Supply , Erection , Testing And Commissioning Of 315 Kva 11 Kv Package Sub Station For Psa Plant In Civil Hospital Phagwara , Distt . Kapurthala ., Phagwara-Punjab

Public Works Department-PWD has published Supply , Erection , Testing And Commissioning Of 315 Kva 11 Kv Package Sub Station For Psa Plant In Civil Hospital Phagwara , Distt . Kapurthala .. Submission Date for this Tender is 23-06-2021. Substation Tenders in Phagwara Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

28219194
Supply , Erection , Testing And Commissioning Of 315 Kva 11 Kv Package Sub Station For Psa Plant In Civil Hospital Phagwara , Distt . Kapurthala .
Open Tender
Indian
Punjab
Phagwara
23-06-2021

Tender Details

Supply , Erection , Testing And Commissioning Of 315 Kva 11 Kv Package Sub Station For Psa Plant In Civil Hospital Phagwara , Distt . Kapurthala .

Key Value

Document Fees
INR 5000 /-
EMD
INR 56000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Supply, erection, testing and commissioning of 315 KVA 11 KV package substation for PSA plant in Civil Hospital, Phagwara, Distt Kapurthala.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, erection, testing and commissioning of 315 KVA 11 KV package substation which include HT switchgear 11 KV 630 amp 1 no Vaccum Circuit Breaker in SF6 (protection CT 1 set, mechanical position indictaor 1 set, voltage presence indication 1 set, manometer 1 no, operating handle 1 no), Transformer 315 KVA / 433 V ONAN Oil Filled Transformer, LT Section Incomer 630 Amp FP ACB 50 KA is 1 No, aluminium busbar ( RYB indication , ammeter , multifunction meter ), Outdoing 250 Amp TP MCCB 36 KA is 4 No , interconnection Bitween Ht Section And Transfomer Through Al. Cable& Transformer to LT Section Through Al. Busbar. Make: ABB/Sudhir/Crompton/Schnieder. Complete in all respect as approved and desired by the engineer incharge at site. BI01010001010000000000000515BI0100001113 1 Job
2 2 PVC INSULATED FR COPPER CONDUCTOR CABLES:\nSupply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
3 2.1 Overall size 16sq.mm (Un-sheathed) BI01010001010000000000000515BI0100001117 20 P.mtr.
4 2.2 Overall size 25sq.mm (Un-sheathed) BI01010001010000000000000515BI0100001118 17 P.mtr.
5 3 XLPE INSULATED ARMOURED CABLES (LOOSE):\nSupply, laying and erection of aluminium conductor XLPE insulated PVC sheathed armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:
6 3.1 Overall size 185sq.mm (3½ Core) Armoured (Loose) BI01010001010000000000000515BI0100001119 75 P.mtr.
7 3.2 Overall size 300sq.mm (3½ Core) Armoured (Loose) BI01010001010000000000000515BI0100001120 75 P.mtr.
8 4 COPPER EARTHING (Upto 14 metre in Length):\nEarthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
9 4.1 Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length) BI01010001010000000000000515BI0100001121 2 Nos.
10 4.2 Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length) BI01010001010000000000000515BI0100001122 1 Nos.
11 5 COPPER EARTHING STRIP (As Additional Length):\nFixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
12 5.1 Additional Length 20mm x 3mm thick Copper Tape BI01010001010000000000000515BI0100001123 20 P.mtr.
13 5.2 Additional Length 25mm x 3mm thick Copper Tape BI01010001010000000000000515BI0100001124 10 P.mtr.
14 6 XLPE INSULATED HT ARMOURED CABLES (LOOSE):\nSupply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid loose in the existing trench or pipe:-
15 6.1 HT Cable Overall size 35sq.mm (3Core) BI01010001010000000000000515BI0100001125 70 P.mtr.
16 7 S/E of Heat shrinkable cable end termination/ Straight through joint kit for 11 KVA /6.6 KV (E) XLPE Cables as approved & desired by Enginer in charge:-
17 7.1 Heat Shrinkable End Termination for cable size 35 sq. mm, 3Core (Indoor Type) BI01010001010000000000000515BI0100001126 2 Nos.
18 8 Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
19 8.1 Double Walled Corrugated HDPE Pipe 120/103.5mm (Outer/ Inner dia.) BI01010001010000000000000515BI0100001127 150 P.mtr.
20 9 Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:-
21 9.1 Aluminium thimble cable Core size 95sq.mm BI01010001010000000000000515BI0100001131 2 P.mtr.
22 9.2 Aluminium thimble cable Core size 120sq.mm BI01010001010000000000000515BI0100001132 2 P.mtr.
23 9.3 Aluminium thimble cable Core size 150sq.mm BI01010001010000000000000515BI0100001133 2 P.mtr.
24 9.4 Aluminium thimble cable Core size 185sq.mm BI01010001010000000000000515BI0100001134 6 P.mtr.
25 10 Supply and erection of heavy duty brass single compression gland for cable end termination duly complete with checknuts etc. including making necessary connections:-
26 10.1 Brass Gland for Aluminium cable 3/3½/4 Core size 185sq.mm BI01010001010000000000000515BI0100001135 2 Each
27 10.2 Brass Gland for Aluminium cable 3/3½/4 Core size 240sq.mm BI01010001010000000000000515BI0100001136 2 Each
28 10.3 Brass Gland for Aluminium cable 3/3½/4 Core size 300sq.mm BI01010001010000000000000515BI0100001137 2 Each
29 11 Making of cement concrete foundation of overall size 17 feet long x 7 feet wide x 3 feet deep x 1 feet height with 1:2:4 cement concrete mixture and suitable size of steel. The outer surface of the foundation shall be finished with pure 1:2 cement plaster and two coats of white snowcem complete in all respect as approved and desired by the Engineer Incharge at site BI01010001010000000000000515BI0100001138 1 Each