Post Graduate Institute Of Medical Education And Research-PGIMER has published Provision Of Electrical Supply And Mgps Connectivity To Psa Plant To Be Installed At Nehru Hospital Extension , Pgimer , Chandigarh ( Sh Electrical Work ) . Submission Date for this Tender is 23-06-2021. Electrical Maintenance Tenders in Nehru Hospital Extension, PGIMER, Chandigarh Chandigarh. Bidders can get complete Tender details and download the document.
Name of Work: Provision of electrical supply and MGPS connectivity to PSA plant to be installed at Nehru Hospital Extension, PGIMER, Chandigarh (SH: Electrical work). | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | L.T. PANEL S.I.T.C of cubical type LT panel floor made of strucural modular sections suitable for 415 V, 3 phase, 4 wire 50 Hz IP 54 AC supply system . Having required front surfacearea, fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work & covers, 2 mm thick for gland plates i/c cleaning & finshing complete with 7 tank process for powder coating in approved shade, having mentioned capacity TPN Aluminium Alloy bus-bar of high conductivty, SMC bus-bar supports,fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25mm x 5 mm at the rear with 2 nos earth stud, solid connections from main Bus-bar to switch gears, top entry type, with required size of al. bus-bars to switch gears control wiring with 1.5/ 2.5 sq mm PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, providing following switchgear :- Incomer Two nos. 630 Amps FP MCCB Microprocessor based having LSIG release and fault breaking capacity 50 KA ( Ics = 100% Icu upto 415 V) ,Phase Indication, Digital multifunction meter with RS 485 Port with 2 Amp Backup MCBs, CTs of ratio 600/5A class 1 accuracy and 5 VA burden-1 set , Breaker 'ON'-'OFF' indicating light with 2 amp MCB , auxiliary contacts for positive interlocking of the breakers as required. Bus coupler one nos. 630 Amps FP MCCB Microprocessor based having LSIG release of fault breaking capacity 50 KA ( Ics = 100% Icu upto 415 V) Breaker 'ON'-'OFF' indicating light with 2 amp MCB , auxiliary contacts for positive interlocking of the breakers as required. Bus Bar TPN aluminium bus-bars of minimum of 800 amps capacity with heat shrinkable coloured sleeves and i/c SMC bus-bars supports at required intervals complete for cross section, size supports & their spacing etc . Outgoing (i)1 no. 400 Amp TP MCCB 36KA Mp Based (ii) 2 nos. 200 Amp TP MCCB 36KA Mp Based \n(ii)2 nos. 100 Amp TP MCCB 36KA Mp Based and 01 no dummy space. All outgoing MCCBs to have:- Microprocessor based LSIG release, Ics=100%Icu, panel mounted rotary extanded handle mechnism and spreader links.\n | BI01010001010000000000000515BI0100001112 | ||
2 | 1.01 | Panel as above | BI01010001010000000000000515BI0100001113 | 1 | Nos |
3 | 2 | Supply of 3.5 core aluminium conductor, XLPE insulated PVC sheathed armoured cable confirming to IS : 7098 (part – I), 1100 v Grade of the following sizes. | BI01010001010000000000000515BI0100001114 | ||
4 | 2.01 | 300 mm2 | BI01010001010000000000000515BI0100001115 | 1000 | Mtr. |
5 | 3 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cables of 1.1 kv grade as reqd. | BI01010001010000000000000515BI0100001116 | ||
6 | 3.01 | 3½ X 300 sq. mm (70mm) | BI01010001010000000000000515BI0100001117 | 8 | Nos |
7 | 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. | BI01010001010000000000000515BI0100001118 | ||
8 | 4.01 | Above 185 sq. mm and upto 400 sq. mm | BI01010001010000000000000515BI0100001119 | 800 | Mtr. |
9 | 5 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. | BI01010001010000000000000515BI0100001120 | ||
10 | 5.01 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | BI01010001010000000000000515BI0100001121 | 200 | Mtr. |
11 | 6 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. | BI01010001010000000000000515BI0100001122 | ||
12 | 6.01 | 300 mm width X 50 mm depth X 1.6 mm thickness | BI01010001010000000000000515BI0100001123 | 100 | Mtr. |
13 | 7 | Supplying and laying of HDPE pipe ISI marked with 160 mm outer dia and 145mm Inner dia, PE100 PN 6 as per ISI. along with all accessories couplers etc. Complete with fitting and cutting, jointing etc. underground (min. 1.0 m below ground level) with drilling machine complete as required. | BI01010001010000000000000515BI0100001124 | 400 | Mtr. |
14 | 8 | Earthing with GI earth plate 600mm x 600mm x 6.0mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe 2.7 metre long etc. with charcoal/ coke and salt as required. | BI01010001010000000000000515BI0100001125 | 2 | Set |
15 | 9 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required | BI01010001010000000000000515BI0100001126 | 20 | RM |
16 | 10 | SITC of clean agent gas based fire suppression system suitable upto 2 cum volume. The clean agent with zero ODP as per NFPA 2001, UL listed, with container BS EN3-8, electrical non conductive clean agent, capacity 2 KG, comprisinging of 30m Heat sensing tube(HST) made of polyamide ( UL/LPCB listed), size of tube 4mm ID and 6mm OD, the HST to be pressurised with dry nitrogen gas confiriing IS:1747 and connected to an extinguishing agent container via a pressue release valve. complete as per specification attached. The pneumatic pressure valve is a direct low pressure valve with inbuilt pressure gauge , integrated ball valve for open/close with in the valve body, with two nos outlets to connect HST. System to have audio-video monitoring panel, microprocessor based to check the health of system and pressure in the tube with indication of AC Power On, System discharge, valve open/closed, Pressure heal;thy, Battery low, etc. System to have power pack having 12V 7 AH 2 nos SMF battery.System to have third party integration facility as fire safety devices. with piezo electric Buzzer 50 dB, job complete with elbow, connectors, Ts, end of line adapter and end of line plug in HST tube as required. Max working pressure is 20 bar, burst pressure at 20 degreeC: 110 deg.C, system operating pressure is 15 bar. System to be LPCB standard LPS 1666:issue 1.0 | BI01010001010000000000000515BI0100001127 | 1 | Nos |
17 | 11 | SITC of one nos. 630 Amps FP MCCB Thermomegnetic based release of fault breaking capacity 50 KA ( Ics = 100% Icu upto 415 V) MCCB with powder coated enclosure suitable to connect 2 nos 3.5 core cables as outgoing and incoming with Aluminium Bus Bar to busduct, MCCB with Extended Rotary Handle and Spreader links complete as required in NHE ground floor c2 block.. | BI01010001010000000000000515BI0100001128 | 1 | Nos |
18 | 12 | SITC of one nos. 630 Amps FP MCCB Thermomegnetic based release of fault breaking capacity 50 KA ( Ics = 100% Icu upto 415 V) MCCB in the existing main LT Panel of opd substation including incoming and outgoing solid interconnections and SMC busbar supports Extended Rotary Handle and Spreader links complete as required. | BI01010001010000000000000515BI0100001129 | 1 | Nos |