Special Repair Of Narmada Pipe Line , Pump House No 05 And 06 And Connected Items At Mil Stn Bhuj And Provn On Uninerrupted Power Supply , Earthing , Air Conditioning And Accessories For Project At Shiyot Under Ge Army Bhuj

Tender Notice

28101729
Corrigendum : Special Repair Of Narmada Pipe Line , Pump House No 05 And 06 And Connected Items At Mil Stn Bhuj And Provn On Uninerrupted Power Supply , Earthing , Air Conditioning And Accessories For Project At Shiyot Under Ge Army Bhuj
Indian
Gujarat
24-06-2021
01-07-2021
03-07-2021

Tender Details

Special Repair Of Narmada Pipe Line , Pump House No 05 And 06 And Connected Items At Mil Stn Bhuj And Provn On Uninerrupted Power Supply , Earthing , Air Conditioning And Accessories For Project At Shiyot Under Ge Army Bhuj

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Jun-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-07-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 86000.00 /-
Tender Value
INR 43 Lakhs /-

BOQ Items

SPECIAL REPAIR OF NARMADA PIPE LINE, PUMP HOUSE NO 05 AND 06 AND CONNECTED ITEMS AT MIL STN BHUJ AND PROVN ON UNINERRUPTED POWER SUPPLY, EARTHING, AIR CONDITIONING AND ACCESSORIES FOR PROJECT AT SHIYOT UNDER GE ARMY BHUJ
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply and laying of power cable of size of FR PVC insulated copper conductor,single core (2.5 sq mmx 2 Run + 1x2.5 Sq mm earth wire) for sub main wiring in PVC casing caping complete all as directed. 600 RM
2 2 M&L for point wiring for One light/fan/exhaust fan/buzzer point controlled by one,one way switch with using 1.5 Sqmm (nominal sectional area) multi stranded copper conductor, single core, FRLS PVC insulated & unsheathed cable, 1100 volts grade with and including PVC casing & caping accessories of adequate size fixed on surface with PVC rawl plugs with and including sunken type pressed steel terminal boxes of required size of not less than 1.6 mm thick factory made and factory painted with top cover 3mm thick plastic laminated sheet fixed with brass screw and washer with all accessories including single core multi-stranded copper conductor 1.5 sqmm size PVC insulated unsheathed cable as earth wire to common earth and connected to earth dolly drawn in same conduit/casing capping complete (a) One 3 pin socket out let 5 amp point independent\nNOTE :- (i) Quoted rate shall be deemed to include the cost of cutting chases in walls / pillars /column etc. of any description for concealing the boxes to required depth & making good the disturbed surface in CM 1:4 including finishing the surface to match with the existing surface. \n(ii) Fittings like switches, sockets, regulators, lamp holders, light fittings shall be measured and paid for separately under appropriate item of Schedule `A'.\n(iii) The quoted rates shall be deemed to be inclusive for provision of covering sunken boards/terminal boxes / junction boxes of any shape and size with 3mm thick laminated sheet fixed with suitable brass screws and cup washers 15 Per Point
3 3 All as per item No-02 here in before but with 4 Sq mm size pvc insulated and unsheathed 1100 volts grade single core stranded (multistrand) copper conductor cable for 3 pin socket outlet 15 amp on independent board and 4 sqmm size earth wire complete all as specified and directed 15 Per Point
4 4 S & F earth plug and socket, single pole, neutral sheet metal enclosures with a two pin, plug and socket 20Amp, 240 volts of Havells or equivalent of L & T with and including one MCB, SP, 20A, 240 Volts all as specified and directed. 16 Each
5 5 S&F switch flush type, 5/6 Amps, single pole, one way, 230 volts AC circuit complete all as specified and directed. 15 Each
6 6 S&F switch socket outlet combination, multipurpose, three pin, 15 Amps & three pin 5 Amps controlled by one switch , flush type, 230 volts AC circuit complete all as specified and directed. 15 Each
7 7 Supplying and fixing sheet metal enclosure powder painted for MCB DB vertical type TPN 8 way double door with dinrail and busbar with IP-43 protection with door earthing and isolated neutral bar and insulated busbar assembly suitable for MCCB of 125 Amps complete all as specified and directed 3 Each
8 8 S&F MCB single pole, 6 to 32 Amps in `C’ series having current rating 10 KA complete all as specified and directed :\n 18 Each
9 9 M/L for Sub main wiring with 2 runs of PVC insulated unsheathed multi stranded single core copper conducter 4 Sqmm drawn through PVC casing capping including accessaries with 4 sqmm PVC insulated earth wire fixed to the existing wall with saddles, screws etc all as directed. Note: 2 runs of cable and one run earth wire and conduit/Casing & Caping will be measured as one length. 70 RM
10 10 Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, earthed of size 50 Sqmm, 3.5 core laid in trenches / poles / fixed to walls etc complete all as specified and directed. 250 RM
11 11 Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, earthed of size 25 Sqmm, 4 core laid in trenches / poles / fixed to walls etc complete all as specified and directed. 350 RM
12 12 Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, earthed of size 16 Sqmm, 4 core laid in trenches / poles / fixed to walls etc complete all as specified and directed. 250 RM
13 13 Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100 volts grade, earthed of size 10 Sqmm, 2 core laid in trenches / poles / fixed to walls etc complete all as specified and directed. 300 RM
14 14 Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed 371.5 Cum
15 15 All as per item No-14 here in before but for additional 1.5 m or part there of in depth beyond the first 1.5 m 5 Cum
16 16 Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil. 276 Cum
17 17 Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils. 107.5 Cum
18 18 Material and labour for sand cushioning in cable trenches over & under the cables, with river washed coarse sand, as per standard practice with proper compaction complete all as specified and directed. (Punned thickness 18 cm shall be considered for payment as per para 19.75 of SSR Part-I). 81 Cum
19 19 Supply and lay un-reinforced precast concrete cable cover , class , LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables. 5000 Each
20 20 S & F GI pipe, light grade, of size 80 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection . 10 RM
21 21 S & F GI pipe, light grade, of size 40 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, complete all as speicifed and directed for cable protection . 30 RM
22 22 M&L for earthing complete with Copper earth plate electrode 600mm X 600mm X 3.15mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to Copper strip 20 X 3 mm , (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth GI earth wire/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’\nNOTE - The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B1 cover 50mm thick reinforced with 8mm dia TMT bars @ 150mm C/C both ways, funnel with watering pipe 14 Each job
23 23 M&L for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized earth lead 32 X 6 mm , (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth GI earth wire/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’\nNOTE - The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B1 cover 50mm thick reinforced with 8mm dia TMT bars @ 150mm C/C both ways, funnel with watering pipe 3 Each job
24 24 Fabricate, Supply, Install, Testing and Commissioning LT Panel Board outdoor type factory made CPRI tested made out of CRCA sheet steel enclusure 3 mm thick including copper bus bar 4 pole 300 Amps capacity including wiring of rated capacity PVC insulated copper conductor cable, insulators, fasteners etc with Digital Ammeter & Voltmeter, selector switches for voltmeter and ammeter, indicator lamp RYB (01 Set), CTs, including MS Angle Frame of size 50 X 50 X 6 mm structure at bottom, PCC foundation 1:2:4 for foundation etc comprising for the following :-\nNote : The contractor shall submit detail Schematic Layout of the Panel Board for approval from Accepting officer before procurement. 1 Each Job
25 24.01 (a) Copper Bus Bar 300 A rating for 3 Phase and 200 A for Neutral - 01 Set
26 24.02 (b) Digital Voltmeter 0 to 500 V
27 24.03 (c) Digital Ammeter 0 to 400 Amps with CT Coils and selector switch - 01 No
28 24.04 (d) LED Indication Lamp for 3 Phase - 01 Set
29 24.05 (e) MCCB 4 Pole 160 Amps 25 KA - 01 Nos (01 No for Incoming)
30 24.06 (f) MCCB 4 Pole 100 Amps 25 KA - 02 Nos (02 No for Outgoing )
31 24.07 (g) MCCB 4 Pole 63 Amps 25 KA - 02 Nos (for Outgoing)
32 25 Supply and fix MCCB thermal magnetic release 3 pole 125 Amps 16 KA including necessary lugs of any size and capacity complete all as specified and directed by Engr-in-charge 3 Each
33 26 Supplying, erecting and fixing in true vertical position, Prestressed cement concrete pole 9Mtr long confirming to IS-1678 (latest version) with minimum cross sectional area 102 x 152 mm at top and 102 x 289mm at bottom, class- 10 with and including all necessary excavation & earth work in any type of soil for foundation of poles, PCC (1:3:6) type C-2 using 40mm graded crushed stone aggregates as in foundations of size not less than 1.2 x 0.6 x 1.65m below ground level, PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates as in plinth block or coping of size 600x600x300mm above ground level, including necessary form work and removing surplus soil to a distance n. exc 50m & depositng where directed. Providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm wide in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enamel painted letter of shape & size complete all as specified and as directed. (Note:- SSR Part-I clause No. 19.5 & 19.52 and other relevant clauses of SSR refers for execution of work and poles shall be procured direclty from the manufacturer mentioned in tender documents) \nNote : The rate quoted by contractor shall exclude the cost for excavation and PCC mix in separate item 10 Each
34 27 Material and labour for PCC 1:3:6 type C2 using 40 mm graded stone aggregate (for poles/stay assembly foundation) including necessary form work. 5 Cum
35 28 Material and labour for PCC 1:2:4 type B1 using 20 mm graded stone aggregate for coping of foundation including necessary form work. 1 Cum
36 29 Supply and fix in repairs Weather Proof PVC Junction Box made out of not less than 2 mm thick of size 250x200x100 mm (approx) complete with hinged door locking arrangement and consisting of 01 No panel mounted connector 4 pole 32 A - 01 No MCB SP 06 Amps 10 KA - 01 No incl 02 Nos Cable Glands suitable for inserting cable not less than 50 sqmm with 02 No 01 mm GI plate (150x50mm) having two holes as per the size of cable glands, fixed with cable gland for earth connectivity confirming to IP 65 complete including fixing on street light pole with MS Clamps, bolts, nuts and washers all as specified and directed by Engr-in-Charge.\n 10 Each
37 30 Supplying,installing, testing and commisioning energy efficient LED street light fitting having nominal power consumption of 45 W with lamps, IP protection 65 and surge protection device of 4 KV including 3 core 1.0 sqmm service cable connected to power supply on 9 mtr pole complete all as specified and directed by Engr-in-charge. 10 Each
38 31 Supply and fixing mounting bracket made out of medium grade GI tubing 32mm bore 1.5 M long & bend to shape including 02 Nos MS Clamps, Nut Bolts, Washers etc complete all as specified and as directed by Engr-in-charge 10 Each
39 32 Supplying, installing, commissioning and testing of split type air conditioning unit indoor / outdoor complete with cordless remote control unit and with in built with BEE 5 star rating inverter type with CFC refrigerant 1.5 tonne capacity complete and comprising of the following :- \na) Room evaporator indoor unit with speed blower fan of approipriate capacity including PCB, thermostatic control, air filter and drain for condensing water,\nb) Outdoor condensing unit of capacity 5175 Kcal / Hr capacity with condensor fan motor of appropriate capacity - 01 No. air cooled condensor of capacity 1.5 TR-01 No. shall be installed outside the building on and including suitable factory made mild steel brackets fixed on wall using fastners for fixing and installing of ACs,\nc) Refrigerant copper pipe of suction and discharge line with insulation, condensing water drain pipe & protected by suitable size of flexible PVC conduit with control valves & safety accessories including complete wiring for evaporator & condensing unit with fixing of suitable size of copper cable,\nd) Making good the disturbed surface to match with the existing surface after pluging the holes complete all as specified and directed. Make :- LG / Blue Star / Voltas as per model approved by the GE.\nNote :- The unit rate quoted by the contractor shall deem to be inclusive of \n(i) Cutting holes in walls / windows of any thickness for installation of AC, connection and making good the disturbed surface to match with the thickness for installation of AC etc, connection.\n(ii) Electric cable of size 4 sqmm copper conductor PVC sheathed and of required length to connect outdoor unit and outdoor unit to voltage stablizer.\n(iii) Copper piping with insulation and drain piping. 7 Each
40 33 Supply and Fix Voltage stabilizer for automatic operation,single phase anturally air cooled indoor type,& designed for input variation between 170 V to 280 V with out put voltage stabilized at 230 V of capacity 4 KVA. 7 Each
41 34 Supply and Fix 10 KVA capacity online double conversion type UPS system suitable for \n(a) Three Phase input Rectifier cum Battery charger ( 300 to 450 V, 47 to 53 HZ, AC)\n(b) Single phase output inverter ( 230V, 50HZ, AC)\n(c ) Inbuilt static switch\n(d) MS Powder coated IP 21 Enclosure with structured black finish\n(e) Inbuilt inverter output isolation transformer\n(f) Front panel LED indications and LCD display for parameters\n(g) SMF Batteries for 30 min stand by time ( 30 Nos of 12V/26AH, along with MS powder coated open rack, Battery inter connecting links, Battery isolator and UPS to battery cable of 5 mtrs length\nMake of Battery : exide / Quanta\nMake of UPS : APLAB / Luminous 2 Each
42 35 Supply and Fix 1 KVA capacity online double conversion type UPS system suitable for \n(a) Single Phase input Rectifier cum Battery charger ( 195 to 265V, 47 to 53 HZ, AC)\n(b) Single phase output inverter ( 230V, 50HZ, AC)\n(c ) Inbuilt static switch\n(d) MS Powder coated IP 21 Enclosure with structured black finish\n(e) Inbuilt inverter output isolation transformer\n(f) Front panel LED indications and LCD display for parameters\n(g) SMF Batteries for 30 min stand by time ( 8 Nos of 12V/26AH, along with MS powder coated open rack, Battery inter connecting links, Battery isolator and UPS to battery cable of 5 mtrs length\nMake of Battery : exide / Quanta\nMake of UPS : APLAB / Luminous 10 Each
43 36 Supply install testing and commissioning of Diesel engine driven genrating set 415 Volts, 3 Phase 4 wire, engine as per IS : 10001/10002 and alteranator as per IS 13364 with AMF panel complete with foundation as per design, control panel with necessary meter and sound proof canopy as per CPCB norms of capacity 40 KVA. Tools and spares complete all as specified and directed and comprising of the following :- 1 Each job
44 36.01 AMF Panel : The AMF Panel microprocessor based outdoor type double door type shall be designed for Automatic ON mains failure operation of the generator sets made with hinged doors, fabricated from 3.15 mm CRCA sheet metal and panel shall complete with interconnections, insulators, two number of earthing lugs and with suitable rating of MCCB at incoming and outgoing ends and shall incorporate the followings - \n(i) Electric contactors for both DG and main supply\n(ii) Main Supply voltage monitor\n(iii) AMF logic unit having protection for over frequency, under frequency, over voltage, under voltage, low lube oil, and high water temperature for engine\n(iv) Main supply voltage monitor\n(v) Combined meter (MFM) for voltage, current, frequency, KVA, KWH and PF\n(vi) Battery charger consisting of Transformer, Rectifier, DC Voltmeter, DC Ammeter, Charging rate selector switch\n(vii) Auto / Manual mode switch\n(viii) MCB using for indicators and meters\n(ix) Hooter 24 V DC\n(x) indicators for main supply and DG supply\n(xi) By pass arrangement
45 36.02 (a) Engine: Diesel engine,direct injection, water cooled 80.2 BHP @ 1500 RPM for continuous duty of suitable for 40 KVA alternator with provision of 10% over load for one hour in every 12 hour running confirming to BS 5514/ISO 3046 standard. Totally enclosed, electric start, compression ignition,4 cylinder, inline, 4 stroke. The engine shall consists of following specification :- \nThe scope of supply includes: \n-Electrical starter motor 12V DC, Battery charging alternator\n- Turbo charger, pulse tuned exhaust manifold, stainless steel exhaust flexible connection\n-Radiator cooling,with turbo charged after cooling\n-Mechanical Fuel injection Pump\n-Electronic Governor \n-Dual spin-on fuel filter \n-Spin-on full flow lub oil filter \n-Residential silencer \n-Dry type air cleaner \n-Recovery bottle \n-Shut-off coil with safeties for LLOP/HWT \n-Flywheel and flywheel housing to suit single bearing alternator \n
46 36.03 (i) Alternator: suitable for operation at 1500 RPM, 415 Volts, \n0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire system, \nconforming to BS 5000 / IS 4722. The Alternator is brushless \ntype, screen protected, revolving field, self excited, self \nregulated through an AVR. The alternator has the following \nfeatures: \n-+ 1.0 % Voltage regulation (max.) in static conditions \n-IP: 23 Enclosure \n-Permissible overload of 10% for one hour in 12 hours of \noperation as per standards
47 36.04 (ii) Mounting arrangement: Engine and alternator are mounted \non a common MS fabricated base frame with AVM pads. The steel shall be TESO / SAIL or equivalent make
48 36.05 (iii) Control panel: The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for a weather-proof, long lasting finish. \nThe control panel consists of following parts: \n-Standard engine instrumentation \n-Multi function meter which measures: \n1) Individual phase current (Amps) \n2) Phase voltages (V) \n3) Generator output frequency (Hz) \n4) Engine water temperature (Deg.C) \n5) Lube oil pressure (kg/cm2) and equipped with hour \ncounter \n-MCCB of suitable rating \n-Key switch \n-Push button (Starter) \n-LED: Battery charging alternator fail indication \n-Current transformers \n-Instrument fuses duly wired and ferruled \n
49 36.06 (iv) Others: -Fuel tank suitable for 8 hours of operation \n-One charged battery 12V, suitable rating AH with battery leads & cable
50 36.07 Acoustic enclosure: \nThe acoustic enclosure is made of 1.6/ 2 mm thick CRCA sheets and structural/ sheet metal base frame duly painted. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75 dBA at 1mtr sound levels specified by Ministry of Environment & Forest. The enclosure has the following features: \n-Specially designed to meet stringent MOEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions, -Single point lifting for easy handling, -Designed to have optimum serviceability -Air inlet louvers specially designed to operate at rated load, -Made on special purpose CNC machines for consistency in quality and workmanship, -Powder coated for long lasting service life and superior finish, -With UV resistant powder coating, can withstand extreme environments, -Use of special hardware for longer life, -Insulation material meets exacting IS 8183 specifications for better sound attenuation, -Flush styling - no projections, -Fluid drains for lube oil and fuel, -Fuel filling point
51 36.08 (v) One set of accessories (As per manufacturer's instructions :
52 36.09 (a) Level indicator on fuel tank
53 36.1 (b) Drain plug
54 36.11 (c) MS class "C" piping, suitable dia and length for fuel inlet from tank to engine as per manufacturers instructions.
55 36.12 (d) Fuel strainer and fuel tank with air vent.
56 36.13 (e) Battery heavy duty 12 Volts lead acid type fully charged, indication of high flow charging changed. - 01 Nos
57 36.14 (f) Cable connection from alternator to DG set control panel as directed
58 36.15 (vi) Two years spare parts suitable for the DG Set
59 36.16 (a) Air filter - 06 Nos
60 36.17 (b) Fuel filter - 06 Nos
61 36.18 (c) Fuel element - 06 Nos
62 36.19 (d) Battery testing meter (Hydro) - 01 No
63 36.2 (e) Suitable fan belt set - 01 set
64 36.21 (f) Regulator cut out - 06 Nos
65 36.22 (vii) Tools (As per manufacturers instructions
66 36.23 (aa) 'D' spanners - 01 Set
67 36.24 (ab) Ring spanners - 01 Set
68 36.25 (ac) Screw driver 5" to 12" - 01 Set
69 36.26 (ad) Cutting plier 9" - 01 No
70 36.27 (ae) Hammer 2 LBS - 01 No
71 36.28 Note : Rate of Cable suitable size for connecting AMN panle to DG set deemed to be included in quoted rate
72 37 PCC 1:3:6 type C2 using 40 mm graded crushed stone aggregate as in foundation, filling mass concrete as in pole complete all as directed. 26.5 Cum
73 38 Taking down existing, 200mm bore cast iron pipe lines / water mains of any description / grade and in position including all fittings, accessories and fixtures etc existing in between pipe line, by taking out and opening any type of joints (Tyton /Gasket / Lead joints) complete all as specified and directed. 200 RM
74 39 Supply, laying, connecting, jointing and testing complete ductile iron pipe with spigot and socket ends centrifugally cast class K-9 , 200 mm (8'') dia ( in any length suitable for titan joint confirming to IS 8329-2000, laid in trenches complete all as specified and directed of size complete all as specified and as directed. 200 RM
75 40 Taking up or down existing 200mm bore of pipe cast iron sluice valves of any description and in any position, removing to store including taking out joints complete all as specified and directed.\n(NOTE : Sluice valves other than those dismantled with taking up or down of cast iron pipe lines shall be measured and paid for under this item) 2 Each
76 41 Supply, installation, fixing, jointing and testing, ISI Marked, 200mm bore of pipe cast iron sluice valve of class PN-1.6 conforming to IS-14846 of 2000 both ends flanged with iron wheel head and stainless steel spindle, long body type, jointed on both ends with and including rubber gasket joints, nut, bolts & washers and tested complete all as specified and directed. 2 Each
77 42 Supplying, fixing, jointing and testing Ductile Iron fittings such as bend, tee, socket, colour, Reducer, Tail Pieces etc. suitable for spigot and socketed/ flanged end pipes OR combination there of upto 150 mm bore and below complete all as specified and directed \nNOTE :- (i) The weight of fittings for the purpose of payment shall be actual weight of fittings or weight of fittings as specified in IS code- 1538 whichever in less.\n(ii) Joints of the fittings shall be measured and paid for separately under appropriate item of Schedule `A' 290 Per\n Kg
78 43 M&L for cutting of existing CI pipe of 80 to 200mm bore pipe line in position for rectifying leakage and reducing to required length, in position, for insertion of collars or other fittings including necessary excavation and earthwork, dewatering etc, if any involved, complete all as specified and directed. 1 Each\n Job
79 44 Roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc Fe 410-W (Gde E- 250) quality A also fastening and fixing and including preparation of new painted surface of steel and iron surface of any description and in any position over 10 cm width or girth and applying two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. 1200 Kg
80 45 M & L for Construction of new PCC solid Masonry valve chamber of size 1200 X900 X 1200 mm (Internal dimensions) with PCC foundation 1:5:10 type D2 using 40 mm graded stone aggregate 150 mm thick 150 mm wide off sets all-round over 100 mm thick hard core , 200 mm thick PCC solid block walls built in CM 1:6, 50 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/Dense soil 3 mm thick MS sheet cover fixed on 25 mm X 25 mm X 4 mm thick angle iron frame with hold fasts embedded in PCC coping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed.\n\nNote :- The retreived materials have been mentioned in the Sch of credit in the tender documents in pdf form. The amount of Sch of credit will be deducted offline from the amount of BOQ at the time of acceptance. 2 Each \nJob
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.

Copyright © 2021 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail