Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Damaged Transformer At Siddharth Nagar Workshop Siddharth Nagar Under Ewd Basti, Siddharth Nagar-Uttar Pradesh

Purvanchal Vidyut Vitaran Nigam Limited has published Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Damaged Transformer At Siddharth Nagar Workshop Siddharth Nagar Under Ewd Basti. Submission Date for this Tender is 01-07-2021. Transformer Supply Tenders in Siddharth Nagar Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

28280683
Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Damaged Transformer At Siddharth Nagar Workshop Siddharth Nagar Under Ewd Basti
Open Tender
Indian
Uttar Pradesh
Siddharth Nagar
01-07-2021

Tender Details

Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Repairing Of 10 , 16 And 25 Kva Amorphous Core Cylindrical Body Type Damaged Transformer At Siddharth Nagar Workshop Siddharth Nagar Under Ewd Basti

Key Value

Document Fees
INR 3540 /-
EMD
INR 45000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Repairing of 11/0.4kv 10,16 and 25 KVA Amorphous core cylindrical Body Damaged Transformer at Siddharth Nagar Workshop Siddharth Nagar Under EWD Basti
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Handling and dragging of transformer from stacking yard to repairing hall.
2 1.01 10KVA item1 1200 Nos
3 1.02 16KVA item2 400 Nos
4 1.03 25KVA item3 100 Nos
5 2 Cutting of Sealed transformers top cover plate smoothly and uniformally by gas/chisel cutter or opening of top cover plat and detanking of core and coil assembly.
6 2.01 10KVA item4 1200 Nos
7 2.02 16KVA item5 400 Nos
8 2.03 25KVA item6 100 Nos
9 3 Dragging of the tank from the repaired hall to yard. & cleaning oil and dust etc. and scraping the rust etc and Washing of Transformer tank with Caustic Soda & water, Caustic soda shall be provided by contractor
10 3.01 10KVA item7 1200 Nos
11 3.02 16KVA item8 400 Nos
12 3.03 25KVA item9 100 Nos
13 4 Painting of inner side of transformer tank and channels with heat proof zinc chromate paint of good quality (Berger, Nerolac, Jenson & Nicholson etc) shall be
14 4.01 10KVA item10 1200 Nos
15 4.02 16KVA item11 400 Nos
16 4.03 25KVA item12 100 Nos
17 5 Dragging out empty tank from yard to repairing hall.
18 5.01 10KVA item13 1200 Nos
19 5.02 16KVA item14 400 Nos
20 5.03 25KVA item15 100 Nos
21 6 Dismantling core and coil assembly and cleaning of dust and dirt from the core assembly and checking of LV and HV leg coils for assessing its reuse, rechecking and recording of physical dimensions of coil and cleaning of core and their components etc.
22 6.01 10KVA item16 1200 Nos
23 6.02 16KVA item17 400 Nos
24 6.03 25KVA item18 100 Nos
25 7 ‘‘Making of complete HV/ LV leg Alu. Leg coils identical to original one with same number of turns, weight etc providing super enameled / DPC conductor/ Strip confirming to IS 1971 /53 in place of old and damage coil. Alu. coil, wire strip will be provided by the department. All coil assembly of identical voltage shall be interchangeable without requiring any special equipment. Coil shall be supported between adjacent sections by insulations, spacers, beamers and other insulations.Rewinding shall be arranged to ensure free circulation of oil to reduced hot spots in winding. The insulation of coil shall be treated with suitable insulating, varnish or equivalent compound to develop the full electrical strength of winding as per original design.
26 7.01 10KVA item19 13200 Kg
27 7.02 16KVA item20 5600 Kg
28 7.03 25KVA item21 2300 Kg
29 8 Assembly of core and coils and fitting of other parts requiring replacement such as press board, making supports between adjacent sections by insulating spares and rapping etc & tapping etc. (Breezing/soldering) required, shall be arrange by the contractor.
30 8.01 10KVA item22 1200 Nos
31 8.02 16KVA item23 400 Nos
32 8.03 25KVA item24 100 Nos
33 9 Shifting and keeping the assembled core coil etc. in Oven from the repairing and assembly place.
34 9.01 10KVA item25 1200 Nos
35 9.02 16KVA item26 400 Nos
36 9.03 25KVA item27 100 Nos
37 10 Taking out assembled core and coils assembly from the OVEN and shifting to repairing hall.
38 10.01 10KVA item28 1200 Nos
39 10.02 16KVA item29 400 Nos
40 10.03 25KVA item30 100 Nos
41 11 Retanking of complete assembly into painted tank and lightening of the assembly in the tank safely. Fitting of all accessories of the transformer.
42 11.01 10KVA item31 1200 Nos
43 11.02 16KVA item32 400 Nos
44 11.03 25KVA item33 100 Nos
45 12 Welding of repaired transformers including of top cover plate by electric core welding filling of gaps or fixing of top cover plate by properly nuts & bolts to prevent seepage of water..
46 12.01 10KVA item34 1200 Nos
47 12.02 16KVA item35 400 Nos
48 12.03 25KVA item36 100 Nos
49 13 Painting of t/f outside with super enamel synethics paint of yellow color in two coats after providing primer of red oxide paint etc. paint & painting materials shall be provided by contractor.
50 13.01 10KVA item37 1200 Nos
51 13.02 16KVA item38 400 Nos
52 13.03 25KVA item39 100 Nos
53 14 Dragging of repaired T/f upto the test cabin/testing place for testing and their re-dragging to yard and its stacking at indentified place after testing
54 14.01 10KVA item40 1200 Nos
55 14.02 16KVA item41 400 Nos
56 14.03 25KVA item42 100 Nos
57 15 Testing the correctness of connection, DVDF, No load, load loss test (where available), High Voltage, impedance voltage, Short Circuit and open circuit test, Voltage ratio on various tap position.
58 15.01 10KVA item43 1200 Nos
59 15.02 16KVA item44 400 Nos
60 15.03 25KVA item45 100 Nos
61 16 Punching and welding of M.S. Plate on outside of transformer of size 100 mm x 50mm x 3 mm containing/ punching.\n(a) of unique number as decided by the\n department with a punch head.\n(b) Date of repair.\n
62 16.01 10KVA item46 1200 Nos
63 16.02 16KVA item47 400 Nos
64 16.03 25KVA item48 100 Nos
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy