provision Of Stabilizer Work Stattion Minor Work At Arakkonam
Open Tender
Indian
Tamil Nadu
Arakkonam
01-07-2021

Tender Details

Special Repairs And Replacement Of Ber Declared Lt Panel At Sub Station F And Provision Of Stabilizer Work Stattion Minor Work At Arakkonam

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Jun-2021 BOQ Corrigendum BOQ 01-07-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 64000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: SPECIAL REPAIRS AND REPLACEMENT OF BER DECLARED LT PANEL AT SUB STATION "F" AND PROVISION OF STABILIZER , WORK STATTION MINOR WORK AT ARAKKONAM (Tender ID. 2021_MES_ 453901 _1)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Disconnecting all electric connection from the existing BER declared 3 Phase LT Panel board with ACB from the existing position including taking up complete LT Panel board with Copper bus bar 3 Phase & Neutral, placing in adjacent location and making connections for restoration of electric supply provisionally including shifting from the existing locations carefully and handed over to MES store on completion of work, without making any damage to walls /floor/building complete including necessary Tools / Plants etc and disconnection of earthing lead connection etc and making good the distrubed portions of the building / walls / ducts / floor / other surfaces etc to match with the existing specification of surfaces complete all as directed . 1 Each Job
2 2 Material and labour for fabricate,Supply,Install,Testing and commissioning of self supported totally enclosed floor mounted on Base channel of size 75 mm x 75 mm and thickness not less than 5 mm Indoor type LT Panel fabricated from CPRI certified Panel builder factory and fabricated made out of CRCA sheet of thickness not less than 2 mm ,dust and vermin proof, hinged, smoothly openable front and rear door, with neoprene rubber gasket, epoxy powder coated including danger plate, earth strip ( 32 x 6 mm) connecting provision - 02 Nos, including ventilation louvers, bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc, complete panel board suitable for 3 phase 4 wire ,415 volts 50 hz, including the following items and connecting all outgoing feeder cables using new suitable size lugs and connecting with earth strip, copper bus bar complete including necessary civil works and writing in coming and out going feeder details as per site requirement and as specified all as specified and directed. 1 Each Job
3 2.01 (i) INCOMMING ;\n ACB rating 1000 Amps,415 Volts, 4P, 50KA ( ICU=ICS=ICW -100% 1sec) Manual drawout Type ACB with microporocessor based trip unit with overload,short circuit,instantaneous earth fault protection, shunt trip and necessary multi function meters,Voltmeter,Ammeter with CT's,Phase indication lamps complete - 03 No.\n
4 2.02 Item No. 2 (Contd/....)\n(ii) OUTGOING :\nMCCB Adjustable Thermal & Fixed Magnetic setting 250 Amps 4P, 50 Hz, 415 Volts with rupturing cap acity 35 KA ( ICU=ICS =100%) - 05 Nos\n(iii) MCCB Adjustable Thermal & Fixed Magnetic setting 160 Amps 4P, 50 Hz, 415 Volts with rupturing cap acity 25 KA ( ICU=ICS=100%) - 05 Nos \n(iv) MCCB Adjustable Thermal & Fixed Magnetic setting 100 Amps 4P, 50 Hz, 415 Volts with rupturing cap acity 25 KA ( ICU=ICS=100%) - 05 Nos \n(v) MCB FP 63 Amps C curve 10kA - 06 Nos\n(vi) MCB FP 32 Amps C curve 10kA - 03 Nos\n(vii) Copper Bus Bar of 1500 Amp rating supported on suitable size porcelain stand with suitable size brass nut, bolt and washers with heat shrinkable colour coded PVC sleaving for three phase and neutral -01 Set.\n(viii) Earth bus of size 32 X 6 mm in the panel - 16 RM\n(ix) Make of ACB, MCCB, MCB - Siemens/Scheneider/ABB/Legrand
5 3 Supply and lay including replacement of Synthetic insulating rubber mat of size 2m x 1m x 12 mm complete all as specified and directed. 2 Each
6 4 Supply and fix copper bus bar 1500A for extension of existing bus bar including suitable size porcelain stand with suitable size brass nut, bolt and washers with heat shrinkable colour coded PVC sleave complete all as specified and directed. 8 Running Metre
7 5 Material and labour for Earthing complete with using galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly underground vertically (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate at a depth not less than 1.5m below ground level connected with and incl galvanised iron strip 32 x 6 mm by means of GI bolts and nuts,check nuts,washers and GI earth strip protected by GI pipe light grade 40 mm bore upto 7.5 mtr and connecting to LT panel etc as per site requirement including necessary excavation, earth work in any type of soil PCC (1:3:6) type C1 chamber and 40 mm thick RCC Cover with 6 mm dia MS bars 10 cm C/C on both ways as reinforcement complete all as shown in electrical plate No. 3 of MES Schedule Part 1 including watering pipe 20 mm dia medium grade with funnel and with mesh , refiling soil all as specified. \nNote:(i) Quoted rate deemend to include necessary earth work PCC chamber, RCC cover, reinforcement removal of surplus soil , site clearance etc. (ii) GI earth strip , GI tubing light grade upto 7.5m deemed to be included in the rate quoted by the contractor. (iii) Beyond 7.5 mtr the GI earth strip 32X6 mm & GI pipe light grade 50 mm dia shall be measured under relevant item of the schedule. (iv) Quotated rate include testing after completion from test point and the desired earth resistance shall be not more than 2 ohm .If the desired result is not obtained the earthing will be re done by the contractor at no extra cost. 2 Each Job
8 6 Supply and fixing/laying GI strip 32x 6mm fixed to wall with porcelain/ ebonite insulator or burried in ground or chases or drawing in pipe complete all as specified and as directed. 18 Running Metre
9 7 Supply , fixing , testing and commissioning servo voltage stabiliser of capacity 160 KVA for automatic operation three phase, naturally oil cooled in and including transformer oil complete, outdoor type and designed for input variation between 340 V to 460 V with output voltage stabilised at 415 with accuracy + 2.5% and speed of correction 8 volts per second including cable termination box for incomming and outgoing cable and necessary platform with minimum 60cm above GL and plan size as recommended by manufacturer complete all as specified and as directed.\nNote: The quoted rate inclusive of connecting the existing outgoing cables of any type to servo voltage stabiliser by using new lugs,glands as per site requirement. 1 Each
10 8 Supply, laying XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 V grade with aluminium conductor of size 150 Sqmm 3.5 core including connecting up with proper size aluminium lugs, glands wherever necessary in LT panels/ bus bar chamber panel etc., all as per site requirement including laying in trenches / on wall / cable tray and testing complete all as specified and as directed \nNote:(i) Rates includes supply and fix necessary glands,lugs, etc.,\n(ii) Excavation/ Earth work shall be measured and paid separately under relevent items.240 Sqmm 3.5 core\nMake: Polycap/ KEI / Havells 30 Running Metre
11 9 Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth; for cable trench etc and getting out in Soft/loose soil complete all as specified and as directed. 2.7 Cum
12 10 Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in Soft/loose soil complete all as specified and as directed 2 Cum
13 12 Removing excavated material to a distance not exc 50 mtr and depositing where directed at level not exc 1.5 mtr above the starting point all as specified and as directed 0.7 Cum
14 13 Supply and lay standard size well burnt bricks,Sub class 'B', laid flat, dry in trenches for cable protection complete all as specified and as directed 0.09 Per 1000 Nos
15 14 Spreading riddled earth as obtained from item No 9 here-in-before for UG cable cushioning complete all as specified and directed 0.72 Cum
16 15 Material and labour point wiring with 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor drawn into including PVC concealed (fixed on wall/roof/ceiling etc), conduit of size not less than 20 mm dia and including provision of 1.5 Sqmm single core PVC insulated FRLS unsheathed multi stranded copper conductor as earth wire and cast iron / pressed steel treminal boxes for mounting switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet cover complete for the following :- Make for PVC conduit : SUDHAKAR / AVON PLAST /FINOLEX . Make for Copper cable: Finolex/Polycab/ Plaza.
17 15.01 One light point controlled by one switch. 4 Point
18 15.02 One 3 pin socket outlet 5 Amps, indipendent board with cables 1.5 Sqmm size. 5 Point
19 16 All as per item ser no-15 above here in before but one 3 pin socket outlet 5/15 Amps, indipendent board with cables 4.0 Sqmm size. Make :- Polycab/Finolex/Plaza 6 Point
20 17 M&L for sub main wiring 2X 4.0 Sqmm for phase and 1X4.0 Sqmm for neutral with PVC FRLS insulated unsheathed multi stranded along with earth wire FRLS PVC insulted copper conductor, single core cable drawn in and including surface/concealed /PVC conduit of appropriate size as specified and as directed. Note:- : 1. Cutting chases for concealed wiring shall be measured and paid seperately. 2. Rate inclusive of old submain wiring.\nMake for Copper cables: Finolex/Polycab / Plaza. Make of PVC Conduit: SUDHAKAR/FINOLEX/AVON PLAST. 18 Running Metre
21 18 S&F Switch piano, flush type single pole , one way 5 amp complete all as specified and as directed.\nMake: Anchor/Cona/Leader 4 Each
22 19 S&F Switch socket combination 2 in 1, 3 pin, 5 Amp flush type complete all as specified and as directed. Make: Anchor/Cona/Leader 5 Each
23 20 S&F Switch socket combination 2 in 1, 3 pin, 5 and 15 Amp flush type universal complete all as specified and as directed. Make: Anchor/Cona/Leader 6 Each
24 21 S&F Ceiling rose three terminals/ PVC/ polycarbonate, isolated body complete all as specified and as directed. Make: Anchor/Cona/Leader 2 Each
25 22 Supply and fix Wall mounted LED indoor spot light type not lesdd than 7 Watt including necessary fixing arrangements complete all as specified and as directed. Make :Crompton / Philips/Surya/wipro Luker 4 Each
26 23 Supply and fix high efficiency modern 18 Watt 1X1 Sqft LED light with panel for recessed dust free installation with high brightneass LEDs for glare free homogenousilluminatin including taking down old unserviceable fittings all as specified and as directed. Make :Crompton /f Philips/Surya/wipro Luker 4 Each
27 24 Supply and fix high efficiency modern 24 Watt 2X2 Sqft LED light with panel for recessed dust free installation with high brightneass LEDs for glare free homogenousilluminatin including taking down old unserviceable fittings all as specified and as directed. Make :Crompton /f Philips/Surya/wipro Luker 12 Each
28 25 Supply and fix Ceiling fan 230 V 1200mm sweep smart saver -50 ogf make Orient / Crompton / Bajaj / Havells complet all as specified and as directed. 1 Each
29 26 S& F for sheet metal enclosure single pole and neutral with a two pin and earth plug and socket complete with one SP MCB 20-32 Amps. Make: Legrand/ Siemens/Scheneider/ABB 1 Each
30 27 M&L for cutting chases on brick walls concrete surfaces not exc 10cm girth and making good in cement mortar (1:3) the existing surface after carryiing out the concealed wiring including necessary finishes all as directed 8 Running Metre
31 28 M L for IInd class HW Timber clean soft wood as in scantling complete all as specified and as directed.\n 0.7 Cum
32 29 S&F 18/ 19mm thick prelaminated particle board, interior grade, Prelaminated one side with decoratve choice lamination and other side balancing white fixed with screws to timber frame work complete all as specified and as directed. 110 Sqm
33 30 S&F External teak wood lipping 6mm thich fixed with nails to 18/ 19 mm thick Particle board complete all as specified and as directed. 55 Running Metre
34 31 S&F 5.5 mm thick sheet glass , ordinary quality and glazing in squares n. exc 0.50 Sqm in each pane complete all as specified and as directed. 5.5 Sqm
35 32 M & L Powder coated (mininmum thickness of powder coating 50 micron) andised aluminium frame for partitions, door , windows, ventilators with one or more rebates including joining cleat for fixing etc complete all as specified and as directed. 50 Kg
36 33 Supply and fix brass locks, drwer grade I of size 50mm, 2 levers complete all as specified and as directed. 20 Each
37 34 Supply and fix 100 mm Butt hinges heavy weight , cold rolled mild steel complete all as specified and as directed. Make :Crompton /f Philips/Surya/wipro Luker 3 Each
38 35 Supply and fix Continuous (piano) hinges, mild steel, bright finish or electrogalvanised, width of flabs 30mm complete all as specified and as directed. 20 Running Metre
39 36 S& F 75mm brass handles, cast type , polished bright complete all as specified and as directed. 20 Each
40 37 S & F aluminium body door closure hydraulically regulated, design No. 3, universal type, suitable for door shutters of 851 to 1000mm in width and weight between 61 to 80 Kg complete all as specified and as directed.\n 1 Each
41 38 Supply Table office (Plutus) in Acacia Finish (Trade Pattern)\nMake: Pepperfry or equivalent as approved by GE 2 Each
42 39 Supply Chairs office Wipro Furnitue Alivio Ergonomic (Fabric, Black ) (Trade Pattern)\nMake: Godrej or equivalent as approved by GE 6 Each
43 40 Supply Store well plain with 4 shelves , making 5 compartments size 1981mmX916mmX486mm (Trade Pattern)\nMake: Godrej or equivalent as approved by GE. Model :Storewell 1 Each
44 41 Supply Book Case steel (FD-1028) 1 Each
45 42 Supply Filling cabinet steel 1375mmx470mmx700mm (FD-397) 1 Each
46 43 Supply Table center with glass Top (Trade Pattern) 1 Each
47 44 Supply Printer Table cabinet for office (Trade Pattern) 1 Each