Indian Oil Corporation Limited-IOCL has published Rate Contract For Carrying Out M And L Repair Works For Crvts-Frvts-Fire Water Tanks- Pipelines , Paintings Etc . , At Depots- Terminals-Afss- Rcds In Kerala State . . Submission Date for this Tender is 13-07-2021. Pipe Laying Tenders in KERALA STATE OFFICE Kerala. Bidders can get complete Tender details and download the document.
Name of Work : RATE CONTRACT FOR CARRYING OUT M&I REPAIR WORKS FOR CRVTS/FRVTS /FIRE WATER TANKS/PIPELINES ETC., AT DEPOTs/TERMINALs/ AFSs/ RCDs IN KERALA STATE | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | DISMANTLING WORKS | BI01010001010000000000000515BI0100001113 | ||
2 | 2 | Dismantling of pipelines (product/ FH) including mechanical/ gas cutting of the pipe lines and removal include dismantling of all above ground & underground pipelines/draining of water etc., complete. | BI01010001010000000000000515BI0100001114 | ||
3 | 3 | Note: a) Necessary earthwork excavation, if required, shall be part of dismantling works. b) The dismantled pipes, valves & flanges shall be handed over to the safe custody of the Corporation. | BI01010001010000000000000515BI0100001115 | ||
4 | 4 | 25 mm dia to 65mm dia | BI01010001010000000000000515BI0100001116 | 1 | M |
5 | 5 | 80 mm dia to 150mm dia | BI01010001010000000000000515BI0100001117 | 1 | M |
6 | 6 | 200 mm dia to 300mm dia | BI01010001010000000000000515BI0100001118 | 1 | M |
7 | 7 | 350 mm dia to 450mm dia | BI01010001010000000000000515BI0100001119 | 1 | M |
8 | 8 | Dismantling and removing the existing CS GATE/ ROSOV/ DBBV/ MOV/ GOV/ NRV/ BALL/ BUTTERFLY/ AUDCO valves of the followings sizes without any damage including removing cable termination wherever required, removing the bolts/nuts/washers, providing proper supports to adjacent pipeline, stacking the same, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001120 | ||
9 | 9 | 50 mm dia | BI01010001010000000000000515BI0100001121 | 1 | EA |
10 | 10 | 80 mm dia | BI01010001010000000000000515BI0100001122 | 1 | EA |
11 | 11 | 100 mm dia | BI01010001010000000000000515BI0100001123 | 1 | EA |
12 | 12 | 150 mm dia | BI01010001010000000000000515BI0100001124 | 1 | EA |
13 | 13 | 200 mm dia | BI01010001010000000000000515BI0100001125 | 1 | EA |
14 | 14 | 250 mm dia | BI01010001010000000000000515BI0100001126 | 1 | EA |
15 | 15 | 300 mm dia | BI01010001010000000000000515BI0100001127 | 1 | EA |
16 | 16 | 350 mm dia | BI01010001010000000000000515BI0100001128 | 1 | EA |
17 | 17 | 400 mm dia | BI01010001010000000000000515BI0100001129 | 1 | EA |
18 | 18 | 450 mm dia | BI01010001010000000000000515BI0100001130 | 1 | EA |
19 | 19 | Dismantling and removing the shell nozzles without any damage to shell plate including cutting, gouging, grinding, stacking the same, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001131 | ||
20 | 20 | 50 mm to 100 mm dia | BI01010001010000000000000515BI0100001132 | 1 | EA |
21 | 21 | 150 mm to 300 mm dia | BI01010001010000000000000515BI0100001133 | 1 | EA |
22 | 22 | 350 mm to 450 mm dia | BI01010001010000000000000515BI0100001134 | 1 | EA |
23 | 23 | Supplying & welding necessary Dummy reinforcement plate for closing the shell nozzle hole as per standards including cutting, gouging, grinding, welding the plate, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001135 | ||
24 | 24 | 50 mm to 100 mm dia (with 8mm thk to 14mm thk new MS plates) | BI01010001010000000000000515BI0100001136 | 1 | EA |
25 | 25 | 150 mm to 300 mm dia (with 8mm thk to 14mm thk new MS plates) | BI01010001010000000000000515BI0100001137 | 1 | EA |
26 | 26 | 350 mm to 450 mm dia (with 8mm thk to 14mm thk new MS plates) | BI01010001010000000000000515BI0100001138 | 1 | EA |
27 | 27 | Dismantling the MS rolling ladder including disconnecting the same from platform, cutting, gouging, grinding & removing the same with suitable capacity crane without any damage to shell plate/deck and stacking the same safely, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001139 | ||
28 | 28 | 8 M dia x 7 M high - FRVTs | BI01010001010000000000000515BI0100001140 | 1 | LS |
29 | 29 | 10 M dia x 9 M high - FRVTs | BI01010001010000000000000515BI0100001141 | 1 | LS |
30 | 30 | 12 M dia x 9 M high - FRVTs | BI01010001010000000000000515BI0100001142 | 1 | LS |
31 | 31 | 16 M dia x 14 M high - FRVTs | BI01010001010000000000000515BI0100001143 | 1 | LS |
32 | 32 | 32 M dia x 15 M high - FRVTs | BI01010001010000000000000515BI0100001144 | 1 | LS |
33 | 33 | 32 M dia x 9.80 M high - FRVTs | BI01010001010000000000000515BI0100001145 | 1 | LS |
34 | 34 | 32 M dia x 15 M high - FRVTs | BI01010001010000000000000515BI0100001146 | 1 | LS |
35 | 35 | 40 M dia x 9.60 M high - FRVTs | BI01010001010000000000000515BI0100001147 | 1 | LS |
36 | 36 | Gas cutting of the shell to annular plate, bottom plate or shell butt welding joint along the seam neatly with minimum wastage and without damaging the existing shell plate. \nThe job also includes:\na) Any other weld joints- butt or fillet of max 25mm thick plate.\nb) Temporarily dismantling the 3" or 4" drain pipes inside the tank and re-installing the same after rectification of the tank.\nc) Stacking the cut plates properly as per site instructions.\nd) Cutting of shell to provide window for taking out dismantled plates or taking in new plates.\n\n | BI01010001010000000000000515BI0100001148 | 1 | M |
37 | 37 | The dismantling of damaged roof supporting structural:\nRate is inclusive of dismantling of roof truss/girders/columns including gusset plates, cleats, supports, roof structural supports, angles, railing angles, flats, curb angles, etc. The theorotical sectional weight of structurals as per IOC's standard drawing will only be considered for calculating the tonnage of dismantlled item. Weight of appurtenances will not be considered for payment purpose.\nDismantled steel structurals will be the property of the contractor and rebate towards this should be considered while quoting. Scaffolding, if required will be paid separately.\n | BI01010001010000000000000515BI0100001149 | 1 | MT |
38 | 38 | Dismantling of structurals:\nGouging / grinding and dismantling of hand rails, wind girders, corroded staircase including pad of support channels of landing platforms from all sides, support angle of staircase step from all sides to the shell plates at the affected places. Dismantled material will be property of party and is to be taken by them. Rebate towards cost of scrap to be considered while quoting for this item. Scaffolding, if required will be paid separately. | BI01010001010000000000000515BI0100001150 | 1 | MT |
39 | 39 | Dismantling the existing combined gauge well pipe (500 mm dia) including cutting, gouging, grinding & removing the same with suitable capacity crane without any damage to shell plate/deck, stacking the same safely, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001151 | ||
40 | 40 | Upto 10 M high tanks - FRVTs | BI01010001010000000000000515BI0100001152 | 1 | LS |
41 | 41 | 10 M to 15 M high tanks - FRVTs | BI01010001010000000000000515BI0100001153 | 1 | LS |
42 | 42 | Degassing & De-sludging into secondary containment like concrete or earth pit, barrels or tank truck etc and cleaning of the bottom of floating roof along with support legs, bottom, roof and shell plates upto resting position of roof in case of FR Tanks and bottom and shell plates upto 1.5 m high of CR Tanks by hydro jetting method with all tool sand tackles and explosion proof degassing unit / sludge pumps etc.\nNote : For above item, the approved sub vendor shall directly report to the Location Incharge and the entire cleaning and degasification process shall be done under supervision of Operating personnel of Terminal. Hot work shall commence only after tank is certified as degassed by the Location Incharge. Water @ 18 lpm and electricity 3 phase for this item shall be provided by IOCL. | BI01010001010000000000000515BI0100001154 | ||
43 | 43 | Vertical tanks(FR/CR) - 8 M dia to 12 M dia | BI01010001010000000000000515BI0100001155 | 1 | LS |
44 | 44 | Vertical tanks(FR/CR) - 14 M dia to 20 M dia | BI01010001010000000000000515BI0100001156 | 1 | LS |
45 | 45 | Vertical tanks(FR/CR) - 20 M dia to 30 M dia | BI01010001010000000000000515BI0100001157 | 1 | LS |
46 | 46 | Vertical tanks(FR/CR) - 40 M dia to 50 M dia | BI01010001010000000000000515BI0100001158 | 1 | LS |
47 | 47 | Dismantling the plates of CRVT/FRVT either partly or in full as directed, by gas cutting from the existing weld seams & removing the MS plates from the tank by mechanical means, with utmost precaution and neatly straightening and storing at place indicated by site engineer anywhere in IOC premises, complete, irrespective of lead and lift as directed. The rate includes the cost of labour, gases, providing necessary temporary supports, safe walk ladder, safety precautions etc., all necessary equipments, all necessary structures, clamps, suitable non-combustible material wedges, etc. complete to the satisfaction of site-in-charge. Plan area and average thickness of roof plates will be considered for calculating the qty of dismantled plates, and weight of appurtenances will not be considered separately, and no extra payment for the same will be made. | BI01010001010000000000000515BI0100001159 | ||
48 | 48 | Note: Contractor has to submit the dismantling methodology clearly stating the restraining techniques to be involved so that circularity of the undamaged (to be retained) shell/ bottom/ roof plates remains undisturbed, prior to commencement of work and has to get it approved from IOCL. Plates and structures, appurtenances should be dismantled with utmost care as these are to be reutilized. | BI01010001010000000000000515BI0100001160 | ||
49 | 49 | a) CRVT/FRVT | BI01010001010000000000000515BI0100001161 | 1 | TON |
50 | 50 | Dismantling and reconnecting, if any after completion of welding, of existing catwalks connected to roof, pipelines connected to tank body etc. including isolation during welding & cutting etc. and re-connection after completion of work. | BI01010001010000000000000515BI0100001162 | 1 | EA |
51 | 51 | Dismantling of Fire/ Jockey pump including removing from the foundation, disconnecting the suction/ delivery of the pump, shifting & stacking the same without any damage, H/O to IOC etc., complete as per instructions at site. | BI01010001010000000000000515BI0100001163 | ||
52 | 52 | Fire pump with Engine set - 288/410/616 KL/HR | BI01010001010000000000000515BI0100001164 | 1 | EA |
53 | 53 | Jockey pump with its connected pipelines - all capacities | BI01010001010000000000000515BI0100001165 | 1 | EA |
54 | 54 | Air-compressors/ Fire pump fuel tank - all capacities | BI01010001010000000000000515BI0100001166 | 1 | EA |
55 | 55 | M&I REPAIR WORKS | BI01010001010000000000000515BI0100001167 | ||
56 | 56 | Replacement of necks of Manholes/ Nozzles of tanks with new necks including careful removal of welding between nozzles and shell plates/ reinforcement plate by light pencil grinding without damaging them, dismantling the manhole/nozzle, supplying & providing the following necks made out of MS plates, bending into shape, welding with radio-graphic quality to shell plates/ reinforcement plate, radiography of welded joints including rectification & re-testing of welds, DP test of weld between each nozzle and reinforcement plate/shell plate after root run and after complete welding, pneumatic test of re-inforcement plate / shell plate after welding completion at 15 PSI, touch-up painting of welded areas as per specification etc., as per IS 803 and B&R drawings and instructions at site. | BI01010001010000000000000515BI0100001168 | ||
57 | 57 | Scope of the works includes a) supplying & welding of necessary bolting flange, supplying & providing cover plate, making joints including handling, straightening, fabricating, erecting, assembling, welding, drilling holes, bolts/ nuts/ washers etc., CAF-9 (or) equivalent 3mm gasket. | BI01010001010000000000000515BI0100001169 | ||
58 | 58 | b) Surface preparation / cleaning / painting works are as per IOC painting scheme specification given in the tender. | BI01010001010000000000000515BI0100001170 | ||
59 | 59 | Neck for Shell Manhole: with MS plate conforming to IS-2062 for neck & cover plate. B&R drg. no. BR/FR/221 & BR/FR/222. | BI01010001010000000000000515BI0100001171 | ||
60 | 60 | Upto 750 mm dia , 12 mm thick | BI01010001010000000000000515BI0100001172 | 1 | EA |
61 | 61 | 750 mm dia , 14 mm thick | BI01010001010000000000000515BI0100001173 | 1 | EA |
62 | 62 | 750 mm dia , 16 mm thick | BI01010001010000000000000515BI0100001174 | 1 | EA |
63 | 63 | 750 mm dia , 18 mm thick | BI01010001010000000000000515BI0100001175 | 1 | EA |
64 | 64 | 750 mm dia , 20 mm thick | BI01010001010000000000000515BI0100001176 | 1 | EA |
65 | 65 | Neck for Shell Nozzle: with MS plate conforming to SA-106 Gr.B upto 250mm dia and IS-226/2062 for for more than 250mm dia for neck plate. SORF & Blind flanges as per Specification given in the tender. B&R drg. no. BR/CR/223, 224,225,226. | BI01010001010000000000000515BI0100001177 | ||
66 | 66 | 50 mm dia 6 mm thick | BI01010001010000000000000515BI0100001178 | 1 | EA |
67 | 67 | 80 mm dia 8 mm thick | BI01010001010000000000000515BI0100001179 | 1 | EA |
68 | 68 | 100 mm dia 10 mm thick | BI01010001010000000000000515BI0100001180 | 1 | EA |
69 | 69 | 150 mm dia 12 mm thick | BI01010001010000000000000515BI0100001181 | 1 | EA |
70 | 70 | 200 mm dia 12 mm thick | BI01010001010000000000000515BI0100001182 | 1 | EA |
71 | 71 | 250 mm dia 12 mm thick | BI01010001010000000000000515BI0100001183 | 1 | EA |
72 | 72 | 300 mm dia 12 mm thick | BI01010001010000000000000515BI0100001184 | 1 | EA |
73 | 73 | 350 mm dia 12 mm thick | BI01010001010000000000000515BI0100001185 | 1 | EA |
74 | 74 | 400 mm dia 12 mm thick | BI01010001010000000000000515BI0100001186 | 1 | EA |
75 | 75 | 450 mm dia 12 mm thick | BI01010001010000000000000515BI0100001187 | 1 | EA |
76 | 76 | Roof Manhole: with MS plate conforming to IS-2062 for neck & cover plate. B&R drg. no. BR/FR/277. | BI01010001010000000000000515BI0100001188 | ||
77 | 77 | 500mm dia | BI01010001010000000000000515BI0100001189 | 1 | EA |
78 | 78 | 80mm/ 100mm dia roof nozzle with pipes as per B&R drg. | BI01010001010000000000000515BI0100001190 | 1 | EA |
79 | 79 | 50mm dia roof nozzle with pipes as per B&R drg. | BI01010001010000000000000515BI0100001191 | 1 | EA |
80 | 80 | Provision of 1 no rim vent of 4" dia as per B&R drawing and providing 6"x4" reducer for one (existing) vent | BI01010001010000000000000515BI0100001192 | 1 | EA |
81 | 81 | Replacement of Centre/ Emergency Drain including dismantling the Old Centre drain and Pipe by Gouging, Cutting without Damage to the Double Deck plate, supply of Seamless 100 mm dia MS pipes (SCH-80), Structural, Plate, reinforcement plate, fabrication, welding, fixing & testing of new 100 mm dia pipe & new re-inforcement plate, necessary stiffeners, DP test etc., as per drawings and as per specifications & instructions at site. | BI01010001010000000000000515BI0100001193 | ||
82 | 82 | Central Drain - as per B&R drg no. BR/FR/295 | BI01010001010000000000000515BI0100001194 | 1 | LS |
83 | 83 | Emergency Drain - as per B&R drg no. BR/FR/267 | BI01010001010000000000000515BI0100001195 | 1 | LS |
84 | 84 | Replacement of damaged web/ flange plate of wind girder including cutting the damaged web plate, butt welding the supplied MS plates neatly without any damage to shell plate/flange plate of wind girder, tools/tackles, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001196 | 1 | KG |
85 | 85 | Supply, Fabrication, Erection of seamless MS pipe for leg supports & air bleeder vents pipes for Existing Double Deck including supplying & providing handle, plate, holes, slot, 38mm dia hot rolled PIN, all lead & lifts, transportation etc., complete as per revised B&R drg no. BR/FR/250, BR/FR/252, BR/FR/265 & connected drgs. and as per instruction at site. Drawing shall be submitted to IOCL for approval. | BI01010001010000000000000515BI0100001197 | ||
86 | 86 | 63.5 mm dia (2.5" NB SCH-80) - Leg supports for FRVT | BI01010001010000000000000515BI0100001198 | 1 | M |
87 | 87 | 38.1 mm dia (1.5" NB SCH-40) - Auto bleeder vent supports for FRVT | BI01010001010000000000000515BI0100001199 | 1 | M |
88 | 88 | Supplying and Providing Sleeves for the Leg Supports in the Double Deck as per the attached drawing including supply of Seamless MS pipes, reinforcement plate, fabrication, welding, fixing, all lead & lifts, transportation etc., complete as per revised B&R drg no. BR/FR/250, BR/FR/252, BR/FR/264, BR/FR/265 and as per instruction at site. Rate is inclusive of dismantling the Old Sleeve Pipe by cutting & gouging without damage to the Double Deck plate. | BI01010001010000000000000515BI0100001200 | ||
89 | 89 | 88.9 mm dia (3.5" NB SCH-80) - Sleeve for Leg support - FRVT | BI01010001010000000000000515BI0100001201 | 1 | EA |
90 | 90 | 203 mm dia (8" NB SCH-40) - Sleeve for Auto bleeder vent - FRVT | BI01010001010000000000000515BI0100001202 | 1 | EA |
91 | 91 | 63.5 mm dia (2.5" NB SCH-40) - Intermediate sleeve/baffle plates/cover for Auto bleeder vent | BI01010001010000000000000515BI0100001203 | 1 | SET |
92 | 92 | Supplying and Providing Neoprene Gaskets for the deck pontoon hatch cover of approved make & as per B&R drg. No. BR/FR/268 & connected drgs., all lead & lifts, transportation etc., complete and as per instruction at site. | BI01010001010000000000000515BI0100001204 | ||
93 | 93 | For 508 mm dia (20") inspection hatch of pontoon - FRVT | BI01010001010000000000000515BI0100001205 | 1 | EA |
94 | 94 | Trimming the concrete surface of shoulder of sand pad foundation including the chipping off the concrete (approx.6mm to 20mm thick) to bring down the surface to below the bottom plate level, surface finishing the undulations with CM 1:3 neatly, curing, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001206 | ||
95 | 95 | For sand pad foundation | BI01010001010000000000000515BI0100001207 | 1 | M2 |
96 | 96 | Providing sand-bitumen mix for voids between bottom plate & bitumen carpet of sand pad pad foundation including hot-mixing with required ratio, packing the same neatly into the gap for upto 50mm thick & 150mm width, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001208 | ||
97 | 97 | For sand pad foundation | BI01010001010000000000000515BI0100001209 | 1 | M |
98 | 98 | Dismantling of existing air vents of 6 inch dia by gas cutting and stacking at designated place within terminal, supply, fabrication, handling and fixing air vents of 10 inch LRB type as per IOCL drg. Ref. S-869 and fixing as per drg. Ref. BR/CR/278 including providing new nozzle on roof of 250 mm dia, SO flanges as required etc. Dismantled air vent material will be property of party and is to be taken by them. Rebate towards cost of scrap to be considered while quoting for this item. | BI01010001010000000000000515BI0100001210 | 1 | EA |
99 | 99 | Drilling tell tale hole on reinforcement pads of manholes of specified dia without damaging the shell and plugging the same by providing threaded screw. | BI01010001010000000000000515BI0100001211 | 1 | EA |
100 | 100 | Supplying and welding 2 nos handles of 12 mm round bars bend in U shape on each pontoon inspection hatch cover. | BI01010001010000000000000515BI0100001212 | 1 | EA |
101 | 101 | Supplying, fixing of existing brass sleeve (ring in two halves) of 50mm depth x 5mm thick in the top and bottom inner circumference of gauge pipe sleeve by brazing and / or fixing to the nut/bolts of gauge well sleeve by means of strips. | BI01010001010000000000000515BI0100001213 | 1 | LS |
102 | 102 | Supplying providing 6 mm thick, 2 ply neoprene gasket as per drawing in between flanges of existing 400 mm dia gauge well housing, providing nut/bolts etc as required. | BI01010001010000000000000515BI0100001214 | 1 | EA |
103 | 103 | Welding:\nCleaning, gouging/grinding as required and carrying out welding of joints of required size wherever required/left out on the tank after surface preparation by grinding if required. Item includes testing of weld joints by DP test, chalk kerosene etc, if required. Scaffolding , if required, will be paid separately. | BI01010001010000000000000515BI0100001215 | ||
104 | 104 | Fillet Weld | BI01010001010000000000000515BI0100001216 | ||
105 | 105 | a) 5-8 mm size | BI01010001010000000000000515BI0100001217 | 1 | M |
106 | 106 | b) Above 8 to 12 mm size | BI01010001010000000000000515BI0100001218 | 1 | M |
107 | 107 | Butt weld from one side for annular plate or both side for shell plates including back gouging as required, based on thickness of shell plate/annular plate to be welded etc. Incase welding of plates of different thickness, thickness of thinner plate will be considered. This item may also be operated for closing of window cut on shell for taking out dismantled plates or taking in new plates. | BI01010001010000000000000515BI0100001219 | ||
108 | 108 | a) 5-10 mm size | BI01010001010000000000000515BI0100001220 | 1 | M |
109 | 109 | b) Above 10 -20 mm size | BI01010001010000000000000515BI0100001221 | 1 | M |
110 | 110 | c) Above 20-30 mm size | BI01010001010000000000000515BI0100001222 | 1 | M |
111 | 111 | "Supply, fabrication, installation & welding of sump on the bottom plate at lowest point. The sump shall be provided as per Drawing No. ENG/131 1/2. However the inner dia of the sump shall be 400 mm to enable insertion through shell manhole. Item includes supply of MS plates of required thickness conforming to IS 2062. The vertical weld of the sump neck is to be fully radiographed. Also the under side of the sump shall be applied with 3 coats of Shalimastic HD @ 200 Microns per coat aggregating 600 Microns after manual cleaning to SSPC SP2. | BI01010001010000000000000515BI0100001223 | 1 | LS |
112 | 112 | Supplying, fabricating, providing cover with mesh for central drain/emergency drain of FRVT as per B&R drawing | BI01010001010000000000000515BI0100001224 | 1 | EA |
113 | 113 | Providing 250mm dia free vent on roof including cutting, removing the roof plate, supplying 250mm dia MS pipes for free vent & its reinforcement plate, SS mesh as per drawing, bending/ shaping, welding, testing, clamps/nuts/bolts, as per B&R drgs. no. BR/CR/278-R1 and its connected drgs., painting as per IOC painting scheme, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001225 | ||
114 | 114 | 250mm dia free vent | BI01010001010000000000000515BI0100001226 | 1 | EA |
115 | 115 | Replacement of existing damaged mesh of free vents with new 2.5 stainless steel mesh including dismantling & removing the old mesh without any damage to the vent pipe, fixing the new mesh with necessary clamps, bolts, nuts as required etc., complete as per specification and instructions at site. | BI01010001010000000000000515BI0100001227 | ||
116 | 116 | 150mm to 250nn dia free vents | BI01010001010000000000000515BI0100001228 | 1 | EA |
117 | 117 | Repainting the internal surface of roof nozzles/ manholes including removing the manhole covers and re-fixing the same without any damage to the existing structures, manual scrapping, supplying and painting etc., complete as per specification and instruction at site. | BI01010001010000000000000515BI0100001229 | ||
118 | 118 | Specification for surface preparation / cleaning / painting works; | BI01010001010000000000000515BI0100001230 | ||
119 | 119 | Clean to SSPC SP 2 hand cleaning wire brushing. | BI01010001010000000000000515BI0100001231 | ||
120 | 120 | One coat of Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron + | BI01010001010000000000000515BI0100001232 | ||
121 | 121 | Amine Adduct Cured HB epoxy liner (F3) with 2 coats of DFT in the range of 100-125 micron. | BI01010001010000000000000515BI0100001233 | ||
122 | 122 | Total DFT min 270 microns | BI01010001010000000000000515BI0100001234 | ||
123 | 123 | All roof nozzles/ manholes - Vertical Tank | BI01010001010000000000000515BI0100001235 | 1 | LS |
124 | 124 | Welding the pitted spot/surface in the bottom plate including cleaning, scrapping, welding built-up, gouging/grinding, supplying & welding patch plate without any damage to bottom plate, DP/vacuum box testing, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001236 | ||
125 | 125 | 150mm x 150mm to 300mm x 300mm size of 8mm MS plate | BI01010001010000000000000515BI0100001237 | 1 | EA |
126 | 126 | Supplying and providing patch plate on the existing bottom plate including vacuum box test, bending to required shape to fit-on to the existing sweating patch plate of bottom plate, chamfering the edges to seat properly on to the bottom plate, welding, conducting dye penetration test etc., complete as per specifications and instructions at site. | BI01010001010000000000000515BI0100001238 | ||
127 | 127 | 150mm x 150mm to 300mm x 300mm - 8mm thick | BI01010001010000000000000515BI0100001239 | 1 | EA |
128 | 128 | 400mm x 400mm to 600mm x 600mm - 8mm thick | BI01010001010000000000000515BI0100001240 | 1 | EA |
129 | 129 | Replacement of existing pad plate of angle cleat on pressure relief line on the shell plate on which sweating observed including gouging the pad plate, weld built & bring flush the gouged places, supplying & welding MS plate as required, as per specification and instructions at site. | BI01010001010000000000000515BI0100001241 | ||
130 | 130 | 230mm x230mm x 5mm thick | BI01010001010000000000000515BI0100001242 | 1 | LS |
131 | 131 | Supplying, fabricating, laying and welding (3 runs min.) above ground pipelines including supplying IS 1239 Heavy grade MS ERW pipes, cutting, beveling and fixing the supplied specials such as elbows, bends, tees, reducers etc complete and hydro testing the pipelines at 10.5 KSC for a minimum period of 4 Hrs., supplying & providing MS structural supports as per B&R drgs, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001243 | ||
132 | 132 | Note: Welding of pipeline should conform to Radiography quality. Any repairs to the defective welding shall be made good at no extra cost. Re radiography of repaired joint shall also be at contractor's cost. IOC painting scheme shall be followed. | BI01010001010000000000000515BI0100001244 | ||
133 | 133 | 80 mm dia overflow pipeline | BI01010001010000000000000515BI0100001245 | 1 | M |
134 | 134 | Supplying & Welding the SORF flanges on the pipelines with 1 run inside and two runs outside, all leads & lifts etc., compete as per specifications and instructions at site. | BI01010001010000000000000515BI0100001246 | ||
135 | 135 | 80 mm (3") dia | BI01010001010000000000000515BI0100001247 | 1 | EA |
136 | 136 | Making flanged joints for both slip on and blind flanges including supplying and fixing 3 mm thk non-metallic gaskets, studs/ nuts etc of approved make for the following sizes as per IOC specifications and site instructions. | BI01010001010000000000000515BI0100001248 | ||
137 | 137 | 80 mm (3") dia | BI01010001010000000000000515BI0100001249 | 1 | EA |
138 | 138 | Supplying the following pipe fittings confirming to ASTM A 234 Gr WPB, Schedule 40, ANSI B 16.9 | BI01010001010000000000000515BI0100001250 | ||
139 | 139 | 90 deg LR bend (1.5D) | BI01010001010000000000000515BI0100001251 | ||
140 | 140 | 80 mm (3") dia | BI01010001010000000000000515BI0100001252 | 1 | EA |
141 | 141 | 45 deg LR bend (1.5D) | BI01010001010000000000000515BI0100001253 | ||
142 | 142 | 80 mm (3") dia | BI01010001010000000000000515BI0100001254 | 1 | EA |
143 | 143 | Carrying out vacuum box test for bottom plate welding including providing necessary vacuum box, tools/tackles, foam solutions etc., carrying out the test/ repeat test if required, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001255 | ||
144 | 144 | Upto 10 M dia vertical tank | BI01010001010000000000000515BI0100001256 | 1 | SET |
145 | 145 | 10 M to 16 M dia vertical tank | BI01010001010000000000000515BI0100001257 | 1 | SET |
146 | 146 | 18 M to 24 M dia vertical tank | BI01010001010000000000000515BI0100001258 | 1 | SET |
147 | 147 | 20 M to 32 M dia vertical tank | BI01010001010000000000000515BI0100001259 | 1 | SET |
148 | 148 | 32 M to 40 M dia vertical tank | BI01010001010000000000000515BI0100001260 | 1 | SET |
149 | 149 | Carrying out Chalk-Kerosene test for the welding joint of bottom plate & shell plate including providing necessary kerosene/chalk, tools/tackles, etc., carrying out the test/ repeat test if required, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001261 | ||
150 | 150 | Upto 10 M dia vertical tank | BI01010001010000000000000515BI0100001262 | 1 | LS |
151 | 151 | 10 M to 16 M dia vertical tank | BI01010001010000000000000515BI0100001263 | 1 | SET |
152 | 152 | 18 M to 24 M dia vertical tank | BI01010001010000000000000515BI0100001264 | 1 | SET |
153 | 153 | 20 M to 32 M dia vertical tank | BI01010001010000000000000515BI0100001265 | 1 | SET |
154 | 154 | 32 M to 40 M dia vertical tank | BI01010001010000000000000515BI0100001266 | 1 | SET |
155 | 155 | Conducting weld inspection of all weld joints on shell by wet Fluorescent Magnetic Particle with UV lamp including supervision by qualified inspector with ASNT level 2 certification. Note: Scaffolding will be paid separately. | BI01010001010000000000000515BI0100001267 | ||
156 | 156 | On shell plate of vertical tanks | BI01010001010000000000000515BI0100001268 | 1 | M |
157 | 157 | Carrying out Magnetic Flux Leakage test using Low Frequency Electromagnetic Technique (LFET) for the Bottom Plates including providing necessary equipments, tools/tackles, etc., carrying out the test/ repeat test if required, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001269 | ||
158 | 158 | On Bottom plate of vertical tanks | BI01010001010000000000000515BI0100001270 | 1 | M2 |
159 | 159 | Providing weld-deposition in the pitted spots on the bottom plate including cleaning thoroughly, building/ deposition the welding into the pitted spots, grinding smoothly without damage to the bottom plate, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001271 | ||
160 | 160 | Per Spot (150mm x 150mm) | BI01010001010000000000000515BI0100001272 | 1 | LS |
161 | 161 | Providing 12mm dia holes (upto 10 holes) on the wind girder wherever required to drain the rain water stagnation without any damage to shell plate & web/flange plate of wind girder, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001273 | 1 | LS |
162 | 162 | Providing 6mm dia holes (upto 3 holes per step) on the angle support of steps of spiral staircase & landing platforms to drain the rain water stagnation without any damage to shell plate & angle support, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001274 | 1 | LS |
163 | 163 | Replacement of corroded (approx 50%) Weather Shields including dismantling, handing over, supplying & fixing new weather shield (GI) plates of same size(500X600X6) with new SS fittings etc., complete as per specification & instructions at site. | BI01010001010000000000000515BI0100001275 | 1 | M |
164 | 164 | Repairs to existing damaged roof structurals such as rafters, girders including providing temporary supports, providing derricks for dismantling, handling, lowering, cutting/dismantling of member joints, re-erection/re-connecting of the same to bring its original shape/position etc complete. Supply of additional roof structure element to replace damaged/twisted members will be paid separately. | BI01010001010000000000000515BI0100001276 | 1 | TON |
165 | 165 | Supply of roof structures such as rafters using ISMC 125x65, ISMC 150x75, ISMC175x75, Girders using ISMC 350x100, stair case, landing platform, platforms for foam pourers etc etc for replacing the damaged sections (if any) and provision of curb angle using ISA 100x100x10 including fabrication, erection, welding, painting the structures etc. complete. | BI01010001010000000000000515BI0100001277 | 1 | TON |
166 | 166 | Supplying and providing of 75mm dia Hatch on roof/gauge well of CRVT/FRVT using 80 mm dia nominal pipe welded with slip-on flange on top of it including supplying and providing reinforcing plate etc. complete as per our specifications and B&R drawing. | BI01010001010000000000000515BI0100001278 | 1 | EA |
167 | 167 | Supplying and providing of 100mm dia Hatch on roof of CRVT using 100 mm dia nominal pipe welded with slip-on flange on top of it including supplying and providing reinforcing plate etc. complete as per our specifications and B&R drawing. | BI01010001010000000000000515BI0100001279 | 1 | EA |
168 | 168 | 220 MM dia gauge hatch with spark proof cover as per drg.no BR/CR/273,274,275,276 | BI01010001010000000000000515BI0100001280 | 1 | EA |
169 | 169 | gauge hatch 150 MM dia as per drg no BR/CR/273 to BR/FR/277 | BI01010001010000000000000515BI0100001281 | 1 | EA |
170 | 170 | All weld defects in Lap joints in Shell plates should be removed by fine grinding and re-welding to be carried out to ensure no further weld defects. Welding to be carried out using E6013 electrode | BI01010001010000000000000515BI0100001282 | 1 | M |
171 | 171 | Carrying out repairs of rolling ladder by welding of hinges to ladder structure at either end/or putting cotter pins, correcting alignment of rolling ladder steps by adjusting the link etc | BI01010001010000000000000515BI0100001283 | 1 | LS |
172 | 172 | Removing washer on One Side of rolling ladder wheel and fixing on other side and adjusting position of wheel so as to make it centric including providing temporary support to ladder etc as required. | BI01010001010000000000000515BI0100001284 | 1 | LS |
173 | 173 | Brass bars brazed to the rolling ladder wheels to be provided | BI01010001010000000000000515BI0100001285 | 1 | LS |
174 | 174 | Supply and providing proper copper bonding connection should be provided between the roof and rolling ladder with earthing wire cable of size 50mm SQ PVC insulated copper wire cable, including replacement of damaged lugs etc as required. | BI01010001010000000000000515BI0100001286 | 1 | M |
175 | 175 | Supply, fabrication, installation, welding, heat treatment if required including fabrication & fixing of cover plates of 6 mm thickness and 500 mm dia in roof manholes, etc. including preparation of drawings, supply of gases, electrodes and other consumables, supply and fixing of bolts, painting the same (external paiting system of tank), nuts and gaskets of approved make wherever required etc. and all labour material for completing the work as per drawings, codes / IOC specifications and site engineer's instructions (As per B&R drawing no. BR/CR/237 & 277) | BI01010001010000000000000515BI0100001287 | ||
176 | 176 | For Roof manholes | BI01010001010000000000000515BI0100001288 | 1 | EA |
177 | 177 | Supply & installation of MS Galvanized "U" clamp of size including providing M16 U-bolts with nuts suitable for the following size of pipeline; | BI01010001010000000000000515BI0100001289 | ||
178 | 178 | 65mm dia | BI01010001010000000000000515BI0100001290 | 1 | EA |
179 | 179 | 80mm dia | BI01010001010000000000000515BI0100001291 | 1 | EA |
180 | 180 | 100mm dia | BI01010001010000000000000515BI0100001292 | 1 | EA |
181 | 181 | 150mm dia | BI01010001010000000000000515BI0100001293 | 1 | EA |
182 | 182 | Supplying, providing, testing, painting 25 mm dia extension of expansion relief line for upto bottom of the tank as per drawing ref BR/CR/283 for CRVT. Item includes supplying and fixing of MS pipes (sch-80), necessary MS structural supports, pad paltes to shell as case may be for holding the pipe in position both inside the tank, providing siphon breaker (12 mm hole) on top most portion, testing the same hydrostatically at 10.5 kg/cm2, all leads & lifts etc., complete as per isntructions. | BI01010001010000000000000515BI0100001294 | ||
183 | 183 | Specification for surface preparation / cleaning / painting works; | BI01010001010000000000000515BI0100001295 | ||
184 | 184 | Clean to SSPC SP 2 hand cleaning wire brushing. | BI01010001010000000000000515BI0100001296 | ||
185 | 185 | One coat of Mastic Coating - P4 (175 µ) + | BI01010001010000000000000515BI0100001297 | ||
186 | 186 | Two coat of Acrylic Polyurethane - F1 (40-45 m each) | BI01010001010000000000000515BI0100001298 | ||
187 | 187 | Total DFT of 255 m | BI01010001010000000000000515BI0100001299 | ||
188 | 188 | 25 mm dia expansion line | BI01010001010000000000000515BI0100001300 | 1 | M |
189 | 189 | Supply and installation of Pressure vacuum relief valves with pressure setting of 75 mm water column and vacuum setting of 25 mm water column including painting the same (external paiting system of valve) as per instructions. | BI01010001010000000000000515BI0100001301 | ||
190 | 190 | 100 mm (4") dia | BI01010001010000000000000515BI0100001302 | 1 | EA |
191 | 191 | 150 mm (4") dia | BI01010001010000000000000515BI0100001303 | 1 | EA |
192 | 192 | Only testing of PV valves | BI01010001010000000000000515BI0100001304 | ||
193 | 193 | 100 mm (4") dia | BI01010001010000000000000515BI0100001305 | 1 | EA |
194 | 194 | 150 mm (4") dia | BI01010001010000000000000515BI0100001306 | 1 | EA |
195 | 195 | Pontoons compartments to be tested with air pressure at 75 MM water column by sealing compartment joints on top and hatch & checking by means of soap water on all joints to ensure the pontoons are free from pinholes/ leakages/ seepage etc. before re-commissioning the tank. | BI01010001010000000000000515BI0100001307 | ||
196 | 196 | Upto 10 M dia vertical tank | BI01010001010000000000000515BI0100001308 | 1 | EA |
197 | 197 | 10 M to 16 M dia vertical tank | BI01010001010000000000000515BI0100001309 | 1 | EA |
198 | 198 | 18 M to 24 M dia vertical tank | BI01010001010000000000000515BI0100001310 | 1 | EA |
199 | 199 | 20 M to 32 M dia vertical tank | BI01010001010000000000000515BI0100001311 | 1 | EA |
200 | 200 | 32 M to 40 M dia vertical tank | BI01010001010000000000000515BI0100001312 | 1 | EA |
201 | 201 | Taking radiographs of tank weld joints (T joints/horizontal/vertical joint) using film size 4" x 8" or 3" x 12 " as required.\nRadiography inspection on tank joints of all types and thickness including providing all necessary equipment as per specifications and instruction of Site Engineer. The radiographs shall be submitted to the engineer in charge at site/ third party inspecting agency.\nRetaking of radiography due to defective welds/defective films/ defective workmanship etc. will be to contractor's account. Necessary scaffolding shall be paid extra. | BI01010001010000000000000515BI0100001313 | 1 | EA |
202 | 202 | Submission of radiographs to Third Party Inspection Agency(PDIL/BVIS/DNV/TUV) and getting evaluation report duly certified by qualified inspector(ASNT Level II) | BI01010001010000000000000515BI0100001314 | 1 | EA |
203 | 203 | Dismantling and removing the existing mechanical seal without any damage to shell plate/deck including weather shield, foam, seal cover, holding down bars, nuts/bolts, stacking the same safely, all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001315 | ||
204 | 204 | For Floating Roof Vertical Tanks- Without Rim Seal Fire Protection System | BI01010001010000000000000515BI0100001316 | 1 | M |
205 | 205 | For Floating Roof Vertical Tanks - With Rim Seal Fire Protection System | BI01010001010000000000000515BI0100001317 | 1 | M |
206 | 206 | Re-fixing of dismantled mechanical seal without any damage to shell plate/deck safely including modification if any of the rim angle (by hot work, drilling and supply of material including rim angle, if required), all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001318 | ||
207 | 207 | For Floating Roof Vertical Tanks- Without Rim Seal Fire Protection System | BI01010001010000000000000515BI0100001319 | 1 | M |
208 | 208 | For Floating Roof Vertical Tanks - With Rim Seal Fire Protection System | BI01010001010000000000000515BI0100001320 | 1 | M |
209 | 209 | Hydrostatic testing of MS pipeline complete as per IOC specification. Supply of sweet water will be paid separately as per item above | BI01010001010000000000000515BI0100001321 | ||
210 | 210 | a) upto 100 mm dia | BI01010001010000000000000515BI0100001322 | 1 | M |
211 | 211 | b) 150 mm dia | BI01010001010000000000000515BI0100001323 | 1 | M |
212 | 212 | c) 200 mm dia | BI01010001010000000000000515BI0100001324 | 1 | M |
213 | 213 | d) 250 mm dia | BI01010001010000000000000515BI0100001325 | 1 | M |
214 | 214 | e) 300 mm dia | BI01010001010000000000000515BI0100001326 | 1 | M |
215 | 215 | f) 350 mm dia | BI01010001010000000000000515BI0100001327 | 1 | M |
216 | 216 | g) 400 mm dia | BI01010001010000000000000515BI0100001328 | 1 | M |
217 | 217 | h) 450 mm dia | BI01010001010000000000000515BI0100001329 | 1 | M |
218 | 218 | Welding of pipeline & pipe fittings joints aboveground for manifold/TLF/pumphouse modification works | BI01010001010000000000000515BI0100001330 | 1 | Inch dia. |
219 | 219 | Conducting Dye penetration test on the new weld joints (shell to bottom plate, pad plates for roof supports, lower deck plate with leg sleeve, manhole neck, rolling ladder etc) after welding. | BI01010001010000000000000515BI0100001331 | 1 | M |
220 | 220 | Conducting pneumatic test of the nozzles/manholes by providing test arrangement including and consumable items for completion of this testing\nas per direction of IOCL. The scope of the work in this items is for single nozzles/ manholes irrespective of size. | BI01010001010000000000000515BI0100001332 | 1 | EA |
221 | 221 | Providing mud packing with clay for the pipelines while carrying out hotwork -\nfor 8" and above dia only | BI01010001010000000000000515BI0100001333 | 1 | EA |
222 | 222 | Post box type cutting, opening of the bottom most strake of tank shellfor a size of1.8 m length and width 0.2 m for taking the MS platesinside the tank. The cut plates may be used for closing the openingafter proper edge preparation including bevelling and welding withproper root gap. The work also includes 100% radiography of the weldjoints before taking water for deck floatation. NOTE: Cost inclusive o fall tools, tackles required for the job to complete to the\nentire satisfaction of Engineer in\ncharge." | BI01010001010000000000000515BI0100001334 | 1 | LS |
223 | 223 | Supply of earthing boss (MS round bar \nof 50 mm dia) and making ofinternal\nthread, fixing on tank shell and\ncarrying out continuouswelding. Work\nalso includes supply of 2 nos brass\nwashers, 1 no. 16 mmdia brass stud and\n1 no MS nut for fixing of earth strip\nto earth boss.Refer: Drg BR/FR/276A | BI01010001010000000000000515BI0100001335 | 1 | EA |
224 | 224 | Provision of lock down latch\narrangement for all the pontoon covers. \nThe work includes cutting,\nfabricating, welding of 5mm/6mm thk\nMSplates for supports, clip/cleats and\nsupply, bending, erection of 6 mmdia round steel rod and fixing, etc.\ncomplete as per the directions\nofEngineer in charge. NOTE: MS plates\nshall be supplied by IOC. Ref B&R\nDrg.BR/FR/268. | BI01010001010000000000000515BI0100001336 | 1 | EA |
225 | 225 | Cutting , removal of the \ndamaged/corroded existing curb angle\nfor about1 m on the tank and replacing \nwith new curb angle including\nsupply,rolling, fabrication of angle\nand welding, etc. complete as per\nthedirections of Engineer in charge. | BI01010001010000000000000515BI0100001337 | 1 | EA |
226 | 226 | Laying and welding (3 runs min.) above ground/ below ground pipelines from supplied MS pipes (pipes to be supplied anywhere within the depot and the contractor shall shift the same to the site of work at no extra cost with all leads and lifts) of the following sizes including cutting, beveling, positioning, setting, welding, fixing the supplied specials such as elbows, bends tees, reducers etc., complete and hydro testing the pipelines at 10.5 KSC for a minimum period of 4 Hrs. The job includes blast cleaning & painting of the outer surfaces of above ground pipeline/ fittings/ specials/ flanges/ blind flanges, all leads & lifts etc., complete as per specifications and instructions at site. | BI01010001010000000000000515BI0100001338 | ||
227 | 227 | Note: a) The primer and paint shall be as per the list of paint manufacturers enclosed. The make and quality of paint shall be decided in consultation with IOC prior to use. b) Pipeline colour coding shall be carried out as per IOC specifications at no extra cost for product piping. c) Successful tenderer shall prepare the complete pipeline routing, wherever required and get the same approved prior to execution of works. | BI01010001010000000000000515BI0100001339 | ||
228 | 228 | Above ground pipeline to be laid on concrete pedestals (which is to be constructed as per the respective item of this schedule) and painting & colour coding the pipeline as per the specifications. Welding of pipeline should conform to Radiography quality. 10% of the joints shall be radiograped and the cost of the same will be paid separately as per respective item, all leads & lifts etc., complete as per specifications and instructions at site. | BI01010001010000000000000515BI0100001340 | ||
229 | 229 | Note: a) Any repairs to the defective welding shall be made good at no extra cost. Re-radiography of repaired joint shall also be at contractor's cost. b) The rates quoted also to include colour coding of pipelines as per the standards. c) The rate shall include providing temporary / moving screen wall for local welding of running pipelines, if required. | BI01010001010000000000000515BI0100001341 | ||
230 | 230 | d) Painting scheme for MS pipeline (A/G)/ fittings/ specials/ flanges: | BI01010001010000000000000515BI0100001342 | ||
231 | 231 | Specification for surface preparation / cleaning / painting works; | BI01010001010000000000000515BI0100001343 | ||
232 | 232 | Surface Preparation : Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001344 | ||
233 | 233 | Primer : Inorganic Zinc Ethyl Silicate (P1) with DFT in the range of 65-75 micron. | BI01010001010000000000000515BI0100001345 | ||
234 | 234 | Intermediate Coat : Polyamide cured HB Epoxy MIO (U1) with DFT in the range of 100 -125 micron. | BI01010001010000000000000515BI0100001346 | ||
235 | 235 | Finish Coat : Two Pack Acrylic Poly-urethane(PU) (F1) with DFT in the range of 40-50 micron. | BI01010001010000000000000515BI0100001347 | ||
236 | 236 | TOTAL min DFT 215 microns | BI01010001010000000000000515BI0100001348 | ||
237 | 237 | 25 mm dia including cost of SCH-80 pipe | BI01010001010000000000000515BI0100001349 | 1 | M |
238 | 238 | 50 mm dia including cost of SCH-80 pipe | BI01010001010000000000000515BI0100001350 | 1 | M |
239 | 239 | 80 mm dia | BI01010001010000000000000515BI0100001351 | 1 | M |
240 | 240 | 100 mm dia | BI01010001010000000000000515BI0100001352 | 1 | M |
241 | 241 | 150 mm dia | BI01010001010000000000000515BI0100001353 | 1 | M |
242 | 242 | 200 mm dia | BI01010001010000000000000515BI0100001354 | 1 | M |
243 | 243 | 250 mm dia | BI01010001010000000000000515BI0100001355 | 1 | M |
244 | 244 | 300 mm dia | BI01010001010000000000000515BI0100001356 | 1 | M |
245 | 245 | 350 mm dia | BI01010001010000000000000515BI0100001357 | 1 | M |
246 | 246 | 400 mm dia | BI01010001010000000000000515BI0100001358 | 1 | M |
247 | 247 | 450 mm dia | BI01010001010000000000000515BI0100001359 | 1 | M |
248 | 248 | Provision of Saddle plates for Product & Hydrant Pipelines over pedestals including cutting and fabrication of saddle plates from supplied MS pipes and welding of the same on pipelines under pedestals with minimum 3 run of welding complete as per specifications, drawings and directions of Engineer in charge. | BI01010001010000000000000515BI0100001360 | ||
249 | 249 | 450 mm dia pipe | BI01010001010000000000000515BI0100001361 | 1 | EA |
250 | 250 | 400 mm dia pipe | BI01010001010000000000000515BI0100001362 | 1 | EA |
251 | 251 | 350 mm dia pipe | BI01010001010000000000000515BI0100001363 | 1 | EA |
252 | 252 | 300 mm dia Pipe | BI01010001010000000000000515BI0100001364 | 1 | EA |
253 | 253 | 250 mm dia pipe | BI01010001010000000000000515BI0100001365 | 1 | EA |
254 | 254 | 200 mm dia pipe | BI01010001010000000000000515BI0100001366 | 1 | EA |
255 | 255 | 150 mm dia pipe | BI01010001010000000000000515BI0100001367 | 1 | EA |
256 | 256 | 100 mm dia pipe | BI01010001010000000000000515BI0100001368 | 1 | EA |
257 | 257 | 80 mm dia pipe | BI01010001010000000000000515BI0100001369 | 1 | EA |
258 | 258 | Underground pipelines to be laid at a depth as per site condition/ laying through hume pipes/ culverts of the following sizes including supplying & providing doping (wrapping & coating), all leads & lifts etc., complete as per specifications and instructions at site. | BI01010001010000000000000515BI0100001370 | ||
259 | 259 | Note : a) Welding of pipeline should be to Radiography quality. 10% of the joints shall be radiograped and the cost of the same will be paid separately as per respective item etc. b) All job as stated above for erection of under ground pipeline shall be included in the quoted rate except payment of radiography. | BI01010001010000000000000515BI0100001371 | ||
260 | 260 | b) Wrapping & coating of MS pipeline (U/G)/ fittings/ specials/ flanges with approved materials as per specifications. | BI01010001010000000000000515BI0100001372 | ||
261 | 261 | 25 mm dia including cost of SCH-80 pipe | BI01010001010000000000000515BI0100001373 | 1 | M |
262 | 262 | 50 mm dia including cost of SCH-80 pipe | BI01010001010000000000000515BI0100001374 | 1 | M |
263 | 263 | 80 mm dia | BI01010001010000000000000515BI0100001375 | 1 | M |
264 | 264 | 100 mm dia | BI01010001010000000000000515BI0100001376 | 1 | M |
265 | 265 | 150 mm dia | BI01010001010000000000000515BI0100001377 | 1 | M |
266 | 266 | 200 mm dia | BI01010001010000000000000515BI0100001378 | 1 | M |
267 | 267 | 250 mm dia | BI01010001010000000000000515BI0100001379 | 1 | M |
268 | 268 | 300 mm dia | BI01010001010000000000000515BI0100001380 | 1 | M |
269 | 269 | 350 mm dia | BI01010001010000000000000515BI0100001381 | 1 | M |
270 | 270 | 400 mm dia | BI01010001010000000000000515BI0100001382 | 1 | M |
271 | 271 | 450 mm dia | BI01010001010000000000000515BI0100001383 | 1 | M |
272 | 272 | Radiography inspection on product pipe joints of all types and thickness of the following sizes including providing all necessary equipment required to perform the work as per our specification and of our site engineer. The radiographs shall be submitted to the the engineer in charge at site/ third party inspecting agency. | BI01010001010000000000000515BI0100001384 | ||
273 | 273 | Note: Re-taking of radiography due to defective welds/ defective films/ defective workmanship etc., will be to contractor's cost. | BI01010001010000000000000515BI0100001385 | ||
274 | 274 | 50 mm dia | BI01010001010000000000000515BI0100001386 | 1 | EA |
275 | 275 | 80 mm dia | BI01010001010000000000000515BI0100001387 | 1 | EA |
276 | 276 | 100 mm dia | BI01010001010000000000000515BI0100001388 | 1 | EA |
277 | 277 | 150 mm dia | BI01010001010000000000000515BI0100001389 | 1 | EA |
278 | 278 | 200 mm dia | BI01010001010000000000000515BI0100001390 | 1 | EA |
279 | 279 | 250 mm dia | BI01010001010000000000000515BI0100001391 | 1 | EA |
280 | 280 | 300 mm dia | BI01010001010000000000000515BI0100001392 | 1 | EA |
281 | 281 | 350 mm dia | BI01010001010000000000000515BI0100001393 | 1 | EA |
282 | 282 | 400 mm dia | BI01010001010000000000000515BI0100001394 | 1 | EA |
283 | 283 | 450 mm dia | BI01010001010000000000000515BI0100001395 | 1 | EA |
284 | 284 | Welding of the supplied WNRF/SORF flanges of the following sizes on the pipelines including setting, positioning, setting, welding with min. three runs outside and one run inside (SORF), all leads & lifts etc., complete as per specifications and instructions at site. | BI01010001010000000000000515BI0100001396 | ||
285 | 285 | 50 mm dia | BI01010001010000000000000515BI0100001397 | 1 | EA |
286 | 286 | 80 mm dia | BI01010001010000000000000515BI0100001398 | 1 | EA |
287 | 287 | 100 mm dia | BI01010001010000000000000515BI0100001399 | 1 | EA |
288 | 288 | 150 mm dia | BI01010001010000000000000515BI0100001400 | 1 | EA |
289 | 289 | 200 mm dia | BI01010001010000000000000515BI0100001401 | 1 | EA |
290 | 290 | 250 mm dia | BI01010001010000000000000515BI0100001402 | 1 | EA |
291 | 291 | 300 mm dia | BI01010001010000000000000515BI0100001403 | 1 | EA |
292 | 292 | 350 mm dia | BI01010001010000000000000515BI0100001404 | 1 | EA |
293 | 293 | 400 mm dia | BI01010001010000000000000515BI0100001405 | 1 | EA |
294 | 294 | 450 mm dia | BI01010001010000000000000515BI0100001406 | 1 | EA |
295 | 295 | Supply & welding slip on flanges conforming to IS2062 GrA, ANSI B16.5- Class # 150 with 3 runs of weld outside and one run of weld inside the flanges as per specifications and standard Drg. enclosed herein. | BI01010001010000000000000515BI0100001407 | ||
296 | 296 | 50 mm dia | BI01010001010000000000000515BI0100001408 | 1 | EA |
297 | 297 | 80 mm dia | BI01010001010000000000000515BI0100001409 | 1 | EA |
298 | 298 | 100 mm dia | BI01010001010000000000000515BI0100001410 | 1 | EA |
299 | 299 | 150 mm dia | BI01010001010000000000000515BI0100001411 | 1 | EA |
300 | 300 | 200 mm dia | BI01010001010000000000000515BI0100001412 | 1 | EA |
301 | 301 | 250 mm dia | BI01010001010000000000000515BI0100001413 | 1 | EA |
302 | 302 | 300 mm dia | BI01010001010000000000000515BI0100001414 | 1 | EA |
303 | 303 | 350 mm dia | BI01010001010000000000000515BI0100001415 | 1 | EA |
304 | 304 | 400 mm dia | BI01010001010000000000000515BI0100001416 | 1 | EA |
305 | 305 | 450 mm dia | BI01010001010000000000000515BI0100001417 | 1 | EA |
306 | 306 | Making flanged joints between flanges slip on and blind flange including supplying and fixing 3 mm thick non metallic gaskets, nuts, bolts of approved make for the following sizes, as per IOCL specifications and site instructions. The flange joint shall also include providing and fixing multistrand copper wire/flat for bonding of product pipelines including provision of lugs.\n | BI01010001010000000000000515BI0100001418 | ||
307 | 307 | 50 mm dia | BI01010001010000000000000515BI0100001419 | 1 | EA |
308 | 308 | 80 mm dia | BI01010001010000000000000515BI0100001420 | 1 | EA |
309 | 309 | 100 mm dia | BI01010001010000000000000515BI0100001421 | 1 | EA |
310 | 310 | 150 mm dia | BI01010001010000000000000515BI0100001422 | 1 | EA |
311 | 311 | 200 mm dia | BI01010001010000000000000515BI0100001423 | 1 | EA |
312 | 312 | 250 mm dia | BI01010001010000000000000515BI0100001424 | 1 | EA |
313 | 313 | 300 mm dia | BI01010001010000000000000515BI0100001425 | 1 | EA |
314 | 314 | 350 mm dia | BI01010001010000000000000515BI0100001426 | 1 | EA |
315 | 315 | 400 mm dia | BI01010001010000000000000515BI0100001427 | 1 | EA |
316 | 316 | 450 mm dia | BI01010001010000000000000515BI0100001428 | 1 | EA |
317 | 317 | Making flanged joints between flanges (WNRF/SORF/BLRF) including supplying and fixing 3 mm thick SW SS gaskets with graphite fillers, studs, nuts, bolts of approved make for the following sizes, as per IOCL specifications and site instructions. The flange joint shall also include providing and fixing multistrand copper wire/flat for bonding of product pipelines including\nprovision of lugs. | BI01010001010000000000000515BI0100001429 | ||
318 | 318 | 600 mm dia | BI01010001010000000000000515BI0100001430 | 1 | EA |
319 | 319 | 500 mm dia | BI01010001010000000000000515BI0100001431 | 1 | EA |
320 | 320 | 450 mm dia | BI01010001010000000000000515BI0100001432 | 1 | EA |
321 | 321 | 400 mm dia | BI01010001010000000000000515BI0100001433 | 1 | EA |
322 | 322 | 350 mm dia | BI01010001010000000000000515BI0100001434 | 1 | EA |
323 | 323 | 300 mm dia | BI01010001010000000000000515BI0100001435 | 1 | EA |
324 | 324 | 250 mm dia | BI01010001010000000000000515BI0100001436 | 1 | EA |
325 | 325 | 200 mm dia | BI01010001010000000000000515BI0100001437 | 1 | EA |
326 | 326 | 150 mm dia | BI01010001010000000000000515BI0100001438 | 1 | EA |
327 | 327 | 100 mm dia | BI01010001010000000000000515BI0100001439 | 1 | EA |
328 | 328 | 80 mm dia | BI01010001010000000000000515BI0100001440 | 1 | EA |
329 | 329 | Making flanged joints between flanges (WNRF/SORF/BLRF) including supplying and fixing 3 mm thk PTFE gaskets, studs/ nuts etc. of approved make for the following sizes as per IOC specifications and site instructions. The flange joints shall also include providing and fixing multistrand copper strip/flat for bonding of product pipelines , Cost of strand/ GI flat shall be paid separately as per rate in RM.\n(for Ethanol) | BI01010001010000000000000515BI0100001441 | ||
330 | 330 | 300 mm dia | BI01010001010000000000000515BI0100001442 | 1 | EA |
331 | 331 | 250 mm dia | BI01010001010000000000000515BI0100001443 | 1 | EA |
332 | 332 | 200 mm dia | BI01010001010000000000000515BI0100001444 | 1 | EA |
333 | 333 | 150 mm dia | BI01010001010000000000000515BI0100001445 | 1 | EA |
334 | 334 | 100 mm dia | BI01010001010000000000000515BI0100001446 | 1 | EA |
335 | 335 | 80 mm dia | BI01010001010000000000000515BI0100001447 | 1 | EA |
336 | 336 | 50 mm dia | BI01010001010000000000000515BI0100001448 | 1 | EA |
337 | 337 | 25 mm dia | BI01010001010000000000000515BI0100001449 | 1 | EA |
338 | 338 | Fixing the supplied CS GATE/ ROSOV/ DBBV/ MOV/ GOV/ NRV/ BALL/ BUTTERFLY/ AUDCO valves of the following sizes on the pipeline including supplying and fixing 3 mm thk non metallic gaskets, studs/nuts etc of approved make for the following sizes as per specifications, existing cable termination wherever required, all lead & lifts, transportation etc., complete and as per instructions at site. | BI01010001010000000000000515BI0100001450 | ||
339 | 339 | Note: a) Painting with approved make, colour, shade including colour coding as per specifications. | BI01010001010000000000000515BI0100001451 | ||
340 | 340 | b) Painting scheme for accessories & valves: | BI01010001010000000000000515BI0100001452 | ||
341 | 341 | Specification for surface preparation / cleaning / painting works; | BI01010001010000000000000515BI0100001453 | ||
342 | 342 | Clean to SSPC SP 2 hand cleaning wire brushing. | BI01010001010000000000000515BI0100001454 | ||
343 | 343 | Two coats of P3 (30-35 m each) + | BI01010001010000000000000515BI0100001455 | ||
344 | 344 | Two coats of F4 (25 m each) | BI01010001010000000000000515BI0100001456 | ||
345 | 345 | Total DFT of 110 m | BI01010001010000000000000515BI0100001457 | ||
346 | 346 | 50 mm dia | BI01010001010000000000000515BI0100001458 | 1 | EA |
347 | 347 | 80 mm dia | BI01010001010000000000000515BI0100001459 | 1 | EA |
348 | 348 | 100 mm dia | BI01010001010000000000000515BI0100001460 | 1 | EA |
349 | 349 | 150 mm dia | BI01010001010000000000000515BI0100001461 | 1 | EA |
350 | 350 | 200 mm dia | BI01010001010000000000000515BI0100001462 | 1 | EA |
351 | 351 | 250 mm dia | BI01010001010000000000000515BI0100001463 | 1 | EA |
352 | 352 | 300 mm dia | BI01010001010000000000000515BI0100001464 | 1 | EA |
353 | 353 | 350 mm dia | BI01010001010000000000000515BI0100001465 | 1 | EA |
354 | 354 | 400 mm dia | BI01010001010000000000000515BI0100001466 | 1 | EA |
355 | 355 | 450 mm dia | BI01010001010000000000000515BI0100001467 | 1 | EA |
356 | 356 | Fixing the following sized (Dia)\nsupplied spectacle dummy, with bothside\nnew gaskets, bolts, nuts etc. | BI01010001010000000000000515BI0100001468 | ||
357 | 357 | 500 mm dia | BI01010001010000000000000515BI0100001469 | 1 | EA |
358 | 358 | 450 mm dia | BI01010001010000000000000515BI0100001470 | 1 | EA |
359 | 359 | 400 mm dia | BI01010001010000000000000515BI0100001471 | 1 | EA |
360 | 360 | 350 mm dia | BI01010001010000000000000515BI0100001472 | 1 | EA |
361 | 361 | 300 mm dia | BI01010001010000000000000515BI0100001473 | 1 | EA |
362 | 362 | 250 mm dia | BI01010001010000000000000515BI0100001474 | 1 | EA |
363 | 363 | 200 mm dia | BI01010001010000000000000515BI0100001475 | 1 | EA |
364 | 364 | 150 mm dia | BI01010001010000000000000515BI0100001476 | 1 | EA |
365 | 365 | 100 mm dia | BI01010001010000000000000515BI0100001477 | 1 | EA |
366 | 366 | 80 mm dia | BI01010001010000000000000515BI0100001478 | 1 | EA |
367 | 367 | Cold cutting of the following sized\nunderground/ Above ground pipelines | BI01010001010000000000000515BI0100001479 | ||
368 | 368 | 500 mm dia | BI01010001010000000000000515BI0100001480 | 1 | EA |
369 | 369 | 450 mm dia | BI01010001010000000000000515BI0100001481 | 1 | EA |
370 | 370 | 400 mm dia | BI01010001010000000000000515BI0100001482 | 1 | EA |
371 | 371 | 350 mm dia | BI01010001010000000000000515BI0100001483 | 1 | EA |
372 | 372 | 300 mm dia | BI01010001010000000000000515BI0100001484 | 1 | EA |
373 | 373 | 250 mm dia | BI01010001010000000000000515BI0100001485 | 1 | EA |
374 | 374 | 200 mm dia | BI01010001010000000000000515BI0100001486 | 1 | EA |
375 | 375 | 150 mm dia | BI01010001010000000000000515BI0100001487 | 1 | EA |
376 | 376 | 100 mm dia | BI01010001010000000000000515BI0100001488 | 1 | EA |
377 | 377 | 80 mm dia | BI01010001010000000000000515BI0100001489 | 1 | EA |
378 | 378 | Pressure testing of Following sized\n(Dia)Valves . Both Gate & EntireValve\ncasing shall be subjected to pressure\nby providing blinding usingDummy,\nBolts/Nuts/Gaskets, tec | BI01010001010000000000000515BI0100001490 | ||
379 | 379 | 500 mm dia | BI01010001010000000000000515BI0100001491 | 1 | EA |
380 | 380 | 450 mm dia | BI01010001010000000000000515BI0100001492 | 1 | EA |
381 | 381 | 400 mm dia | BI01010001010000000000000515BI0100001493 | 1 | EA |
382 | 382 | 350 mm dia | BI01010001010000000000000515BI0100001494 | 1 | EA |
383 | 383 | 300 mm dia | BI01010001010000000000000515BI0100001495 | 1 | EA |
384 | 384 | 250 mm dia | BI01010001010000000000000515BI0100001496 | 1 | EA |
385 | 385 | 200 mm dia | BI01010001010000000000000515BI0100001497 | 1 | EA |
386 | 386 | 150 mm dia | BI01010001010000000000000515BI0100001498 | 1 | EA |
387 | 387 | 100 mm dia | BI01010001010000000000000515BI0100001499 | 1 | EA |
388 | 388 | 80 mm dia | BI01010001010000000000000515BI0100001500 | 1 | EA |
389 | 389 | Installing the supplied auto recirculation valves as per specifications on the product pump headers at the TLF pump house including supplying, providing and welding flanges of matching sizes.\nNote:\na. The job includes mechanical cleaning of valves and painting of the valves with 2 coats of P3 primer and 2 coats F4 finish paint of approved colour and shade as per the directions of site in charge. The job includes providing and fixing impulse as per manufacturer's recommendations.\nb. Bonding of the valves shall be done using multistrand copper wire/flat for bonding of product pipelines including provision of lugs. | BI01010001010000000000000515BI0100001501 | ||
390 | 390 | 100 mm dia (suitable for 2400 - 4800 LPM - MS/ SKO/ HSD TLF\npumps) | BI01010001010000000000000515BI0100001502 | 1 | EA |
391 | 391 | 80 mm dia (suitable for 900 - 1800 LPM - MS/ SKO/ HSD TLF pumps) | BI01010001010000000000000515BI0100001503 | 1 | EA |
392 | 392 | Installing the supplied bucket type (100 mesh) strainers as per specs and drawing for the product pumps for the following LPM & pipeline sizes:\nNote: The strainers shall be cleaned and painted with 2 coats of P3 primer and 2 coats of F4 finish paint of approved colour and shade etc as per the directions of the site engineer & the rates quoted should include the same. | BI01010001010000000000000515BI0100001504 | ||
393 | 393 | 300 mm dia (Bucket type) | BI01010001010000000000000515BI0100001505 | 1 | EA |
394 | 394 | 250 mm dia (Bucket type) | BI01010001010000000000000515BI0100001506 | 1 | EA |
395 | 395 | 200 mm dia (Bucket type) | BI01010001010000000000000515BI0100001507 | 1 | EA |
396 | 396 | 150 mm dia (Bucket type) | BI01010001010000000000000515BI0100001508 | 1 | EA |
397 | 397 | 100 mm dia (Bucket type) | BI01010001010000000000000515BI0100001509 | 1 | EA |
398 | 398 | Installing the supplied Y type (40 mesh) strainers as per specs and drawing for the hydrant / water piping system including fire water pumps & sprinkler/foam headers for the following LPM & pipeline sizes:\nNote: The strainers shall be cleaned and painted with 2 coats of P3 primer and 2 coats of F4 finish paint of approved colour and shade etc as per the directions of the site engineer & the rates quoted should include the same. | BI01010001010000000000000515BI0100001510 | ||
399 | 399 | 300 mm (Y type) & flowrate 616KL/HR | BI01010001010000000000000515BI0100001511 | 1 | EA |
400 | 400 | 250 mm (Y type) & flowrate 410KL/HR | BI01010001010000000000000515BI0100001512 | 1 | EA |
401 | 401 | 150 mm (Y type) & flowrate 2400 LPM | BI01010001010000000000000515BI0100001513 | 1 | EA |
402 | 402 | 100 mm (Y type) & flowrate 1500 LPM | BI01010001010000000000000515BI0100001514 | 1 | EA |
403 | 403 | Installing the supplied thermal relief valves for the product pipeline and fixing the same on the pump discharge lines to TLF including painting the valves and connected piping with 2 coats of P3 primer and 2 coats of F4 finish paint of approved colour and shade as per the directions of site engineer.\nNote:\na. The 20/ 25 mm dia piping connected to the TRVs shall be measured and paid separatey under respective items.\nb. The job also includes providing and fixing 8SWG copper wire for the flange joints of the assembly. | BI01010001010000000000000515BI0100001515 | 1 | EA |
404 | 404 | Dismantling of the power driven product pumpsets installaed at IOC Premises without causing damage to pumpsets and its accessories. Item includes disconnection of pipeline, removing of electrical cables, foundation bolt, Handling & Placing at suitable place as per instrcutions.\nNote: The pumpsets shall be kept anywhere within the premises. The cost of foundation dismantling if required shall\nbe measured & paid separately under respective civil items. | BI01010001010000000000000515BI0100001516 | ||
405 | 405 | 600 LPM X 30-50 M Head (Submersible Turbine Pump)\n | BI01010001010000000000000515BI0100001517 | 1 | EA |
406 | 406 | 1200 LPM X 30-50 M Head (Submersible Turbine Pump)\n | BI01010001010000000000000515BI0100001518 | 1 | EA |
407 | 407 | 6000 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001519 | 1 | EA |
408 | 408 | 4800 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001520 | 1 | EA |
409 | 409 | 3600 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001521 | 1 | EA |
410 | 410 | 2400 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001522 | 1 | EA |
411 | 411 | 1800 LPM X 30-40 M Head (OCF Pump) | BI01010001010000000000000515BI0100001523 | 1 | EA |
412 | 412 | 1200 LPM X 20-40 M Head (OCF Pump) | BI01010001010000000000000515BI0100001524 | 1 | EA |
413 | 413 | 900 LPM X 20-40 M Head (OCF Pump) | BI01010001010000000000000515BI0100001525 | 1 | EA |
414 | 414 | Mounting, installing, aligning, testing and commissioning of the power driven product pumpsets supplied by IOC without causing damage to pumpsets and its accessories. Pumpsets shall be erected and aligned as per manufacturer's drawings.\nNote: The pumpsets shall be supplied anywhere within the premises and the contractor shall undertake to lead the same to the foundations at no extra cost. The cost of foundation shall\nbe measured & paid separately under respective civil items. | BI01010001010000000000000515BI0100001526 | ||
415 | 415 | 600 LPM X 30-50 M Head (Submersible Turbine Pump)\nNote: The pumpsets shall be erected with all accessories on UG tank manhole plates as per manufacturer's recommendations | BI01010001010000000000000515BI0100001527 | 1 | EA |
416 | 416 | 1200 LPM X 30-50 M Head (Submersible Turbine Pump)\nNote: The pumpsets shall be erected with all accessories on UG tank manhole plates as per manufacturer's recommendations | BI01010001010000000000000515BI0100001528 | 1 | EA |
417 | 417 | 6000 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001529 | 1 | EA |
418 | 418 | 4800 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001530 | 1 | EA |
419 | 419 | 3600 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001531 | 1 | EA |
420 | 420 | 2400 LPM X 30-60 M Head (OCF Pump) | BI01010001010000000000000515BI0100001532 | 1 | EA |
421 | 421 | 1800 LPM X 30-40 M Head (OCF Pump) | BI01010001010000000000000515BI0100001533 | 1 | EA |
422 | 422 | 1200 LPM X 20-40 M Head (OCF Pump) | BI01010001010000000000000515BI0100001534 | 1 | EA |
423 | 423 | 900 LPM X 20-40 M Head (OCF Pump) | BI01010001010000000000000515BI0100001535 | 1 | EA |
424 | 424 | Installation of the supplied diesel engine driven fire pumpsets mounted on common base frame on foundations including grouting of supplied foundation bolts without causing damage to the pumps\n/ foundation & accessories. The pumpset (fire engines) shall be installed including supplying and providing AVM pads, grouting the foundation bolts into the the pockets provided in the foundation and aligning the pumpset etc. complete as per directions of site in charge.\nNote: a. The job includes transportation of fire engines from any location inside the Terminal / Installation / Depot premises to the Fire Water Pumphouse at no extra cost.\nb. The item rate quoted should also include cooling water piping with fittings etc complete.\nc. Civil works for foundation will be paid separately Fire Pumpset Size : 616 Cum/ Hr X 105 M head. | BI01010001010000000000000515BI0100001536 | 1 | EA |
425 | 425 | Installation of the supplied diesel engine driven fire pumpsets mounted on common base frame on foundations including grouting of supplied foundation bolts without causing damage to the pumps\n/ foundation & accessories. The pumpset (fire engines) shall be installed including supplying and providing AVM pads, grouting the foundation bolts into the the pockets provided in the foundation and aligning the pumpset etc. complete as per directions of site in charge.\nNote: a. The job includes transportation of fire engines from any location inside the Terminal / Installation / Depot premises to the Fire Water Pumphouse at no extra cost.\nb. The item rate quoted should also include cooling water piping with fittings etc complete.\nc. Civil works for foundation will be paid separately. Fire Pumpset Size : 410 Cum/ Hr X 88 M head. | BI01010001010000000000000515BI0100001537 | 1 | EA |
426 | 426 | Installation of supplied fuel tanks on MS structural supports including supplying and providing medium duty MS lines for supply and return lines to the fire pump from the fuel tank. The MS structural supports for fuel tank shall be blast cleaned to SA 2 1/2 and painting with two coats of P3 primer and two coats of F4 finish paint of approved colour & shade as per enclosed specifications and as per directions of site in charge\nNote : The item rate should include MS structural supports for the above job. Tenderers to note that fuel tanks shall be located such as to provide for gravity flow for fuel to the fire pumps. | BI01010001010000000000000515BI0100001538 | 1 | EA |
427 | 427 | Installing the supplied starter/ auto starter assembly of the fire pumps including supplying and erecting the same on ISA 65 x 6 including necessary CC support pillars, blast cleaning of the structures to SA 2 1/2 and painting the structure with two coats of P3 primer and F4 finished paint as per enclosed specification and as per directions of site in charge | BI01010001010000000000000515BI0100001539 | 1 | EA |
428 | 428 | Supplying and fixing battery stand using ISA 65 x 6 MS angle iron supports with necessary foundation including providing teak wood plank 20 mm thk for positioning 2x12 V batteries & connecting the same with starter/auto starter assembly / rechargers etc. complete Note: The structurals shall be mechanical cleaned and painted with 2 coats of P3 primer and 2 coats of F4 finish paint of approved colour and shade as per site directions. | BI01010001010000000000000515BI0100001540 | 1 | EA |
429 | 429 | Supplying, fabricating, welding, erecting with suitable supports 150 mm dia medium duty MS ERW tube as per IS 1239 for exhaust line of fire pumps including installing and erecting the supplied metalic bellows and silencer; the exhaust pipe shall be adequately supported in the fire pump house with suitable arrangements; the entire exhaust pipe shall be lagged using 12 mm dia asbestos rope and cladding the line in 22 g aluminium sheet with necessary riveting and fixing;\nThe exhaust pipe outside the fire pump house shall be taken to a minimum height of 3 mtrs. above the roof and supported by means of suitable brackets / guy wires / angle support; The exhaust shall also be provided with suitable arrangements so as to prevent water from entering the pipes. The entire work arrangement shall be completed as per specifications and directions of site in charge.\nNote: a. The asbestos rope shall be as per IS supplied by M/s.\nChampion/ M/s. Hindustan Composites. B. The\napproximate length of 150 mm dia line shall be 15 m per set c. The exhaust line after the silencer shall be painted with 2 coats of primer and two coats of heat resistant aluminium paint and the rates quoted to include the same. | BI01010001010000000000000515BI0100001541 | 1 | EA |
430 | 430 | Supplying and fixing electric pressure switches of approved make and connecting the same to the delivery headers of the Jockey pumps and Main hydrant pumps with necessary sockets welded on the headers, accessories etc complete. | BI01010001010000000000000515BI0100001542 | 1 | EA |
431 | 431 | Supplying and fixing 150 mm dia pressure gage (0-20 KSC) to the delivery lines of fire pumps, jockey pumps & hydrant network, including supplying and welding necessary sockets on the pipelines including 3 way pressure differential valve, etc. complete and as per directions of site in charge. | BI01010001010000000000000515BI0100001543 | 1 | EA |
432 | 432 | Interconnection between the starter panels of Fire pumps/ Jockey pumps/ make up water pumps/ pressure switches and Annunciation panel for auto starting of the fire pumps/ jockey pumps as per the logic defined in enclosed documents.; Entire interconnections shall be established using 2 C, 1.1 KV grade armoured copper cable of size\n1.5 sqmm;The cable shall be laid at all places including clamping etc complete as required; The job shall be complete in all respects and specifications as per the logic and requirements to put the entire system in AUTO mode as per the specifications.\nNote: Tenderers to note that all cabling to be taken underneath flooring of fire pump house shall be adequately protected by suitable sized B class GI piping. Also all cables to be laid above ground shall be neatly dressed and tagged. | BI01010001010000000000000515BI0100001544 | 1 | EA |
433 | 433 | Fixing the supplied FH line fittings on the Fire hydrant pipelines including supplying and fixing 3mm thick gaskets/ nuts/ studs and all other materials as per enclosed specifications and as directed at site.\nNote: The fittings shall be painted with two coats of F4 finish paint of approved colour and shade over 2 coats of P3 primer. The rates quoted should include the same. | BI01010001010000000000000515BI0100001545 | ||
434 | 434 | Double hydrant Points with individual control valves | BI01010001010000000000000515BI0100001546 | 1 | EA |
435 | 435 | 100 mm Water / Water cum Foam Monitors | BI01010001010000000000000515BI0100001547 | 1 | EA |
436 | 436 | 150 mm dia long range water cum foam monitors (500-750 GPM\nmanual HVLR) | BI01010001010000000000000515BI0100001548 | 1 | EA |
437 | 437 | Installation of IOCL supplied Remote operated High volume Long Range Water Monitors including the following :\n(a) Erection of Motors\n(b) Fixing of Proximity sensors\n(c) Erection of MOV Gate valve\n(d) Erection of Remote Control Panel\n(e) Fixing of Control & Junction Box\n(f) Laying of power cable from Control Panel to HVLR Motors\n(g) Laying of Control cable from Remote Control Panel to HVLR Signal Junction Box\n(h) Laying of Signal cable from Remote Control Panel to HVLR Signal Junction Box\n(i) Supply and Fixing of cable tray from Remote Control Panel to HVLR Junction Box\n(j) Glanding & termination of power , control & signal cables\n(k) Installation of Gaskets & stud bolts. as directed by IOCL or EIC\n(l) Making the stub connection with necessary reinforcement pad as applicable,\n(m) Suppiled foam container for HVLRM including erecting the same with necessary CC support as per specification and direction of site incharge.\n(n) Installation of suppiled Jet Ratio Control Pump(JRCP) for HVLRM including erecting the same with necessary CC support as per specification and direction of site incharge.\nNote:\na)The job also include the MS fabricated working platform wherever required without any extra cost. | BI01010001010000000000000515BI0100001549 | 1 | EA |
438 | 438 | Installation of suppiled control panel assembly with necessary canopy of the HVLRM including supply and erecting the same on ISA 65 x 6 including necessary CC support pillars, painting as per IOCL specifications and directions of site in charge. | BI01010001010000000000000515BI0100001550 | 1 | EA |
439 | 439 | Supplying and providing MS structural supports in ISA 65 X 6 for hose boxes supplied by IOC including cutting and welding and providing necessary CC 1:2:4 support pillars for the structures. The job also includes blast cleaning of the structures to SA 2 1/2 and painting with two coats of P3 primer and two coats of F4 finish paint as per specifications and as per colour and shade as directed by site in charge.\nNote : The stand shall be fixed with hose box at levels as indicated on drawings. | BI01010001010000000000000515BI0100001551 | 1 | EA |
440 | 440 | Installing, aligning testing and commissioning of the supplied jockey pump set of capacity 18.5 -100 Cum/hr x 110 m Head for fire hydrant automation; the job includes grouting foundation bolts in the pockets of the foundatoion etc complete.\nNote:\n1.The job also includes connecting the jockey pump to its control panel by a 3 C, 1.1 KV grade armoured aluminium cable of required size including necessary glanding/ gland\nearthing etc complete. (approximate length of cable not to exceed 25 m). Item rate quoted should include the same.\n2. Foundation shall be paid for separately as per the measurement under respective civil items. | BI01010001010000000000000515BI0100001552 | 1 | EA |
441 | 441 | Drain Pan arrangement for Product Pump / Fire Water Pump /\nJockey Pump | BI01010001010000000000000515BI0100001553 | 1 | EA |
442 | 442 | Installation, aligning and commissioing of make up water pump / calibration tower pump to be erected on the RCC slab of the UG water sump on suitable foundation inlcuding foundation bolts/ grouting etc.\nNote:\n1. The foundation and foundation bolts/ grouting shall be measured and paid separately under respective civil items. The pumps shall be connected to the starter to be located on gantry of calibration tower by a 3 1/2 C, 1.1 KV grade armoured Al. cable (approx. 40 m) of adequate rating including glanding/ gland earthing at both ends etc complete\n2. Suitable protection in MS angle frame work/ sheet steel for the pumps shall also be provided. The rates quoted to include the same. Capacity of Make up Water Pump (90 Cum/ Hr X 36 m head) | BI01010001010000000000000515BI0100001554 | 1 | EA |
443 | 443 | SUPPLY OF MATERIALS TO SITE | BI01010001010000000000000515BI0100001555 | ||
444 | 444 | Note: 1. All items under this section shall be quoted for supply to site including unloading. Third party inspection for the supply items shall be in tenderer's scope. Approval of TPI agency shall be obtained from IOCL on award of contract & engaged for inspection & clearance of all materials as per agreed QAP to be firmed up after placement of order by the Corporation. | BI01010001010000000000000515BI0100001556 | ||
445 | 445 | Supply of Mild Steel Plates of suitable width and length ranging in thickness from 5 mm to 28 mm as required, conforming to IS 2062 Gr. 'B' / IS 2062 E250B, Fully Killed (Un-trimmed and un-normalized condition of approved make). Rate should also include cost of inspection by IOCL approved 3rd Party inspection agency as listed elsewhere in the tender document. | BI01010001010000000000000515BI0100001557 | 1 | MT |
446 | 446 | Supply of pipes | BI01010001010000000000000515BI0100001558 | ||
447 | 447 | Sch 40, B 36.10, ASTM A106 Gr B Seamless | BI01010001010000000000000515BI0100001559 | ||
448 | 448 | 25 mm dia | BI01010001010000000000000515BI0100001560 | 1 | M |
449 | 449 | 50 mm dia | BI01010001010000000000000515BI0100001561 | 1 | M |
450 | 450 | 65 mm dia | BI01010001010000000000000515BI0100001562 | 1 | M |
451 | 451 | 80 mm dia | BI01010001010000000000000515BI0100001563 | 1 | M |
452 | 452 | 100 mm dia | BI01010001010000000000000515BI0100001564 | 1 | M |
453 | 453 | 150 mm dia | BI01010001010000000000000515BI0100001565 | 1 | M |
454 | 454 | 200 mm dia | BI01010001010000000000000515BI0100001566 | 1 | M |
455 | 455 | 250 mm dia | BI01010001010000000000000515BI0100001567 | 1 | M |
456 | 456 | 300 mm dia | BI01010001010000000000000515BI0100001568 | 1 | M |
457 | 457 | 350 mm dia | BI01010001010000000000000515BI0100001569 | 1 | M |
458 | 458 | 400 mm dia | BI01010001010000000000000515BI0100001570 | 1 | M |
459 | 459 | 450 mm dia | BI01010001010000000000000515BI0100001571 | 1 | M |
460 | 460 | Supply of following Weld neck type- WNRF as per ASTM A- 105 Class 150; ANSI B 16.5 | BI01010001010000000000000515BI0100001572 | ||
461 | 461 | 25 mm dia | BI01010001010000000000000515BI0100001573 | 1 | EA |
462 | 462 | 50 mm dia | BI01010001010000000000000515BI0100001574 | 1 | EA |
463 | 463 | 80 mm dia | BI01010001010000000000000515BI0100001575 | 1 | EA |
464 | 464 | 100 mm dia | BI01010001010000000000000515BI0100001576 | 1 | EA |
465 | 465 | 150 mm dia | BI01010001010000000000000515BI0100001577 | 1 | EA |
466 | 466 | 200 mm dia | BI01010001010000000000000515BI0100001578 | 1 | EA |
467 | 467 | 250 mm dia | BI01010001010000000000000515BI0100001579 | 1 | EA |
468 | 468 | 300 mm dia | BI01010001010000000000000515BI0100001580 | 1 | EA |
469 | 469 | 350 mm dia | BI01010001010000000000000515BI0100001581 | 1 | EA |
470 | 470 | 400 mm dia | BI01010001010000000000000515BI0100001582 | 1 | EA |
471 | 471 | 450 mm dia | BI01010001010000000000000515BI0100001583 | 1 | EA |
472 | 472 | Supply of following SORF type- Material for SORF flanges to conform to ASTM A-105 class 150 ; ANSI B 16.5 | BI01010001010000000000000515BI0100001584 | ||
473 | 473 | 25 mm dia | BI01010001010000000000000515BI0100001585 | 1 | EA |
474 | 474 | 50 mm dia | BI01010001010000000000000515BI0100001586 | 1 | EA |
475 | 475 | 80 mm dia | BI01010001010000000000000515BI0100001587 | 1 | EA |
476 | 476 | 100 mm dia | BI01010001010000000000000515BI0100001588 | 1 | EA |
477 | 477 | 150 mm dia | BI01010001010000000000000515BI0100001589 | 1 | EA |
478 | 478 | 200 mm dia | BI01010001010000000000000515BI0100001590 | 1 | EA |
479 | 479 | 250 mm dia | BI01010001010000000000000515BI0100001591 | 1 | EA |
480 | 480 | 300 mm dia | BI01010001010000000000000515BI0100001592 | 1 | EA |
481 | 481 | 350 mm dia | BI01010001010000000000000515BI0100001593 | 1 | EA |
482 | 482 | 400 mm dia | BI01010001010000000000000515BI0100001594 | 1 | EA |
483 | 483 | 450 mm dia | BI01010001010000000000000515BI0100001595 | 1 | EA |
484 | 484 | Supply of following BLRF flanges As per ASTM A- 105 Class 150; ANSI B 16.5 | BI01010001010000000000000515BI0100001596 | ||
485 | 485 | 25 mm dia | BI01010001010000000000000515BI0100001597 | 1 | EA |
486 | 486 | 50 mm dia | BI01010001010000000000000515BI0100001598 | 1 | EA |
487 | 487 | 80 mm dia | BI01010001010000000000000515BI0100001599 | 1 | EA |
488 | 488 | 100 mm dia | BI01010001010000000000000515BI0100001600 | 1 | EA |
489 | 489 | 150 mm dia | BI01010001010000000000000515BI0100001601 | 1 | EA |
490 | 490 | 200 mm dia | BI01010001010000000000000515BI0100001602 | 1 | EA |
491 | 491 | 250 mm dia | BI01010001010000000000000515BI0100001603 | 1 | EA |
492 | 492 | 300 mm dia | BI01010001010000000000000515BI0100001604 | 1 | EA |
493 | 493 | 350 mm dia | BI01010001010000000000000515BI0100001605 | 1 | EA |
494 | 494 | 400 mm dia | BI01010001010000000000000515BI0100001606 | 1 | EA |
495 | 495 | 450 mm dia | BI01010001010000000000000515BI0100001607 | 1 | EA |
496 | 496 | Supply of Auto Recirculation valves as per specifications ( ASTM-A216 GR WCB) | BI01010001010000000000000515BI0100001608 | ||
497 | 497 | 80 mm dia | BI01010001010000000000000515BI0100001609 | 1 | EA |
498 | 498 | 100 mm dia | BI01010001010000000000000515BI0100001610 | 1 | EA |
499 | 499 | 150 mm dia | BI01010001010000000000000515BI0100001611 | 1 | EA |
500 | 500 | 200 mm dia | BI01010001010000000000000515BI0100001612 | 1 | EA |
501 | 501 | Supply of Thermal Relief Valves as per specifications ASTM-A216 GR WCB TRIM SS 410 | BI01010001010000000000000515BI0100001613 | ||
502 | 502 | Inlet 25 mm X Outlet 25 mm | BI01010001010000000000000515BI0100001614 | 1 | EA |
503 | 503 | Inlet 25 mm X Outlet 50 mm | BI01010001010000000000000515BI0100001615 | 1 | EA |
504 | 504 | Supply (Class-800) CS Gate Valve for pressure relief lines as per enclosed specification\nGate Vlv API 602 CL800 SWE Bltd Bonnet Handwheel Operator\nA105 Trim 8 to API 600 602 (13% Cr Hard faced Seat) OS&Y Graphite Gland Packing API 598 Solid Wedge | BI01010001010000000000000515BI0100001616 | ||
505 | 505 | 20 mm dia | BI01010001010000000000000515BI0100001617 | 1 | EA |
506 | 506 | Supply (Class-150) CS Gate Valve for pneumatic piping system: Gate Vlv MSS SP- 80 CL150 FTE Thd.Bonnet Handwheel Operator B 62 Cl.C83600 Bronze trim PTFE Gland Packing I.S.R.S. API 598 Solid Wedge | BI01010001010000000000000515BI0100001618 | ||
507 | 507 | 50 mm dia | BI01010001010000000000000515BI0100001619 | 1 | EA |
508 | 508 | 25 mm dia | BI01010001010000000000000515BI0100001620 | 1 | EA |
509 | 509 | Supply of Y type (40 mesh) strainers as per specs and drawing for the hydrant / water piping system including fire water pumps & sprinkler/foam headers for the following LPM & pipeline sizes: | BI01010001010000000000000515BI0100001621 | ||
510 | 510 | 300 mm (Y type) & flowrate 616KL/HR | BI01010001010000000000000515BI0100001622 | 1 | EA |
511 | 511 | 250 mm (Y type) & flowrate 410KL/HR | BI01010001010000000000000515BI0100001623 | 1 | EA |
512 | 512 | 150 mm (Y type) & flowrate 2400 LPM | BI01010001010000000000000515BI0100001624 | 1 | EA |
513 | 513 | 100 mm (Y type) & flowrate 1500 LPM | BI01010001010000000000000515BI0100001625 | 1 | EA |
514 | 514 | Supplying 3 Ph, 440 V NFLP type mono block motor pumpset with base frame & required accessories including heavy duty GM foot valve for the suction side of the pump etc as per specifications. Makeup Water Pump : Capacity of pump: 90 Cum/ Hr X 36 M head. | BI01010001010000000000000515BI0100001626 | 1 | EA |
515 | 515 | PIPE FITTINGS | BI01010001010000000000000515BI0100001627 | ||
516 | 516 | Supplying the following sizes of Bend/ Tees/ Reducer made of carbon steel seamless pipes with beveled ends as per enclosed specifications for the following sizes Note: The fittings shall be as per ASTM A 234 Grade WPB schedule 40 and dimensions as per ASME B 16.9 & all fitting should be forged fitting . | BI01010001010000000000000515BI0100001628 | ||
517 | 517 | Note: The quantities given are only indicative. The actual quantities to be supplied will be based on the finalized drawing for pipeline routing, as per site requirements and to be approved by the site engineer. | BI01010001010000000000000515BI0100001629 | ||
518 | 518 | 90°LR Bend (1.5D) | BI01010001010000000000000515BI0100001630 | ||
519 | 519 | 25 mm dia | BI01010001010000000000000515BI0100001631 | 1 | EA |
520 | 520 | 50 mm dia | BI01010001010000000000000515BI0100001632 | 1 | EA |
521 | 521 | 80 mm dia | BI01010001010000000000000515BI0100001633 | 1 | EA |
522 | 522 | 100mm dia | BI01010001010000000000000515BI0100001634 | 1 | EA |
523 | 523 | 150 mm dia | BI01010001010000000000000515BI0100001635 | 1 | EA |
524 | 524 | 200 mm dia | BI01010001010000000000000515BI0100001636 | 1 | EA |
525 | 525 | 250 mm dia | BI01010001010000000000000515BI0100001637 | 1 | EA |
526 | 526 | 300 mm dia | BI01010001010000000000000515BI0100001638 | 1 | EA |
527 | 527 | 350 mm dia | BI01010001010000000000000515BI0100001639 | 1 | EA |
528 | 528 | 400 mm dia | BI01010001010000000000000515BI0100001640 | 1 | EA |
529 | 529 | 450 mm dia | BI01010001010000000000000515BI0100001641 | 1 | EA |
530 | 530 | 45°LR Bend (1.5D) | BI01010001010000000000000515BI0100001642 | ||
531 | 531 | 25 mm dia | BI01010001010000000000000515BI0100001643 | 1 | EA |
532 | 532 | 50 mm dia | BI01010001010000000000000515BI0100001644 | 1 | EA |
533 | 533 | 80 mm dia | BI01010001010000000000000515BI0100001645 | 1 | EA |
534 | 534 | 100mm dia | BI01010001010000000000000515BI0100001646 | 1 | EA |
535 | 535 | 150 mm dia | BI01010001010000000000000515BI0100001647 | 1 | EA |
536 | 536 | 200 mm dia | BI01010001010000000000000515BI0100001648 | 1 | EA |
537 | 537 | 250 mm dia | BI01010001010000000000000515BI0100001649 | 1 | EA |
538 | 538 | 300 mm dia | BI01010001010000000000000515BI0100001650 | 1 | EA |
539 | 539 | 350 mm dia | BI01010001010000000000000515BI0100001651 | 1 | EA |
540 | 540 | 400 mm dia | BI01010001010000000000000515BI0100001652 | 1 | EA |
541 | 541 | 450 mm dia | BI01010001010000000000000515BI0100001653 | 1 | EA |
542 | 542 | Equal Tee | BI01010001010000000000000515BI0100001654 | ||
543 | 543 | 25 x 25 x 25 mm | BI01010001010000000000000515BI0100001655 | 1 | EA |
544 | 544 | 50 x 50 X 50 mm | BI01010001010000000000000515BI0100001656 | 1 | EA |
545 | 545 | 80 X 80 X 80 mm | BI01010001010000000000000515BI0100001657 | 1 | EA |
546 | 546 | 100 X 100 X 100 mm | BI01010001010000000000000515BI0100001658 | 1 | EA |
547 | 547 | 150 X 150 X 150 mm | BI01010001010000000000000515BI0100001659 | 1 | EA |
548 | 548 | 200 X 200 X 200 mm | BI01010001010000000000000515BI0100001660 | 1 | EA |
549 | 549 | 250 X 250 X 250 mm | BI01010001010000000000000515BI0100001661 | 1 | EA |
550 | 550 | 300 X 300 X 300 mm | BI01010001010000000000000515BI0100001662 | 1 | EA |
551 | 551 | 400 X 400 X 400 mm | BI01010001010000000000000515BI0100001663 | 1 | EA |
552 | 552 | UNEQUAL TEE | BI01010001010000000000000515BI0100001664 | ||
553 | 553 | 200 x 200 x 100 mm | BI01010001010000000000000515BI0100001665 | 1 | EA |
554 | 554 | 200 x 200 x 80 mm | BI01010001010000000000000515BI0100001666 | 1 | EA |
555 | 555 | 150 x 150 x 100 mm | BI01010001010000000000000515BI0100001667 | 1 | EA |
556 | 556 | 150 x 150 x 80 mm | BI01010001010000000000000515BI0100001668 | 1 | EA |
557 | 557 | 100 x 100 x 80 mm | BI01010001010000000000000515BI0100001669 | 1 | EA |
558 | 558 | 200 X 200 X150 mm | BI01010001010000000000000515BI0100001670 | 1 | EA |
559 | 559 | 250 X 250 X 100 mm | BI01010001010000000000000515BI0100001671 | 1 | EA |
560 | 560 | 250 X 250 X 150 mm | BI01010001010000000000000515BI0100001672 | 1 | EA |
561 | 561 | 300 x 300 x 100 mm | BI01010001010000000000000515BI0100001673 | 1 | EA |
562 | 562 | 300 X 300 X 150 mm | BI01010001010000000000000515BI0100001674 | 1 | EA |
563 | 563 | 300 X 300 X 200 mm | BI01010001010000000000000515BI0100001675 | 1 | EA |
564 | 564 | 300 X 300 X 250 mm | BI01010001010000000000000515BI0100001676 | 1 | EA |
565 | 565 | 350 X 350 X 300 mm | BI01010001010000000000000515BI0100001677 | 1 | EA |
566 | 566 | 400 x 400 X 300 mm | BI01010001010000000000000515BI0100001678 | 1 | EA |
567 | 567 | 450 X 450 X 150 mm | BI01010001010000000000000515BI0100001679 | 1 | EA |
568 | 568 | 450 X 450 X 250 mm | BI01010001010000000000000515BI0100001680 | 1 | EA |
569 | 569 | 450 X 450 X 300 mm | BI01010001010000000000000515BI0100001681 | 1 | EA |
570 | 570 | Reducers (Concentric/ Eccentric) | BI01010001010000000000000515BI0100001682 | ||
571 | 571 | Reducers (Concentric) | BI01010001010000000000000515BI0100001683 | ||
572 | 572 | 250 X 150 mm | BI01010001010000000000000515BI0100001684 | 1 | EA |
573 | 573 | 150 X 100 mm | BI01010001010000000000000515BI0100001685 | 1 | EA |
574 | 574 | 150 X 80 mm | BI01010001010000000000000515BI0100001686 | 1 | EA |
575 | 575 | 100 X 80 mm | BI01010001010000000000000515BI0100001687 | 1 | EA |
576 | 576 | Reducers (Eccentric) | BI01010001010000000000000515BI0100001688 | ||
577 | 577 | 350 X 250 mm | BI01010001010000000000000515BI0100001689 | 1 | EA |
578 | 578 | 250 X 200 mm | BI01010001010000000000000515BI0100001690 | 1 | EA |
579 | 579 | 250 X 150 mm | BI01010001010000000000000515BI0100001691 | 1 | EA |
580 | 580 | 150 X 100 mm | BI01010001010000000000000515BI0100001692 | 1 | EA |
581 | 581 | 150 X 100 mm | BI01010001010000000000000515BI0100001693 | 1 | EA |
582 | 582 | 100 X 80 mm | BI01010001010000000000000515BI0100001694 | 1 | EA |
583 | 583 | 300 X 200 mm (ECCEN) | BI01010001010000000000000515BI0100001695 | 1 | EA |
584 | 584 | 250 X 200mm (CONC) | BI01010001010000000000000515BI0100001696 | 1 | EA |
585 | 585 | 300 X 200 mm (CONC) | BI01010001010000000000000515BI0100001697 | 1 | EA |
586 | 586 | 300 x 150mm (CONC) | BI01010001010000000000000515BI0100001698 | 1 | EA |
587 | 587 | Supplying the following sizes of CS Gate Valves (flanged) as per Specification | BI01010001010000000000000515BI0100001699 | ||
588 | 588 | 20 mm dia | BI01010001010000000000000515BI0100001700 | 1 | EA |
589 | 589 | 25 mm dia | BI01010001010000000000000515BI0100001701 | 1 | EA |
590 | 590 | 50 mm dia | BI01010001010000000000000515BI0100001702 | 1 | EA |
591 | 591 | 80 mm dia | BI01010001010000000000000515BI0100001703 | 1 | EA |
592 | 592 | 100mm dia | BI01010001010000000000000515BI0100001704 | 1 | EA |
593 | 593 | 150 mm dia | BI01010001010000000000000515BI0100001705 | 1 | EA |
594 | 594 | 200 mm dia | BI01010001010000000000000515BI0100001706 | 1 | EA |
595 | 595 | Supplying the following sizes of Check Valves (flanged) as per Specification | BI01010001010000000000000515BI0100001707 | ||
596 | 596 | 150 mm dia | BI01010001010000000000000515BI0100001708 | 1 | EA |
597 | 597 | 250 mm dia | BI01010001010000000000000515BI0100001709 | 1 | EA |
598 | 598 | 300 mm dia | BI01010001010000000000000515BI0100001710 | 1 | EA |
599 | 599 | Supplying the following sizes of Check\nValves (flanged) as perSpecification | BI01010001010000000000000515BI0100001711 | ||
600 | 600 | 25 mm dia | BI01010001010000000000000515BI0100001712 | 1 | EA |
601 | 601 | 50 mm dia | BI01010001010000000000000515BI0100001713 | 1 | EA |
602 | 602 | 80 mm dia | BI01010001010000000000000515BI0100001714 | 1 | EA |
603 | 603 | Making , supply and Fixing of GI Groove\ncoupling | BI01010001010000000000000515BI0100001715 | ||
604 | 604 | 100 mm Dia | BI01010001010000000000000515BI0100001716 | 1 | EA |
605 | 605 | 80 mm Dia | BI01010001010000000000000515BI0100001717 | 1 | EA |
606 | 606 | 65 mm Dia | BI01010001010000000000000515BI0100001718 | 1 | EA |
607 | 607 | Design, fabrication, supply to site,\nerection, testing and commissioningof\nFoam Concentrate Tank & associated\nsystem comprising of thefollowing; | BI01010001010000000000000515BI0100001719 | ||
608 | 608 | a) Foam concentrate tank in 3 mm thk, SS 304 with cover and lockingarrangement, vent pipe, fill pipe, level indicator with suitabletransparent PVC tubing and control valves (2 no, 3/4 "" SS SW valve)b) 2 nos, 20/ 25/ 32 mm dia outlets as per design for connections to beestablished to inductors at tanks along with providing and fixing 2 no SSSW valves.c) Drain line with 1 no, 20/25 mm dia valve as per design.d) Piping in SS 304 (3 mm thk) from tank to the inductor to be fitted onthe main fire hydrant line. This pipe shall be taken as 25 mm dia and total length upto 10 RM.e) MS structural staging for mounting the foam concentrate tank withsuitable approach for filling/draining the foam and for operating the tank for FF purpose.f) Shed/ cover for the entire foam concentrate tank and its fittings inMS structurals with asbestos sheet top.g) MS structural support shall be painted as per IOC painting scheme | BI01010001010000000000000515BI0100001720 | ||
609 | 609 | Note: a) All valves on the tank shall\nbe of SS 304 ball valves and offire\nsafe quality & flanged ends.b) The\ncontractor shall submit the detailed\ndesign & fabricationdrawings along with\nBill of materials (BOM) and get the\nsame approved byIOC, before procurement\nof materials and execution of the above\nwork.c) Foam concentrate solution shall\nbe supplied by IOCL. " | BI01010001010000000000000515BI0100001721 | ||
610 | 610 | Stainless Steel (SS 304) Tank - 1500 Lts | BI01010001010000000000000515BI0100001722 | 1 | EA |
611 | 611 | Stainless Steel (SS 304) Tank - 2000 Lts | BI01010001010000000000000515BI0100001723 | 1 | EA |
612 | 612 | Stainless Steel (SS 304) Tank - 3000 Lts | BI01010001010000000000000515BI0100001724 | 1 | EA |
613 | 613 | FABRICATION & ERECTION WORKS | BI01010001010000000000000515BI0100001725 | ||
614 | 614 | Providing and fixing double rows scaffolding system up to required height made with 40 mm dia NB M.S. tube, , M.S. tube challies, M.S. clamps including M.S. staircase system in the scaffolding and working platform as required etc., complete as per drawing & specification and maintaining it in a serviceable condition for the required duration and removing it there after (all materials belongs to Contractor). | BI01010001010000000000000515BI0100001726 | ||
615 | 615 | The scaffolding system shall be stiffened with bracings, runners, connection with the tank etc., wherever required for inspection of work at required locations with essential safety features for the workmen as per directions and approval of Engineering-charge. | BI01010001010000000000000515BI0100001727 | ||
616 | 616 | Note: a) Scaffolding should be retained till the completion of hydro-stat test/ calibration/ painting as per requirement. | BI01010001010000000000000515BI0100001728 | ||
617 | 617 | b) For External Scaffolding -Payments shall be made for actual area of scaffolding provided based on requirement. Area of scaffolding will be measured on the basis of actual height of scaffolding provided multiplied by actual average length/circumference of scaffolding provided. | BI01010001010000000000000515BI0100001729 | ||
618 | 618 | c) For tank Internal scaffolding- payment will be made on the basis of covered shell area & roof area of the tank. | BI01010001010000000000000515BI0100001730 | ||
619 | 619 | For vertical tanks | BI01010001010000000000000515BI0100001731 | 1 | M2 |
620 | 620 | Providing and fixing Hydraulic Jacking System including positioing the same on the bottom plate without any damage, necessary supports with MS structural/ Pipes, gazzet plates etc., complete as per standards/ instructions and maintaining it in a serviceable condition for the required duration and removing it there after (all materials belongs to Contractor). | BI01010001010000000000000515BI0100001732 | ||
621 | 621 | Note: a) Hydraulic Jacking System should be retained till the replacement of shell/ bottom plates works are completed as per requirement. | BI01010001010000000000000515BI0100001733 | ||
622 | 622 | b) The payment for the Jacking System (external/ internal) will be made on the basis of perimeter of shell of the tank. | BI01010001010000000000000515BI0100001734 | ||
623 | 623 | For vertical tanks - inside | BI01010001010000000000000515BI0100001735 | 1 | M |
624 | 624 | For vertical tanks - outside the tanks with MS structural supports. | BI01010001010000000000000515BI0100001736 | 1 | M |
625 | 625 | Fabricating, erecting, welding, testing and commissioning SHELL/ BOTTOM/ ROOF plates for vertical tanks as per the approved design, specifications and B&R drawings with required steel plates supplied by IOC. All other items such as labour, equipment, power, consumables etc., shall be supplied by contractor. All leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001737 | ||
626 | 626 | Note : a) IOCL shall supply steel plates only for bottom, shell, double deck roof, wind girders and reinforcement plates of shell appurtenances. | BI01010001010000000000000515BI0100001738 | ||
627 | 627 | b) Item rate should include shifting of steel plates within the premises and conducting various tests on tanks during fabrication as per attached TESTING PROCEDURE. Item includes Radiographic Inspection of welds as per attached RADIOGRAPHIC INSPECTION PROCEDURE. | BI01010001010000000000000515BI0100001739 | ||
628 | 628 | Shell/ bottom/ Roof/ deck plates - without jacking system | BI01010001010000000000000515BI0100001740 | 1 | TON |
629 | 629 | Shell plates - with jacking system | BI01010001010000000000000515BI0100001741 | 1 | TON |
630 | 630 | Supplying and providing steps for spiral staircase including supplying & fabricating MS gratings, pad plate, supports, handrail, testing as per as per B&R drgs. No. BR/CR/233 & BR/CR/234, painting the same (external paiting system of tank), all leads & lifts etc., complete in all respects as per instructions at site. | BI01010001010000000000000515BI0100001742 | ||
631 | 631 | MS grating steps for spiral staircase | BI01010001010000000000000515BI0100001743 | 1 | EA |
632 | 632 | Supplying and filling with water for conducting hydro test/ floatation test and checking the leaks including supply of water, conveying pipes, water pump, all the material and labour as required etc., complete as directed at site. | BI01010001010000000000000515BI0100001744 | ||
633 | 633 | Note: a) Water shall be removed after completion of hydrostatic testing of tanks & emptied from the tank including cleaning of the bottom plate & sump and boxing up of the tank before water filling and removal of manholes covers after testing with necessary supply of bolts, studs/ nuts/ gaskets etc., to ensure leak proof. | BI01010001010000000000000515BI0100001745 | ||
634 | 634 | b) Water is to be filled till full height of tank. Payment will be made for total quantity of water mathematically or arithmetically calculated, as per size of tank. | BI01010001010000000000000515BI0100001746 | ||
635 | 635 | For vertical tanks - all capacities | BI01010001010000000000000515BI0100001747 | 1 | KL |
636 | 636 | Carrying out hydro test of tanks EXCLUDING supply of water. \nWater conveying pipes, water pumps, all material and labour, as required shall be arranged by the contractor Including providing rubber gasket for hydro testing. WATER shall be provided by IOCL within terminal premises. However the vendor shall make all necessary arrangements to pump the water into tank & to drain out the water also at no extra cost to IOCL. | BI01010001010000000000000515BI0100001748 | ||
637 | 637 | For vertical tanks - all capacities | BI01010001010000000000000515BI0100001749 | 1 | KL |
638 | 638 | Calibration of tanks- Bottom calibration with actual physical measurement by water meter & tank shell by strapping periphery of different strakes above and below the horizontal weld joints (or) by using optical ranging method. Item includes cost towards statutory payment to be made to the authorities and all other incidental costs. Item includes preparation & submission of calibration charts in quadruplicate duly approved by the tank calibration authority. Water required for the calibration shall be arranged by the successful tenderer at his own cost. | BI01010001010000000000000515BI0100001750 | ||
639 | 639 | Upto 10 M dia vertical tank | BI01010001010000000000000515BI0100001751 | 1 | SET |
640 | 640 | 10 M to 16 M dia vertical tank | BI01010001010000000000000515BI0100001752 | 1 | SET |
641 | 641 | 18 M to 24 M dia vertical tank | BI01010001010000000000000515BI0100001753 | 1 | SET |
642 | 642 | 20 M to 32 M dia vertical tank | BI01010001010000000000000515BI0100001754 | 1 | SET |
643 | 643 | 32 M to 40 M dia vertical tank | BI01010001010000000000000515BI0100001755 | 1 | SET |
644 | 644 | Boxing up of the tank after completion of all works and inspection including supplying, fixing 3 mm CAF 9 gaskets of approved make as per IS 2712 - 1979 with new sets of bolts, studs & nuts confirming to IS 1363 & 1367 and washers of approved quality. Job includes for all manholes, nozzles, inlet/outlet valves. water draw off valves etc., complete to ensure leak proof as per instruction at site. | BI01010001010000000000000515BI0100001756 | ||
645 | 645 | For vertical tanks | BI01010001010000000000000515BI0100001757 | 1 | SET |
646 | 646 | Supplying and providing temporary screen wall as per site requirements using MS section frame work and GI sheets for carrying out the hot work within the licensed premises. The screen wall will be dismantled and taken out after completion of works & shall remain contractor's property. | BI01010001010000000000000515BI0100001758 | ||
647 | 647 | Note: a) The contractor shall submit the details of design & drawings of the screen wall to be erected at site & approved prior commencement of work. | BI01010001010000000000000515BI0100001759 | ||
648 | 648 | b) The screen wall shall be in position at all time, stable & strong till the completion of work in all respects. | BI01010001010000000000000515BI0100001760 | ||
649 | 649 | i) Fixed | BI01010001010000000000000515BI0100001761 | 1 | M2 |
650 | 650 | ii) Mobile with wheels (or) movable | BI01010001010000000000000515BI0100001762 | 1 | M2 |
651 | 651 | Supplying and providing temporary screen wall as per site requirements using the available scaffolding structure and GI sheets with required fastners for carrying out the hot work within the licensed premises. The screen wall will be dismantled and taken out after completion of works & shall remain contractor's property. | BI01010001010000000000000515BI0100001763 | 1 | M2 |
652 | 652 | DRAWINGS:\nSubmission of detailed design/ fabrication drawings for the different size of tanks for approval of IOCL. Item includes submission of as built drawings (4 sets) including submission of drawings on a CD after completion of tank fabrication work as per enclosed specifications. Note: The drawings should be made in reference to the attached directional drawings and as per requirement of IS 803 & API 650. | BI01010001010000000000000515BI0100001764 | 1 | EA |
653 | 653 | RE-PAINTING WORKS | BI01010001010000000000000515BI0100001765 | ||
654 | 654 | Removal of existing internal paint including primer completely by grit blasting to SA 2 1/2. Scaffolding if required will be paid separately. | BI01010001010000000000000515BI0100001766 | 1 | M2 |
655 | 655 | UNDERSIDE OF TANK BOTTOM PLATE : ZONE-A & ZONE-B : FIRST TIME PAINTING\nApplicable for NEW CR/IFR/FR PRODUCT & WATER tank\n1. Surface Preparation as per SA 2½\n2. Primer : P1-Inorganic Zinc Ethyl Silicate : Single Coat: DFT- 65-75µ\n3. Finish Coat : F3-Amine Adduct cured HB Epoxy Liner : Two coats : DFT- 100-125µ per coat\nTotal Min DFT 265µ | BI01010001010000000000000515BI0100001767 | 1 | M2 |
656 | 656 | RE-PAINTING OF TANKS: (including all material/ labour) Surface preparation and painting of the following tanks as per details of painting specification given under and the Techno-Commercial bid; Note: Application for External/ Internal painting for tanks shall be carried out by means of AIRLESS SPRAY PAINTING SYSTEM only. | BI01010001010000000000000515BI0100001768 | ||
657 | 657 | Surface preparation by cleaning & painting the outside surface of tank shell upto & including curb angle, upper side surface of roof, wind girders, roof, stairs and shell appurtenances of CONE/ FLOATING ROOF tanks including all fittings and appurtenances etc., providing IOC logo with tank writing work as per enclosed specifications and drawings. | BI01010001010000000000000515BI0100001769 | ||
658 | 658 | Note : Area to be painted & type of paint shall be as per IOC Painting scheme given in the tender. Finish paint colour shall be as per requirement of white oil or black oil tanks. | BI01010001010000000000000515BI0100001770 | ||
659 | 659 | NEW CONSTRUCTION- PAINTING EXTERNAL SURFACES: (including all material/ labour); | BI01010001010000000000000515BI0100001771 | ||
660 | 660 | PRODUCT TANKS - HSD/ SKO/ ATF/ MS/ NAPHTHA/ FO/ LDO/ WATER | BI01010001010000000000000515BI0100001772 | ||
661 | 661 | For ZONE A (Corrosive Zone) - External Surface of un-insulated equipment including storage tanks (product & water services - shell & roof top), piping & structures (upto 120 deg C) | BI01010001010000000000000515BI0100001773 | 1 | M2 |
662 | 662 | Surface Preparation : Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001774 | ||
663 | 663 | Primer : Inorganic Zinc Ethyl Silicate (P1) with DFT in the range of 65-75 micron. | BI01010001010000000000000515BI0100001775 | ||
664 | 664 | Intermediate Coat : Polyamide cured HB Epoxy MIO (U1) with DFT in the range of 100 -125 micron. | BI01010001010000000000000515BI0100001776 | ||
665 | 665 | Finish Coat : Two Pack Acrylic Poly-urethane(PU) (F1) with DFT in the range of 40-50 micron. | BI01010001010000000000000515BI0100001777 | ||
666 | 666 | TOTAL min DFT 215 microns | BI01010001010000000000000515BI0100001778 | ||
667 | 667 | For ZONE B (Non-Corrosive Zone) - External Surface of un-insulated equipment including storage tanks (product & water services - shell & roof top), piping & structures (upto 120 deg C) | BI01010001010000000000000515BI0100001779 | 1 | M2 |
668 | 668 | Surface Preparation : Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001780 | ||
669 | 669 | Primer : Red Oxide Zinc Phosphate Primer (P3) with 2 coats of DFT in the range of 30-35 micron. | BI01010001010000000000000515BI0100001781 | ||
670 | 670 | Finish Coat : Aluminium Finish Paint (F2) with 2 coats of DFT in the range of 15-20 micron. | BI01010001010000000000000515BI0100001782 | ||
671 | 671 | TOTAL min DFT 90 microns | BI01010001010000000000000515BI0100001783 | ||
672 | 672 | RE-PAINTING EXTERNAL SURFACES: (including all material/ labour); | BI01010001010000000000000515BI0100001784 | ||
673 | 673 | PRODUCT TANKS - HSD/ SKO/ ATF/ MS/ NAPHTHA/ FO/ LDO/ WATER | BI01010001010000000000000515BI0100001785 | ||
674 | 674 | For ZONE A & B- External Surface of buried tanks/ piping. Underside of tank and external surface of buried vessels/ tanks / piping. | BI01010001010000000000000515BI0100001786 | 1 | M2 |
675 | 675 | Surface Preparation : Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001787 | ||
676 | 676 | Primer : Inorganic Zinc Ethyl Silicate (P1) with DFT in the range of 65-75 micron. | BI01010001010000000000000515BI0100001788 | ||
677 | 677 | Finish Coat : Amine Adduct Cured HB epoxy liner (F3) with 2 coats of DFT in the range of 100-125 micron. | BI01010001010000000000000515BI0100001789 | ||
678 | 678 | TOTAL min DFT 265 microns | BI01010001010000000000000515BI0100001790 | ||
679 | 679 | For ZONE A (Corrosive Zone) - External Surface of un-insulated equipment including storage tanks (product & water services - shell & roof top), piping & structures (upto 120 deg C) | BI01010001010000000000000515BI0100001791 | 1 | M2 |
680 | 680 | Surface Preparation : i) SSPC SP2 - Hand Cleaning / Wire brush or ii) SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001792 | ||
681 | 681 | Primer : Self Priming HB Epoxy mastic Coating (P4) with DFT in the range of 100 -125 micron. | BI01010001010000000000000515BI0100001793 | ||
682 | 682 | Intermediate Coat : Polyamide cured HB Epoxy MIO (U1) with DFT in the range of 100 -125 micron. | BI01010001010000000000000515BI0100001794 | ||
683 | 683 | Finish Coat : Two Pack Acrylic Poly-urethane(PU) (F1) with DFT in the range of 40-50 micron. | BI01010001010000000000000515BI0100001795 | ||
684 | 684 | TOTAL min DFT 240 microns | BI01010001010000000000000515BI0100001796 | ||
685 | 685 | For ZONE B (Non Corrosive Zone) - External Surface of un-insulated equipment including storage tanks (product & water services - shell & roof top), piping & structures (upto 120 deg C) | BI01010001010000000000000515BI0100001797 | 1 | M2 |
686 | 686 | Surface Preparation : i) SSPC SP2 - Hand Cleaning / Wire brush or ii) SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001798 | ||
687 | 687 | Primer : Red Oxide Zinc Phosphate Primer (P3) with DFT in the range of 30-35 micron. | BI01010001010000000000000515BI0100001799 | ||
688 | 688 | Finish Coat : Aluminium Finish Paint (F2) with 2 coats of DFT in the range of 15-20 micron. | BI01010001010000000000000515BI0100001800 | ||
689 | 689 | TOTAL min DFT 60 microns | BI01010001010000000000000515BI0100001801 | ||
690 | 690 | INTERNAL SURFACES: (including all material/ labour); | BI01010001010000000000000515BI0100001802 | ||
691 | 691 | PRODUCT TANKS - HSD/ SKO/ ATF/ MS/ NAPHTHA/ FO/ LDO & WATER | BI01010001010000000000000515BI0100001803 | ||
692 | 692 | For ZONE A & B-Internal Surface of tanks in Hydrocarbon service except ATF (In case of full painting/repainting) | BI01010001010000000000000515BI0100001804 | 1 | M2 |
693 | 693 | Surface Preparation :Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001805 | ||
694 | 694 | Primer : Inorganic Zinc Ethyl Silicate (P1) with DFT in the range of 65-75 micron. | BI01010001010000000000000515BI0100001806 | ||
695 | 695 | Intermediate Coat : Epoxy Zinc Phophate (P5) with DFT in the range of 35-40 micron. | BI01010001010000000000000515BI0100001807 | ||
696 | 696 | Finish Coat : Amine Adduct Cured HB epoxy liner (F3) with 2 coats of DFT in the range of 100-125 micron. | BI01010001010000000000000515BI0100001808 | ||
697 | 697 | TOTAL min DFT 300 microns | BI01010001010000000000000515BI0100001809 | ||
698 | 698 | For ZONE A & B-Internal Surface of tanks in ATF service (In case of full painting/repainting) | BI01010001010000000000000515BI0100001810 | 1 | M2 |
699 | 699 | Surface Preparation :Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001811 | ||
700 | 700 | Primer : Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron. | BI01010001010000000000000515BI0100001812 | ||
701 | 701 | Intermediate Coat : Epoxy Zinc Phophate (P5) with DFT in the range of 35-40 micron. | BI01010001010000000000000515BI0100001813 | ||
702 | 702 | Finish Coat : Amine Adduct Cured HB epoxy liner (F3) with 2 coats of DFT in the range of 100-125 micron. | BI01010001010000000000000515BI0100001814 | ||
703 | 703 | TOTAL min DFT 305 microns | BI01010001010000000000000515BI0100001815 | ||
704 | 704 | For ZONE A & B-Internal Surface of tanks in water (Fire water, Industrial water) in case of full painting/repainting. | BI01010001010000000000000515BI0100001816 | 1 | M2 |
705 | 705 | Surface Preparation : Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001817 | ||
706 | 706 | Primer : Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron. | BI01010001010000000000000515BI0100001818 | ||
707 | 707 | Finish Coat : Solvent less HB epoxy liner (F4) with 2 coats of DFT 250 micron each. | BI01010001010000000000000515BI0100001819 | ||
708 | 708 | TOTAL min DFT 575 microns | BI01010001010000000000000515BI0100001820 | ||
709 | 709 | For ZONE A & B-Internal Surface of Pontoon of floating roof tanks | BI01010001010000000000000515BI0100001821 | 1 | M2 |
710 | 710 | Surface Preparation : i) SSPC SP2 - Hand Cleaning / Wire brush or ii) SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001822 | ||
711 | 711 | Primer : Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron. | BI01010001010000000000000515BI0100001823 | ||
712 | 712 | TOTAL min DFT 70 microns | BI01010001010000000000000515BI0100001824 | ||
713 | 713 | For ZONE A & B-Internal Surface of tanks in Hydrocarbon service including tanks on ATF service ( in case of patch / touch-up painting) | BI01010001010000000000000515BI0100001825 | 1 | M2 |
714 | 714 | Surface Preparation : SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001826 | ||
715 | 715 | Primer : Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron. | BI01010001010000000000000515BI0100001827 | ||
716 | 716 | Finish Coat : Amine Adduct Cured HB epoxy liner (F3) with 2 coats of DFT in the range of 100-125 micron. | BI01010001010000000000000515BI0100001828 | ||
717 | 717 | TOTAL min DFT 270 microns | BI01010001010000000000000515BI0100001829 | ||
718 | 718 | For ZONE A & B-Internal Surface of tanks in water (Fire water, Industrial water) service requiring patch/ touch up painting. | BI01010001010000000000000515BI0100001830 | 1 | M2 |
719 | 719 | Surface Preparation : SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001831 | ||
720 | 720 | Primer : Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron. | BI01010001010000000000000515BI0100001832 | ||
721 | 721 | Finish Coat : Solvent less HB epoxy liner (F4) with 2 coats of DFT 250 micron each. | BI01010001010000000000000515BI0100001833 | ||
722 | 722 | TOTAL min DFT 575 microns | BI01010001010000000000000515BI0100001834 | ||
723 | 723 | For ZONE A & B-Internal Surface of tanks in water (Fire water, Industrial water) service requiring patch/ touch up painting (In case the water tank is presently painted with Coal Tar Epoxy paint) | BI01010001010000000000000515BI0100001835 | 1 | M2 |
724 | 724 | Surface Preparation : SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001836 | ||
725 | 725 | Finish Coat :Two coats of Coal Tar Epoxy (150 microns) | BI01010001010000000000000515BI0100001837 | ||
726 | 726 | TOTAL min DFT 300 microns | BI01010001010000000000000515BI0100001838 | ||
727 | 727 | For ZONE A & B-Internal Surface of tanks in Hydrocarbon service except ATF (In case of only blasting and application of Primer) | BI01010001010000000000000515BI0100001839 | 1 | M2 |
728 | 728 | Surface Preparation :Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001840 | ||
729 | 729 | Primer : Inorganic Zinc Ethyl Silicate (P1) with DFT in the range of 65-75 micron. | BI01010001010000000000000515BI0100001841 | ||
730 | 730 | TOTAL min DFT 65 microns | BI01010001010000000000000515BI0100001842 | ||
731 | 731 | For ZONE A & B-Internal Surface of tanks in ATF/WATER service (In case of only blasting and application of Primer) | BI01010001010000000000000515BI0100001843 | 1 | M2 |
732 | 732 | Surface Preparation :Blast clean to SA 2 1/2 | BI01010001010000000000000515BI0100001844 | ||
733 | 733 | Primer : Polyamide cured epoxy zinc phosphate primer (P2) with DFT in the range of 70-75 micron. | BI01010001010000000000000515BI0100001845 | ||
734 | 734 | TOTAL min DFT 70 microns | BI01010001010000000000000515BI0100001846 | ||
735 | 735 | RE-PAINTING OF PIPELINES: | BI01010001010000000000000515BI0100001847 | ||
736 | 736 | Pipeline (AG) of all Product/ Water & its fittings including colour coding as required for Zone A locations. | BI01010001010000000000000515BI0100001848 | ||
737 | 737 | Surface Preparation : i) SSPC SP2 - Hand Cleaning / Wire brush or ii) SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001849 | ||
738 | 738 | Primer : Self Priming HB Epoxy mastic Coating (P4) with DFT in the range of 100 -125 micron. | BI01010001010000000000000515BI0100001850 | ||
739 | 739 | Intermediate Coat : Polyamide cured HB Epoxy MIO (U1) with DFT in the range of 100 -125 micron. | BI01010001010000000000000515BI0100001851 | ||
740 | 740 | Finish Coat : Two Pack Acrylic Poly-urethane(PU) (F1) with DFT in the range of 40-50 micron. | BI01010001010000000000000515BI0100001852 | ||
741 | 741 | TOTAL min DFT 240 microns | BI01010001010000000000000515BI0100001853 | ||
742 | 742 | 50 / 65 mm dia | BI01010001010000000000000515BI0100001854 | 1 | M |
743 | 743 | 80 mm dia | BI01010001010000000000000515BI0100001855 | 1 | M |
744 | 744 | 100 mm dia | BI01010001010000000000000515BI0100001856 | 1 | M |
745 | 745 | 150 mm dia | BI01010001010000000000000515BI0100001857 | 1 | M |
746 | 746 | 200 mm dia | BI01010001010000000000000515BI0100001858 | 1 | M |
747 | 747 | 250 mm dia | BI01010001010000000000000515BI0100001859 | 1 | M |
748 | 748 | 300 mm dia | BI01010001010000000000000515BI0100001860 | 1 | M |
749 | 749 | 350 mm dia | BI01010001010000000000000515BI0100001861 | 1 | M |
750 | 750 | 400 mm dia | BI01010001010000000000000515BI0100001862 | 1 | M |
751 | 751 | 450 mm dia | BI01010001010000000000000515BI0100001863 | 1 | M |
752 | 752 | 500 mm dia | BI01010001010000000000000515BI0100001864 | 1 | M |
753 | 753 | 550 mm dia | BI01010001010000000000000515BI0100001865 | 1 | M |
754 | 754 | 600 mm dia | BI01010001010000000000000515BI0100001866 | 1 | M |
755 | 755 | 650 mm dia | BI01010001010000000000000515BI0100001867 | 1 | M |
756 | 756 | 700 mm dia | BI01010001010000000000000515BI0100001868 | 1 | M |
757 | 757 | Pipeline (AG) of all Product/ Water & its fittings including colour coding as required for Zone B locations. | BI01010001010000000000000515BI0100001869 | ||
758 | 758 | Surface Preparation : i) SSPC SP2 - Hand Cleaning / Wire brush or ii) SSPC SP-3 - Power Tool Cleaning | BI01010001010000000000000515BI0100001870 | ||
759 | 759 | Primer : Red Oxide Zinc Phosphate Primer (P3) with DFT in the range of 30-35 micron. | BI01010001010000000000000515BI0100001871 | ||
760 | 760 | Finish Coat : For all product piplines Aluminium Finish Paint (F2) with 2 coats of DFT in the range of 15-20 micron. For Fire lines Synthetic Enamel (F6) 2 coats of DFT in the range of 15-20 micron. | BI01010001010000000000000515BI0100001872 | ||
761 | 761 | TOTAL min DFT 60 microns | BI01010001010000000000000515BI0100001873 | ||
762 | 762 | 50 / 65 mm dia | BI01010001010000000000000515BI0100001874 | 1 | M |
763 | 763 | 80 mm dia | BI01010001010000000000000515BI0100001875 | 1 | M |
764 | 764 | 100 mm dia | BI01010001010000000000000515BI0100001876 | 1 | M |
765 | 765 | 150 mm dia | BI01010001010000000000000515BI0100001877 | 1 | M |
766 | 766 | 200 mm dia | BI01010001010000000000000515BI0100001878 | 1 | M |
767 | 767 | 250 mm dia | BI01010001010000000000000515BI0100001879 | 1 | M |
768 | 768 | 300 mm dia | BI01010001010000000000000515BI0100001880 | 1 | M |
769 | 769 | 350 mm dia | BI01010001010000000000000515BI0100001881 | 1 | M |
770 | 770 | 400 mm dia | BI01010001010000000000000515BI0100001882 | 1 | M |
771 | 771 | 450 mm dia | BI01010001010000000000000515BI0100001883 | 1 | M |
772 | 772 | 500 mm dia | BI01010001010000000000000515BI0100001884 | 1 | M |
773 | 773 | 550 mm dia | BI01010001010000000000000515BI0100001885 | 1 | M |
774 | 774 | 600 mm dia | BI01010001010000000000000515BI0100001886 | 1 | M |
775 | 775 | 650 mm dia | BI01010001010000000000000515BI0100001887 | 1 | M |
776 | 776 | 700 mm dia | BI01010001010000000000000515BI0100001888 | 1 | M |
777 | 777 | Pipeline (UG) of all Product/ Water & its fittings | BI01010001010000000000000515BI0100001889 | ||
778 | 778 | Clean to SSPC SP 2 hand cleaning wire brushing. | BI01010001010000000000000515BI0100001890 | ||
779 | 779 | Coating/ Wrapping tape as per specification in the tender. | BI01010001010000000000000515BI0100001891 | ||
780 | 780 | 80 mm dia | BI01010001010000000000000515BI0100001892 | 1 | M |
781 | 781 | 100 mm dia | BI01010001010000000000000515BI0100001893 | 1 | M |
782 | 782 | 150 mm dia | BI01010001010000000000000515BI0100001894 | 1 | M |
783 | 783 | 200 mm dia | BI01010001010000000000000515BI0100001895 | 1 | M |
784 | 784 | 250 mm dia | BI01010001010000000000000515BI0100001896 | 1 | M |
785 | 785 | 300 mm dia | BI01010001010000000000000515BI0100001897 | 1 | M |
786 | 786 | 350 mm dia | BI01010001010000000000000515BI0100001898 | 1 | M |
787 | 787 | 400 mm dia | BI01010001010000000000000515BI0100001899 | 1 | M |
788 | 788 | 450 mm dia | BI01010001010000000000000515BI0100001900 | 1 | M |
789 | 789 | 500 mm dia | BI01010001010000000000000515BI0100001901 | 1 | M |
790 | 790 | Repainting of GI pipelines & its\nfittingsClean to SSPC SP 2 hand\ncleaning wire brushing.One coat of Etch\nPrimer (6 micron)One coat of Mastic Coating\n- P4 (175 micron)Two coat of Acrylic\nPolyurethane - F1 (40-45 micron each)Total\nDFT of 261 micron | BI01010001010000000000000515BI0100001902 | ||
791 | 791 | 25 mm dia | BI01010001010000000000000515BI0100001903 | 1 | M |
792 | 792 | 50 / 65 mm dia | BI01010001010000000000000515BI0100001904 | 1 | M |
793 | 793 | 80 mm dia | BI01010001010000000000000515BI0100001905 | 1 | M |
794 | 794 | 100 mm dia | BI01010001010000000000000515BI0100001906 | 1 | M |
795 | 795 | 150 mm dia | BI01010001010000000000000515BI0100001907 | 1 | M |
796 | 796 | 200 mm dia | BI01010001010000000000000515BI0100001908 | 1 | M |
797 | 797 | 250 mm dia | BI01010001010000000000000515BI0100001909 | 1 | M |
798 | 798 | 300 mm dia | BI01010001010000000000000515BI0100001910 | 1 | M |
799 | 799 | All types of Valves | BI01010001010000000000000515BI0100001911 | ||
800 | 800 | Clean to SSPC SP 2 hand cleaning wire brushing. | BI01010001010000000000000515BI0100001912 | ||
801 | 801 | One coat of Zinc Phosphate - P3 (30-35 µ each) + | BI01010001010000000000000515BI0100001913 | ||
802 | 802 | Two coat of Synthetic Enamel Paint - F4 (25 m each) | BI01010001010000000000000515BI0100001914 | ||
803 | 803 | Total DFT of 80 m | BI01010001010000000000000515BI0100001915 | ||
804 | 804 | 50 / 65 mm dia | BI01010001010000000000000515BI0100001916 | 1 | EA |
805 | 805 | 80 mm dia | BI01010001010000000000000515BI0100001917 | 1 | EA |
806 | 806 | 100 mm dia | BI01010001010000000000000515BI0100001918 | 1 | EA |
807 | 807 | 150 mm dia | BI01010001010000000000000515BI0100001919 | 1 | EA |
808 | 808 | 200 mm dia | BI01010001010000000000000515BI0100001920 | 1 | EA |
809 | 809 | 250 mm dia | BI01010001010000000000000515BI0100001921 | 1 | EA |
810 | 810 | 300 mm dia | BI01010001010000000000000515BI0100001922 | 1 | EA |
811 | 811 | 350 mm dia | BI01010001010000000000000515BI0100001923 | 1 | EA |
812 | 812 | 400 mm dia | BI01010001010000000000000515BI0100001924 | 1 | EA |
813 | 813 | 450 mm dia | BI01010001010000000000000515BI0100001925 | 1 | EA |
814 | 814 | 500 mm dia | BI01010001010000000000000515BI0100001926 | 1 | EA |
815 | 815 | 550 mm dia | BI01010001010000000000000515BI0100001927 | 1 | EA |
816 | 816 | 600 mm dia | BI01010001010000000000000515BI0100001928 | 1 | EA |
817 | 817 | 650 mm dia | BI01010001010000000000000515BI0100001929 | 1 | EA |
818 | 818 | 700 mm dia | BI01010001010000000000000515BI0100001930 | 1 | EA |
819 | 819 | Painting of Indian Oil logo on the\nTanks as per the required dimension\nouter surface of Tanks with 2 coats of\nSynthetic Enamel Paint (min25µ for each\ncoat). Item includes supply of Paint,\nAccessories, Labouretc including making\nthe surface clean as per the\ninstruction ofEngineer-in-charge.\nScaffolding shall be paid extra. | BI01010001010000000000000515BI0100001931 | 1 | EA |
820 | 820 | SPRINKLER & FOAM POURER SYSTEM | BI01010001010000000000000515BI0100001932 | ||
821 | 821 | Supply, fabricating, welding (3 runs min.), laying and erection above ground/ under ground pipelines including supplying of IS 1239 Heavy grade MS ERW pipes of the following sizes as described below, cutting, beveling and welding the supplied fittings such as elbows, bends, tees, reducers, painting as below etc., complete and hydro testing the pipelines at 10.5 KSC for a minimum period of 4 Hrs. | BI01010001010000000000000515BI0100001933 | ||
822 | 822 | Note: a) Erection of sprinkler riser/ring shall be done only after hot dip galvanizing of the pre-fabricated section. Payment for hot dip galvanizing will be paid under separate item. | BI01010001010000000000000515BI0100001934 | ||
823 | 823 | b) Painting shall be as per IOC painting scheme. | BI01010001010000000000000515BI0100001935 | ||
824 | 824 | A/G pipeline | BI01010001010000000000000515BI0100001936 | ||
825 | 825 | 50 mm dia | BI01010001010000000000000515BI0100001937 | 1 | M |
826 | 826 | 65 mm dia | BI01010001010000000000000515BI0100001938 | 1 | M |
827 | 827 | 80 mm dia | BI01010001010000000000000515BI0100001939 | 1 | M |
828 | 828 | 100 mm dia | BI01010001010000000000000515BI0100001940 | 1 | M |
829 | 829 | 150 mm dia | BI01010001010000000000000515BI0100001941 | 1 | M |
830 | 830 | 200 mm dia | BI01010001010000000000000515BI0100001942 | 1 | M |
831 | 831 | U/G pipeline with doping as per specification | BI01010001010000000000000515BI0100001943 | ||
832 | 832 | 80 mm dia | BI01010001010000000000000515BI0100001944 | 1 | M |
833 | 833 | 100 mm dia | BI01010001010000000000000515BI0100001945 | 1 | M |
834 | 834 | 150 mm dia | BI01010001010000000000000515BI0100001946 | 1 | M |
835 | 835 | 200 mm dia | BI01010001010000000000000515BI0100001947 | 1 | M |
836 | 836 | Supply, installation & painting of following # 150 ANSI B 16.5 flanged CS Gate Valves/ Butterfly valves/ CS Ball Valves/ SS ball vales of approved make & of the following sizes on including supplying & fixing 3 mm thk non metallic gaskets, studs/nuts, painting as per specification etc of approved make as per specifications enclosed & site instructions. | BI01010001010000000000000515BI0100001948 | ||
837 | 837 | Note: Painting shall be as per IOC painting scheme. | BI01010001010000000000000515BI0100001949 | ||
838 | 838 | CS Flanged type Butterfly valves | BI01010001010000000000000515BI0100001950 | ||
839 | 839 | 150 mm dia | BI01010001010000000000000515BI0100001951 | 1 | EA |
840 | 840 | CS Flanged type Ball valves | BI01010001010000000000000515BI0100001952 | ||
841 | 841 | 25 mm dia | BI01010001010000000000000515BI0100001953 | 1 | EA |
842 | 842 | 50 mm dia | BI01010001010000000000000515BI0100001954 | 1 | EA |
843 | 843 | 80 mm dia | BI01010001010000000000000515BI0100001955 | 1 | EA |
844 | 844 | 100 mm dia | BI01010001010000000000000515BI0100001956 | 1 | EA |
845 | 845 | 150 mm dia | BI01010001010000000000000515BI0100001957 | 1 | EA |
846 | 846 | 200 mm dia | BI01010001010000000000000515BI0100001958 | 1 | EA |
847 | 847 | CS Flanged type Knife Edge Valve | BI01010001010000000000000515BI0100001959 | ||
848 | 848 | 100 mm dia | BI01010001010000000000000515BI0100001960 | 1 | EA |
849 | 849 | 150 mm dia | BI01010001010000000000000515BI0100001961 | 1 | EA |
850 | 850 | 200 mm dia | BI01010001010000000000000515BI0100001962 | 1 | EA |
851 | 851 | Supply of #100 wafer type butterfly valve of approved make to suit SORF/WNRF flanges on pipelines.\nANSI 150 class API 609 AWWA-C504 BS 5155 | BI01010001010000000000000515BI0100001963 | ||
852 | 852 | 80mm dia | BI01010001010000000000000515BI0100001964 | 1 | EA |
853 | 853 | 100mm dia | BI01010001010000000000000515BI0100001965 | 1 | EA |
854 | 854 | 150mm dia | BI01010001010000000000000515BI0100001966 | 1 | EA |
855 | 855 | 200mm dia | BI01010001010000000000000515BI0100001967 | 1 | EA |
856 | 856 | 250mm dia | BI01010001010000000000000515BI0100001968 | 1 | EA |
857 | 857 | Supply & installation of basket type strainer with body IS 3589 ERW with end flanges having # 150 rating & as per ANSI B 16.5 including supplying & fixing 3 mm thk non metallic gaskets, studs/nuts etc of approved make . Strainer shall have filter with SS 304 wire mesh (100 mesh)/perforated sheet & with 1/2" screwed ball valve at the bottom for drain provision. Strainer shall be tested hydro-statically to 15 kg/sqcm. Allowable pressure drop: 0.5 kg/sqcm under clean condition & 0.8 kg/sqcm under clogged condition. Capacity & size to be as per latest OISD 117, design to be submitted for approval from IOCL. | BI01010001010000000000000515BI0100001969 | ||
858 | 858 | Note: Painting shall be as per IOC painting scheme. | BI01010001010000000000000515BI0100001970 | ||
859 | 859 | 65 mm dia | BI01010001010000000000000515BI0100001971 | 1 | EA |
860 | 860 | 80 mm dia | BI01010001010000000000000515BI0100001972 | 1 | EA |
861 | 861 | 100 mm dia | BI01010001010000000000000515BI0100001973 | 1 | EA |
862 | 862 | 150 mm dia | BI01010001010000000000000515BI0100001974 | 1 | EA |
863 | 863 | 200 mm dia | BI01010001010000000000000515BI0100001975 | 1 | EA |
864 | 864 | 250 mm dia | BI01010001010000000000000515BI0100001976 | 1 | EA |
865 | 865 | Supply & installation of following UL/FM listed accessories for fixed water spray & foam pourer system on tanks & FH line of approved make & of the following sizes on including supplying & fixing 3 mm thk non metallic gaskets, studs/nuts, painting as per specification etc of approved make as per specifications enclosed & site instructions. | BI01010001010000000000000515BI0100001977 | ||
866 | 866 | Note: a) Size, capacity, K factor etc of the accessories shall be as per design confirming to latest OISD 117, design to be submitted for approval by IOCL. | BI01010001010000000000000515BI0100001978 | ||
867 | 867 | b) Painting shall be as per IOC painting scheme. | BI01010001010000000000000515BI0100001979 | ||
868 | 868 | In-line foam inductor | BI01010001010000000000000515BI0100001980 | ||
869 | 869 | 65 mm dia | BI01010001010000000000000515BI0100001981 | 1 | EA |
870 | 870 | 80 mm dia | BI01010001010000000000000515BI0100001982 | 1 | EA |
871 | 871 | 100 mm dia | BI01010001010000000000000515BI0100001983 | 1 | EA |
872 | 872 | 150 mm dia | BI01010001010000000000000515BI0100001984 | 1 | EA |
873 | 873 | Foam Maker - FRVT | BI01010001010000000000000515BI0100001985 | ||
874 | 874 | 50mm dia | BI01010001010000000000000515BI0100001986 | 1 | EA |
875 | 875 | 65mm dia | BI01010001010000000000000515BI0100001987 | 1 | EA |
876 | 876 | 80mm dia | BI01010001010000000000000515BI0100001988 | 1 | EA |
877 | 877 | Foam Pourer - FRVT | BI01010001010000000000000515BI0100001989 | ||
878 | 878 | 80mm dia | BI01010001010000000000000515BI0100001990 | 1 | EA |
879 | 879 | 100mm dia | BI01010001010000000000000515BI0100001991 | 1 | EA |
880 | 880 | Foam Chamber - CRVT | BI01010001010000000000000515BI0100001992 | ||
881 | 881 | 50mm dia | BI01010001010000000000000515BI0100001993 | 1 | EA |
882 | 882 | 65mm dia | BI01010001010000000000000515BI0100001994 | 1 | EA |
883 | 883 | 80mm dia | BI01010001010000000000000515BI0100001995 | 1 | EA |
884 | 884 | 100mm dia | BI01010001010000000000000515BI0100001996 | 1 | EA |
885 | 885 | 150mm dia | BI01010001010000000000000515BI0100001997 | 1 | EA |
886 | 886 | Foam Deflector - CRVT | BI01010001010000000000000515BI0100001998 | ||
887 | 887 | 80mm dia | BI01010001010000000000000515BI0100001999 | 1 | EA |
888 | 888 | 100mm dia | BI01010001010000000000000515BI0100002000 | 1 | EA |
889 | 889 | 150mm dia | BI01010001010000000000000515BI0100002001 | 1 | EA |
890 | 890 | 200mm dia | BI01010001010000000000000515BI0100002002 | 1 | EA |
891 | 891 | 250mm dia | BI01010001010000000000000515BI0100002003 | 1 | EA |
892 | 892 | MV SS Spray nozzles | BI01010001010000000000000515BI0100002004 | ||
893 | 893 | K-Factors - K18 | BI01010001010000000000000515BI0100002005 | 1 | EA |
894 | 894 | K-Factors - K22 to K-53 | BI01010001010000000000000515BI0100002006 | 1 | EA |
895 | 895 | K-Factors - K54 to K-102 | BI01010001010000000000000515BI0100002007 | 1 | EA |
896 | 896 | Installation of IOC supplied Spray Nozzles: Handling, erection, testing & commissioning of Medium Velocity Water Spray Nozzle of 1/2" BSPT male thread including all necessary consumables complete in all respect as per instructions. | BI01010001010000000000000515BI0100002008 | ||
897 | 897 | All type of spray nozzle | BI01010001010000000000000515BI0100002009 | 1 | EA |
898 | 898 | Supply & welding of SORF Flanges as per ASTM A 105 # Class 150 & as per ANSI B 16.5 (3 runs outside & 1 run inside) of following sizes. | BI01010001010000000000000515BI0100002010 | ||
899 | 899 | 50 mm dia | BI01010001010000000000000515BI0100002011 | 1 | EA |
900 | 900 | 65 mm dia | BI01010001010000000000000515BI0100002012 | 1 | EA |
901 | 901 | 80 mm dia | BI01010001010000000000000515BI0100002013 | 1 | EA |
902 | 902 | 100 mm dia | BI01010001010000000000000515BI0100002014 | 1 | EA |
903 | 903 | 150 mm dia | BI01010001010000000000000515BI0100002015 | 1 | EA |
904 | 904 | Making flanged joints for both slip on and blind flanges including supplying and fixing 3 mm thk non-metallic gaskets, studs, nuts washers etc., of approved make for the following sizes as per IOC specifications and site instructions. | BI01010001010000000000000515BI0100002016 | ||
905 | 905 | 65 mm dia | BI01010001010000000000000515BI0100002017 | 1 | EA |
906 | 906 | 80 mm dia | BI01010001010000000000000515BI0100002018 | 1 | EA |
907 | 907 | 100 mm dia | BI01010001010000000000000515BI0100002019 | 1 | EA |
908 | 908 | 150 mm dia | BI01010001010000000000000515BI0100002020 | 1 | EA |
909 | 909 | Supplying the following pipe fittings confirming to ASTM A 234 Gr WPB, Schedule 40, ANSI B 16.9 | BI01010001010000000000000515BI0100002021 | ||
910 | 910 | 90 deg LR bend (1.5D) | BI01010001010000000000000515BI0100002022 | ||
911 | 911 | 65 mm dia | BI01010001010000000000000515BI0100002023 | 1 | EA |
912 | 912 | 80 mm dia | BI01010001010000000000000515BI0100002024 | 1 | EA |
913 | 913 | 100 mm dia | BI01010001010000000000000515BI0100002025 | 1 | EA |
914 | 914 | 150 mm dia | BI01010001010000000000000515BI0100002026 | 1 | EA |
915 | 915 | 45 deg LR bend (1.5D) | BI01010001010000000000000515BI0100002027 | ||
916 | 916 | 65 mm dia | BI01010001010000000000000515BI0100002028 | 1 | EA |
917 | 917 | 80 mm dia | BI01010001010000000000000515BI0100002029 | 1 | EA |
918 | 918 | 100 mm dia | BI01010001010000000000000515BI0100002030 | 1 | EA |
919 | 919 | 150 mm dia | BI01010001010000000000000515BI0100002031 | 1 | EA |
920 | 920 | Forged/ Fabricated Tee | BI01010001010000000000000515BI0100002032 | ||
921 | 921 | 150 x 150 x 150 mm | BI01010001010000000000000515BI0100002033 | 1 | EA |
922 | 922 | 150 x 150 x 80 mm | BI01010001010000000000000515BI0100002034 | 1 | EA |
923 | 923 | 80 x 80 x 50 mm | BI01010001010000000000000515BI0100002035 | 1 | EA |
924 | 924 | 150 x 150 x 100 x 100 mm - 4 way fabricated plus | BI01010001010000000000000515BI0100002036 | 1 | EA |
925 | 925 | 150 x 150 x 65 x 65 mm - 4 way fabricated plus | BI01010001010000000000000515BI0100002037 | 1 | EA |
926 | 926 | Supplying following BLRF Flanges as per ASTM A 105 # Class 150 & as per ANSI B 16.5 | BI01010001010000000000000515BI0100002038 | ||
927 | 927 | 80 mm dia | BI01010001010000000000000515BI0100002039 | 1 | EA |
928 | 928 | 100 mm dia | BI01010001010000000000000515BI0100002040 | 1 | EA |
929 | 929 | 150 mm dia | BI01010001010000000000000515BI0100002041 | 1 | EA |
930 | 930 | Supply & welding of 1/2" NPT one side threaded MS sockets for fixing of sprinkler nozzles on to sprinkler rings | BI01010001010000000000000515BI0100002042 | 1 | EA |
931 | 931 | Supplying & fixing of 1/2" GI Pipe for fixing spray nozzles at a distance of 600mm from the main header pipe. | BI01010001010000000000000515BI0100002043 | 1 | M |
932 | 932 | Providing hot dip galvanizing to the following items with minimum 360 gm/sqm as per IS 4736 which include fabricated pipes with flanges, fittings forming part of sprinkler header, raiser & rings inside the tank dyke. | BI01010001010000000000000515BI0100002044 | ||
933 | 933 | 65 mm dia | BI01010001010000000000000515BI0100002045 | 1 | M |
934 | 934 | 80 mm dia | BI01010001010000000000000515BI0100002046 | 1 | M |
935 | 935 | 100 mm dia | BI01010001010000000000000515BI0100002047 | 1 | M |
936 | 936 | 150 mm dia | BI01010001010000000000000515BI0100002048 | 1 | M |
937 | 937 | 200 mm dia | BI01010001010000000000000515BI0100002049 | 1 | M |
938 | 938 | Supplying and fixing 100 mm dial pressure gauges on the foam/ sprinkler headers including supplying and welding suitable sockets, provision of 3 way gauge cock, necessary tubing etc complete in all respects and as per directions at site. | BI01010001010000000000000515BI0100002050 | 1 | EA |
939 | 939 | Supplying and fixing 150 mm dial pressure gauges on the foam/ sprinkler headers including supplying and welding suitable sockets, provision of 3 way gauge cock, necessary tubing etc complete in all respects and as per directions at site. | BI01010001010000000000000515BI0100002051 | 1 | EA |
940 | 940 | MECHANICAL SHOE SEAL (PRIMARY & SECONDARY) | BI01010001010000000000000515BI0100002052 | ||
941 | 941 | Design, supply and provision of sealing system comprising of Primary Seal of Mechanical Shoe Seal hanger type and Secondary Seal of Rim Mount Viper Type for sealing the rim gap alround the double deck roof of the floating roof vertical tank including supplying & fixing the mechanical shoe seal, providing necessary fixing arrangements, all stud bolts, nuts, fasteners, washers, testing & commissioning for its smooth operation as per manufacturer recommendations, all leads & lifts etc., complete as per specifications and drawings in all respects as per instructions at site. | BI01010001010000000000000515BI0100002053 | ||
942 | 942 | Note: a) Successful tenderer shall submit detailed drawing from the seal manufacturer including obtaining approval from IOC listed TPI agency as per specifications, BOM for the seal to be installed. | BI01010001010000000000000515BI0100002054 | ||
943 | 943 | b) Guarantee/ warrantee certificates for the sealing system shall be supplied by the manufacturer directly to IOC as part of the above work. | BI01010001010000000000000515BI0100002055 | ||
944 | 944 | c) Rate include dismantling of existing foam seal safely without any damage to seal/ tank/ double deck and handing over & stacking the same anywhere in the depot. | BI01010001010000000000000515BI0100002056 | ||
945 | 945 | For FRVT | BI01010001010000000000000515BI0100002057 | 1 | M |
946 | 946 | Supply, handling, erection, testing & commissioning of Cast Carbon Steel ASTM - A 216, Gr. WCB Double Flanged Gate Valve as per BS : 1414 ; API-600 , Class # 150, with stainless steel rising spindle & internal working parts, flange drilled as per ANSI B 16.5 Cl # 150,raised face and hand wheel including supply & welding of companion SORF flanges, ANSI B 16.5, Cl # 150, nuts, bolts, gaskets etc., complete in all respect as per instructions. | BI01010001010000000000000515BI0100002058 | ||
947 | 947 | 65 mm dia | BI01010001010000000000000515BI0100002059 | 1 | EA |
948 | 948 | 80 mm dia | BI01010001010000000000000515BI0100002060 | 1 | EA |
949 | 949 | 100 mm dia | BI01010001010000000000000515BI0100002061 | 1 | EA |
950 | 950 | 150 mm dia | BI01010001010000000000000515BI0100002062 | 1 | EA |
951 | 951 | 200 mm dia | BI01010001010000000000000515BI0100002063 | 1 | EA |
952 | 952 | 250 mm dia | BI01010001010000000000000515BI0100002064 | 1 | EA |
953 | 953 | Supply, handling, cutting, edge preparation, fabrication, welding, erection (under or above ground), supporting, testing & commissioning of S.S. Pipe IS:316 marked, schedule-40, including supply & welding of all necessary S.S. fittings such as elbow, reducer, tee, nipple , socket etc., and S.S. Flanges with S.S.nuts & bolts, gaskets & washers, U-bolts etc., complete in all respect as per the instructions. | BI01010001010000000000000515BI0100002065 | ||
954 | 954 | 25 mm dia | BI01010001010000000000000515BI0100002066 | 1 | M |
955 | 955 | 32 mm dia | BI01010001010000000000000515BI0100002067 | 1 | M |
956 | 956 | 50 mm dia | BI01010001010000000000000515BI0100002068 | 1 | M |
957 | 957 | 65 mm dia | BI01010001010000000000000515BI0100002069 | 1 | M |
958 | 958 | 80 mm dia | BI01010001010000000000000515BI0100002070 | 1 | M |
959 | 959 | Supply, handling, cutting, edge preparation, fabrication, welding(3 runs minimum), erection (under or above ground), supporting, testing & commissioning of SS pipes of following sizes conforming to ASTM A312 TP 304, Material SS-304 Grade, Sch-40/80 S Seamless with Plain/Bevel end conforming to dimesions ASME B36.19.Including supply & welding of all necessary S.S. fittings such as elbow, reducer, tee, nipple , socket etc., and S.S. Flanges with S.S.nuts & bolts, gaskets & washers, U-bolts etc., complete in all respect as per the instructions. | BI01010001010000000000000515BI0100002071 | ||
960 | 960 | 40 mm NB (SCH 40S Bevel End) | BI01010001010000000000000515BI0100002072 | 1 | M |
961 | 961 | 65 mm NB (SCH 40S Bevel End) | BI01010001010000000000000515BI0100002073 | 1 | M |
962 | 962 | 80 mm NB (SCH 40S Bevel End) | BI01010001010000000000000515BI0100002074 | 1 | M |
963 | 963 | 100 mm NB (SCH 40S Bevel End) | BI01010001010000000000000515BI0100002075 | 1 | M |
964 | 964 | 40 mm NB (SCH 80S Bevel End) | BI01010001010000000000000515BI0100002076 | 1 | M |
965 | 965 | 65 mm NB (SCH 80S Bevel End) | BI01010001010000000000000515BI0100002077 | 1 | M |
966 | 966 | 80 mm NB (SCH 80S Bevel End) | BI01010001010000000000000515BI0100002078 | 1 | M |
967 | 967 | 100 mm NB (SCH 80S Bevel End) | BI01010001010000000000000515BI0100002079 | 1 | M |
968 | 968 | Supply, handling, erection, testing & commissioning of Female Screwed (BSPT) lever operated Stainless Steel Ball Valve suitable for handling corrosive liquid. The valve should have S.S.body-ASTM A 351 CF 8M,Ball & stem AISI 316,seat test pressure 10kg/sq.cm.The job includes the supply & fittings of all necessary S.S. fittings required etc., complete in all respect as per the instructions. | BI01010001010000000000000515BI0100002080 | ||
969 | 969 | 25 mm dia | BI01010001010000000000000515BI0100002081 | 1 | EA |
970 | 970 | 32 mm dia | BI01010001010000000000000515BI0100002082 | 1 | EA |
971 | 971 | 50 mm dia | BI01010001010000000000000515BI0100002083 | 1 | EA |
972 | 972 | 65 mm dia | BI01010001010000000000000515BI0100002084 | 1 | EA |
973 | 973 | 80 mm dia | BI01010001010000000000000515BI0100002085 | 1 | EA |
974 | 974 | Supply, handling, erection, testing & commissioning of Class 150 Flanged type Stainless Steel Ball Valve suitable for handling corrosive liquid. The valve should have S.S.body-ASTM A 351 CF 8M,Ball & stem AISI 316,seat test pressure 10kg/sq.cm.The job includes the supply & fittings of all necessary S.S. fittings required etc., complete in all respect as per the instructions. | BI01010001010000000000000515BI0100002086 | ||
975 | 975 | 25 mm dia | BI01010001010000000000000515BI0100002087 | 1 | EA |
976 | 976 | 32 mm dia | BI01010001010000000000000515BI0100002088 | 1 | EA |
977 | 977 | 50 mm dia | BI01010001010000000000000515BI0100002089 | 1 | EA |
978 | 978 | 65 mm dia | BI01010001010000000000000515BI0100002090 | 1 | EA |
979 | 979 | 80 mm dia | BI01010001010000000000000515BI0100002091 | 1 | EA |
980 | 980 | 100 mm dia | BI01010001010000000000000515BI0100002092 | 1 | EA |
981 | 981 | Supply, handling, erection,testing & commissioning of Stainless Steel Female Screwed (BSPT) horizontal type Non-Return Valve/Check Valve with all S.S.internals ,seat test pressure 10kg/sq.cm. The job includes the supply & fittings of all necessary S.S. fittings required etc., complete in all respect as per the instructions. | BI01010001010000000000000515BI0100002093 | ||
982 | 982 | 25 mm dia | BI01010001010000000000000515BI0100002094 | 1 | EA |
983 | 983 | 32 mm dia | BI01010001010000000000000515BI0100002095 | 1 | EA |
984 | 984 | 50 mm dia | BI01010001010000000000000515BI0100002096 | 1 | EA |
985 | 985 | 65 mm dia | BI01010001010000000000000515BI0100002097 | 1 | EA |
986 | 986 | 80 mm dia | BI01010001010000000000000515BI0100002098 | 1 | EA |
987 | 987 | Supply, handling, erection,testing & commissioning of Class 150 Flanged type Stainless Steel Non-Return Valve/Check Valve with all S.S.internals ,seat test pressure 10kg/sq.cm. The job includes the supply & fittings of all necessary S.S. fittings required etc., complete in all respect as per the instructions. | BI01010001010000000000000515BI0100002099 | ||
988 | 988 | 25 mm dia | BI01010001010000000000000515BI0100002100 | 1 | EA |
989 | 989 | 32 mm dia | BI01010001010000000000000515BI0100002101 | 1 | EA |
990 | 990 | 50 mm dia | BI01010001010000000000000515BI0100002102 | 1 | EA |
991 | 991 | 65 mm dia | BI01010001010000000000000515BI0100002103 | 1 | EA |
992 | 992 | 80 mm dia | BI01010001010000000000000515BI0100002104 | 1 | EA |
993 | 993 | 100 mm dia | BI01010001010000000000000515BI0100002105 | 1 | EA |
994 | 994 | OTHER WORKS | BI01010001010000000000000515BI0100002106 | ||
995 | 995 | Supplying & Providing cathodic protection sacrificial Anode of the bottom plate including design, supply, fixing of the same as per requirement and instruction at site. | BI01010001010000000000000515BI0100002107 | ||
996 | 996 | For vertical tanks | BI01010001010000000000000515BI0100002108 | 1 | EA |
997 | 997 | Supply of Standard Reference Electrodes \n(Cu-CuSO4 half cell or CalomelReference\nCell or Silver-Silver Chloride Cell or\nZinc Reference Cell)with insulated \ncopper wires & appropriate mounting\narrangements in MSstructural frame/\nclamps etc | BI01010001010000000000000515BI0100002109 | 1 | SET |
998 | 998 | Supply of Terminal Box powder coated\nwith IP 67 enclosure, ISI MarkedDigital\nmeter with a sensitivity of (+/-)\nVolts inlcuding pushbutton with\nmultiway selector switch including\nnecessary mountingarrangement in MS\nstructural frame/ clamps etc | BI01010001010000000000000515BI0100002110 | 1 | SET |
999 | 999 | Installation of supplied Standard \nReference Electrodes at the top of\nthetank by welding the mounting\narrangement etc | BI01010001010000000000000515BI0100002111 | 1 | SET |
1000 | 1000 | Installation of supplied Terminal box by welding/ clamping at top of thetank | BI01010001010000000000000515BI0100002112 | 1 | SET |
1001 | 1001 | Providing detailed engineering documentation comprisng of the following drawings & documentation in 3 sets:\na. Water conductivity test report inclduing temperature variations\nb. Design basis & calculations including surface area, current demand, current drain as applicable\nc. Minimum net mass of Anode\nd. Anode resistance calculations\ne. Current output calculations\nf. Anode installation design & arrangement\ng. Provision for electrical continuity checking\nh. Any other required documentation | BI01010001010000000000000515BI0100002113 | 1 | LS |
1002 | 1002 | Arranging for visit from OEM of\nSacrifical Anode system\nduringcommissioning of water tanks for\nconducting testing inlcuding\nelectricalcontinuity, current output/\ndrain, anode resistance,\ncathodicpolarization. Charges shall\ninclude boarding, lodging,\nair/rail/roadtransportation, insurance,\nlocal conveyance, communication,\nstationery& all other incidentals\nrequired for performance of the testing\n&submission of reports to IOCL. Item is\nbased on visit of 1 no Enigneerfrom OEM\nfor a day | BI01010001010000000000000515BI0100002114 | 1 | LS |
1003 | 1003 | Supply & Installation, testing, commissioning & customization of Fall arrestor system with Safety harness, complete. For ensuring correct\ninstallation, horizontal life line shall be proof loaded at site to a static force of 6 KN by the vendor.\nTank Lorry Filling (TLF) bays, Tank Truck (TT) sealing gantry, TT surprise check gantry: THE WORK INCLUDES SUPPLY & INSTALLATION of horizontal\nlifeline with accessories for Fall arrestor system including 1 no. Shock absorber (SS 304 to limit impact force in event of fall to less than 6.5 KN),\nUpto 10 m Steel wire rope (minimum 8 mm dia of SS 316), 2 no. Retractable fall arrestor (with SS wire rope of 4.5 mm dia & length as required at\nsite), 2 no. Carriage body (SS 316 with friction free movement), 1 no. Tensioner (SS 304 with swageless termination of end wire), 2 no. Extremity\nplates, 1 no. Cable extremity (if required), 2 no. Anti static Full body adjustable harness & any other material to complete the job. Fall arrestor\nsystem shall be provided in TLF bays, TT calibration area, and Surprise Checking Platform, as required at the location & as mentioned in the\ntender. Items shall be provided in line with the material specifications as mentioned in attached 'Data Sheet'. The above requirement is typical\nand vendor shall provide the site specific quantities and any additional items required for efficient working of the system at no extra cost. ITEM\nALSO INCLUDES Customisation and installation of horizontal life line system on the gantry | BI01010001010000000000000515BI0100002115 | 1 | EA |
1004 | 1004 | Design, Supply,Installation,Testing & Commissioning of Retractable stairs for Tank Wagon Decanting Gantry at Railway siding as per IOCL technical specification and drawings. The item includes packing/forwarding, freight with transit Insurance and TPI charges | BI01010001010000000000000515BI0100002116 | 1 | EA |
1005 | 1005 | Design, Supply,Installation,Testing & Commissioning of Retractable stairs for Tank Lorry Filling Gantry at TLF shed, TT calibration facility, TT checking facility etc. as per IOCL technical specification and drawings. The item includes packing/forwarding, freight with transit Insurance and TPI charges | BI01010001010000000000000515BI0100002117 | 1 | EA |
1006 | 1006 | Cuting and removing the roof eye bolts and re-placeing the same as per the drawing after welding of patch plate on the roof. The job include supply of 20 mm dia eye bolts etc complete as per instruction at site engineer. | BI01010001010000000000000515BI0100002118 | ||
1007 | 1007 | NOTE : Care should be taken not to damage any part of the tank while dismantling. Welding of patch plate will be paid as per the respective items in this workorder. | BI01010001010000000000000515BI0100002119 | ||
1008 | 1008 | For vertical tanks | BI01010001010000000000000515BI0100002120 | 1 | EA |
1009 | 1009 | Fabricating, erecting, welding of 5 mm thk MS patch plate on roof of Cone Roof Vertical Tank as per the specifications with required steel plates supplied by IOC any where within the premises. All other items such as labour, equipment, power, consumables etc., shall be supplied by the Contractor. | BI01010001010000000000000515BI0100002121 | ||
1010 | 1010 | For vertical tanks - upto 300mmx300mm size | BI01010001010000000000000515BI0100002122 | 1 | EA |
1011 | 1011 | Transportation of materials like MS plates/ MS Pipes/ Valves including arranging truck, manpower, equipments, all leads & lifts, taking necessary insurance for materials, co-ordination, loading & unloading, stacking etc., complete as per instructions. | BI01010001010000000000000515BI0100002123 | ||
1012 | 1012 | Between 0 to 100 KMs | BI01010001010000000000000515BI0100002124 | ||
1013 | 1013 | MS Plates/ MS Pipes - all thickness/ all dia | BI01010001010000000000000515BI0100002125 | 1 | TON |
1014 | 1014 | All types of Valves - 150mm to 600mm size | BI01010001010000000000000515BI0100002126 | 1 | EA |
1015 | 1015 | Every additional KM above 100 KMs | BI01010001010000000000000515BI0100002127 | ||
1016 | 1016 | MS Plates/ MS Pipes - all thickness/ all dia | BI01010001010000000000000515BI0100002128 | 1 | KM |
1017 | 1017 | All types of Valves - 150mm to 600mm size | BI01010001010000000000000515BI0100002129 | 1 | KM |
1018 | 1018 | Transportation of materials like MS plates/ MS Pipes including arranging trailor, manpower, equipments, all leads & lifts, taking necessary insurance for materials, co-ordination, loading & unloading, stacking etc., complete as per instructions. | BI01010001010000000000000515BI0100002130 | ||
1019 | 1019 | Between 0 to 100 KMs | BI01010001010000000000000515BI0100002131 | ||
1020 | 1020 | MS Plates/ MS Pipes - all thickness/ all dia | BI01010001010000000000000515BI0100002132 | 1 | TON |
1021 | 1021 | Every additional KM above 100 KMs | BI01010001010000000000000515BI0100002133 | ||
1022 | 1022 | MS Plates/ MS Pipes - all thickness/ all dia | BI01010001010000000000000515BI0100002134 | 1 | KM |
1023 | 1023 | Providing 8 guage copper wire bonding for the flange joints | BI01010001010000000000000515BI0100002135 | 1 | EA |
1024 | 1024 | Dismantling and re-fixing the existing MS structural catwalk with grating without any damage including cutting, welding, stacking the same safely, re-fixing the same wherever required, necessary grouting, all leads & lifts etc., complete in all respects as per instructions. | BI01010001010000000000000515BI0100002136 | ||
1025 | 1025 | Old Catwalk with gratings | BI01010001010000000000000515BI0100002137 | 1 | M2 |
1026 | 1026 | Supplying and providing stand post on the exisitng Fire Hydrant line including suppy of MS pipe, reinforcement plate, cutting, welding, SORF flange, all leads & lifts etc., complete as per specification & instructions. | BI01010001010000000000000515BI0100002138 | ||
1027 | 1027 | 80mm dia | BI01010001010000000000000515BI0100002139 | 1 | EA |
1028 | 1028 | 100mm dia | BI01010001010000000000000515BI0100002140 | 1 | EA |
1029 | 1029 | Pipeline Identification and marking using suitable Pipeline Locator, measuring distances, GPS tracking, Conducting CIPS and DCVG Survey. Collection of data and compiling with respect to pipeline / ROW features / references, calculation of %IR Loss, bell hole inspection and repair, identification of coating holidays and prioritization for coating refurbishment - for all dia of pipelines. | BI01010001010000000000000515BI0100002141 | ||
1030 | 1030 | DCVG Survey as per procedure outlined in the tender document including installation of temporary CP for the purpose, if required - survey for every 1 M interval. | BI01010001010000000000000515BI0100002142 | 1 | KM |
1031 | 1031 | CIPS Survey as per procedure outlined in the tender document for cathodically protected pipelines only - survey for every 1 M interval. | BI01010001010000000000000515BI0100002143 | 1 | KM |
1032 | 1032 | Verification of defect spots by Bell Hole inspection as per procedure outlined in the tender document . | BI01010001010000000000000515BI0100002144 | 1 | EA |
1033 | 1033 | Repair of defect spot exposed through bell hole inspection using vendor supplied Cold Applied Tape as per procedure outlined in the tender document . | BI01010001010000000000000515BI0100002145 | 1 | EA |
1034 | 1034 | Carrying out ultrasonic thickness survey for the pipelines for various dia (Spot shall have 4 readings i.e. 12 O'Clock, 3 O'Clock, 6 O'Clock & 9 O'Clock) with necessary ultrasonic thickness gauge, man power, tools & tackles, transportaion etc., leasd & lifts wherever required including submission of reports as per requirements and instructions. | BI01010001010000000000000515BI0100002146 | ||
1035 | 1035 | Above ground pipelines of all dia. | BI01010001010000000000000515BI0100002147 | 1 | EA |
1036 | 1036 | Under ground pipeline of all dia upto 2M depth - including earth work excavation & back filling. | BI01010001010000000000000515BI0100002148 | 1 | EA |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy