Airports Authority Of India has published Facility Management Of Fire Fighting System And Fire Alarm System At Chennai Airport 2021-2023. Submission Date for this Tender is 25-06-2021. Fire Alarm Systems Tenders in Chennai Airport Tamil Nadu. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | SH1: Fire fighting system |
2 | Facility management services for fire hydrant and sprinkler Systems at Chennai Airport as per inventory, monitoring and maintenance activities to ensure the serviceability on round the clock basis including maintaining records/ data entry/ Supervision of the total system etc as per the specifications & directions of Engineer-In-Charge. (Refer Annexure-A1 for inventory of equipments, Annexure-B1 for monitoring & maintenance activities, Annexure-C Man power details) |
3 | For First Year |
4 | For Second Year |
5 | Supply and replacement ofboth side bearings, mechanical seal, petty materials like stud bolts, gland packing, gasket, rubber bush for coupling etc. cleaning and greasing of bearings, reassembling, realignment of thepump with motor, testing,commissioning and painting etc. complete as required. Approved Makes:Siemens,Alstom,Kirlosker. |
6 | Kirloskar 85HP to 92 HP |
7 | Kirloskar 60HP to 75 HP |
8 | Kirloskar/Mather-platt 15HP |
9 | Dismantling of following valves from the existing fire fighting water pipe line, Complete removal as required etc. |
10 | For 6" and 8" Gate/Non Return /Foot valves |
11 | From 2" to 4" Gate/Non Return/Foot valves |
12 | Providing & fixing of following size MS C classIS:1239heavy type pipe with doubletype welding, Suitable Bends and arranging scaffoding with proper jointing with nuts ,bolts and channel in the pipe fixing on surfaceetc. complete with flanges, bends, tees. supports etc. by welding with approved make & specification as required.complete as required as perthe direction of E.I.C |
13 | 25 mm( IS:1239, Heavy class) |
14 | 32 mm ( IS:1239, Heavy class) |
15 | 40 mm ( IS:1239, Heavy class) |
16 | 80mm ( IS:1239, Heavy class) |
17 | 100mm ( IS:1239, Heavy class) |
18 | 150mm ( IS:1239, Heavy class) |
19 | Providing & fixing of following size MS C classIS:1239heavy type pipe with doubletype welding, Suitable Bends and arranging scaffoding with proper jointing with nuts ,bolts and channel in the pipe fixing under ground all type of flooring with suitable 4mm thick insulation wrapping tar sheet etc. complete with flanges, bends, tees. supports etc. by welding with approved make & specification as required.complete as required as perthe direction of E.I.C (Excluding excavation & concreting) |
20 | 80mm (IS: 1239, Heavy class) |
21 | 100mm ( IS:1239, Heavy class) |
22 | 150mm ( IS:1239, Heavy class) |
23 | Providing and fixing the following size of lever operated butterfly valves of approved make after dismantling the existing damaged one i/c replacement of the gasket, nut, bolts etc. as required. |
24 | 65mm dia (PN 16 Rated) |
25 | 80mm dia (PN 16 Rated) |
26 | 100mm dia (PN 16 Rated) |
27 | 125mm dia (PN 16 Rated) |
28 | 150mm dia (PN 16 Rated) |
29 | 200mm dia (PN 16 Rated) |
30 | 250mm dia (PN 16 Rated) |
31 | 300mm dia (PN 16 Rated) |
32 | Providing and fixing the following size of Non return valves/ check Valve/ Gate valves of approved make after dismantling the existing damaged one i/c replacement of the gasket, nut, bolts etc. as required. |
33 | 100 mmNon return valve |
34 | 150 mm Non return valve |
35 | 200 mm dia Non return valve |
36 | 100 mmswing type water check valve |
37 | 150 mm swing type water check valve |
38 | 80mm sluice Gate valve |
39 | 150mm sluice Gate valve |
40 | Dismantling of following existing faulty sprinkler flexible hose drops from the system, which are inside the false ceiling, supplying and installing new flexible hose drops up to 1.5Mtr length along with all required connectors, threading, coupler etc. as required. |
41 | Fabrication, Supply and Fixing of 6mm thick chequered plates including providing and fixing 40mm×40mm×6mm angle iron supports on cable trenches, Fire hydrant tanks, 25mm×6mm MS flat around the chequered plate by welding, providing lifting hook, painting etc., as required. |
42 | Providing one welder and one Khalasi along with Electric welding/ gas cutting machine and welding rods/ Oxygen Acetlyne gas for carrrying out leak arresting/ welding of fire fighting lines or other welding works during any urgent Preventive Maintenance/ Breakdown Maintenance/ Emergency work as and when required. |
43 | Wrapping of existing Mild steel pipe with suitable 4mm thick insulation of tar felt sheet as per the specifications & directions of E.I.C. |
44 | Supply & replacement of following suitable parts in hydrant delivery/ Landing valves(Single/ Double head), First aid Hose reel drums, other related accessories and valves in Fire hydrant and sprinkler system (as and when required basis). |
45 | Coupling washer |
46 | Seating washer |
47 | Gasket of suitable thickness |
48 | Nut bolts 12mm dia, 3" long |
49 | Rubber hose 20mm x 30 Mtr. Suitable for First aid Hose reel drum |
50 | O ring seal inside First aid Hose reel drum |
51 | 25mm forged brass Ball Valve |
52 | Brass Shutoff Nozzle with 1/2" ball valve |
53 | Hose clamps for rubber hose |
54 | 25mm GM Air release valve (Screwed type) |
55 | Providing &Replacement of 100mm dia Pressure gauges, 0-200PSI, H. Guru make or as per the approved make, specifications & directions of E.I.C. Approved makes : H Guru, Jaspin & General instruments |
56 | Providing & Replacement of pressure switch suitable for the existing system with a pressure range of 1 to 10 Bar. Approved makes : Danfoss & Swizer |
57 | Disconnecting and dismantling of burnt out Induction motor from the system. Complete dismantling of burntout stator winding and thorough cleaning of stator slots.Rewinding the stator with Class "F" polyester coated super enameled copper wire and insulating materials i/c. baking, varnishing, finishing and refixing the stator in the motor frame & re-installation in Fire pump room including transportation to and fro from Pump room etc as required. Approved Makes : Seimens, Alstom & Kirlosker. |
58 | 10 to 12.5HP |
59 | Painting with two coats of Synthetic enamel paint of approved shade and colour over a coat of red oxide primer over pipe lines including cleaning/ scrapping and remarking the existing indications/numbers with white paint/sticker etc., as required. |
60 | Providing Minor Civil Repair Works as required as detailed below: |
61 | Earth work (all types of soil) in excavation by mechanical means (Hydraulic excavator) /manual means including disposal of excavated earth, disposed earth to be levelled and neatly dressed. |
62 | Demolishing cement concrete manually/mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - Charge. |
63 | Laying cement concrete in 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 20mm nominal size) i/c curing etc. |
64 | Cement mortar in 1:6 (1 cement: 6 coarse sand)i/c curing etc. |
65 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: 1:6 (1 cement: 6 coarse sand)i/c curing etc. |
66 | Cement plaster 12mm mix 1:6i/c curing etc. |
67 | Supplying and filling in plinth with river sand under floors, including watering, ramming, consolidating and dressing complete. |
68 | Carriage of materials by Mechanical Transport including loading ,unloading and stacking complete for a lead of 1 Km. Earth/ building rubbish/ similar unserviceable, dismantled or waste material |
69 | Providing& fixing of MS fire boxwith nut and bolt as per standard etc. complete as required. Approved makes : Minimax, Newage & Safex |
70 | Providing & replacement of SS holding lugs with nut and bolt etc. complete as required. Approved makes : Minimax, Newage & Safex |
71 | Providing & fixing of female couplingwith nut and bolt etc. complete as required. Approved makes : Minimax,Newage & Safex |
72 | Providing & fixing of MS wheel with nut and bolt with suitable as complete as required. Approved makes : Minimax, Newage & Safex |
73 | Providing & fixing MS trim kit and gong bell for alarm valve 150 NB with nut and bolt etc. complete as required. Approved makes : Minimax, Newage & Safex |
74 | Providingof 15mm and 50 mm ball valveetc. complete as required. Approved makes : Zoloto, Sant &Audco |
75 | Providing & fixing of pressure gauge needle valve set with suitable existing pipe etc.complete as required. Approved makes : Minimax, Newage & Safex |
76 | Providing & fixingof hose reel nozzlewith exisiting suitablenut and bolt etc. complete as required. Approved makes : Minimax, Newage & Safex |
77 | Providing and Fixingof hose reelSS nozzlewith nut and bolt etc. complete as required. Approved makes: Minimax, Newage & Safex |
78 | Providing & fixing of hydrant valve PVC cap, disk washer with nut and screws etc. complete as required. Approved makes : Minimax, Newage & Safex |
79 | Supply of Exide express battery 12V 180 Ampsetc. complete as required. |
80 | Providing and fixing of soleloid valve (model ISD - 15) SS 30 body nitrle dia phragmwith nut and bolt etc. complete as required. |
81 | Providing & fixing of MS 1" heavy class C type etc. complete as required. Approved makes : Zoloto,Sant & Audco |
82 | Providing & fixing of MSkey & SS branch with washers etc withcomplete as required . Approved makes : Zoloto,sant & Audco |
83 | Providing & fixing ofsuitable glass with screws and nuts with fire box etc. complete as required. |
84 | Providing & fixing of fire fighting hosewith nut in fire box each length of 15 meters with suitable couplingsetc, complete as required. Approved makes: Minimax, Newage & Safex |
85 | Providing & fixing of Nipple etc. complete as required. Approved makes : Minimax,Newage & Safex |
86 | Supply of distilled water etc. complete as required. |
87 | Providing& fixing of 200 mm PN16Butter fly valve hand levertypewithsuitable nut and bolt with washersetc. complete as required. |
88 | Providing & fixingof 250 mm PN16 Butter fly valvewheel type with nut and bolt with washersetc. complete as required |
89 | Providing & fixing of 100 mm Butter fly valve hand type with nut and boltwithwashers etc. complete as required. |
90 | Supply& fixing of 150 mm PN16 Butter fly valve and hand type & 150mm flanges with nut and bolt with washersetc. complete as required. |
91 | Supply of 25mm ball valve etc.complete as required. |
92 | Providing & fixing of hose reel drum set with hose 20mm x 30 mtr, hose reel nozzle with nut, bolt, clamp etc. complete as required. Approved makes: Minimax,Newage & Safex |
93 | Providing & fixing of Double headed landing hydrant valve with nut, bolt, washer, gaskets etc., complete as required.. Approved makes: Minimax,Newage & Safex |
94 | Providing & fixing of single headed fire hydrant landing valve with suitablebolt nuts and gaskets, etc., complete as required. Approved makes : Minimax, Newage & Safex |
95 | Numbering of Fire hydrant box/Fire hydrant landing pipe with double coated Red enamel paintwith numbering in white paint of suitable size as complete asrequired.. Approved makes :Minimax, Newage & Safex |
96 | Dismantling of following damaged existing MS Heavy class pipes from the system which are on surface and under ground at a depth of 1.5 metres from ground level and shifting the same to AAI stores etc complete as required. |
97 | 25 mm to 80mm |
98 | 100mm to 150mm |
99 | Providing & Fixing of Sprinkler bulb with washer, gaskets, nipple etc., complete as required. |
100 | SH2: Fire Alarm system |
101 | Fire Alarm system & VESDA: Monitoring & Maintenance of Fire Alarm Systems at T1 & T4 as per inventorycomprising of Fire Alarm system (Low Ceiling), VESDA (High ceiling) and Monitoring and supervision of BMS on round the clock basis including maintaining records/ reports/ Supervision of the total system etc up to the specifications & directions of Engineer-In-Charge. (Excluding software & spares for BMS) (Refer Annexure-A2 for inventory of Fire alarm system, VESDA and BMS. Annexure-B2 for monitoring & maintenance activities, Annexure-C for man power) |
102 | For First Year |
103 | For Second Year |
104 | Monitoring & Maintenance of Fire Alarm Systems at AIT (T3-Terminal) as per inventorycomprising of Fire Alarm system and related PA system Monitoring and supervision round the clock basis including maintaining records/ reports/ Supervision of the total system etc up to the specifications & directions of Engineer-In-Charge.(Refer Annexure-A3 for inventory of Fire alarm system, Annexure-B2 for monitoring & maintenance activities, Annexure-C for Man power) |
105 | For First Year |
106 | For Second Year |
107 | Providing mobile communication facility at four locations with annual package of Rs. 1498/- for one year for each mobiles etc., as requiredfor the entire contract period. |
108 | For First Year |
109 | For Second Year |
110 | Providing & Fixing of Temporal Horn, 84.4/79.4 dB, 15,30,75,110 cd Strobe, red complete as required. XLSG1R-HDVM. Make : Honeywell/EST |
111 | Providing & Fixing of Single Input Module complete as required.SIGA-CT1. Make: Honeywell/EST |
112 | Providing & Fixing of Detector Base - Standard complete as required. SIGA-SB. Make : Honeywell/EST |
113 | Providing & Fixing of Intelligent Fixed Temperature Heat Detector - 135F complete as required. XLS-HFS. Make : Honeywell/EST |
114 | Providing & Fixing of Isolator Module complete as required. XLS-IM. Make : Honeywell/EST |
115 | Providing & Fixing of Intelligent Photoelectric Smoke Detector with basecomplete as required. XLS-PS. Make : Honeywell/EST |
116 | Providing & Fixing of Intelligent 3D Multisensor Detector with base - Photoelectric, Heat complete as required. XLS-PHS. Make : Honeywell/EST |
117 | Providing & Fixing of Signal module - single source complete as required. SIGA - CC1. Make : Honeywell/EST |
118 | Providing & Fixing of Control relay module complete as required. SIGA - CR. Make: Honeywell/EST |
119 | Providing & Fixing of Manual pull station - Lexan complete as required. XLS-278. Make: Honeywell/EST |
120 | Providing & Fixing of Network communication board complete as required. 3-RS 485B. Make: Honeywell/EST |
121 | Providing & Fixing of RS232 communication board complete as required. 3-RS 232. Make: Honeywell/EST |
122 | Providing & Fixing of LCD operator interface complete as required. 3-LCD. Make: Honeywell/EST |
123 | Providing & Fixing of Dual Signature Driver Controller complete as required. 3-DSDC1. Make: Honeywell/EST |
124 | Providing & Fixing of Booster power supply - 7 Amps complete as required. 3-PPS/M-230. Make: Honeywell/EST |
125 | Providing & Fixing of CPU complete as required. 3-CPU3.Make: Honeywell/EST |
126 | Providing & Fixing of F-Box complete as required. 32004871-009/U. Make: Honeywell/EST |
127 | Providing & Fixing of 12V, 65 AH, SMF battery complete as required. Make: Exide |
128 | Providing & Fixing of VESDA complete as required. |
129 | Make : FAAST System Sensor model ; 8100 |
130 | Make: VLP 400 Xtralis |
131 | Make: VLP 250 Xtralis |
132 | Providing & Fixing of 110 / 220VAC to 24VDC 1.5Amp Power Supply (FM Approved) complete as required. VPS220E, Approved make : Polycab |
133 | Providing of 2 core 1.5 Sq.mm Copper conductor overall PVC sheathed GI wire Braided (flexible Armoured) FRLS grade cable complete as required. Approved make : Polycab |
134 | Laying of one number 2 core 1.5 Sq.mm Copper conductor overall PVC sheathed GI wire Braided (flexible Armoured) FRLS grade cable on surface for fire alarm circuit etc., complete as required. Approved make : Polycab |
135 | Providing & Fixing of Repeater Panel complete as required. (XLS-LCDANN). Make : Honeywell/EST |
136 | Providing & Fixing of Pla relay complete as required. (Pla mpc-2c-24D-5A-L). Approved makes : Seimens, L&T & Areva |
137 | Providing & Fixing of power supply for Pla relay complete as required. (230/24v Dc). Approved makes : Seimens, L&T & Areva |
138 | Providing & Fixing of Fire fighters telephone wall plate complete as required. (6833-1). Make: Honeywell/EST |
139 | Providing & Fixing of PCB Mount 8 pole relay complete as required. Approved makes : Seimens, L&T & Areva |
140 | Providing & Fixing of Morelyloop card complete as required. Make: Morely |
141 | Providing & Fixing of Desktop Speaker as required. Make: Zebronics |
142 | Providing & Fixing of power supply for SMPS complete as required. (230/24v Dc) |
143 | Solo A5 -001 Smoke Dedector Tester 250 ml |
144 | Solo A10S -001 HFC Free Smoke Dedector Tester 250 ml |
145 | Smoke Detector Testing Kit (Aerosol Dispenser and Telescopic Access Poles (6m Maximum Reach) ) |
146 | Providing & Fixing ofHorn cum strobecomplete as required.XLSG1R-HDVM. Make : Honeywell/EST |
147 | SUB HEAD: III AMC ofKIRLOSKAR make Diesel Engines. |
148 | Inspection and service contract for kirloskar make Diesel Engines located at various fire fighting pump rooms as per Manufacturer"s standard Instructions/ catalogues/ Practices as required. |
149 | Model-6R1080T, Sr.No : 6H.2419.16/ 1000032 at Utility Building, Sprinkler. |
150 | Second Year |
151 | Model-6R1080T, Sr.No : 6H.2419.16/ 1000056 at Utility Building, Hydrant. |
152 | Second Year |
153 | Model-RB66FE, Sr.No : 4H.2280.16/1920011 at Admin Fire Pump House. |
154 | Second Year |
155 | Model-4R1040T, Sr.No : 4H.2431.16/ 0900011 at Spice JetHanger |
156 | Second Year |
157 | Supply of B-Check spares including transportation,loading,unloading etc complete as required for second year |
158 | KOEL CARE Super Genuine oil |
159 | 20 litresc CAN |
160 | 13 litres CAN |
161 | SPINON LUBE OIL FILTER |
162 | FUEL FILTER KIT 1.1 LTR |
163 | Freight Charges |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail