Providing Annual Maintenance Contract , Repair And Replacement Of Defective Parts Etc Of Fire Sensing System In The New Opd Block , Icu , Auditorium And New Administrative Block In Gmsh Sec-16 , Chandigarh . ( 2021-2022 ) ., Chandigarh-Chandigarh

Chandigarh Administration Engineering Department has published Providing Annual Maintenance Contract , Repair And Replacement Of Defective Parts Etc Of Fire Sensing System In The New Opd Block , Icu , Auditorium And New Administrative Block In Gmsh Sec-16 , Chandigarh . ( 2021-2022 ) .. Submission Date for this Tender is 30-06-2021. Fire Protection System Tenders in Chandigarh Chandigarh. Bidders can get complete Tender details and download the document.




Tender Notice

28280970
Providing Annual Maintenance Contract , Repair And Replacement Of Defective Parts Etc Of Fire Sensing System In The New Opd Block , Icu , Auditorium And New Administrative Block In Gmsh Sec-16 , Chandigarh . ( 2021-2022 ) .
Open Tender
Indian
Chandigarh
Chandigarh
30-06-2021

Tender Details

Providing annual maintenance contract , Repair And Replacement Of Defective Parts Etc Of Fire Sensing System In The New Opd Block , Icu , Auditorium And New Administrative Block In Gmsh Sec-16 , Chandigarh . ( 2021-2022 ) .

Key Value

Document Fees
Refer document
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work:Providing AMC, repair and replacement of defective parts etc of fire sensing system in the New OPD block, ICU, Auditorium and new administrative block in GMSH Sec-16, Chandigarh. (2021-2022)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Providing complete AMC for addressable fire alarm system installed at GMSH Sec-16, Chandigarh under the AMC the firm shall provide mtc service of the system of preventive mtc, the service must be carried out weekly and the complaint call must be attended by the firm in addition to the general mtc within two hours from the time of such calls. During mtc period the firm is fully responsible for cleaning/ dusting of complete system and to keep the system in working condition all the time including cost of replacement of defective components. The firm shall maintain log book at site for recording all the mtc work done at site will be provided by the supplier for the smooth operation of the system. if there is any delay in attending the calls and or repairing the defective equipment beyond time limit of one day will attract penalty @Rs.500/- per day. The bidder will undertake the supplies of necessary mtc equipment and spare parts will be made available for all the equipments. The system maintain by the agency as per below mention systems.
2 1.01 Bosch make four loop fire alarm panel with installed smoke sensors, MCP etc. (New OPD block = ICU )
3 1.02 Siemens make four loop fire alarm panel with installed smoke sensors, MCP etc (Administrative block)
4 1.03 Notifier make two loop fire alarm panel with installed smoke sensors, MCP etc. (Auditorium) NSR 1 Nos.job for 12 months
5 2 Supply, installations, testing and commissioning of intelligent multisensor detector with integrated fault isolator/ isolator base,
6 2.01 The intelligent multi criteria detector shall have integrated fault isolator/ fault isolator base as per NFPA style 7 to make ensure complete system working without losing any detector incase of cable fault. Be an addressable device that is designed to monitor a minimum of photoelectric and thermal technologies in a single sensing device. The design shall include the ability to adapt to its environment by utilizing a built in microprocessor to determine its environment and choose the appropriate sensing settings. The detector design shall allow a wide sensitivity window, as per UL/ VDS. This detector shall utilize advanced electronics that react to slow smoldering fires and thermal properties all within a single sensing device.
7 2.02 The microprocessor design shall be capable of selecting the appropriate sensitivity levels based on the environment type it is in and then have the ability to automatically change the setting as the environment changes (as walls as are moved or as the occupancy changes)
8 2.03 The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena.
9 2.04 There shall be feature to use detectors as smoke only or heat only or combined by able or disable photo or thermal part depending upon site requirement.
10 2.05 Make: Notifier (NFS3030)/ Siemens (fire finder)/ Bosch.
11 2.06 Certification: UL/VDS/LPCB-UK.
12 2.07 Standards: NFPA/EN.
13 2.08 S/I/T/C multisensory detector NSR1 20 nos.
14 3 Manual call point
15 3.01 Supply, installation, testing and commissioning of addressable manual call point break glass unit with integrated fault isolator or separate isolator modules as per NFPA style 7 with necessary fixing arrangement with key complete as required.
16 3.02 Makes: Notifier/ Siemens (Fire finder)/ Bosch.
17 3.03 Certification: UL/ VDS/ LPCB-UK.
18 3.04 Standards: NFPA/ EN54. NSR2 2 nos.
19 4 Multi tone hooter
20 4.01 Supply, installation & testing of addressable loop powered multi tone sounder of 80-90 db, with integrated short circuit isolator (incase of non loop powered conventional hooter, vendor needs to consider cost of power cable in this items. Client shall not pay extra for power cable. Power for hooter shall be provided from main panel only to have battery back up as well. Local power supply for hooter shall not be acceptable).
21 4.02 Makes: Notifier/ Siemens (fire finder)/ Bosch.
22 4.03 Certification: UL/ VDS/ LPCB-UK.
23 4.04 Standards: NFPA/ EN54. NSR3 1 nos.
24 5 DSR 1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
25 5.01 3 x 1.5 sq. mm NSR4 200 mtr.