Special Repair To Lt Panels At Af Station Suryalanka As Per Boq And Tender Document, SURYALANKA-Andhra Pradesh

Military Engineer Services-MES has published Special Repair To Lt Panels At Af Station Suryalanka As Per Boq And Tender Document. Submission Date for this Tender is 30-06-2021. Electrical Panel Tenders in SURYALANKA Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

28211602
Corrigendum : Special Repair To Lt Panels At Af Station Suryalanka As Per Boq And Tender Document
Open Tender
Indian
Andhra Pradesh
SURYALANKA
30-06-2021

Tender Details

Special Repair To Lt Panels At Af Station Suryalanka As Per Boq And Tender Document

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-Jun-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 30-06-2021

Key Value

Document Fees
INR 300 /-
EMD
INR 9600.0 /-
Tender Value
INR 4.80 Lakhs /-

BOQ Items

Name of Work: SPECIAL REPAIR TO LT PANELS AT AF STATION SURYALANKA
Sl. No. Description of Item of Works Item Code / Make Approximate No. of Units Required UNIT
1 1 S&F 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat or circular stranded of size 10 Sqmm including taking down old unserviceable cable complete all as specified 100 RM
2 2 S&F 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat or circular stranded of size 16 Sqmm including taking down old unserviceable cable complete all as specified 100 RM
3 3 Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with stranded aluminium conductors, 1100 volts grade of size 10Sqmm 4 core including taking down old unserviceable cable complete all as specified 50 RM
4 4 All as per item no 3 above but cross-sectional area 16 sqmm 4 core 50 RM
5 5 All as per item no 3 above but cross-sectional area 25 sqmm 4 core 50 RM
6 6 All as per item no 3 above but cross-sectional area 50 sqmm 3.5 core 70 RM
7 7 All as per item no 3 above but cross-sectional area 95 sqmm 3.5 core \n\nNote for 3 to 7 :- Earthwork excavation / returning filling shall be measured and paid separately under respective items\n 50 RM
8 8 Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft/loose soil/sand including taking out unserviceable LT Cable for laying of new cable.\nNote:-The labour element for raising / taking out of cable / pipe shall be included in relevant items of S&F cables. 46 CUM
9 9 Returning, filling-in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified. 26 CUM
10 10 Supply and spread dry river sand for cushioning and covering of UG cables in trenches all as specified and directed. \nNote:- only punned thickness shall be measured and paid. 14 CUM
11 11 Supply and laying common burnt bricks, sub class 'B', of size 230 x 115 x 75 mm laid dry and abutting each other with gap between adjacent slab not exceeding 10mm over under ground cable for cable protection in trenches all as specified and directed. 1.336 1000\nNos
12 12 Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. 20 CUM
13 13 M&L for earthing in repair complete with galvanized iron or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.5 m below ground level connected to galvanized earth strip 32X6 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with 8 mm dia TMT bar both ways @ 140 c/c and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I and specified including provision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation and earth work & connecting the earthing to an earthing test point /transformer neutral/body/ LT panel etc. and testing on completion, complete all as specified & directed. 5 Each
14 14 Supply, installation, commissioning and testing LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 150 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / bus bar and other connection items shall be provided, the space between ground to panel shall be 60 cm with PCC foundation , LT panel shall be provided with necessary locking arrangement, danger notice sticker, provn of cable entry and exit arrangement for Al cable size upto 120 Sqmm and glands, thimbling for connection of cable to MCCBs/bus bar etc and internal wiring with FRLS copper wires of suitable size and marking of each MCCB function with suitable size letter and including provn of following item and taking down of existing LT panel complete :- (Location - Pichora panel) 1 Each Job
15 14.1 (A) Main Incoming\n(a) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 01 No.\n(b) On load changeover 4 pole 100 Amp capacity - 01 \n(Open execution)\n(c) LED Multifunctional Panel meter to measure voltage, current frequency, power factor, kWH, etc with all connected CTs \n(d) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set\n(B) Main Outgoing\n(a) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 02 No. \n(b) MCB TPN 6-32 Amps, 10 kA, C Curve - 07 Nos \nNote:- The rate quoted shall be
16 15 Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 240 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / bus bar and other connection items shall be provided, the space between ground to panel shall be 60 cm with PCC foundation , LT panel shall be provided with necessary locking arrangement, danger notice sticker, provn of cable entry and exit arrangement for Al cable size upto 120 Sqmm and glands, thimbling for connection of cable to MCCBs/bus bar etc and glands, internal wiring with FRLS copper wires of suitable size and marking of each MCCB function with suitable size letter and including provn of following item and taking down of existing LT panel complete :-\n( Location - Offrs Mess back side corner road ) 1 Each Job
17 15.1 (A) Main Incoming\n(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 20 KA - 01 No.\n(ii) LED Multifunctional Panel meter to measure voltage, current frequency, power factor, kWH, etc with all connected CTs \n(iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set\n(B) Main Outgoing\n(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 02 No. \n(ii) MCB TPN 6-32 Amps, 10 kA, C Curve - 02 Nos
18 16 Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 240 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / bus bar and other connection items shall be provided, the space between ground to panel shall be 60 cm with PCC foundation for LT Panel, LT panel shall be provided with necessary locking arrangement, danger notice sticker, provn of cable entry and exit arrangement for Al cable size upto 120 Sqmm and glands, thimbling for connection of cable to MCCBs/bus bar etc and glands, internal wiring with FRLS copper wires of suitable size and marking of each MCCB function with suitable size letter and including provn of following item and taking down of existing LT panel complete :-\n(Location - Offrs Mess) 1 Each Job
19 16.1 (A) Main Incoming\n(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 200 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 01 No.\n(ii) LED Multifunctional Panel meter to measure voltage, current frequency, power factor, KWH, etc with all connected CTs \n(iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set\n(B) Main Outgoing\n(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 03 No. \n(ii) MCB TPN 6-32 Amps, 10 kA, C Curve - 02 Nos
20 17 Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 150 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / bus bar and other connection items shall be provided, the space between ground to panel shall be 60 cm with PCC foundation, LT panel shall be provided with necessary locking arrangement, danger notice sticker, provn of cable entry and exit arrangement for Al cable size upto 120 Sqmm and glands, thimbling for connection of cable to MCCBs/bus bar etc and glands, internal wiring with FRLS copper wires of suitable size and marking of each MCCB function with suitable size letter and including provn of following item and taking down of existing LT panel complete :--\n(Location - Offrs Beach guard room back) 1 Each Job
21 17.1 (A) Main Incoming\n(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 26 KA - 01 No.\n(ii) LED Multifunctional Panel meter to measure voltage, current frequency, power factor, kWH, etc with all connected CTs \n(iii) LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set\n(B) Main Outgoing\n(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 03 No. \n(ii) MCB TPN 6-32 Amps, 10 kA, C Curve - 04 Nos .\n\nNote For item No.14 to 17 :- \n(i) The quoted rate for the items shall inclusive of necessary cost for earthwork excavation, returning filling and removal of excess soil complete for foundation of Panel boards.\n(ii)The existing Panel boards shall become the propery of Contractor and shall be issued to the contractor as shown in Schedule of credit.