Comprehensive Maintenance Of Standby Dg Sets , Amf Panel , Apfc Panel And Allied Accessories At 6 Wg Af , Kancharapara , Jafferpore , Los Dum Dum And Barasat Under Ge ( Af ) Barrackpore, 6 WG AF, KANCHARAPARA, JAFFERPORE, LOS DUM DUM-West Bengal

Military Engineer Services-MES has published Comprehensive Maintenance Of Standby Dg Sets , Amf Panel , Apfc Panel And Allied Accessories At 6 Wg Af , Kancharapara , Jafferpore , Los Dum Dum And Barasat Under Ge ( Af ) Barrackpore. Submission Date for this Tender is 03-07-2021. Diesel Generators Tenders in 6 WG AF, KANCHARAPARA, JAFFERPORE, LOS DUM DUM West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

28126162
Corrigendum : Comprehensive Maintenance Of Standby Dg Sets , Amf Panel , Apfc Panel And Allied Accessories At 6 Wg Af , Kancharapara , Jafferpore , Los Dum Dum And Barasat Under Ge ( Af ) Barrackpore
Open Tender
Indian
West Bengal
6 WG AF, KANCHARAPARA, JAFFERPORE, LOS DUM DUM
03-07-2021

Tender Details

Comprehensive Maintenance Of Standby Dg Sets , Amf Panel , Apfc Panel And Allied Accessories At 6 Wg Af , Kancharapara , Jafferpore , Los Dum Dum And Barasat Under Ge ( Af ) Barrackpore

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 26-Jun-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 03-07-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 40000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Comprehensive maintenance of standby DG Sets, AMF Panel , APFC Panel and allied accessories at 6 WG AF, Kancharapara, Jafferpore, Los Dum Dum & Barasat under GE (AF) Barrackpore.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Carryout periodical routine maintenance consisting of Checking, Inspection, Maintenance, and servicing complete including replacement of unserviceable parts of the DG set comprising of (Engine/Alternator/Control Panel/AMF panel) .Attending breakdown and testing of DG Set complete, i.e, engine, Alternator, etc for efficient functioning including provision of all consumables items like cotton , waste cloth , kerosine oil etc. Maintenance will be carried out all as specified for various capacity of DG sets here in after complete all as specified and directed by Engr-In-Charge. \n Note: (i) Spare parts shall be measured and paid separately under respective items as shown below.\n(II) Labour charges for dismantling / Taking down and replacement /refixing of new spare parts as when required as deemed to be included in unit rate quoted. (a) 320 KVA DG , (Location- 6 Wing) MAKE : KIRLOSKAR (Sl No.- DV8.1201/1200118 Item No 1 1 Each Job
2 2 (b) All as per item No 1 but for 200 KVA DG, (Location- 6 Wing) MAKE : KIRLOSKAR (Sl No.- F6.3622/1200162 Item No 2 1 Each Job
3 3 (c) All as per item No 1 but for 160 KVA DG set, (Location- Jafferpore AF Camp) MAKE : Kirloskar (Engine Sr No. - 6K1080TAG2 Item No 3 1 Each Job
4 4 (d) All as per item No 1 but for 125 KVA DG set, (Location- 6 Wing) MAKE : Kirloskar (Engine Sr No. - 4H-7906/1820188 and Make- Eicher Item No 4 2 Each Job
5 5 (e) All as per item No 1 but for 75 KVA DG set, (Location- Los Dum Dum ) MAKE : Kirloskar (Engine Type 4R1040TA SR-I, Engine Sr No. - 4H.3523/0920255 & 4H.3523/0920259 Item No 5 2 Each Job
6 6 (f) All as per item No 1 but for 63 KVA DG, (Location- 6 Wing & Jafferpore AF camp ) MAKE : Kirloskar \n(Engine Type 4R1040TA SR-I, Engine Sr No 4H.3501/0800953), Engine Sr No.- 4H.3445/1420190, Sr No.- 4R810TAG1 Item No 6 3 Each Job
7 7 (g) All as per item No 1 but for 45 KVA DG, (Location- 6 Wing) , KE : Kirloskar , Engine Type HA494T,\n Engine Sr No 04.2445/1220277 and Engine Sr No 3H 8503/1620318\n\n Item No 7 2 Each Job
8 8 (h) All as per item No 1 but for 40 KVA DG, (Location- 6 Wing) , MAKE : Eicher Item No 8 1 Each Job
9 9 (j) All as per item No 1 but for 30 KVA DG, (Location- Los Dum Dum) , MAKE : Eicher Item No 9 1 Each Job
10 10 (k) All as per item No 1 but for 20 KVA DG set, (Location- Jafferpore & Kancharapara AF Camp) , MAKE : Kirloskar (Engine Sr No. - 2H.8303/1520219, Engine Sr No.- 2H8303/1521319\n Item No 10 2 Each Job
11 11 (l) All as per item No 1 but for 15 KVA DG, (Location- 6 Wing & Kancharapara AF camp ) \nMONTHLY INSPECTION AND PREVENTIVE MAINTENANCE\nContractor shall provide qualified trained service engineer from OEM/Authorised by OEM as refered item No 1 above to visit at site with material and labour , testing equipment to check / inspection and routine maintenance all as specified and directed by Engr-In-Charge of the following\n(a) DG set servicing (B-check, C-check)\n(b) DG set Maintenance/Health checkup.\n(c) Control Panel/APFC Panel/Alternator troubleshooting only\n(d) Replacement of avr, water pump, starter motor, charging alternator, Fuel, coolant & lube oil hose, solenoid as per requirement. (e) Check lube oil level and conditioning of lube oil, top up/refill if required.\n(f) The oil filters shall be replaced whenever oil is changed.\n(g) The air filters shall be cleaned periodically with compressed air, check batteries and top up the distilled water if required.\n(h) Check functioning of alternator. (I) Engine safety viz. high water temperature gauge, oil pressure gauge, oil temperature gauge and high speed gauge shall be checked for their functions and repaired/ replaced if required.\n(J) Coolant level and conditioning of coolant shall be checked and refilled if required.\n(k) Check fan and alternator drive belts and tightened if required. (l) The governor shall be checked and tuned for proper functioning (m) Check for leaks if any and shall be rectified.\n(n) Checking and servicing of engine for smooth running, its unusual sound and color of smoke and exhaust and set it right in case of deviations (o) Checking of wiring system and repairing/replacement as and when required\n(p) Checking of battery terminal an de-sulphating (n) Diagnosis of faults in engine and Alternator and its rectification\nSPECIAL INSPECTION AND MAINTENANCE\nDuring operation if machine become unserviceable for that contractor shall provide qualified trained authorised service Engineer and technicians from OEM/Authorised by OEM to visit at site with material & labor, testing equipment to check and attend complaints as and when called and rectify the fault within 24 hours of the DG set by following all the recommendations and instruction given in the mannual and service instruction. Item No 11 3 Each Job
12 12 Supply only following unserviceable spare parts with new one confirming to the existing respective parts nos for DG set capacity 320 KVA (a) Fuel Filter with gasket and washer Item No 12 2 Each set
13 13 (b) All as per item No 12 but O Ring - L.O.PUMP Item No 13 2 Each
14 14 (c) All as per item No 12 but Oil Filter with gasket and washer Item No 14 1 Each set
15 15 (d) All as per item No 12 but Belt V Section (BX58-Pitch Length 1520) Item No 15 1 Each
16 16 (e) All as per item No 12 but V Warapped Belt, SPB AR 1170 (Set of 3 Nos) Item No 16 1 Each
17 17 (f) All as per item No 12 but V Warapped Belt SPB AR 1230 (Set of 3 Nos) Item No 17 2 Each
18 18 (g) All as per item No 12 but Temperature thermostat Item No 18 1 Each
19 19 (h) All as per item No 12 but Generator control unit Item No 19 1 Each
20 20 (j) All as per item No 12 but Air filter with gasket and washer Item No 20 2 Each
21 21 (k) All as per item No 12 but AIR PIPE (DV8) FROM TURBO COMPRESSOR OUT TO CAC Item No 21 4 Each
22 22 (l) All as per item No 12 but calibration of fuel injection pump including minor repair and servicing of injector nozzeles complete. Item No 22 1 Each set
23 23 Supply only following unserviceable spare parts with new one confirming to the existing respective parts nos for DG set capacity 160 to 200 KVA (a) Oil filter with gasket and washer Item No 23 4 Each set
24 24 (b) All as per item No 23 but Poly V Belt (4PK-1570) Item No 24 2 Each
25 25 (c) All as per item No 23 but Poly V Belt (8PK:983) Item No 25 1 Each
26 26 (d) All as per item No 23 but Air Filter with gasket and washer Item No 26 4 Each
27 27 (e) All as per item No 23 but FUEL FILTER with gasket and washer Item No 27 4 Each set
28 28 (f) All as per item No 23 but Temperature thermostat Item No 28 1 Each
29 29 (g) All as per item No 23 but SET OF COPPER WASHERS FOR 6SL1500TA Item No 29 1 Each
30 30 (h) All as per item No 23 but Generator control unit Item No 30 1 Each
31 31 (j) All as per item No 23 but BRACKET FOR FUEL FILTER- Item No 31 1 Each
32 32 (k) All as per item No 23 but calibration of fuel injection pump including minor repair and servicing of injector nozzeles complete Item No 32 1 Each
33 33 Supply only following unserviceable spare parts with new one confirming to the existing respective parts nos for DG set capacity 125 KVA (a) Spin on Fuel Filter Item No 33 2 Each set
34 34 (b) All as per item No 33 but O Ring - L.O.PUMP Item No 34 2 Each
35 35 (c) All as per item No 33 but V Belt (XPA 1345)RAW EDGED COGGED--(FENNER/HILTON) Item No 35 2 Each
36 36 (d) All as per item No 33 but Poly V Belt Item No 36 4 Each
37 37 (e) All as per item No 33 but Dismentling the nozzel and complete servicing, re-assemble and testing the same. Item No 37 2 Each
38 38 (f) All as per item No 33 but Air filter with gasket and washer Item No 38 2 Each
39 39 (g) All as per item No 33 but Oil filter with gasket and washer Item No 39 2 Each
40 40 (h) All as per item No 33 but calibration of fuel injection pump including minor repair and servicing of injector nozzeles Item No 40 2 Each
41 41 Supply only following unserviceable spare parts with new one confirming to the existing respective parts nos for DG set capacity 40 to 75 KVA . (a) Oil filter with gasket and washer Item No 41 4 Each set
42 42 (b) All as per item No 41 but Fuel filter with gasket and washer Item No 42 4 Each set
43 43 (c) All as per item No 41 but Air filter with gasket and washer Item No 43 4 Each set
44 44 (d) All as per item No 41 but On delay timer Item No 44 4 Each
45 45 (e) All as per item No 41 but Gasket for cylinder head, 1.10mm thick, Item No 45 1 Each
46 46 (f) All as per item No 41 but THERMOSTAT ELEMENT(74 DEG) - WTIL NO.DEV358, Item No 46 2 Each
47 47 (g) All as per item No 41 but FUEL PIPE - FUEL FILTER TO FUEL PUMP (HA4 BS III), Item No 47 1 Each
48 48 (h) All as per item No 41 but V Belt (XPA 1345)RAW EDGED COGGED--(FENNER/HILTON), Item No 48 3 Each
49 49 (j) All as per item No 41 but WATER PUMP AND FAN PULLEY(POLY V BELT)-120 PCD, Item No 49 3 Each
50 50 (k) All as per item No 41 but HOSE ( RADIATOR TO WATER PUMP PIPE (45X45X130L), Item No 50 3 Each
51 51 (l) All as per item No 41 but CONNECTOR ASSEMBLY FOR CONTROL PANEL WITH KG934 UNIT Item No 51 4 Each
52 52 (m) All as per item No 41 but GENERATOR CONTROL UNIT KG934 LEVEL Item No 52 3 Each
53 53 (n) All as per item No 41 but ENGINE WIRING HARNESS S/F KG934 UNIT (PUMP SIDE CONTROL PANEL) Item No 53 2 Each
54 54 (o) All as per item No 41 but calibration of fuel injection pump including minor repair and servicing of injector nozzeles Item No 54 3 Each
55 55 Supply only following unserviceable spare parts with new one confirming to the existing respective parts nos for DG set capacity 15 to 30 KVA .(a) Air Filter with gasket and washer Item No 55 6 Each set
56 56 (b) All as per item No 55 but Fuel Filter with gasket and washer Item No 56 6 Each set
57 57 (c) All as per item No 55 but Oil Filter with gasket and washer, Item No 57 6 Each set
58 58 (d) All as per item No 55 but On delay timer Item No 58 2 Each
59 59 (e) All as per item No 55 but V Belt (AVX 101500) SPZ Item No 59 2 Each
60 60 (f) All as per item No 55 but Gasket for rocker cover high temparature application- Item No 60 2 Each
61 61 (g) All as per item No 55 but GENERATOR CONTROL UNIT Item No 61 2 Each
62 62 (h) All as per item No 55 but SAFETY ELEMENT FOR AIR CLEANER Item No 62 2 Each
63 63 (j) All as per item No 55 but Fuel pump mounted stop solenoide Item No 63 2 Each
64 64 (k) All as per item No 55 but Fuel pipe (7.5, 14 x 14B, 700 WB)- Item No 64 2 Each
65 65 (l) All as per item No 55 but calibration of fuel injection pump including minor repair and servicing of injector nozzeles Item No 65 2 Each
66 66 Dismantling of radiator assembly from generating set and re-fixing the same after proper cleaning/repair of the same with caustic soda and brazing the tube if any leakage is found complete all as directed for following capacities of DG Set\n(a) 320 KVA DG Set, (Make : Kirloskar) Item No 66 1 Each Job
67 67 (b) All as per item No 66 but 200 KVA DG Set, (Make : Kirloskar) Item No 67 1 Each Job
68 68 (c) All as per item No 66 but 160 KVA DG Set, (Make : Kirloskar) Item No 68 1 Each Job
69 69 (d) All as per item No 66 but 125 KVA DG Set, (Make : Kirloskar) Item No 69 1 Each Job
70 70 (e) All as per item No 66 but 75 KVA DG Set, (Make : Kirloskar) Item No 70 2 Each Job
71 71 (f) All as per item No 66 but 63 KVA DG Set, (Make : Kirloskar) Item No 71 3 Each Job
72 72 (g) All as per item No 66 but 45 KVA DG Set, (Make : Kirloskar) Item No 72 1 Each Job
73 73 Disconnecting the self starter (12V) from the engine body, dismantling the same, checking for identification of faulty spares and reassemblig the same after replacement/renewal of the following spares, if required, including refixing to its original position all as specified and directed Item No 73 4 Job
74 74 S&F fixing following spares for fixing in repair against the faulty one for the self starter(12V) -\n(a) Supply only clutch assembly (Make : LUCAS TVS) Item No 74 3 EACH
75 75 (b) All as per item No 74 but Supply only Bendex pinion (Make : LUCAS TVS) Item No 75 3 EACH
76 76 (c) All as per item No 74 but Supply only Solenoid switch (Make : LUCAS TVS) Item No 76 3 EACH
77 77 (d) All as per item No 74 but Supply only Carbon Brush (Make : LUCAS TVS) Item No 77 3 EACH
78 78 (e) All as per item No 74 but Supply only Armature Field Coil (Make : LUCAS TVS) Item No 78 3 EACH
79 79 (f) All as per item No 74 but Supply only Bush (Make : LUCAS TVS) Item No 79 2 EACH
80 80 (g) All as per item No 74 but Supply only Self armature coil (Make : LUCAS TVS) Item No 80 2 EACH
81 81 Disconnecting the self starter (24V) from the engine body, dismantling the same, checking for identification of faulty spares and reassemblig the same after replacement/renewal of the following spares, if required, including refixing to its original position all as specified and directed\nNote :- spares, required to be replaced, shall be measured and paid under respective items mentioned here in under. Item No 81 4 Job
82 82 S&F fixing following spares for fixing in repair against the faulty one for the self starter(24V)\n(a) Supply only clutch assembly (Make : LUCAS TVS) Item No 82 2 EACH
83 83 (b) All as per item No 82 but Supply only Bendex pinion (Make : LUCAS TVS) Item No 83 2 EACH
84 84 (c) All as per item No 82 but Supply only Solenoid switch (Make : LUCAS TVS) Item No 84 2 EACH
85 85 (d) All as per item No 82 but Supply only Carbon Brush (Make : LUCAS TVS) Item No 85 2 EACH
86 86 (e) All as per item No 82 but for Supply only Armature Field Coil (Make : LUCAS TVS) Item No 86 2 EACH
87 87 (f) All as per item No 82 but for Supply only Bush (Make : LUCAS TVS) Item No 87 2 EACH
88 88 (g) All as per item No 82 but for Supply only Self armature coil (Make : LUCAS TVS) Item No 88 2 EACH
89 89 Supply and fixing Automatic voltage regulator 12 Volt of the following DG capacity including taking down old unserviceable one, complete all as specified & directed. \n(a) 12 Volt, suitable for 15 KVA DG Set, Item No 89 1 Each set
90 90 (b) All as per item No 89 but for 12 Volt, suitable for 20 KVA DG Set, Item No 90 1 Each set
91 91 (c) All as per item No 89 but for 12 Volt, suitable for 45 KVA DG Set, Item No 91 1 Each set
92 92 (d) All as per item No 89 but for12 Volt, suitable for 63 KVA DG Set, Item No 92 1 Each set
93 93 (e) All as per item No 89 but for 12 Volt, suitable for 75 KVA DG Set, Item No 93 1 Each set
94 94 (f) All as per item No 89 but 12 Volt, suitable for 160 KVA DG Set, Item No 94 1 Each set
95 95 Supply and fixing Automatic voltage regulator, 24 Volt, suitable for 320 KVA DG Set, including taking down old unserviceable one, complete all as specified & directed.\n Item No 95 1 Each set
96 96 Supply and fixing Automatic voltage regulator, 24 Volt, suitable for 200 KVA DG Set, including taking down old unserviceable one, complete all as specified & directed. Item No 96 1 Each set
97 97 S&F power contactor assembly 25 Amp, 3 pole 415 volt suitable for 15 KVA DG Set. Item No 97 1 Each
98 98 Supply only Power contactor of various capacity Including taking out old unserviceable one , complete all as given below \n(a) 400 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz. Item No 98 1 Each
99 99 (b) All as per item No 98 but 225 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz. Item No 99 1 Each
100 100 (c) All as per item No 98 but 160 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz. Item No 100 1 Each
101 101 (d) All as per item No 98 but 140 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz.\n Item No 101 1 Each
102 102 (e) All as per item No 98 but 110 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz.\n Item No 102 1 Each
103 103 (f) All as per item No 98 but 100 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz.\n Item No 103 1 Each
104 104 (g) All as per item No 98 but 80 Amps, 3 Pole with 2 NO & 2 NC auxilary contact of coil rating 415 Volt, 50 Hz. Item No 104 1 Each
105 105 Supply only Din fuse bases (fixed type) of various rating including taking down old unserviceable one complete all as given below \n(a) 630 Amps, voltage 415 Volt, CD-2 fuse type .) Item No 105 1 Each
106 106 (b) All as per item No 105 but 400 Amps, voltage 415 Volt, CD-2 fuse type\n Item No 106 1 Each
107 107 (c) All as per item No 105 but 250 Amps, voltage 415 Volt, CD-00 fuse type\n Item No 107 1 Each
108 108 (d) All as per item No 105 but 160 Amps, voltage 415 Volt, CD-00 fuse type\n Item No 108 1 Each
109 109 (e) All as per item No 105 but 125 Amps, voltage 415 Volt, CD-00 fuse type\n Item No 109 1 Each
110 110 Supply only HBC fuse link of various rating including taking out old unserviceable one all are given below\n(a) 125 Amps of breaking capacity of 80 KA & rated voltage 415 Volt of size 02, DIN type, \n Item No 110 1 Each
111 111 (b) All as per item No 110 but 160 Amps of breaking capacity of 80 KA & rated voltage 415 Volt of size 02, DIN type,\n Item No 111 1 Each
112 112 (c) All as per item No 110 but 200 Amps of breaking capacity of 80 KA & rated voltage 415 Volt of size 02, DIN type, Item No 112 1 Each
113 113 (d) All as per item No 110 but 315 Amps of breaking capacity of 80 KA & rated voltage 415 Volt of size 02, DIN type, \n Item No 113 1 Each
114 114 (e) All as per item No 110 but 400 Amps of breaking capacity of 80 KA & rated voltage 415 Volt of size 02, DIN type\n Item No 114 1 Each
115 115 (f) All as per item No 110 but 630 Amps of breaking capacity of 80 KA & rated voltage 415 Volt of size 02, DIN type,\n Item No 115 1 Each
116 116 Supply only current transformer tap wound, ring type rated burden 5 VA, for ammeter, of ratio 250/5, complete all as specefied and as directed. \n Item No 116 10 Each
117 117 Supply only Voltmeter 0-500V digital type with selector switch flush mounting square type in repair. Item No 117 5 Each
118 118 Supply only fixing of Ammeter digital type 0-300V with selector switch flush mounting square type with CT's of suitable size in repair. Item No 118 5 Each
119 119 Supply only indicator lamp LED type, 220 volt AC (RED/YELLOW/BLUE) for each Phase, including taking down old unserviceable one, complete all as specefied and as directed. Item No 119 15 Each
120 120 Supply only lead acid batteries including acesories like terminal clamps, copper cable of required size and length, petroleum jelly and baterry initial charging of the following , \n(a) 12 Volts, 100 AH, 25 plates , Item No 120 5 Each
121 121 (b) All as per item No 120 but 12 Volts, 180 AH, 25 plates Item No 121 5 Each
122 122 Supply only Battery charger 10 A, 12 Volt DC. Item No 122 3 Each
123 123 Supply only Battery charger 10 A, 24 Volt DC. Item No 123 2 Each
124 124 Supply only in replacement MCCB, 4 pole, 100 Amps, 415 Volts, breaking capacity 16 KA, adjustable thermal and adjustable magnetic setting fixed-in-repairs, including taking out old unserviceable MCCB of any description complete all as specified and as directed. Item No 124 1 Each
125 125 Supply only in replacement MCCB, 4 pole, 63 Amps, 415 Volts, breaking capacity 16 KA, adjustable thermal and adjustable magnetic setting fixed-in-repairs, including taking out old unserviceable MCCB of any description complete all as specified and as directed. Item No 125 1 EACH
126 126 Supply only DC Relay Board of AMF panel of varoius capacity of DG set complete including taking down old UNSV all as directed by Engr-in-charge Item No 126 4 EACH
127 127 Supply and filling of Engine oil 15W40 to topup/ refilling of all DG set of various capacity, model & location as mentioned here-in-before as per the standard practice . Item No 127 307 Ltr
128 128 Supply and filling of Coolant suitable for DG set Item No 128 181 Ltr
129 129 Supply and pouring distilled water for battary and radiator as directed. Item No 129 100 Ltr
130 130 Supply only BATTERY CABLE ASSEMBLY (FOR -VE & +VE) for connection of Battery to Self with copper Lugs, copper cable and copper connector of baterry as per existing size for both terminal, complete all as specified and directed. Item No 130 5 Each
131 131 Supply only of glass wool insulation (50mm thick), duly wrapped over the exhaust pipe (80 - 100 mm dia) of generating set including cladding over the insulation with aluminium foil tape complete all as directed. \nNote :- Length of exhaust pipe shall be taken into account for measurement. Item No 131 15 RM
132 132 Supplying and laying PVC insulated, armoured,heavy duty electric control cable with copper conductor, 1100 volts grade, cross sectional area 2.50 sqmm 8 core including taking down U/S cable, complete all as specified and directed. Make Havells/Plaza Item No 132 15 RM
133 133 Supply only 3 Phase 415 V , AC, 50 Hz (R,Y,B &N) DIGITAL LINE VOLTAGE MONITOR , MODEL PR-07, including taking down old unserviceable one, complete all as specified & directed.\n Item No 133 6 Each
134 134 S&F in repair changer over switch (SS Enclosure) complete with of capacity 200 Amp, 415 Volt, 4 pole, 50 HZ . \n Item No 134 1 Each
135 135 M&L for Earthing complete with copper earth plate electrode of size 600x600x3.15 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to 20×3mm copper strip as earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, earth testing point, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed.( GI wire upto 7.5m including testing consider in this item). Item No 135 2 Each
136 136 M&L for Earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI earth strip of size 32 x 6 mm earth lead by means of nuts, bolts, check nuts, washers of galvanized iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 45 x 45 x 5cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed after taking down old earthing.( GI strip upto 7.5m including testing is deemed included in the item). Item No 136 3 Each
137 137 S&F Oil pressure Sensors including taking down old unserviceable one, complete all as specified & directed. Item No 137 4 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail