Military Engineer Services-MES has published Shifting Of Electric Meters Incl Sub Main Wiring Repair Maint Of Earthing Incl Accessories And Rewiring Repair And Maint Of Em Fitting And Fixture In Certain Otm Accn Under The Area Of Age Bri Army Central In Army Area Jodhpur ( 9028/E8 ) . Submission Date for this Tender is 21-07-2021. Electrification Work Tenders in GE (A) Central Multan Line Army Area Jodhpur Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 20-Jun-2021 | corrigendum | BOQ | 28-06-2021 |
2 | 28-Jun-2021 | corrigendum | Date | 14-07-2021 |
3 | 12-Jul-2021 | corrigendum3 | Other | 14-07-2021 |
4 | 14-Jul-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 21-07-2021 |
Name of Work: SHIFTING OF ELECTRIC METERS INCL SUB MAIN WIRING, REPAIR/MAINT OF EARTHING INCL ACCESSORIES AND REWIRING,REPAIR AND MAINT OF E/M FITTING AND FIXTURE IN CERTAIN OTM ACCN UNDER THE AREA OF AGE B/R-I (ARMY) CENTRAL IN ARMY AREA JODHPUR | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down and re-fixing and connecting electric meters of any capacity and any make all as specified and direced by Engr-in-charge. | 400 | Each | |
2 | 2 | Taking down of unsv electric meter of any make any capacity and deposit to it to E/M Store and Supply and fix electronic meters temper proof LCD display with polycarbonate cover 230 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH all as specified and directed by Engr-in-charge. | 150 | Each | |
3 | 3 | Supply and fixing in repair poly carbonate transparent energy meter protection cover temper proof suitable for single phase energy meter etc complete. | 140 | Each | |
4 | 4 | Supply and fix Electric Engrey meter box for mounting of electric meter of any make, any capacity, as per IS-11731, shock proof, weatherproof, fixed at pole, surface of wall or concealed in wall and making good the distrubed surface all as specified and directed by Engr-in-Charge. Make sintex, sainik or equavilent | 200 | Each | |
5 | 5 | Taking down copper/aluminium sub main wiring surface/ concealed complete, including fixture and fittings removing materials from site of work complete or removing materials to store for keeping in safe custody or for taking credit and making good disturbed surfaces of walls, floors, etc | 1300 | RM | |
6 | 6 | M&L in repairs sub main wiring with PVC insulated and unsheathed 2 x 6 Sq mm single core multistrandred copper conductor cable passing through existing PVC / steel conduit and making good the distrurbed surface of wall incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed cable as earth wire. Note :- Two runs of cable 6 Sqmm and One run of 6 Sqmm shall be measured as one unit length. | 380 | RM | |
7 | 7 | M&L in repairs sub main wiring with PVC insulated and unsheathed 2 x 6 Sq mm single core multistrandred copper conductor cable passing through in and including PVC conduit fixed on surface ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- Two runs of cable 6 Sqmm and One run of 6 Sqmm along with conduit shall be measured as one unit length. | 580 | RM | |
8 | 8 | M&L in repairs sub main wiring with PVC insulated and unsheathed 2x 6 Sq mm single core multistrandred copper conductor cable passing through in and including PVC conduit , concealing in walls (by means of chasing including making good existing surface and matching existing surface ) ISI marked and conduit accessaries fixed on surface of wall, ceiling etc, making good the distrurbed surface, incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed as earth wire. Note :- Two runs of cable 6 Sqmm and One run of 6 Sqmm along with conduit shall be measured as one unit length. | 280 | RM | |
9 | 9 | M&L in repairs sub main wiring with PVC insulated and unsheathed 2 x 6 Sq mm single core multistrandred copper conductor cable passing through in and including PVC cassing-N-capping (20 to 32 mm) and making good the distrurbed surface of wall incl 6 Sq mm single core copper conductor cable PVC insulated and unsheathed cable as earth wire. Note :- Two runs of cable 6 Sqmm and One run of 4 Sqmm shall be measured as one unit length. | 60 | RM | |
10 | 10 | S&F sheet metal enclosure SPN 240 Volts having 2 pin and earth plug and socket complete with one single pole MCB 20 Amps all as specified Make:Legrand or equivalent ABB/Scheinder.complete all as specified and directed by Engr-in-charge. | 20 | Each | |
11 | 11 | Supply and fixing Triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole 63 amp MCB complete all as specified and directed by Engr-in-charge. | 25 | Each | |
12 | 12 | S&F sheet metal enclosures 240 volt with suitable rated bus bar for double door IP-42 DB's suitable for one MCB SPN as incoming and 2 MCB SP as out going,SPN 4Way complete all as specified and directed by Engr-in-charge. Make :-Havells/Legrand/ Indo Asian/ABB | 16 | Each | |
13 | 13 | S&F sheet metal enclosures 240 volt with suitable rated bus bar for double door IP-43 DB's suitable for one MCB SPN as incoming and 6 MCB SP as out going SPN 8 way complete all as specified and directed by Engr-in-charge. Make :-Havells/Legrand/ABB | 44 | Each | |
14 | 14 | S&F Vertical Distribution Board, double Door, suitable for 'A' Frame FP MCCB 100A made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, TPN 4 way, 415 volts with bus bar rating 300 Amps, dust and vermin proof, suitable for incorporation of MCB’s and MCCB etc and making all necessary connections, duly flush of wall surface, complete all as specified and directed. Make : Havells Cat Part No DHDLVSRWGOFO04 / Schneider Elect / Legrand / ABB Note : MCCB & MCB will be measured and paid separately under respective items | 26 | Each | |
15 | 15 | S&F sheet metal enclosures 415 volt TPN 4 way with 200 Amp rated bus bar, double door IP-43 DB's suitable for With one No 100 Amp 10 KA TPN MCCB as incoming complete all as specified and directed by Engr-in-charge. Make :-Havells/Legrand/ABB | 24 | Each | |
16 | 16 | Supply and Fix MCB Single pole"C" series 5-32 Amps ISI marked.Make :-Havells/Legrand/ABB | 240 | Each | |
17 | 17 | Supply and Fix MCB Single pole & neutral "C" series 40 Amps ISI marked.Make :-Havells/Legrand | 40 | Each | |
18 | 18 | Supply and Fix MCB Single pole & neutral "C" series 63. Amps ISI marked.Make :-Havells/Legrand/ ABB | 84 | Each | |
19 | 19 | Supply and fixing in repair MCB TPN C Curve 63 Amps Make: Legrand /Havells/ABB | 32 | Each | |
20 | 20 | Supply and fixing in repair MCCB 100 amp TPN, 415 volts 16 KA rupturing capacity including proper thimbles, fixing on DB'S complete all as specified and directed Make : Legrand/ABB | 15 | Each | |
21 | 21 | Supply and fixing in repair MCCB 125 amp TPN, 415 volts 16 KA rupturing capacity including proper thimbles, fixing on DB'S complete all as specified and directed Make : Legrand/ABB | 10 | Each | |
22 | 22 | Supply and fixing in repair MCCB 200 amp TPN, 415 volts 16 KA rupturing capacity including proper thimbles, fixing on DB'S complete all as specified and directed Make : Legrand/ABB | 6 | Each | |
23 | 23 | Earthing complete with galvanised steel earth plate electrode 60 x x60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) wih top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in elevtrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion . Note : Rates are deemed to be included for necessary earth work , earth pit with RCC cover of size 300X300 x25 mm etc complete | 40 | Each | |
24 | 24 | Earthing complete with galvanised steel earth plate electrode 60 x x60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) wih top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in elevtrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion . Note : Rates are deemed to be included for necessary earth work , earth pit with RCC cover of size 300X300 x25 mm etc complete | 20 | Each | |
25 | 25 | Supply and fixing Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire all as specified and directed by EIC. | 160 | RM | |
26 | 26 | Supply and fixing Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required , but 25x4mm galvanised iron strip all as specified and directed by EIC. | 180 | RM | |
27 | 27 | Removing existing unsv earthing for maintenance and Supply and fix Galvanised, steel earth plate, size of 60cmx60cmx6 mm all as specified and directed by Engr-in-charge. | 30 | Each | |
28 | 28 | Supply and laying Common salt commercial and laying in earthing pit in layers all as specifed and direced by Engr -in- charge. | 6 | Qtl | |
29 | 29 | Supply and laying Charcoal dust/Breeze and laying in earthing pit in layers all as specifed and direced by Engr -in- charge. | 6 | Qtl | |
30 | 30 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for laying of cables etc. and n.exc 1.5m in depth and getting out in any type of soil. | 27 | Cum | |
31 | 31 | Returning, filling in trenches with excavated soil, including spreading, levelling watering and well remain in la ers not exceeding 25cm thick complete. | 20 | Cum | |
32 | 32 | Removing excavated material (soil) not exceeding 50 meter and deposing where directed at a level not exceeding 1.5 meter above the starting point. | 10 | Cum | |
33 | 33 | sand cushioning to under ground cable using river sand and gently punning or cushioning ot cable all as specified. | 10 | Cum | |
34 | 34 | S & L Jodhpur stone cable quarry faced stone slab cover 40 to 50 mm thick, 25cm to 30 cm long laid dry and abutting each other with gap between adjacent slab not exceeding 10mm over under ground cables for protection | 50 | Nos | |
35 | 35 | M & L pipe galvanized iron light grade complete with all fitting laid in road crossing and on pole building complete all as specified and directed ISI marked of 40mm bore. | 60 | RM | |
36 | 36 | Supply and laying or fixing or passing through pipe,1100 volts grade heavy duty cable with PVC insulated aluminium solid stranded conductor served with an inner sheathing of PVC tape and overall pvc sheathed 10sq mm nominal cross sectional area 2 core | 200 | RM | |
37 | 37 | Supply and laying or fixing or passing through pipe,1100 volts grade heavy duty cable with PVC insulated aluminium solid stranded conductor served with an inner sheathing of PVC tape and overall pvc sheathed 16 sq mm nominal cross sectional area. | 150 | RM | |
38 | 38 | Supply, laying, testing and commissioning of LT cable, XLPE insulated, PVC sheathed, galvanized steel strip armoured electric power cable with stranded aluminium conductor, 1100 volts grade of size 16 sqmm 3.5 core confirming to IS:7098 (Part-I), suitable for earthed system, laid in duct/trench/along pole/wall etc including nuts, bolts, washers, saddles & screws etc and making connection, complete all as directed. | 180 | RM | |
39 | 39 | Supply, laying, testing and commissioning of LT cable, XLPE insulated, PVC sheathed, galvanized steel strip armoured electric power cable with stranded aluminium conductor, 1100 volts grade of size 25 sqmm 3.5 core confirming to IS:7098 (Part-I), suitable for earthed system, laid in duct/trench/along pole/wall etc including nuts, bolts, washers, saddles & screws etc and making connection, complete all as directed. | 180 | RM | |
40 | 40 | Supply, laying, testing and commissioning of LT cable, XLPE insulated, PVC sheathed, galvanized steel strip armoured electric power cable with stranded aluminium conductor, 1100 volts grade of size 50 sqmm 3.5 core confirming to IS:7098 (Part-I), suitable for earthed system, laid in duct/trench/along pole/wall etc including nuts, bolts, washers, saddles & screws etc and making connection, complete all as directed. | 160 | RM | |
41 | 41 | Taking down copper/aluminium point wiring surface/ concealed (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting, bell etc. removing materials from site of work complete or removing materials to store for keeping in safe custody or for taking credit and making good disturbed surfaces of walls, floors, etc. | 720 | Point | |
42 | 42 | M&L for point wiring complete with using 1.5 sq mm single core multi stranded copper conductor PVC (FRLS) insulated unsheathed cable confirming to IS-694,1100 Volts grade ISI Marked( Make: Havells/polycab ) passing in and including PVC conduit fixed on PVC saddle and clamp (ISI Marked) with accessories fixed on surface of wall / roof / ceiling etc in sunken pressed steel terminal boxes in wall,including 3.00 mm thick plastic laminated hylem sheet and 1.50 sq mm PVC insulated unsheathed stranded copper conductor(FRLS) cable for common earth and connecting to earth dolly material and labour for :-(a) One light point controlled by one, one way switch | 110 | Point | |
43 | 43 | (b) One fan point controlled by one way switch. | 42 | Point | |
44 | 44 | (c) One socket outlet 3 pin 5/6 Amps on same board | 32 | Point | |
45 | 45 | (d) One socket outlet 3 pin 5/6 Amp on independent board | 48 | Point | |
46 | 46 | All as per item No 42 above but with using 2.5 Sq mm single core multistanded copper conductor cable and 2.5 sq mm PVC insulated unsheathed stranded copper conductor for common earth wire for 6 pin 16 Amp socket outlet on independent board . | 24 | Point | |
47 | 47 | M&L for Point wiring complete with 1.5 sq mm single core multi stranded copper conductor PVC (FRLS) insulated unsheathed cable confirming to IS-694,1100 Volts grade ( Make: Havells,polycab) ( ISI Marked) passing in PVC cassing-N-capping 25/32 mm dia fixed on surface of wall/roof/ceiling with existing/new sunken pressed steel terminal boxes including 3.00 mm thick plastic laminated sheet top cover and 1.50 sq mm PVC insulated unsheathed stranded copper conductor(FRLS) cable for common earth and connecting to earth dolly material and labour for:-(a) One light point controlled by one, one way switch | 96 | Point | |
48 | 48 | (b) One fan point controlled by one way switch. | 32 | Point | |
49 | 49 | (c) One socket outlet 3 pin 5/6 Amps on same board | 32 | Point | |
50 | 50 | (d) One socket outlet 3 pin 5/6 Amp on independent board | 48 | Point | |
51 | 51 | All as per item No 47 above but with using 2.5 Sq mm single core multistanded copper conductor cable including 2.5 sq mm PVC insulated unsheathed stranded copper conductor for common earth wire for 6 pin 16 Amp socket outlet on independent board . | 24 | Point | |
52 | 52 | M&L for concealed Point wiring complete with 1.5 sq mm single core multi stranded copper conductor PVC (FRLS) insulated unsheathed cable confirming to IS-694,1100 Volts grade ISI Marked , class V ( Make: Havells, polycab ) in concealed PVC conduit (ISI Marked) not less than 20 mm dia heavy duty with accessories etc and including sunken pressed steel terminal boxes in wall, including 1.50 sq mm PVC insulated unsheathed stranded copper conductor (FRLS) cable for common earth and connecting to earth dolly material and labour for (Note- rates of chasing/cutting & making goods shall be included in the unit rate) :-(a) One light point controlled by one-one way switch. | 96 | Point | |
53 | 53 | (b) One ceiling fan/Exhaust fan point controlled by one, one way switch through Regulator. | 32 | Point | |
54 | 54 | (c) One three pin 5/6 Amp socket on same board with other switches. | 32 | Point | |
55 | 55 | (d) One three pin 5/6 Amp socket on independent board. | 48 | Point | |
56 | 56 | All as per item No. 52 above but with 2.5 Sq.mm. (nominal area) cable for one 3 Pin 16 amp socket on independent board including one 1.5 sqmm copper conductor multi stranded green colour PVC insulated unsheathed cable 1100 volts grade as earth wire upto common earth & connected to earth dolly complete all as specified and directed by Eng.-in-charge. | 24 | Per Point | |
57 | 57 | S&F switch piano flush type single pole one way 6 Amp ISI Marked.Make: Havells/Legrand/ABB | 648 | Each | |
58 | 58 | S&F switch piano flush type single pole one way 16 Amp ISI Marked.Make: Havells/Legrand/ABB | 72 | Each | |
59 | 59 | S&F socket outlet 2 in 1, 5 pin, 6 Amp flush type ISI Marked.Make: Havells/Legrand/ABB | 240 | Each | |
60 | 60 | S&F socket outlet 2 in 1, 6 pin, 6 and 16 amp flush type ISI Marked.Make: Havells/Legrand/ABB | 72 | Each | |
61 | 61 | M & L for Ceiling rose, 3 terminal/PVC/ polycarbonate, isolated body.Make: Havells/Legrand/ABB | 408 | Each | |
62 | 62 | M & L for Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fitting. Make:Havells/Leader | 80 | Each | |
63 | 63 | Supply and fix socket type(2 Module) electonic fan regulator flush type ISI Marked.Make: Havells/Legrand/ABB | 80 | Each | |
64 | 64 | Taking down and re-fixing/ hanging only ceiling fan (M.D. supply) and connecting up including provision of cable from ceiling rose or connector to fan | 72 | Each | |
65 | 65 | Taking down and refixing only exhaust fan (M.D.supply) and connecting up including provision of cable from ceiling rose/connector to fan | 24 | Each | |
66 | 66 | Supply and fixing repair electronic driver as per sample for LED fitting up to 15watt Make Crompton/Havells/CG/Philips. | 14 | Each | |
67 | 67 | Supply and fixing repair electronic driver as per sample for LED fitting up to 36watt Make Crompton/Havells/CG/Philips. | 16 | Each | |
68 | 68 | Supply and fixing in repair MCB SP C Curve 5-32 Amps Make: Legrand /Havells/ABB | 220 | Each | |
69 | 69 | Supply and fixing in repair MCB SPN C Curve upto 40 amp Amps Make: Legrand /Havells/ABB | 25 | Each | |
70 | 70 | Supply and fixing in repair MCB SPN C Curve 63 Amps Make: Legrand /Havells/ABB | 40 | Each | |
71 | 71 | Supply and fixing in repair MCB TPN C Curve 63 Amps Make: Legrand /Havells/ABB | 22 | Each | |
72 | 72 | Fixing LED batten fittings 20/22 watt, ,branded make such as Havells/Surya/ Phillips/Bajaj etc.including 1Nos tube rod complete with all accessories. | 150 | Each | |
73 | 73 | S&F LED bulk head light10 watt complete with all accessories pre wired and including connecting up to fiting with flexible cable of suitable size..Make: Crompton/ Havells/Phillips/Bajaj/ CG | 20 | Each | |
74 | 74 | S & F LED tube road upto 22 watt incl connection complete all as specified and directed. Make: CG/ Havells | 30 | Each | |
75 | 75 | S&F Decorative wall light made up of high grade engineering plastic material suitable for 9 W LED lamp cap part Havells -LHFOFWE1TZ1W012 or equivalent in CG/Bajaj | 14 | Each | |
76 | 76 | Supply and fixing repair one bakelite sheet not less then 3mm thick after removing all connection including cutting/chassing to accommedate existing fitment and making connection including cadmium plated screws with cup washer of fwg size:-(a) 10'' x 8'' | 40 | Each | |
77 | 77 | (b) All as per item No 76 above but size 7'' x 5'' | 40 | Each | |
78 | 78 | (c ) All as per item No 76 above but size 5'' x 5'' | 60 | Each | |
79 | 79 | Supply only GLS Coloured Lamp Red,Green,Milky,0-60 Watt Make Philps/CG/Havell | 40 | Each | |
80 | 80 | Supply and fixing in repair PVC conduit 20/25mm ISI (MMS) grade all as specified and directed.Make : Polycab/Plaza/Kalinga | 150 | RM | |
81 | 81 | Supply and fixing in repair PVC cassing Capping 25mm ISI (MMS)all as specified and directed. Make : Polycab/Plaza/Kalinga | 150 | RM | |
82 | 82 | Supply and fixing repair PVC insulated and unsheathed FRLS single core multistranded copper conductor for repair, in existing conduit of size 1.5 sqmm as in replacement of any defective/burnt circuit. | 120 | RM | |
83 | 83 | Supply and fixing repair PVC insulated and unsheathed FRLS single core multistranded copper conductor for repair, in existing conduit of size 2.5 sqmm as in replacement of any defective/burnt circuit. | 150 | RM | |
84 | 84 | Supply and fixing repair PVC insulated and unsheathed FRLS single core multistranded copper conductor for repair, in existing conduit of size 4.0 sqmm as in replacement of any defective/burnt circuit. | 80 | RM | |
85 | 85 | Supply and fixing repair PVC insulated and unsheathed FRLS single core multistranded copper conductor for repair, in existing conduit of size 6.0 sqmm as in replacement of any defective/burnt circuit. | 80 | RM | |
86 | 86 | Supply and fix remote bell ding dong type all as specified and direcected by Engr-in-charge. | 6 | Each | |
87 | 87 | Supply and fix in repair 2-Watt LED Wall Light (bed light) for reading all as specified and directed by Engr-in-charge make Philips 30975 or equivalent in Havells/ crompton etc. | 6 | Each | |
88 | 88 | Supply and fix in repair LED Surface Downlighter (False Ceiling Light) 12 watt of size 173.5 x 173.5 mm all as specified and directed by engr-in Charge. Make crompton/havells/Philips | 18 | Each | |
89 | 89 | supply and fix in repair Spot light 6 Watts Black/ white Body LED Spot Light, Focus Light (Warm White) all as specified and directed by engr-in- charge Make crompton/havells/Philips | 18 | Each | |
90 | 90 | Supply and fix emergency bulb 12 watt, 6500k 220-240 Volt 50 Hz PF > .90 with Battery backup upto 4hr all as specified and directed by Engr-in-charge Make: Polycab Aelius 12W Emergency Bulb (White) or equivent in havells/ crompton | 80 | Each | |
91 | 91 | S & F Street light bracket made out of medium grade GI Pipe 32mm dia bent to shape including GI Clamps nut,bolts washers,reducer of required size for suitable any type fittings etc complete including necessary painting all as specified and directed by Engr-in Charge. | 42 | Each | |
92 | 190 | Note for all above items:-All items in BOQ are for"Materials and labour /Supply and fix" and to be executed in "Repairs" unless otherwise specifically mentioned as "Supply only" or "fixing only" in BOQ. Contractors are required to quote their rates accordingly. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail