Completion Of Incomplete/Balance Works For Construction Of 650 Bedded Hospital Alongwith Otm Accn Incl Lift , Central Ac Plant , Hot Water Supply , Fire Hydrant , Sprinkler System , Fire Alarm System And External Services For Command Hospital ( Nc ), Udhampur-Jammu And Kashmir

Military Engineer Services-MES has published Completion Of Incomplete/Balance Works For Construction Of 650 Bedded Hospital Alongwith Otm Accn Incl Lift , Central Ac Plant , Hot Water Supply , Fire Hydrant , Sprinkler System , Fire Alarm System And External Services For Command Hospital ( Nc ). Submission Date for this Tender is 13-09-2021. Passenger Lift Tenders in Udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

28056750
Corrigendum : Completion Of Incomplete/Balance Works For Construction Of 650 Bedded Hospital Alongwith Otm Accn Incl Lift , Central Ac Plant , Hot Water Supply , Fire Hydrant , Sprinkler System , Fire Alarm System And External Services For Command Hospital ( Nc )
Open Tender
Indian
Jammu And Kashmir
Udhampur
13-09-2021

Tender Details

Completion Of Incomplete/Balance Works For Construction Of 650 Bedded Hospital Alongwith Otm Accn Incl Lift , Central Ac Plant , Hot Water Supply , Fire Hydrant , Sprinkler System , Fire Alarm System And External Services For Command Hospital ( Nc ) At Udha

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Jun-2021 D9 Other 28-07-2021
2 10-Jun-2021 D8 Other 28-07-2021
3 10-Jun-2021 D7 Other 28-07-2021
4 10-Jun-2021 D6 Other 28-07-2021
5 10-Jun-2021 D5 Other 28-07-2021
6 10-Jun-2021 D4 Other 28-07-2021
7 10-Jun-2021 D3 Other 28-07-2021
8 10-Jun-2021 D2 Other 28-07-2021
9 10-Jun-2021 D1 Other 28-07-2021
10 10-Jun-2021 Additional Drawings Other 28-07-2021
11 10-Jun-2021 D10 Other 20-07-2021
12 05-Jul-2021 Corr No. 02 Date 28-07-2021
13 19-Jul-2021 Corr No. 03 Date 25-08-2021
14 10-Aug-2021 Corr No. 04 Other 25-08-2021
15 14-Aug-2021 Revision of critical dates Date 06-09-2021
16 14-Aug-2021 Revised BOQ BOQ 06-09-2021
17 25-Aug-2021 Corr No. 07 Other 06-09-2021
18 06-Sep-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 13-09-2021

Key Value

Document Fees
INR 3000 /-
EMD
INR 1500000.0 /-
Tender Value
INR 121.50 Crore /-

BOQ Items

Name of Work: COMPLETION OF INCOMPLETE/ BALANCE WORKS FOR CONSTRUCTION OF 650 BEDDED HOSPITAL ALONGWITH OTM ACCN INCL LIFT, CENTRAL AC PLANT, HOT WATER SUPPLY, FIRE HYDRANT, SPRINKLER SYSTEM, FIRE ALARM SYSTEM AND EXTERNAL SERVICES FOR COMMAND HOSPITAL (NC) AT UDHAMPUR
Sl. No. Item Description Item Code / Make Quantity Unit
1 1 Sch 'A' Part - I (Building Works) \nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
2 2 Construction of balance works for main hospital building incl Admin block,auditorium,basement, porches, ramps, stair case,fire escape stair case, lift wells etc. complete all as specified and shown on drawings.\nNote:- 1. The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to---\n2. These Go ahead approvals/approvals in principle accorded on cancelled contract shall remain in this contract too. The detail of AIPs alongwith details of works are enclosed as Appendix G to the Particular Specifications. The contractor shall consider these changes while quoting his lumpsum considering the effect of changes based on the details attached under this item. This provision is deemed to be included in the rate quoted by the contractor. 1 Each Block
3 3 Construction of balance works for block of MNS Officer Mess for 52 officers including stair case complete all as specified and as shown on drawings.\nNote:The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
4 4 Construction of balance works for block of JCO's Mess and Club for 32 JCO's including stair case complete all as specified and as shown on drawings.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
5 5 Construction of block of Cook House and Dining Hall for 40 Trainees complete all as specified and as shown on drawing.\n 1 Each Block
6 6 Construction of balance works for block of Cook House and Dining Hall for single Hav/ORs for 151 to 250 men complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
7 7 Construction of block of SM barrack for 40 Havs and 75 ORs incl stair case complete all as specified and as shown on drawing.\n 1 Each Block
8 8 Construction of balance works for block of SM barrack for 40 Havs and 75 ORs incl stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
9 9 Construction of balance works for block of SM barrack for 40 ORs (Trainees) incl stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
10 10 Construction of balance works for block of single living accn for 4 JCO's incl scooter shed and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
11 11 Construction of balance works for block of single living accn for 4 JCO's incl scooter shed and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
12 12 Construction of balance works for block of four servant quarters incl stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to---\n 1 Each Block
13 13 Construction of balance works for block of four single living quarters for Major (Trainee Officers) incl stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
14 14 Construction of block of three single living servant quarter and two garrages for Major (Trainee Officers) incl garrages and stair case complete all as specified and as shown on drawing. 1 Each Block
15 15 Construction of balance works for block of eight single living quarters for Capt and below (MNS Officers) incl garage and stair case complete all as specified and as shown on drawing.\nNote:-The details of balace work are as per Annexure-I enclosed at Srl Page Nos.- to-- 1 Each Block
16 16 Construction of balance works for block of eight single living quarters for Capt and below (MNS Officers) incl garage and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
17 17 Construction of balance works for block of twelve single living servant quarters for MNS Officers incl stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
18 18 Construction of balance works for block of twelve single living servant quarters for MNS Officers incl stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
19 19 Construction of balance works for block of single married quarter for Major General (Commandent) incl servant quarter and garage complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
20 20 Construction of balance works for block of four married quarters for Major to Brig incl servant quarter, garages and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
21 21 Construction of balance works for block of four married quarters for Major to Brig incl servant quarter, garages and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
22 22 Construction of balance works for block of six married quarters for JCO's incl scooter shed, garage and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
23 23 Construction of balance works for block of six married quarters for ORs incl scooter shed and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
24 24 Construction of balance works for block of six married quarters for ORs incl scooter shed and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
25 25 Construction of balance works for block of five married quarters for ORs incl scooter shed and stair case complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
26 26 Construction of block of four married quarters (type-II) for Non Combats incl stair case complete all as specified and as shown on drawing. 1 Each Block
27 27 Construction of block of nine Guest Suits complete all as specified and as shown on drawing.\n 3 Each Block
28 28 Construction of block of Guard house and Armoury complete all as specified and as shown on drawing. 1 Each Block
29 29 Construction of block of welfare amenities incl stair case complete all as specified and as shown on drawing. 1 Each Block
30 30 Construction of balance works for block of family welfare centre complete all as specified and as shown on drawing.\nNote:-The details of balace work are as per Annexure-I enclosed at Srl Page Nos.- to-- 1 Each Block
31 31 Construction of block of religious institute complete all as specified and as shown on drawing. 1 Each Block
32 32 Construction of block of senitry post complete all as specified and as shown on drawing. 3 Each Block
33 33 Construction of balance works for block of garrage for Car/Gypsy five bays and four bays for lorry 3 ton including apron complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
34 34 Construction of block of garrage for Car/Gypsy five bays incl apron for MNS Officer Mess complete all as specified and shown on drgs. 1 Each Block
35 35 Construction of balance works for block of garrage for one Ton and Ambulance 12 bays including apron for MNS Officer Mess complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
36 36 Construction of balance works for block of repair bays (two Nos) with inspection pit (one No) incl apron complete all as specified and as shown on drawing.\nNote:-The details of balace work are as per Annexure-I enclosed at Srl Page Nos.- to-- 1 Each Block
37 37 Construction of balance works for block of MT store, Driver change room & technical office complete all as specified and as shown on drawing.\nNote:-The details of balace work are as per Annexure-I enclosed at Srl Page Nos.- to--\n 1 Each Block
38 38 Construction of balance works for block for housing incinerator incl accessories complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
39 39 Construction of single ramp complete all as specified and as shown on drawing. 1 Each
40 40 Construction of block of Petrol and lubricant store complete all as specified and as shown on drawing. 1 Each Block
41 41 Construction of washing platform complete all as specified and as shown on drawing. 1 Each
42 42 Construction of balance works for block of AC plant complete all as specified and as shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each Block
43 43 Construction of balance works for platform for single transformer of size 3000 x2500mm, 1200mm high from NGL, with brick construction including steps, XPM fencing fixed on angle iron posts up to 1200mm height with gate and locking arrangement, painting etc. complete all as specified and shown on drawing.\nNote:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.- to--- 1 Each
44 44 Construction of under ground RCC sump 3 lakh litres capacity with monholes, vent pipe, puddle plates, rungs and other details complete all as specified and shown on drawings.\nNote :- Inlet, outlet and over flow pipes with valves and duck foot bend etc shall be measured and paid for separately. 1 Each Block
45 45 Construction of balance works for Gate Complex-I comprising of two ornamental steel gates 5.40m wide, two wicket gates 1.2m wide, guard rooms, security rooms, surmounted with side pillars, domes, arches, insignia of brass metal letters, sign board etc complete all as specified and shown on drawings.\nNote:-The details of balace work are as per Annexure-I enclosed at Srl Page Nos.- to-- 1 Each Block
46 46 Construction of Gate Complex-II comprising of one ornamental steel gates 5.40m wide, two wicket gates 1.2m wide, guard rooms, security rooms, surmounted with side pillars, domes, arches, insignia of brass metal letters, sign board etc complete all as specified and shown on drawings. 1 Each Block
47 47 Total Amount of Sch 'A' Part - II (Sec A) (Internal Eletcrification) 1 Lump \nSum
48 48 Sch 'A' Part - II (SEC-B ) (INTERNAL ELECTRIC SUPPLY )\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
49 49 Supplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, Aluminium bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.(MNS officer's Mess)\nNCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. \nBUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOINGS \n6 Nos. 25A 4P, MCB (10KA).\nSpace for 2 Nos.25A 4P, MCB 1 Each
50 50 All as per Srl item 3.01 above but following mountings. (Servant quarters for Capt & Below of 12)\nINCOMER : 1 No.40 Amps. 4P MCB(10 KA).\nBUS BARS : 63 Amps. TP&N copper bus bars.\nOUT GOING\nSpace for 12 Nos. Single phase electronic meters \n13 Nos 6A DP MCB (10KA) 1 Each
51 51 All as per Srl item 3.01 above but following mountings.(single accn for Captain and below of 8 T/S)\nINCOMER : 1 No.80 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nBUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics).\nOUT GOING \nSpace for 8 Nos. Single phase electronic meters \n8 Nos 25A DP MCB (10KA) \n1 Nos. 6A DP, MCB ( 10KA) 2 Each
52 52 All as per Srl item 3.01 hereinbefore but following mountings. \n(Single JCO)\nINCOMER : 1 No.40 Amps. 4P MCB(10 KA).\nBUS BARS : 63 Amps. TP&N copper bus bars.\nOUT GOINGS :-\nSpace for 4 Nos. Single phase electronic meters \n4 Nos 20A DP MCB (10KA) \n1 Nos. 16A DP, MCB ( 10KA)\n1 Nos. 6A DP, MCB ( 10KA) 2 Each
53 53 All as per Srl item 3.01 hereinbefore but following mountings.(SM barracks for 150 Hav& 230 OR's).\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nBUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics).\nOUT GOING \n8 Nos 25A 4P, MCB (10KA) 2 Each
54 54 All as per Srl item 3.01 hereinbefore but following mountings.(single Accn for Major and md accn for non combats). \nINCOMER : 1 No.40 Amps. 4P MCB(10 KA).\nBUS BARS : 100 Amps. TP&N copper bus bars.\nINCOMER : 1 No.40 Amps. 4P MCB(10 KA).\nBUS BARS : 100 Amps. TP&N copper bus bars.\nOUT GOINGS :-\nSpace for 4 Nos. Single phase electronic meters \n4 Nos 25A DP, MCB (10KA) \n1 Nos. 6A DP, MCB ( 10KA) 2 Each
55 55 All as per Srl item 3.01 hereinbefore but following mountings.(servant quarters and garage for Major).\nINCOMER : 1 No.25 Amps. DP MCB(10 KA).\nBUS BARS : 63 Amps. SP&N copper bus bars.\nOUT GOINGS :-\nSpace for 3 Nos. Single phase electronic meters \n4 Nos. 6A DP, MCB ( 10KA). 1 Each
56 56 All as per Srl item 3.01 hereinbefore but following mountings.(MD accn for JCO).\nINCOMER : 1 No.63 Amps. 4P MCB(10 KA).\nBUS BARS : 100 Amps. TP&N copper bus bars.\nOUT GOINGS :-\nSpace for 6 Nos. three phase electronic meters \n6 Nos. 25A 4P, MCB ( 10KA).\n1 Nos. 6A DP, MCB ( 10KA) 1 Each
57 57 All as per Srl item 3.01 hereinbefore but following mountings.(MD accn for ORS).\nINCOMER :1 No.63 Amps. 4P MCB(10 KA)\nBUS BARS : 100 Amps. TP&N copper bus bars\nOUT GOINGS :-\nSpace for 6 Nos. Singke phase electronic meters \n6 Nos. 25A DP, MCB ( 10KA).\n1 Nos. 6A DP, MCB ( 10KA) 3 Each
58 58 All as per Srl item 3.01 hereinbefore but following mountings.(welfare amenity).\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nBUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics).\nOUT GOINGS :-\n4 Nos. 25A 4P, MCB ( 10KA).\n4 Nos. 16A 4P, MCB ( 10KA)\nSpace for 2Nos. 25A 4P, MCB 1 Each
59 59 All as per Srl item 3.01 hereinbefore but following mountings.(servant quarters for block of 4).\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nBUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics).\nOUT GOINGS :-\nSpace for 4 Nos. Single phase electronic meters\n5 Nos. 6A DP, MCB ( 10KA)\n\n 1 Each
60 60 Hospital Building\nAll as per Srl item 3.01 hereinbefore but following mountings. (Major to Brigadier).\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nBUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics).\nOUT GOINGS :-\nSpace for 4 Nos. three phase electronic meters\n4 Nos. 25A 4P, MCB ( 10KA)\n1 Nos. 6A DP, MCB ( 10KA)\n\n\n 2 Each
61 61 Supply only 1000 mm wide and 6mm thick corrugated insulation rubber matting suitable for 1100 volts grade. 50 RM
62 62 Earthing \nMaintenance free earthing of make Electrolytic Earthing comprising of type 'K' copper 2.4 mm wall thickness, hollow tube 12 feet long, 2.125 inches outer diameter completely filled with non hazardous metallic salts (Tettafill) to achieve an earth resistance of less than 1 ohms and connected to earthing test point all as specified or indicated including testing on completion. 35 Each
63 63 RISING MAINS, CABLE TRAY & LT CABLES(for Sub mains /Main)\nCompact Sandwich Rising mains\nSupply, Fixing ,inspection, handling, shifting, assembling, installation in correct assigned position of compact Sandwich construction copper rising mains (distribution bus trunking) and making proper connections, testing and commissioning 4 pole raising mains of copper bus bars with tap off connection points at every 1000mm intervals, expansion joints, fire barriers incl necessary support and louvers for ventilation, fabricated including 2 nos.of 50x6mm copper earthing conductor through out the length of the rising mains ( phase sequence should be matched with the incoming breaker provided at LT Panel ). Thrust pad shall be provided for each rising main for necessary support to rising main and to prevent the bus bar expansion in downward direction with end cover to close the end of rising main and to provode extra supports to bus bars at end, of following rating :-
64 64 (a) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 400A with short circuit withstand of 35 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and ond one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-7,9,10,11,12 96 RM
65 65 (b) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 630A with short circuit withstand of 40 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and ond one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-4,6,8 88 RM
66 66 (c) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 800A with short circuit withstand of 50 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and ond one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-3,4,6,8 52 RM
67 67 (d) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 1600A with short circuit withstand of 50 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and ond one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-1 24 RM
68 68 Supply, Fixing ,inspection, handling, shifting, assembling, installation in correct assigned position and including making proper connections, testing and commissioning MCCB Adopter Boxes fabricated out of 16 gauge CRCA sheet steel in cubical formation, dust and vermin proof and coupled with Rising mains. Boxes shall be treated with anticrrossive process before powder coating as per specifications, 2 nos. earthing terminals shall be provided. Boxes shall be suitable for connecting of rising mains at top and aluminuum cables at bottom, of following rating :-
69 69 (a) 400 Amp TPN End Feed unit complete with provision of 400 amps , TPN, MCCB of 35 KA (Ics) 6 Each
70 70 (b) 630 Amp TPN End Feed unit complete with provision of 630 amps,TPN, MCCB of 40 KA (Ics) 3 Each
71 71 (c) 800 Amp TPN End Feed unit complete with provision of 800 amps,4P, MCCB of 50 kA (Ics) 2 Each
72 72 (d) 1600 Amp TPN End Feed unit complete with provision of 1600 amps,4P, ACB ,MDO,Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 kA (Ics) 1 Each
73 73 Supply, Fixing ,inspection, handling, shifting, assembling, installation in correct assigned position and including making proper connections, testing and commissioning Tap off Boxes fabricated out of 16 gauge CRCA sheet steel in cubical formation, dust and vermin proof and mounted on the Rising mains. Boxes shall be treated with anticrrossive process before powder coating as per specifications, 2 nos. earthing terminals, including providing of following MCCB's as required with all accessories and adequate space shall be provided for cables terminations, of following rating:-
74 74 (a) Tap off /Plug in box complete with 63A Amp, TPN, MCCB of 25 KA (Ics) 3 Each
75 75 (b) Tap off /Plug in box complete with 100A Amp, TPN, MCCB of 25 KA (Ics) 6 Each
76 76 (c) Tap off /Plug in box complete with 125A Amp, TPN, MCCB of 25 KA (Ics) 8 Each
77 77 (d) Tap off /Plug in box complete with 160A Amp, TPN, MCCB of 25 KA (Ics) 13 Each
78 78 (e) Tap off /Plug in box complete with 200A Amp, TPN, MCCB of 25 KA (Ics) 14 Each
79 79 (f) Tap off /Plug in box complete with 250A Amp, TPN, MCCB of 35 KA (Ics) 2 Each
80 80 (g) Tap off /Plug in box complete with 300A Amp, TPN, MCCB of 35 KA (Ics) 4 Each
81 81 (h) Tap off /Plug in box complete with 400A Amp, TPN, MCCB of 35 KA (Ics) 3 Each
82 82 (k) Tap off /Plug in box complete with 630A Amp, TPN, MCCB of 35 KA (Ics) 1 Each
83 83 Perforated type GI cable trays for supporting LT sub main cables fabricated from perforated 2mm thick MS CRCA sheet duly galvanised with expention coupler plates duly galvanised, with bolts washer and nuts. knock out hole cable connections as per approved design. including supporting steel, fish plates, fixing accessories, nut bolts, down rods, dash fastners complete as required. as per specifications, for following sizes :-
84 84 (a) 150mm wide x 40mm x 40mm. 1800 RM
85 85 (b) 300mm wide x 40mm x 40mm. 270 RM
86 86 (c) 450mm wide x 40mm x 40mm. 814.6 RM
87 87 (d) 600mm wide x 40mm x 40mm. 223.7 RM
88 88 (e) 750mm wide x 40mm x 40mm. 122.2 RM
89 89 (f) 1000mm wide x 40mm x 40mm. 150 RM
90 90 Supply, laying, testing and commissioning of 1.1 KV XLPE armoured / PVC insulated, PVC sheathed aluminium/copper conductor cables confirming to IS: 1554 part 1-1976 with latest amendment laid over existing Cable tray including clamping the cables to support, complete all as specified, of following sizes :-
91 91 (a) 3.5 core x 35 sq.mm XLPE armoured, aluminium conductor cable 200 RM
92 92 (b) 3.5c x 50 sq.mm XLPE armoured, aluminium conductor cable 350 RM
93 93 (c) 3.5 core x 70 sq.mm XLPE armoured, aluminium conductor cable 360 RM
94 94 (d) 3.5 core x 95 sq.mm XLPE armoured, aluminium conductor cable 600 RM
95 95 (e) 3.5 core x 120 sq.mm XLPE armoured, aluminium conductor cable 500 RM
96 96 (f) 3.5 core x 150 sq.mm XLPE armoured, aluminium conductor cable 200 RM
97 97 (g) 3.5 core x 185 sq.mm XLPE armoured, aluminium conductor cable 50 RM
98 98 (h) 3.5 core x 240 sq.mm XLPE armoured, aluminium conductor cable 100 RM
99 99 (j) 3.5 core x 300 sq.mm XLPE armoured, aluminium conductor cable 150 RM
100 100 (k) 3.5 core x 400 sq.mm XLPE armoured, aluminium conductor cable 50 RM
101 101 (l) 4 core x 6 sq.mm armoured copper cable 4529 RM
102 102 (m) 4 core x 10 sq.mm armoured copper cable 4626 RM
103 103 (n) 4 core x 16 sq.mm armoured copper cable 2065 RM
104 104 (o) 2 core x 10 sq.mm armoured copper cable 1600 RM
105 105 Cable end termination of 1.1 KV XLPE / PVC insulated, aluminium / copper conductor armoured cables, including supplying and fixing of crimping alumiinum/ copper lugs, double compression heavy duty glands with earthing facility at both ends of cables,including taping of cable leads with insulation tape etc ,complete all as specified, of following sizes :-
106 106 (a) 4 core x 25 sq.mm XLPE armoured, aluminium conductor cable 80 Each
107 107 (b) 3.5 core x 35 sq.mm XLPE armoured, aluminium conductor cable 10 Each
108 108 (c) 3.5 core x 50 sq.mm XLPE armoured, aluminium conductor cable 10 Each
109 109 (d) 3.5 core x 70 sq.mm XLPE armoured, aluminium conductor cable 10 Each
110 110 (e) 3.5 core x 95 sq.mm XLPE armoured, aluminium conductor cable 20 Each
111 111 (f) 3.5 core x 120 sq.mm XLPE armoured, aluminium conductor cable 16 Each
112 112 (g) 3.5 core x 150 sq.mm XLPE armoured, aluminium conductor cable 6 Each
113 113 (h) 3.5 core x 185 sq.mm XLPE armoured, aluminium conductor cable 4 Each
114 114 (j) 3.5 core x 240 sq.mm XLPE armoured, aluminium conductor cable 4 Each
115 115 (k) 3.5 core x 300 sq.mm XLPE armoured, aluminium conductor cable 4 Each
116 116 (l) 3.5 core x 400 sq.mm XLPE armoured, aluminium conductor cable 4 Each
117 117 (m) 4 core x 6 sq.mm armoured copper cable 500 Each
118 118 (n) 4 core x 10 sq.mm armoured copper cable 400 Each
119 119 (o) 4 core x 16 sq.mm armoured copper cable 100 Each
120 120 (p) 2 core x 10 sq.mm armoured copper cable 100 Each
121 121 Supplying and drawing in existing conduit Wiring for TV outlet with coaxial cable double screened, aluminium. foiled, tinned copper ATC braid having an impedance of 75 Ohms and singal losses not more then 6 db etc as reqd. 2365 RM
122 122 ESDB-1,NSDB-2 (BASEMENT)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, Copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.63 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch\n(ii) Ammeter of range 0-60 Amps. with selector switch and required CT's.(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOINGS :-\n4 Nos. 25A 4P, MCB (10KA).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB 2 Each
123 123 NSDB-4(BASEMENT)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, Copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL :-\n(i) Voltmeter of range 0-500 volts with selector switch\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOINGS :-\n1 No. 25A 4P, MCB (10KA).TYPE-D.\n3 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.40A 4P, MCB.\n 1 Each
124 124 ESDB-3(BASEMENT)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.63 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL :-\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-60 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOINGS : 5 Nos. 25A 4P, MCB (10KA).TYPE-D.\nNote :(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.25A 4P, MCB. 1 Each
125 125 ESDB-5(Ground FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing,Copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOINGS :-\n5 Nos. 25A 4P, MCB (10KA).TYPE-D.\n3 Nos. 40A 4P, MCB (10KA).TYPE-D.\n2 Nos. 63A 4P, MCCB (25KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.\n 1 Each
126 126 ESDB-7(Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.630 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-600 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 800 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOINGS :-\n3 Nos. 25A 4P, MCB (10KA).TYPE-D.\n3 Nos. 32A 4P, MCB (10KA).TYPE-D.\n6 Nos. 40A 4P, MCB (10KA).TYPE-D.\n3 Nos. 63A 4P, MCB (10KA).TYPE-D.\n4 Nos. 63A 4P, MCCB (25KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.40A 4P, MCB. 2 Each
127 127 NSDB-8(Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 4100 Kg
128 128 OUTGOINGS : 6 Nos. 40A 4P, MCB (10KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB
129 129 ESDB-9(Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing,Copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
130 130 OUTGOINGS : 3 Nos. 25A 4P, MCB (10KA).TYPE-D.\n3 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.40A 4P, MCB.
131 131 NSDB-10(Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL \n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
132 132 OUTGOINGS :\n4 Nos. 25A 4P, MCB (10KA).TYPE-D.\n1 No. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.25A 4P, MCB.
133 133 ESDB-11(Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases.\nINDICATING PANEL \n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
134 134 OUTGOINGS : 9 Nos. 25A 4P, MCB (10KA).TYPE-D, 1 No. 40A 4P, MCB (10KA).TYPE-D, 1 No. 63A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.25A 4P, MCB.
135 135 NSDB-12 (Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases. \nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
136 136 OUTGOINGS : 1 No. 25A 4P, MCB (10KA).TYPE-D, 6 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.40A 4P, MCB.
137 137 NSDB-16 (Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse.\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
138 138 OUTGOINGS : 2 Nos. 25A 4P, MCB (10KA).TYPE-D, 3 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
139 139 ESDB-55 (Ground FL.)for Auditorium\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.250 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-250 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
140 140 OUTGOINGS :\n14 Nos. 25A 4P, MCB (10KA).TYPE-D, \n2 Nos. 40A 4P, MCB (10KA).TYPE-D, \n1 No. 63A 4P, MCCB (25KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
141 141 ESDB-56 (Ground FL.)for Auditorium\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
142 142 OUTGOINGS : 5 Nos. 25A 4P, MCB (10KA).TYPE-D, 4 Nos. 40A 4P, MCB (10KA).TYPE-D, \nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.25A 4P, MCB.
143 143 ESDB-57 (Ground FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.300 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-300 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 400 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
144 144 OUTGOINGS :\n1 Nos. 63A 4P, MCCB (25KA). \n2 Nos. 100A 4P, MCCB (25KA). \n1 Nos 125A 4P, MCCB (25KA).\n1 Nos 160A 4P, MCCB (25KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.100A 4P, MCCB.
145 145 ESDB-17 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
146 146 OUTGOINGS : \n1 No. 20A 4P, MCB (10KA).TYPE-D, \n1 No. 25A 4P, MCB (10KA).TYPE-D, \n6 Nos. 32A 4P, MCB (10KA).TYPE-D, \n2 Nos. 40A 4P, MCB (10KA).TYPE-D, \n1 No. 63A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB
147 147 ESDB-18 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
148 148 OUTGOINGS : \n1 No. 25A 4P, MCB (10KA).\nTYPE-D, 6 Nos. 40A 4P,\nMCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
149 149 ESDB-19 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
150 150 OUTGOINGS : \n6 Nos. 25A 4P, MCB (10KA).\nTYPE-D, 3 Nos. 40A 4P, \nMCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b)Spare Space only for 2 Nos.25A 4P, MCB
151 151 NSDB-20 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
152 152 OUTGOINGS : \n2 Nos. 25A 4P, MCB (10KA).TYPE-D, \n 4 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
153 153 ESDB-21 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.250 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-250 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
154 154 OUTGOINGS : \n7 Nos. 25A 4P, MCB (10KA).TYPE-D, \n2 Nos. 40A 4P, MCB (10KA).TYPE-D, \n2 Nos. 63A 4P, MCCB (25KA).TYPE-D, \n1 No. 100A 4P, MCCB (25KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
155 155 ESDB-22 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
156 156 OUTGOINGS : \n 1 No. 25A 4P, MCB (10KA).TYPE-D, \n5 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
157 157 ESDB-23 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
158 158 OUTGOINGS : \n6No. 25A 4P, MCB (10KA).TYPE-D, \n2 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
159 159 NSDB-24 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
160 160 OUTGOINGS : \n1No. 25A 4P, MCB (10KA).TYPE-D, \n4Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
161 161 ESDB-25 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.63 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-60 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
162 162 OUTGOINGS : \n5No. 25A 4P, MCB (10KA).TYPE-D, \n1Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
163 163 NSDB-26 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.63 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-60 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
164 164 OUTGOINGS : \n5No. 25A 4P, MCB (10KA).TYPE-D, \n1Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
165 165 ESDB-27 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
166 166 OUTGOINGS : \n4No. 25A 4P, MCB (10KA).TYPE-D, \n2Nos. 32A 4P, MCB (10KA).TYPE-D.\n1No. 40A 4P, MCB (10KA).TYPE-D, \n2Nos. 63A 4P, MCB (10KA).TYPE-D.\n1Nos. 63A 4P, MCCB (25KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
167 167 NSDB-28 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
168 168 OUTGOINGS : \n3No. 25A 4P, MCB (10KA). \n2Nos. 40A 4P, MCB (10KA).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
169 169 ESDB-29 (1st FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.300 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-300 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 400 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 2 Each
170 170 OUTGOINGS : \n3 Nos. 20A 4P, MCB (10KA).TYPE-D, \n2 Nos. 32A 4P, MCB (10KA).TYPE-D, \n4 Nos. 40A 4P, MCB (10KA).TYPE-D, \n1 No. 63A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
171 171 ESDB-30 (2nd FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.250 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-250 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
172 172 OUTGOINGS : \n2 Nos. 25A 4P, MCB (10KA), \n3 Nos. 32A 4P, MCB (10KA), \n2 Nos. 40A 4P, MCB (10KA), \n3 Nos. 63A 4P, MCCB (25KA)\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
173 173 ESDB-31 (2nd FL.)\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
174 174 OUTGOINGS : \n1 No. 20A 4P, MCB (10KA).TYPE-D, \n5 Nos. 25A 4P, MCB (10KA).TYPE-D, \n2 Nos. 32A 4P, MCB (10KA).TYPE-D, \n3 Nos. 40A 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB..
175 175 ESDB-59 (2nd FL.) for ICU beds\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.300 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-300 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 400 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
176 176 OUTGOINGS : \n11 No. 40A DP, MCB (10KA).TYPE-D, \n\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A DP, MCB..
177 177 NSDB-32 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
178 178 OUTGOINGS : \n5 No. 40A, 4P, MCB (10KA).TYPE-D, \n\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB..
179 179 NSDB-33 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.400 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-400 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 500 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
180 180 OUTGOINGS : \n6 Nos. 25A, 4P, MCB (10KA).TYPE-D, \n1 No. 40A, 4P, MCB (10KA).TYPE-D, \n3 Nos. 63A, 4P, MCB (10KA).TYPE-D, \n2 Nos. 63A, 4P, MCCB (25KA). \n\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
181 181 NSDB-34 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
182 182 OUTGOINGS : \n2 Nos. 25A, 4P, MCB (10KA).TYPE-D, \n4 No. 40A, 4P, MCB (10KA).TYPE-D, \n\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
183 183 ESDB-35 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
184 184 OUTGOINGS : \n8 Nos. 25A, 4P, MCB (10KA).TYPE-D, \n2 No. 63A, 4P, MCB (10KA).TYPE-D, \nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
185 185 NSDB-36 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
186 186 OUTGOINGS : \n5 Nos. 40A, 4P, MCB (10KA).TYPE-D, \n \nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
187 187 ESDB-37 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
188 188 OUTGOINGS : \n1 No. 20A, 4P, MCB (10KA).TYPE-D, \n5 Nos. 25A, 4P, MCB (10KA).TYPE-D, \n2 Nos. 40A, 4P, MCB (10KA).TYPE-D.\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
189 189 ESDB-38 (2nd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
190 190 OUTGOINGS : \n4 No. 25A, 4P, MCB (10KA).TYPE-D, \n1 Nos. 40A, 4P, MCB (10KA).TYPE-D, \nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
191 191 ESDB-58 (2nd FL.) for OT UPS \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.400 Amps. 4P MCCB(35 KA Ics) with Adjustable thermal & Adjustable magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-400 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 500 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
192 192 OUTGOINGS : \n8 Nos. 63A, 4P, MCCB (25KA lcs). \nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.63A 4P, MCCB.
193 193 ESDB-39 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
194 194 OUTGOINGS : \n11 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n2 Nos. 40A, 4P, MCB (10KA ).TYPE-D \nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
195 195 NSDB-40 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
196 196 OUTGOINGS : \n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
197 197 ESDB-41 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
198 198 OUTGOINGS : \n4 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n1 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
199 199 NSDB-42 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 2 Each
200 200 OUTGOINGS : \n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
201 201 ESDB-43 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
202 202 OUTGOINGS : \n6 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n3 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
203 203 NSDB-44 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
204 204 OUTGOINGS : \n1 No. 25A, 4P, MCB (10KA ).TYPE-D\n5 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
205 205 ESDB-45 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
206 206 OUTGOINGS : \n1 No. 16A, 4P, MCB (10KA ).TYPE-D\n3 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n3 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
207 207 NSDB-46 (3rd FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
208 208 OUTGOINGS : \n4 No. 40A, 4P, MCB (10KA ).TYPE-D\n1 Nos. 63A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.40A 4P, MCB.
209 209 ESDB-47 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
210 210 OUTGOINGS : \n4 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n2 Nos. 40A, 4P, MCB (10KA ).TYPE-D\n2 Nos. 63A, 4P, MCCB (10KA ).\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos.25A 4P, MCB.
211 211 NSDB-48 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
212 212 OUTGOINGS : \n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 40A 4P, MCB.
213 213 ESDB-49 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
214 214 OUTGOINGS : \n3 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n2 Nos. 40A, 4P, MCB (10KA ).TYPE-D\n1 Nos. 63A, 4P, MCCB (25KA (lcs) )\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 25A 4P, MCB.
215 215 NSDB-50 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
216 216 OUTGOINGS : \n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 40A 4P, MCB.
217 217 NSDB-51 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
218 218 OUTGOINGS : \n5 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\n1 No. 63A, 4P, MCCB (25KA (lcs))\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 25A 4P, MCB.
219 219 ESDB-52 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.200 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-200 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 300 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
220 220 OUTGOINGS : \n6 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 40A 4P, MCB.
221 221 ESDB-53 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
222 222 OUTGOINGS : \n3 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 25A 4P, MCB.
223 223 NSDB-54 (4th FL.) \nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-160 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
224 224 OUTGOINGS : \n1 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n4 Nos. 40A, 4P, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 40A 4P, MCB.
225 225 ELEVATOR PANEL-3\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-120 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
226 226 OUTGOINGS : \n2 Nos. 40A, 4P, MCCB (25KA (lcs))\n1No. 63A, DP, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 63A DP, MCB.\n(c) Spare Space only for 1 Nos. 63A 4P, MCCB.
227 227 ELEVATOR PANEL-4\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 1 Each
228 228 OUTGOINGS : \n2 Nos. 40A, 4P, MCCB (25KA (lcs))\n1No. 63A, DP, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 63A DP, MCB.\n(c) Spare Space only for 1 Nos. 63A 4P, MCCB.
229 229 ELEVATOR PANEL-5 &6\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.63 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 100 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 2 Each
230 230 OUTGOINGS : \n1 Nos. 40A, 4P, MCCB (25KA (lcs))\n1 No. 40A, DP, MCB (10KA ).TYPE-D\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 40A DP, MCB.\n(c) Spare Space only for 1 Nos. 63A 4P, MCCB.
231 231 MAIN PANEL KITCHEN\nSupplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMER : 1 No.160 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-100 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse .\nBUS BARS : 1 Set of 200 Amps. TP&N Copper bus bars of suitable length, Bus bars shall be insulated by heat shrinkable sleaves & clip on shrounds for joints. Bus bars shall be designed to with stand a fault level of 25 KA at 415 volts. 2 Each
232 232 OUTGOINGS : \n2 Nos. 25A, 4P, MCB (10KA ).TYPE-D\n2 Nos. 40A, 4P, MCB (10KA ).TYPE-D\n16 Nos. 16A, DP, RCBO (100mA )\n15 Nos. 25A, DP, RCBO (100mA )\n2 Nos. 16A, DP, MCB (10KA ).TYPE-D\n2 Nos. 25A, DP, MCB (10KA ).TYPE-D\n2 Nos. 32A, DP, MCB (10KA )\nNote :-\n(a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. \n(b) Spare Space only for 2 Nos. 40A DP, MCB.\n(c) Spare Space only for 1 Nos. 63A 4P, MCCB.
233 233 UPS BYPASS PANEL (for 20,22,24,30 KVA UPS)\nSupplying, installation, testing and commissioning of UPS bypass panel made of 1.6 mm thick CRCA sheet steel enclosure of approved make design and painted with approved paint shade complete with cotrol wiring, including following :-\nINCOMER :\n 1 No.63 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & fixed magnetic releases. \n1 No.63 Amps. 4P, 415 volts, BYPASS SWITCH complete with handle ,extension shaft, channel set.\nINDICATING PANEL\n(i) Voltmeter of range 0-500 volts with selector switch.\n(ii) Ammeter of range 0-60 Amps. with selector switch and required CT's.\n(iii) 3 nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse. 22 Each
234 234 Refrifgerator electric driven, single phase, capacity 300/310 litres, frost free, AC, 230 volts all as specified of approved make as directed by GE . 7 Each
235 235 Refrifgerator electric driven, single phase capacity 180 litres, frost free AC, 230 volts all as specified of approved make as directed by GE . 74 Each
236 236 Water cooler, electric driven, single phase, 230 volts AC, having storage capacity 80 Ltr and cooling capacity 40 ltr per hour and connecting to existing water supply line with G.I. pipe of suitable dia complete all as specified of approved make as directed by GE. 50 Each
237 237 Water cooler, electric driven, single phase, 230 volts AC, having storage capacity 180 Ltr and cooling capacity 150 ltr per hour and connecting to existing water supply line with G.I. pipe of suitable dia complete all as specified of approved make as directed by GE. 5 Each
238 238 Water cooler, electric driven, single phase, 230 volts AC, having storage capacity 120 Ltr and cooling capacity 60 ltr per hour and connecting to existing water supply line with G.I. pipe of suitable dia complete all as specified of approved make as directed by GE. 4 Each
239 239 Deep freezer, hard top, 320 ltr capacity, double door, AC 230 volts complete all as specified of approved make as directed by GE. 9 Each
240 240 Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 1 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE. 77 Each
241 241 Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 2 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE. 7 Each
242 242 Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 3 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE. 68 Each
243 243 Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 5 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE. 7 Each
244 244 Split type air conditioner 1.5 Ton capacity, single phase, air cooled complete in all respects 2 Each
245 245 Total Amount of Sch 'A' Part - III (Internal Water Supply) 1 Lump \nSum
246 246 Total Amount of Sch 'A' Part - IV (Plumbing Works) 1 Lump \nSum
247 247 Total Amount of Sch 'A' Part - V (Site clearnace, Terrace cutting and Earth Work for basement & services) 1 Lump \nSum
248 248 Total Amount of Sch 'A' Part - VI (Sewage Disposal Work) 1 Lump \nSum
249 249 Total Amount of Sch 'A' Part - VII (Area Drainage Work) 1 Lump \nSum
250 250 Total Amount of Sch 'A' Part - VIII (Protective Work) 1 Lump \nSum
251 251 Total Amount of Sch 'A' Part - IX (Road, Path, Culvert and Hard Standing Work) 1 Lump \nSum
252 252 Total Amount of Sch 'A' Part - X (Security Fencing, Boundary Wall 7 Gate) 1 Lump \nSum
253 253 Total Amount of Sch 'A' Part - XI (Basket Ball, Foot Ball and Volley Ball Ground) 1 Lump \nSum
254 254 Total Amount of Sch 'A' Part - XII (Sec A) (External Electrification) 1 Lump \nSum
255 255 PART- XII(SEC-B) : LIST OF WORKS AND PRICES FOR EXTERNAL ELECTRIFICATION \nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
256 256 Supplying, installing, testing and commissioning in correct alignment position, effecting proper connections, of continous rating 500KVA outdoor type, oil filled, off circuit tap changer, step down transformer with the following specifications conforming to IS-2026\nNo load voltage Ratio : 11/0.433 KV\nNo. of phases / Freq. : 3 Phase/50 Hz.\nNo. of phases / Freq. : 3 Phase/50 Hz.\nNo. of phases / Freq. : 3 Phase/50 Hz.\nType : Core type, double copper wound\nCooling : ONAN\nVector Group : DYN 11\nTemperature rise (Oil winding) : 50/55 Deg.\nTaps Changer :- OFF CIRCUIT TYPE\nTaps on HV for HV\nVariation : -7.5% to +7.5% in\n : steps of 2.5% each (off circuit type)\nTermination Box (HV) : Air filled cable box suitable for 11KV\n3x95 Sq.mm. XLPE cables.\nTermination box (LV) : Air filled cable box suitable for 1.1KV\n2 run of 3.5x300 sq.mm. Al. Cond. XLPE Cable, PVC insulated .\nThe transformer shall be supplied with following fittings:\n(a) Oil Conservator with drain valve.\n(b) Magnetic oil level indicator.\n(c) Dehydrating Silica gel breather with oil seal.\n 1 Each
257 257 (d) First filling of filtered oil as per IS-335 including make up fill during installation of transformer plus 10% extra oil.\n(e) Off circuit switch.\n(f) Lifting lugs\n(g) Earthing terminals - 2 Nos. for body earthing and one additional for neutral for broughtout on a bushing.\n(h) Pocket Thermometer.\n(i) Air release hole with plug\n(j) Top filter valve - 1 No.\n(k) Radiator with top and bottom shut off valves.\n(l) Inspection cover.\n(m) 100mm dial magnetic oil level gauge with max pointer and low level alarm contacts.\n(n) Rating and Diagram plate.\n(o) 4 Nos Bi-directional Plain / Flanged Rollers.\n(p) 150mm dia winding temperature indicator with max pointer.\n(q) 150mm dia oil temperature indicator with max pointer.\n(r) Disconnecting facility for HV cable box.\n(s) Jacking lugs\n(t) Bottom drain cum filter valve
258 258 Design, manufacturing, supply, installation, testing, commissioning main LT feeder pillar-5 of following sizes and fabricated out of 3.15 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top and complete with interconnections, with copper wires, tapes, bonding to earth and painting complete as required and as per technical specification. The LT feeder pillar shall consist of MCCB as incoming and MCCB/MCB as outgoing.\nNote: This panel shall be a FRONT and REAR operated, withcable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Main LT Feeder Pillar.Degree of protection of IP-57 \nINCOMING\nOne number 800 Amps, 4 pole ACB, MDO micro processor (with O/L, S/C, INST E/F release at 50 KA (Ics)\nINDICATING PANEL\nThe Indicating panel of incoming panel shall be provided with thefollowings :\n(a) Intelligent panel meter-Quasar (96mm square) covering 25 electric parameters with RS 485 port.\n(b) 3 number phase indicating lamp, each lamp shall have one toggle switch back up with HRC fuses.\n(c) Red/Green ON/OFF indicating lights for incoming and outgoing ACBS/MCCBs..\n 1 Each
259 259 BUS BARS\n1 Set of 1000Amps TPN Copper Bus bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 433 volts. \nOUTGOING\n2 Nos. of 100 Amps TP+IN, MCCB of 25KA service breaking capacity and 100Amp (Adjustable thermal & adjustable magnetic setting) trip setting and heavy duty solid Isolating Neutral link as required and heavy duty solid Isolating Neutral link.\n2 Nos. of 200 Amps TP+IN, MCCB of 35KA service breaking capacity and 200Amp (Adjustable thermal & adjustable magnetic setting) trip setting and heavy duty solid Isolating Neutral link as required and heavy duty solid Isolating Neutral link.\n(i) MCCB, 04 pole, 10 KA (Ics), 25 Amp, 415 volts-01 No. \n(ii) MCCB, 04 pole, 10 KA (Ics), 40 Amp, 415 volts - 04 Nos.\n(iii) MCCB, 04 pole, 15 KA (Ics), 63 Amp, 415 volts - 02 Nos.. \nSpare Space only for 2 Nos-20A DP MCB, 2 Nos-25A 4P MCB & 2 Nos 63A/200A TP MCCB\n\n
260 260 1) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. \n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming ACB shall have ON & OFF lamp indication\n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection.\n(iv) Engraved Al-Plates shall be provided for each Feeder. \n(v) Main feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturer. \n\n
261 261 Supply, installation, testing, commissioning feeder pillar-1 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top, interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/ MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as per technical specification. The LT feeder pillar shall consist of MCCB as incoming and MCCB as outgoing.\nNote: This panel shall be a FRONT operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\nINCOMING\na) 1 No. of 100 Amps,4p, MCCB of 25 KA (Ics) service breaking capacity and 100 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required.\nINDICATING PANEL\n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following: (b) Voltmeter of range 0-500 volts with selector switch.and backed up with HRC fuse.\n\n 1 Each
262 262 (c) Ammeter of range 0-100A with selector switch and required CT's.\n(d) 3 Nos. phase indicating lamps, each lamp shall have one toggle switch backed up with HRC fuse. \n(e) Space for Electronic Energy meter of suitable capacity & CT's\n(f) Red/ Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBs / MCBs.\nBUS BAR\n1 Set of 200Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOING\n(i) MCCB, 04 pole, 10 KA (Ics), 25 Amp, 415 volts - 04 Nos\n(ii) MCCB, 04 pole, 10 KA (Ics), 40 Amp, 415 volts - 01 No. \nSpare space for MCCB, 04 pole, 40 Amp, 10 KA (Ics), 415 volts -01 No.\nNotes:\n(1) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON,lamp indication \n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection.\n(iv) Engraved Al-Plates shall be provided for each Feeder.\n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers.\n
263 263 Supply, installation, testing, commissioning feeder pillar-2 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as per technical specification. The LT feeder pillar shall consist of MCCB as incoming and MCCB as outgoing. \nNote: This panel shall be a FRONT operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\n INCOMING\n1 No. of 300 Amps ,4P, MCCB of 35KA service breaking capacity and 200 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required.\nINDICATING PANEL\n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following:\n(b) Voltmeter of range 0-500 volts with selector switch.and backed up with HRC fuse.\n(c) Ammeter of range 0-200A with selector switch and required CT's.\n.\n 1 Each
264 264 (d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. (e) Space for Electronic Energy meter of suitable capacity & CT's\n(f) Red/Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs.\nBUS BAR\n1 Set of 300Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of\n25 KA at 415 volts.\nOUTGOING\n4 Nos. of 63 Amps, TP+IN, MCCB of 10KA and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.\n3 Nos, 40 Amps, 04 pole, MCCB, 10 KA (Ics).\nNotes:\n(i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication.\n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection.\n(iv) Engraved Al-Plates shall be provided for each Feeder. \n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers\n
265 265 Supply, installation, testing, commissioning feeder pillar-3 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top, interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as per technical specification. The LT feeder pillar shall consist of MCCB as incoming and MCCB as outgoing. \nNote: This panel shall be a FRONT/operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\nIN COMING\n1 No. of 630 Amps ,4P, MCCB of 35KA service breaking capacity and 630 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required. \nIN DICATING PANEL\n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following:\n(b) Voltmeter of range 0-500 volts with selector switch.and backed up with HRC fuse.\n(c) Ammeter of range 0-630A with selector switch and required CT's.\n(d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. (e) Space for Electronic Energy meter of suitable capacity & CT's\n(f) Red/ Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBs / MCBs.\n 1 Each
266 266 BUS BAR :1 Set of 800Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOING\n1 No. of 63 Amps, TP+IN, MCCB of 25 KA (Ics) and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.\n4 No. of 100 Amps, TP+IN, MCCB of 25 KA (Ics) and 100 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.\n2 Nos. of 125 Amps, TP+IN, MCCB of 25 KA (Ics) and 125 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.\n5 Nos 40A 4P MCC 40 mp\nSpace only for MCCB, 10 KA, 2 Nos 63A/125A TP MCCB. Spare\nNotes:\n(i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication.\n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection.\n(iv) Engraved Al-Plates shall be provided for each Feeder. \n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers.\n\n
267 267 Supply, installation, testing, commissioning feeder pillar - 4 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top, interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as technical specification. The LT feeder pillar shall consist of MCCB as incoming and MCCB as outgoing.\nNote: This panel shall be a FRONT operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\nINCOMING: 1 No. of 125 Amps ,4P, MCCB of 35 KA (Ics) service breaking capacity and 125 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required.\nINDICATING PANEL\n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following: \n(b) Voltmeter of range 0-500 volts with selector switch.and backed up with HRC fuse. \n(c) Ammeter of range 0-125A with selector switch and required CT's.\n(d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. \n\n 1 Each
268 268 (e) Space for Electronic En meter of suitable capacity & CT's\n(f) Red/ Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs.\nBUS BAR :1 Set of 200Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOING\n4 Nos. of 63 Amps, TP+IN, MCCB of 15 KA (lcs) and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.\n1No-6A,DP, MCB 10KA\nSpare Space only for 1 No-25 Amps, DP, MCB & 1 No 63A TP MCCB. \nNotes:\n(i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication\n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. \n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers.\n\n\n
269 269 Supply, installation, testing, commissioning feeder pillar 6 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top, interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as per technical specification. The LT feeder pillar shall consist of MCCB as incoming and MCCB as outgoing \nNote: This panel shall be a FRONT operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\nINCOMING : 1 No. of 250 Amps ,4P, MCCB of 35 KA (Ics) service breaking capacity and 250 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required.\nINDICATING PANEL \n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following: \n(b) Voltmeter of range 0-500 volts with selector switch.and backed up with HRC fuse.\n(c) Ammeter of range 0-250A with selector switch and required CT's.\n(d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. (e) Space for Electronic Energy meter of suitable capacity & CT's\n(f) Red/Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs.\n 1 Each
270 270 BUS BAR: 1 Set of 300Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts\nOUTGOING\n4 Nos. of 100 Amps, TP+IN, MCCB of 25 KA (Ics) and 100 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.\n2 Nos, 25 Amps, 04 pole, 16 KA (Ics), MCCB \n1 No - 40 Amps, D4 pole, MCCB, 10 KA (Ics)\nSpare Space only for 2 Nos-40 Amps, 04 pole, MCCB\nNotes:\n(i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication.\n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection.\n(iv) Engraved Al-Plates shall be provided for each Feeder.\n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers.\n\n\n
271 271 Supply, installation, testing, commissioning feeder pillar - 7 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top, interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as per technical specification. The LT feeder pillar shall consisit of MCCB as incoming and MCCB as outgoing.\nNote: This panel shall be a FRONT/operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\nIN COMING : 1 No. of 200 Amps ,4P, MCCB of 35 KA (Ics) service breaking capacity and 200 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required. \nIN DICATING PANEL\n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following:\n(b) Voltmeter of range 0-500 volts with selector switch.and backed up with HRC fuse. (c) Ammeter of range 0-200A with selector switch and required CT's. \n(d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. \n\n 1 Each
272 272 (e) Space for Electronic Energy meter of suitable capacity & CT's\n(f) Red/ Green ON/OFF indicating lights for incomer MCCB & ON in dication lights for outgoing MCCBS/MCBs.\nBUS BAR: 1 Set of 300Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOING\n4 Nos. of 63 Amaps, TP+IN, MCCB of 10 KA (Ics) and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. \n1 No. of 100 Amps, TP+IN, MCCB of 25 KA (Ics) and 100 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.(for S/L) Spare Space only for 2 No 63A TP MCCB.\nNotes:\n(i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON,lamp indication.\n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection.\n(iv) Engraved Al-Plates shall be provided for each Feeder.\n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers.\n
273 273 Supply, installation, testing, commissioning feeder pillar - 8 of following sizes and fabricated out of 2 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top, interconnections, copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and powder coated painting complete as required and as per technical specification. The LT feeder pillar shall consisit of MCCB as incoming and MCCB as outgoing. \nNote: This panel shall be a FRONT/operated, with cable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Feeder Pillar. Degree of protection of IP-57\nINCOMING : 1 No. of 100 Amps ,4P, MCCB of 25 KA (Ics) service breaking capacity and 100 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required. \nINDICATING PANEL\n(a) The Indicating panel of each Transformer incomer MCCB shall be provided with the following:\n(b) Voltmeter of range 0-500 volts with selector switch.and backed required up with HRC fuse.\n(c) Ammeter of range 0-100A with selector switch and required CT's.\n(d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. \n\n 1 Each
274 274 (e) Space for Electronic Energy meter of suitable capacity & CT's\n(f) Red/Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs.\nBUS BAR 1 Set of 200Amps TPN Copper Bus Bars of suitable length and of sulable cross section. Bus bar shall be insulated by heat shrinkable seaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts.\nOUTGOING\n03 Nos-40 Amps, 04 pole, 10 KA (Ics), MCCB. \nSpare Space only for 4 Nos-25A DP MCB, 1No-40A 4P MCB & 1 No 63A TP MCCB.\nNotes:\n(i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing.\n(ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication. \n(iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection\n(iv) Engraved Al-Plates shall be provided for each Feeder. \n(v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vi) PCC work in foundation as recommended by manufacturers. \n
275 275 Supplying, installation, testing and commissioning of L.T. panel for main power house fully compartmentalized cubical type fabricated out of 2mm thick CRCA sheet, floor/wall mounted totally enclosed, powder coated painting, painted after seven tank process, extensible on both sides, switch board suitable for use on 1 Phase/3-phase, 50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/Sqmm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMING\n1 No x 1600 amps,4P, ACB MDO, Microprocessor (with O/L,S/C.INST. EF) Releases of 50 kA (Ics) for incommer -1\n1 No x 1600 amps,4P, ACB MDO, Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 kA (Ics) for incommer-2\n1 No x 1600 amps,4P, ACB MDO, Microprocessor (with O/L,S/C,INST. EF) Releases of 50 kA (Ics) for Bus Coupler \nINDICATING PANEL\n(a) The Indicating panel of each incomer ACB shall be provided with the following:\n(b) Provide L&T make Intelligent panel meter- Quasar ( 96mm x 96mm) covering 25 electrical parameters with RS 485 port for all incomming and outgoing ACBS.\n(c) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse.\n(d) Space for Electronic Energy meter of suitable capacity & CT's\n(e) Red/ Green ON / OFF indicating lights for both incomers and Bus coupler ACBS & ON indication lights for outgoing ACBs /MCCBs\n(f) Mechanically interlocking shall be provided with two Incomers and the Bus coupler ACBs\n 1 Each
276 276 BUS BARS: 1 Set of 2000Amps TPN Copper Bus bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 50 KA at 433 volts.\nOUTGOING\n(i) 1 No- 1250 Amps, 3 pole and neutral, ACB, MDO, Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 KA (Ics)\n(ii) 2 Nos. of 100 Amps, 3 pole and neutral, MCCB of 25 KA (Ics) service breaking capacity and 100 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required.\n(iii) 01 No - 630 Amps, 04 pole, MCCB, 35 KA (Ics) micro processor type.\n(iv) 01 No 400 Amps, 04 pole, MCCB, 35 KA (Ics), micro processor type.\n(v) 01 No - 300 Amps, 04 pole, MCCB, 25 KA (Ics), micro processor type. \n(vi) 01 No - 200 Amps, 04 pole, MCCB, 25 KA (Ics), micro processor type. \nNotes:\n(1) The LT Panel shall be as shown in schematic drawing & GA drawing.\n(ii) All ACB/ MCCB's shall be provided with rotary operated mechanism.\n(iii) All ACB / MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing AC B/MCCB For Cable Connection., REAR\n(iv) This panel shall be a FRONT operated, with cable entry from the Top and bottom. The fault with standing capacity shall be 50 KA. Earth bus shall be part of the LT panel).\n(v) Engraved Al-Plates shall be provided for each Feeder. \n(vi) LT panel shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. \n(vii) PCC work in foundation as recommended by manufacturers.\n
277 277 Supplying, installation, testing and commissioning of L.T. panel for main sub station room fully compartmentalized cubical type fabricated out of 2mm thick CRCA sheet, floor/wall mounted totally enclosed powder coated painting, painted after seven tank process, extensible on both sides, switch board suitable for use on 1 Phase/3-phase, 50 Hz system having required ault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/Sqmm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.\nINCOMING: 1 No x 800 amps,4P, ACB,MDO, Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 kA (Ics) for incomer\nINDICATING PANEL\n(a) The Indicating panel of each incomer ACB shall be provided with the following: \n(b) Provide L&T make Intelligent panel meter- Quasar (96mm x 96 mm) covering 25 electrical parameters with RS 485 port for all incomming and outgoing ACBs. \n(c) 3 Nos. phase indicating lamps; each lamp shall have one toggleswitch backed up with HRC fuse.\n(d) Space for Electronic Energy meter of suitable capacity & CT's\n(e) Red/ Green ON/OFF indicating lights for both incomers and\nBus coupler ACBS & ON indication lights for outgoing ACBS /MCCBs\nBUS BARS: 1 Set of 1000Amps TPN Copper Bus bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 50 KA at 430 volts\n\n 1 Each
278 278 OUTGOING\n3 Nos. of 100 Amps ,4P, MCCB of 25 KA (Ics) service breaking capacity and 100 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required.\n1 No. of 160 Amps 4P, MCCB of 25 KA (Ics) service breaking capacity and 160 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required. \n1 No. of 200 Amps 4P, MCCB of 25 KA (Ics) service breaking capacity and 200 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required.\n1 No. of 250 Amps ,4P, MCCB of 25 KA (Ics) service breaking capacity and 250 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required.\nNotes:\n(i) The LT Panel shall be as shown in schematic drawing & GA drawing.\n(ii) All ACB/ MCCB's shall be provided with rotary operated mechanism.\n(iii) All ACB / MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing AC B/MCCB For Cable Connection., \n(iv) This panel shall be a FRONT/operated, with cable entry from the Top and bottom. The fault with standing capacity shall be 50 KA. Earth bus shall be part of the LT panel).\n(v) Engraved Al-Plates shall be provided for each Feeder.\n(vi) LT panel shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved.\n(vii) PCC work in foundation as recommended by manufacturers.\n
279 279 Rubber insulating corrugated matt of size 2000mm x 1000mm, 15mm thickness suitable for 1100 volts grade conforming to IS complete. 20 Each
280 280 Sch 'A' Part - XIII (EXTERNAL WATER SUPPLY AND SOLAR WATER HEATING SYSTEM) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
281 281 Ductile iron pressure pipes with spigot and socketed type, centrifugally cast, K-9 (as per IS-8329), in any length, laid in trenches complete all as specified, for
282 282 (a) 80mm nominal bore 990 RM
283 283 (b) 100mm nominal bore\nNote : Earth work, fittings and joints shall be measured and paid for separately. 150 RM
284 284 Rubber gasket joint for Spigot and Socket pipes and fittings complete all as specified, for
285 285 (a) 80mm bore 198 Each
286 286 (b) 100mm bore 30 Each
287 287 Lead joint for Spigot and Socket pipes and fittings complete all as specified, for
288 288 (a) 80mm bore 100 Each
289 289 (b) 100mm bore 100 Each
290 290 (c) 150mm bore 150 Each
291 291 Jointing with rubber or fibre board gasket for Flanged Pipes and fitting incl nuts, bolts, washers etc complete all as specified, for
292 292 (a) 100mm bore 25 Each
293 293 (b) 150mm bore 15 Each
294 294 Tubes, 'medium grade', galvanised iron, with all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified, of following bores:-
295 295 (a) 20mm nominal bore 260 RM
296 296 (b) 25mm nominal bore 130 RM
297 297 (c) 40mm nominal bore 330 RM
298 298 (d) 50mm nominal bore 400 RM
299 299 (e) 80mm nominal bore 15 RM
300 300 (f) 100mm nominal bore 10 RM
301 301 (g) 150mm nominal bore 10 RM
302 302 Gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed complete, for pipes of :-
303 303 (a) 25mm bore 5 Each
304 304 (b) 32mm bore 2 Each
305 305 (c) 40mm bore 5 Each
306 306 (d) 50mm bore 25 Each
307 307 Construction of masonry valve pit of size 1050 x 1050 x 1200mm (internal dimensions) including excavation and earth work in any type of soil, PCC 1:4:8, type D-2 in foundation, brick masonry in CM 1:4, 15mm thick plaster in CM 1:6 and flush pointing the hidden surfaces as the work proceeds, angle iron 35 x 35 x 6mm frame, MS sheet 10 SWG in cover including painting, locking arrangement etc., complete all as specified and shown on drawing. 29 Each
308 308 All as per Srl item 15.07 above but of size 750x750x750mm 30 Each
309 309 Centrifugally Cast (Spun) ductile iron pressure pipes with socket & spigot ends confirming to IS: 8329/2000 for water supply lines (external works) in standard lengths classification K 7 suitable for Push-on-joint (Rubber Gasket D jointing) with cement mortar lining inside the pipes and outside zinc coating as per IS: 8329/2000, laid in trenches complete all as specified, of following bores:-
310 310 (a) 100mm bore 535 RM
311 311 (b) 150mm bore\n\n\nNote : Earth work, fittings and joints shall be measured and paid for separately. 1120 RM
312 312 D.I specials of Class K-12 as per IS: 9523 for pipes upto 150mm bore complete all as specified. 4100 Kg
313 313 Rubber gasket SBR (Tyton) joint for Spigot and Socket pipes and fittings complete all as specified, for
314 314 (a) 100mm bore 297 Each
315 315 (b) 150mm bore 224 Each
316 316 C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (the tail pieces, tapers etc. if required will be paid separately) suitable for 150mm bore and 80mm dia inlet connection complete all as specified. 2 Each
317 317 Butterfly valve class-I, P.N. 1.6, conforming to IS 13095-1991 complete with flanges, bolts, nuts, gasket etc. as per specifications complete in all respect hydraulically tested to 20kg/sqcm, suitable for
318 318 (a) 80mm bore 4 Each
319 319 (b) 100mm bore 15 Each
320 320 (c) 150mm bore. 10 Each
321 321 Cast iron double flanged horizontal type with gunmetal seat non-return valve confirming to class - I of IS : 5312 including nuts, bolts, 1.5 mm thick compressed asbestos gasket including painting complete all as specified, for
322 322 (a) 80mm bore. 4 Each
323 323 (b) 150mm bore. 2 Each
324 324 Supply, Installation, testing & commissioning of horizontal monobloc pumping set with C.I. body and bronze impeller, shaft of carbon steel and C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles, A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads as required, M.S fabricated base plate, suction and dilevery pipe including headers, bolted to cement concrete foundations complete. Recycle Water Supply Capacity/Flow Rate - 800 LPM, Head-40m, Capacity not less than 7.5 WHP complete 2 Each
325 325 Supply, Installation, testing & commissioning of horizontal monobloc pumping set with C.I. body and bronze impeller, shaft of carbon steel and C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads as required, M.S fabricated base plate, section and dilevery pipe including headers, bolted to cement concrete foundations complete. Recycle Water Supply Capacity/Flow Rate - 200 LPM, Head-20m, Capacity not less than 2 WHP complete. 2 Each
326 326 Supplying, installing, testing and commissioning of Solar water heating system at 60o/70oC consisting of solar Flat Plate collectors (Cu-Cu) with ultrasonic welded fins including structural supporting frames, Heat Exchanger Stainless steel-304 hot water storage tank of 3mm thickness (minimum) of required capacity with installation over MS/Civil supports, electric panel for power back up, isolation valves, GI piping, insulation with aluminium cladding, on-line Pressure/Re-circulation pump and any other necessary works required to provide staisfactory functioning complete all as specified fixed on floor or roof with fixing arrangements as per manufactures instructions and connecting to cold water supply but excluding cold water tank and pipe line, for following capacities:- \n
327 327 (a) 200litres 3 Each
328 328 (b) 300litres 1 Each
329 329 (c) 500litres 1 Each
330 330 (d) 1000litres 6 Each
331 331 Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS:10910 on 12mm dia steel bar conforming to IS:1786 having minimum cross section 23mm x25mm and over all minimum length 263mm and width 165mm with minimum 112mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length 138mm as per standard drawing and suitable to withstand the bend test and chemical resistance test as per specifications and having manufacturer's permanent identification mark visible even after fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6, type C-1, using graded stone aggregate 20mm complete as per design. (for sewage disposal) 515 Each
332 332 Supplying, fixing, testing and commissioning of Non-clog type Submersible single stage pump with bronze impellar, SS shaft suitable for solids handling upto 40 mm size, coupled to submersible including electric motor, panel and necessary cabling complete with pressure gauge on each pump outlet with low level cut off, level controller for automatic operation in the sump, pump capacity 7.5Lps (450 lpm) at 10 m head (for Sewage disposal and drainage disposal in Basement toilets) (One working + one stand by) 8 Each
333 333 Puddle flanges fabricated out of 600mm long G.I. pipe welded around with 6mm thick MS plate and MS flange at one end of suitable size and properly fixed in RCC wall, slab etc of OHT/UGT etc, complete for following bore of pipes :-
334 334 (a) 65mm bore 2 Each
335 335 (b) 80mm bore 5 Each
336 336 (c) 100mm bore 5 Each
337 337 (d) 150mm bore 5 Each
338 338 Total Amount of Sch 'A' Part - XIV (Demolition of Buildings/ Structures) 1 Lump \nSum
339 339 PART- XV : LIST OF WORKS AND PRICES FOR SHADOWLESS, LANDSCAPE AND STREET LIGHTING SYSTEM\nSCHEDULE `A' PART-XV, Sec-II is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green filed under Col-6.
340 340 Mobile O.T. Light \n(Conforming to IEC 60601-1 & 60601-2-41 Safety Standard ‘CE’ Marking). (Single Dome, 04 Reflectors Mobile O.T. Light). Four reflectors with four halogen bulbs, high performance, mobile O.T. light mounted on rugged stand. O. T. light having heat absorbing colour correcting filters and shadow reducing diffusers. Fully spring balanced provided with focusing cum autoclavable handle of the centre of the dome. Cool, white and brilliant light field. Low voltage transformer integrated in the base. Intensity control and switch provided on the main stand. Pre-treated Epoxy powder coated. 16 Each
341 341 Ceiling O.T. Light with Battery Backup\n(Conforming to IEC 60601-1 & 60601-2-41 Safety Standard ‘CE’ Marking). Ceiling mounted O.T. light having single dome. Dome consisting of seven glass dichroic reflectors with seven halogen bulbs, heat absorbing colour correcting filters and shadow reducing diffusers. Fully spring balanced. Dome without holes completely sealed to prevent dust fitted with focusing cum autoclavable handles. Supplied with low voltage unit. Epoxy powder finish. 10 Each
342 342 Decorative Street lantern fitting HPSV 150 watt with die cast aluminium supporting ring, upper hemisphere spun aluminium both painted mistral grey or any combination of colours on required PU finish. An optical compartment having tightness level IP 66 sealsafe as per standard IEC-EN 60598 with empty weight 4.5 Kgs and comprising of a single piece deep draw aluminium anodised reflector sealed to a frosted acrylic protector, integral control gear and suitable for 150W HPSV lamp. The luminiare is opened without tools by releasing toogle clips situated at the collar of the ring. \nMake : Philips - CGP-431 or equivalent of make mentioned in Appx 'B'. 184 Each
343 343 Decorative Pole 8m with twin Filia bracket made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 140mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suitable into the pole. 13 Each
344 344 Decorative Pole 8m with single Filia bracket made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 140mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suitable into the pole. 165 Each
345 345 Supplying, laying, jointing and testing in trenches/ducts or fixed to wall/poles or passed through pipe, 1100 volts grade, armoured, heavy duty LT XLPE Cable with stranded aluminium conductor of nominal cross section area 50 Sqmm 3.5 Core, complete all as specified. 326 Rm
346 346 All as per Srl item 06 above but cross section area 16 Sqmm 4 core complete all as specified. 51 Rm
347 347 All as per Srl item 06 above but cross section area 25 Sqmm 4 core complete all as specified. 489 Rm
348 348 All as per Srl item 06 above but cross section area 10 Sqmm 4 Core complete all as specified. 927 Rm
349 349 All as per Srl item 06 above but cross section area 10 Sqmm 2 Core complete all as specified. 937 Rm
350 350 All as per Srl item 06 above but cross section area 6 Sqmm 2 Core complete all as specified. 2617 Rm
351 351 LT feeder piller box, out door type, with canopy having slant of 600, water, dust and vermin proof, made of 14SWG CRCA sheet and angleiron 50x50x6mm frame, powder coated inside and out side having thickness 50 micron (min) in light gray shade or seisems gray shade, duly wired with copper wiring and having electronic grade copper bar. The panel shall be front and back openable with locking arrangement, painted in two coats with dray paint over one coat of red Oxide zinc chrome primer, mounted on angle iron 50x50x6mm legs grooted in PCC foundations, 100 Amp Copper bas bars, mounted on DMC insulators, bakelite terminal blocks for outgoing connections in the cable along and shall be consisting by providing of following accessories:- 2 Each
352 352 (a) Copper bus bar chamber 200 Amp, TPN - 01 No.\n(b) Incoming MCCB, 100 Amp, 4 Pole and 25KA - 01 No.\n(c) Out going MCCB TP 63 Amp - 02 Nos.\n(d) Out going MCB SPN 40 Amp - 04 Nos.\n(e) Voltmeter 0 to 500 Volts square type - 01 Nos.\n(f) Phase indicating lamp - 01 Set of three.\n(g) Complete internal wiring of incoming, out going MCCB/MCB with suitable size of signal core unseathed coper cable with lugs - 01 job.
353 353 LT feeder piller box, out door type, with canopy having slant of 600, water, dust and vermin proof, made of 14SWG CRCA sheet and angleiron 50x50x6mm frame, powder coated inside and out side having thickness 50 micron (min) in light gray shade or seisems gray shade, duly wired with copper wiring and having electronic grade copper bar. The panel shall be front and back openable with locking arrangement, painted in two coats with dray paint over one coat of red Oxide zinc chrome primer, mounted on angle iron 50x50x6mm legs grooted in PCC foundations, 100 Amp Copper bas bars, mounted on DMC insulators, bakelite terminal blocks for outgoing connections in the cable along and shall be consisting by providing of following accessories:- 2 Each
354 354 (a) Copper bus bar of suitable size, 100 Amps colour coated with heat strinkable sleeves - 04 Nos.\n(b) Incoming MCCB, 63 Amp, 4 Pole and 25KA - 01 No.\n(c) Out going MCB SPN 40 Amp - 04 Nos.\n(d) Voltmeter 0 to 500 Volts square type - 01 Nos.\n(e) Phase indicating lamp - 01 Set of three.\n(f) Complete internal wiring of incoming, out going MCCB/MCB with suitable size of signal core unseathed coper cable with lugs - 01 job.
355 355 Copper bus bar chamber, 4 strips, 100 Amp with CRCA sheet 1.6mm and MS angle Iron 45x45x6mm frame of size 1000x600x300mm size with front opening door having 1 incoming and 4 outgoing cable hole (20mm dia) with rubber bushes/glands including 4 Nos angle iron legs grouted in PCC foundation complete all as directed. 7 Each
356 356 GI Pipe, light grade, 40mm dia for protection of cable at road/drain crossing etc. including all fittings, laid in trenches, under floor or ducts. 1018 Rm
357 357 Street light luminaire HPSV 70 watt (single) with IP 66 Optical compartment tightness level & IP 66 Control Gear tightness level (according to standard IEC-EN 60598) with an Impact resistance of IK 08(according to standard IEC-EN 62262).The luminaire should be Ultra compact with the miniR reflector and its empty weight should not exceed 2.2 Kgs.The body and cover are made from high quality painted die cast aluminium alloy.The optical Compartment consists of a deep drawn, anodised & polished alluminium reflector and a curve glass protector. The control gear is mounted on aplate that can be removed without tools, suitable for mounting with 70W HPSV lamp incl connecting and testing complete.\nMake : Philips - SPP 202 or equivalent of make mentioned in Appx 'B'. 1 Each
358 358 Decorative Pole 4m (ATG) made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 114mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suited into the pole erected to truely vertical position complete all as specified. 40 Each
359 359 Street light luminaire HPSV 70 watt (twin) with IP 66 Optical compartment tightness level & IP 66 Control Gear tightness level (according to standard IEC-EN 60598) with an Impact resistance of IK 08(according to standard IEC-EN 62262).The luminaire should be Ultra compact with the miniR reflector and its empty weight should not exceed 2.2 Kgs.The body and cover are made from high quality painted die cast aluminium alloy.The optical Compartment consists of a deep drawn, anodised & polished alluminium reflector and a curve glass protector. The control gear is mounted on aplate that can be removed without tools, suitable for twin mounting with 70W HPSV lamps incl connecting and testing complete.\nMake : Philips - SPP 202 or equivalent of make mentioned in Appx 'B'. 1 Each
360 360 Decorative Pole 6m (ATG) with "T" mounting bracket made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 114mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suited into the pole erected to truely vertical position complete all as specified. 14 Each
361 361 Decorative Bollard CFL luminaire 1x26 watt made of Extruded Aluminium body with Top,Shaft & Base diameter of 181mm, base and cover in cast Aluminium, glass protector, spun Aluminium internal louvers, painted white, removable control gear plate with and incl 26 W CFL Lamp, incl making connection and testing complete. 1 Each
362 362 Shrub/Tree Uplighter  1x50W PAR High pressure cast Aluminium housing, 8mm thick tempered glass,suitable for and providing PAR 20/50W Lamp incl making connections and testing complete. 1 Each
363 363 Torch light 1x70w CDMT- the column is comprised of a cylinder of 2 m which is cadium plated and a light conductor of 3 m made of opaline acrylic. The Sealsafe® optical compartment (IP 66 according to IEC-EN 60598), fitted with an Aluminium reflector, situated at the bottom of the light conductor. At the top of the cylinder, another reflector, made from Aluminium, reflects the light towards the ground.The Impact resistance of PMMA is IK 08(according to IEC-EN 62262) and the empty weight of the luminaire should not be less than 57 Kgs.The lamp and the control gear - on a removable plate - are accessed via a hatch incl making connections and testing complete. 4 Each
364 364 Recessed/Step Light - LED 1.2W with IP67 protection and cover ring made of stainless steel with die cast aluminium housing with 230V/24V DC,20W transformer suitable for 1-15 no. LEDs incl making connection and testing complete. 1 Each
365 365 Ground Embedded flood light 1x50 W CDMT (IP67) - a pressure die cast painted Aluminium alloy body and cover – cover attached to the body with 4 nos. stainless steel rapid closing mechanisms; toughened 19mm thick glass protector capable of withstanding load of 3 tons; a double gasket recessed into the body, removable control gear tray, pre-wired with 2.5 sq mm, 3 core copper flexible cable 1.5m long with spun and anodised Aluminium reflector. Access to the lamp by unclipping 4 quick-acting closures made of stainless steel with empty weight of 6.58kgs and impact resistance of IK10 as per EN 50102 incl making connection and testing complete.\nMake : Philips - DBP523 or equivalent of make mentioned in Appx 'B'. 1 Each
366 366 Decorative lantern MOON 1x70W HPSV (Sealsafe IP66) with Die cast aluminium supporting ring, upper hemisphere spun aluminium both painted mistral grey or any combination of colours on required PU finish. An optical compartment having tightness level IP 66 sealsafe as per standard IEC-EN 60598 with empty weight is 4.5 Kgs and comprising of a single piece deep draw aluminium anodised reflector sealed on to a frosted acrylic protector, integral control gear and suitable for and including 70W Metal Halide lamp. The luminiare is opened without tools by releasing toogle clips situated at the collar of the ring. This gives acess both to the Electrical CG positioned on a removable plate and to the lamp holder support plug. Access to the lamp is easily gained by rotating the plug incl making connections and testing complete.\nMake : Philips - CGP-431 or equivalent of make mentioned in Appx 'B'. 1 Each
367 367 MCB, SP, 6 Amp, 240 V, 'C' curve complete all as specified. 217 Each
368 368 PCC 1:3:6, type C-2, using 40mm graded crushed stone aggregate for foundation filling and mass concrete of poles etc. 73.54 Cum
369 369 Dry sand cushioning to under ground cable, provided with a layer 8cms thick before laying the cable and 15cms thick after laying and stretching the cable complete all as specified. 780 Cum
370 370 Sub class 'B' bricks, well burnt, as in cable protection cover, laid dry, flat, over sand cushioning with width equal to the length of brick, transversally along the length the cable complete all as specified. 67257 Each
371 371 L T feeder piller box made out of CRCA sheet 3.15mm thick and 50x50x6mm angle iron base frame with 4 Nos legs, out door type, including & providing following accessories:-\n(a) Copper bus bar chamber 100 Amp, TPN - 01 No.\n(b) Incoming MCCB, 63 Amp, 4 Pole and 25KA (lcs) - 01 No.\n(c) Out going MCB SPN 40 Amp - 04 Nos.\n(d) Voltmeter 0 to 500 Volts square type - 01 Nos.\n(e) Phase indicating lamp - 01 Set of three.\n(f) Complete internal wiring of incoming, out going MCCB/MCB with suitable size of signal core unseathed coper cable with lugs - 01 job. 2 Each
372 372 EARTHING WORK FOR LIGHTING, RECYCLE WATRER SUPPLY, VARIOUS TREATMENT PLANTS, INCINERATOR, MECHANICAL, LAUNDRY AND AC.
373 373 Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6.00mm thick burried directly in ground (earth plate not less than 2.25m deep below normal ground level)with top edge of the plate not less than 1.5m below normal ground level connected to and including GI earth wire 4.00 mm dia by means of steel bolts, nuts, check nuts and washers, PCC 1:2:4 type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle,light grade GI watering pipe 20mm bore with funnel, wire mesh and medium grade GI protection pipe 15mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, including excavation and earth work in any type of soil, removal of surplus spoil to a distance not exc. 50m complete all as shown in electrical plate No.3 of MES Schedule 2009 (Part-l) and connected to main control board all as specified including testing on completion. 88 Set
374 374 All as per Srl item 17.33 above but GI earth strip 32x6mm without protection pipe 60 Set
375 375 Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or fixed to poles or any other indicated situation or on cable tray for loop earthing etc. as required with 20x3.15mm Galvanised iron strip. 545 RM
376 376 All as per Srl item 17.34 above but G.I wire 4mm dia 800 RM
377 377 Supplying, laying, jointing and testing in trenches/ducts or fixed to wall/poles or passed through pipe, 1100 volts grade, armoured, heavy duty LT XLPE Cable with stranded aluminium conductor of nominal cross section area 16 Sqmm 2 Core, complete all as specified. 436 RM
378 378 Supplying, laying, jointing and testing in trenches/ducts or fixed to wall/poles or passed through pipe, 1100 volts grade, armoured, heavy duty LT XLPE Cable with stranded aluminium conductor of nominal cross section area 6 Sqmm 4 Core, complete all as specified. 5543 RM
379 379 RCC M-25 (design mix), using 20 mm graded crushed stone aggregate as in foundations, including rafts, footings, foundation beam; plinth beams; bases of columns, etc.; basement slabs, under-reamed piles and mass concrete, complete all as specified and as directed by Engr-in-Charge. 226.32 Cum
380 380 TMT mild steel bars, 16 mm dia and over, as in reinforcement, cut to length, bent to shape required including cranking, bending spirally or hooping for columns, hooking ends and binding with and including MS wire (annealed not less than 0.9mm dia) , complete all as specified and as directed by Engr-in-Charge. 5923 Kg
381 381 All as per serial item No. 17.36 here in before but 10 mm dia. 4506 Kg
382 382 All as per serial item No. 17.36 here in before but 8 mm dia. 2192 Kg
383 383 Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, 20mm dia x 600 mm, complete all as specified and directed. 2063 Kg
384 384 Use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter, to obtain rough finished flat surfaces of concrete complete all as specified and as directed. 1128 Sqm
385 385 PART- XVI : LIST OF WORKS AND PRICES FOR RECYCLE WATER SUPPLY\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
386 386 High density polyethylene pipes (HDPE) and fittings of pressure rating 10kg/sqcm PE 100 grade conforming to IS: 4984 including jointing, laid in trenches complete, for following bores :-
387 387 (a) 25mm bore 490 RM
388 388 (b) 32mm bore 50 RM
389 389 (c) 40mm bore 265 RM
390 390 (d) 50mm bore 265 RM
391 391 Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed, for pipes of :-
392 392 (a) 25mm bore 15 Each
393 393 (b) 40mm bore 4 Each
394 394 (c) 50mm bore 5 Each
395 395 Construction of masonry valve pit of size 1050 x 1050 x 1200mm (internal dimensions) including excavation and earth work in any type of soil, PCC 1:4:8, type D-2 in foundation, type C-1, brick masonry in CM 1:4, 15mm thick plaster in CM 1:6 and flush pointing the hidden surfaces as the work proceeds, angle iron 35 x 35 x 6mm frame, MS sheet 10 SWG in cover including painting, locking arrangement etc., complete all as specified and shown on drawing. 8 Each
396 396 All as per Srl item 18.03 above but of size 750x750x750mm 39 Each
397 397 Reinforced concrete pipes, class NP2, laid and jointed complete with collars (for encasing of HDPE pipe), bore of pipe.
398 398 (a) 150mm 80 RM
399 399 (b) 200mm 50 RM
400 400 SFRC (Steel Fibre Reinforced Concrete) Cover and frame (Light duty LD-2.5 grade designation) 610x450mm internal diameter conforming to I.S 12592. (for Butterfly Valve chamber), complete all as specified. 8 Each
401 401 Un plasticized (UPVC) class-III pipes and fittings of pressure rating 6 Kgs / cm2 conforming to IS: 4985 including jointing and laid in trenches complete, of following sizes :-\n
402 402 (a) 75mm outer dia 260 RM
403 403 (b) 90mm outer dia 940 RM
404 404 (c) 110mm outer dia 350 RM
405 405 (d) 160mm outer dia 220 RM
406 406 Puddle flanges fabricated out of 600mm long GI/MS pipe welded with 6mm thick M S plates along with flanges of suitable size and properly fixed in walls and top slabs of UGT complete, of following sizes :-\n
407 407 (a) 65mm dia 2 Each
408 408 (b) 80mm dia 3 Each
409 409 (c) 100mm dia 3 Each
410 410 (d) 150mm dia 3 Each
411 411 Gunmetal garden hydrant (pop-up sprinkler) fixed on irrigation pipe line complete, for 25mm dia 52 Each
412 412 Butterfly valve confirming to type P.N. 1.6 of IS 13095-1991 complete with flanges, bolts, nuts, gasket etc. complete in all respect hydraulically tested to 20kg/sqcm, complete all as specified, of following sizes :-\n
413 413 (a) 65mm diameter Class - I 2 Each
414 414 (b) 80mm diameter Class - I 2 Each
415 415 (c) 100mm diameter Class - I 3 Each
416 416 (d) 150mm diameter Class - I 1 Each
417 417 Cast iron double flanged horizontal type with gunmetal seat non-return valve confirming to class - I of IS : 5312 including nuts, bolts, 1.5 mm thick compressed asbestos gasket including painting complete of following sizes :-\n
418 418 (a) 65mm diameter Class - I 2 Each
419 419 (b) 80mm diameter Class - I 2 Each
420 420 C.I 'Y' strainer with flanged end of approved make and making connection to pipe complete in all respects, of following sizes :-\n(a) 65mm dia nominal bore 2 Each
421 421 Supply, Installation, testing & commissioning of Horizontal monoblock pumping set with C.I. body and bronze impeller, shaft of carbon steel and C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads as required, M.S fabricated base plate, section and dilevery pipe including headers, bolted to cement concrete foundations complete. Recycle Water Supply Capacity/Flow Rate - 800 LPM, Head-20m, Capacity not less than 5 WHP complete 2 Each
422 422 Supply, installation, testing and commissioning of panel suitable for 415 V, 3 phase, 4 wires, 50 Hz power distribution system, floor/wall mounting, sheet metal enclosed, dust and vermin proof with Aluminium busbars separate earth bus bars throughout the length of the panel, incoming and outgoing feeder accommodated in a modular multitier arrangement. The painting shall done as per relevant IS codes/as specified in the specifications. Adequate size cable alley shall be provided for each cable bending and termination. Bus bars shall be provided with heat shrinkable colour coded PVC sleeves, inlcuding necessary suitable size Cables, etc. complete.\nThe panels shall be suitable for cable entry from top/Bottom. The minimum fault rupturing of all incoming and outgoing switches/breakers shall be as specified. The panels shall be fabricated after the approval of fabrication drawings and shall be comprising by providing the followings:-\nIncoming:\nOne (1) No. 200 Amp, 25 KA (Ics), TPN, MCCB with adjustable thermo magnetic release as incomer.\nOne (1) No. (0-500V) digital type voltmeter.\nOne (1) No. (0-200A) digital type Ammeter with suitable C.T.’s for metering.\nOne (1) No. earth leakage relay with multiple trip setting with CBCT. 1 Each
423 423 One (1) set of R, Y, B phase indication lamps and MCCB ON/OFF indication Lamps.\nBusbars :\n250 Amp, TPN copper busbar insulated with heat shrinkable sleeves and shall be color coded mounted on insulators\nOutgoings:\nEight (8) Nos. 63 Amp, TP, MCCB, 25 KA (Ics).\nEight (8) Nos., 16 Amp, TP, MCB with thermal range 10 Amp to16 Amp\nStarter:\nStarter complete with Auto /Manual selector switch, start / stop Push Button,O/L Relay with Single phasing preventer feature, ON-OFF and Trip Indicating lamps,AC3 duty contactors Auxellarycontacts for Building Automation System, interlocking etc suitable for the motor H.P. as specified below :-\nDOL starter suitable for5 HP motors \nWater Level Controller with level switches :\nWater level controller shall be provided for each starter with sufficient nos. of low/high level switches for the auto operation of the pumps. Cost for wiring from level switches to the starter panel is deemed to include the rate quoted by tenderer.
424 424 Sch 'A' Part - XVII (ETP, WTP, CSP AND STP)
425 425 Effluent Treatment Plant capacity 0.3MLD as per drawings and all as specified herein after :-\n(a) Diffused Aeration System.\nConstruction, supply, installation of diffused aeration system complete with diffuser membranes made of EPDM rubber extruded membrane, with diffusers evenly spaced and adequately supported for equalization tank - 01 Job (b) Effluent Transfer Pumps Horizontal single stage open impeller suitable for solids upto 10 mm coupled to a horizontal TEFC electric motor and mounted on a MS fabricated base plate , with pressure gauge on each pump outlet, automatic duty switchover after each operation complete. Pump Capacity 8.33 lps (500 lpm) at 10 m head - 02 Set (c) Tube settler with flash mixing Tank \nSelf supporting ETP unit comprising of mixing tank for flash mixer, mixed solution tank and the main tube settler unit as per manufacturer’s design fabricated from 6 mm MS plates strengthened with MS structural members, painted inside with epoxy paint - 01 Set 1 Job
426 426 (d) Chemical Dosing Pumps \nChemical dosing metering pumps mounted on 100 lit MSEP/PVC containers with lids complete with suction and delivery piping, injection assembly, complete with connection with solution making and storage tanks for continuous supply of chemicals. Dosing pump capacity as per manufacturer’s design. For Lime , Alum , poly-electrolyte and dosing for \nMSEP/HDPE self supporting solution making tanks each of 200 ltr capacity provided with water connection and agitation for proper mixing of the chemicals - 03 Set (e)Solution making and storage tanks \nMSEP/HDPE self supporting solution making tanks each of 200 ltr capacity provided with water connection and agitation for proper mixing of the chemicals - 03 Set (f) Flash Mixer \nElectrical vertical flash mixer for mixing and preparing dosing solution installed in the flash mixer tank on the ETP - 01 Set (g) Sludge Transfer Pumps\nHorizontal, centrifugal type with TEFC electric motor and mounted on a MS fabricated base plate, with pressure gauge on each pump outlet, automatic duty switchover after each operation complete in all respects \nPump Capacity 2 Cum/hour at 10 m head - 02 No
427 427 WATER SOFTENING PLANT Supplying, installation, testing and commissioning of water softener fabricated from MS plate as per IS:2825 (shell & thick dished ends) complete with initial charge of resins. GI class 'C' face piping, CI butterfly valves, pressure gauge, hydraulic brine injector, accessories, painting inside with epoxy paint and outside with two coats of red oxide primer and two or more coats of synthetic enamel paint, regeneration capacity complete with resins of approved quality comprising of following parameters:- (a) Inlet (TDS) - 700-1000 PPM (Approx.) (b) Inlet (Hardness) - 400-1000 PPM (Approx.) (c) Outlet (Hardness) - Commercially Zero Capacity - 55000 LPH (55 Cum/hour) \nRegeneration Period - 12 hrs. \nOBR - 550 Cum \nOperating Pressure - 3.0kg/Sq.cm \nTest pressure - 5.5 Kg/Sq.cm \nSuggested Resin Quantity - 8370 Lit. \nSuggested Height - 2600 mm \nSuggested dia - 2400 mm \nBrain Tank - 1 No. (100 lit. capacity) 1 Set
428 428 CENTRAL SEWAGE TREATMENT PLANT \nSupply, installation, testing & commissioning of Central Sewage Treatment Plant capacity 1MLD as per drawings and all as specified here in after :- 1 Each
429 429 (a) Coarse Bar Screen\nFabrication, Supply & Installation of coarse bar screen in MSEP of suitable size for 1.0 MLD and capable of holding particles upto 20 mm.- 02 Nos
430 430 (b) Fine Bar Screen\nFabrication, Supply & Installation of fine bar screen in MSEP of suitable size for 1.0 MLD and capable of holding particles upto 6 mm.- 02 Nos
431 431 (c) Main Sewage Pumps \nSubmersible single stage open impeller suitable for solids upto 40 mm size coupled to submersible electric motor complete with pressure gauge on each pump outlet complete with low level cut off, level controller to operate 2nd pump if 1st pump fails to meet the demand, automatic duty switch over after each operation in the STP.complete in all respects \nPump Capacity 52 Cum per hour at 9 m head \n(Two working + one stand by)- 03 Nos
432 432 (d) Air Blower for the FAB Reactor\nElectrically operated twin lobe air blowers and TEFC electric induction motor mounted on a common MS base plate with belt drive, belt protection guard, suction silencer and all accessories and supports. \nBlower capacity 500 cum/hr (each), 12.5 HP- 02 Nos
433 433 (e) Attached Growth bio reactor \nManufacture, supply, installation of Attached Growth Bio Reactor (AGBR) suitable for 95% BOD removal efficiency, provided with PVC media, with specific surface area not less than 350 sq.m/cu.m . Media may be structured or floating type. The reactor should be complete with supports, as per specifications and as directed by GE. - 02 Nos
434 434 (f) Diffused aeration System \nSupply, installation of diffused aeration system complete with diffuser membranes made of EPDM rubber extruded membrane, with diffusers evenly spaced and adequately supported for following tanks. Pipe grid shall be separately measured as per piping rates, complete all as per specifications and as directed by GE.- 01 Set ( i) Aeration units (ii) Main Equalization tank ( iii) Sludge Holding Tank (iv) Treated Water Tank
435 435 (g) Clarifier mechanism \nManufacture, supply, installation, testing and commissioning of clarifier mechanism complete with scrapper mechanism for scrapping sludge at the bottom.- 01 Set For Clarifier of main STP
436 436 For Clarifier of main STP \n(h) Main Filter \nMS fabricated /FRP multilayer filter vertical , pressure type dished ends fitted with internal distribution pipe on top, collector pipes and arms at bottom, inlet and outlet header complete with initial charge of filter media, face piping, accessories, working pressure 2.4 kg/sqcm ( Test pressure 3.75 kg/sq.cm. The vessel shall be painted with two coats of red oxide zinc chrome primer and two coats of paint. Capacity 60,000 liter per hour \nFiltarion velocity 10,000 liter per hour /sqm - 01 No
437 437 (i) Activated carbon filter \nMS fabricated /FRP multilayer filter vertical , pressure type dished ends fitted with internal distribution pipe on top, collector pipes and arms at bottom, inlet and outlet header complete with initial charge of filter media, face piping, accessories, Working Pressure 2.4 kg/sqcm ( Test pressure 3.75 kg/sq.cm. The vessel shall be painted with two coats of red oxide zinc chrome primer and two coats of paint. Capacity 60,000liter per hour . Filtarion velocity. 10,000 liter per hour /sqm. - 01 No
438 438 (j) Chlorination Pumps \nChemical dosing metering pumps mounted on 90 lit PVC containers with lids complete with suction and delivery piping, injection assembly, one set of buckets and containers for making solution for each pump complete in all respects. capacity as per manufacturer’s design. For Chlorine dosing of final effluent - 02 Nos.
439 439 (k) Instrumentation \nMagnetic type flow meter giving reading in liter per minute/liter per hour. \n(a) On Main STP inlet - 01 No (b) Level Controllers - 03 No
440 440 Float type suitable to work in sewage water without cleaning \n(l) Piping\nSupply, erection, jointing and testing MS pipes for waste water lines with necessary fittings, specials & supports as per technical specifications, etc. all pipes above ground shall be complete with two coats of red oxide zinc chrome primer and enamel paint , shade shall be as specified. - 01Job
441 441 (m) Valves\nSupply, Fixing and testing CI Butterfly valves for waste water lines with necessary fittings, specials & supports as per technical specifications, etc. complete all as specified and as directed by GE. - 01 Job
442 442 (n) Filter press \nDesign, supply & installation of filter press in cast iron frame and polypropelene plates of size 24”x24” (min) with 32 plates with electric driven hydraulic power pack system complete in every respect required for efficient operation. - 01 Set
443 443 (o) Filter Press Feed Pumps\nHorizontal single stage open impeller suitable for solids upto 65 mm coupled to a horizontal TEFC electric motor and mounted on a MS fabricated base plate, with pressure gauge on each pump outlet, automatic duty switchover after each operation complete in all respects.\nPump Capacity 5 Cum/hour at 10 m head - 01 Set
444 444 COLD STORAGE PLANT \nSupplying, instalation , testing and commissioning of pre fabricated cold storage plant electrically driven with suitable cooling/freezing units with control panel and all other accessories complete for temperature range minus 6 Deg C to 6 Deg C for 1.25 TR capacity details as under :- (a) Room Dimension (Mt.) (2.39X2.39X2.4) (b) Room Temperature (+) 4° C (c) Ambient Temp. (45° C) (d) Material to be stored. (Pharma Products) (e) Product Incoming Rate (300 Kgs/Day) (f) Product Entry Temp. (20-22o C) (g) Pull down time (12 hours) (h) Insulation (i) Walls and Ceiling (60 mm PUF with prepainted CRCA sheet). (ii) Floor (60mm PUF Panels). (j) Sliding Door size (0.9 x 1.9 m) (k) Refrigeration unit (R-134A 15,000 BTUH (1.25 TR. 1 Each
445 445 Supplying, instalation , testing and commissioning of pre fabricated cold storage plant electrically driven with suitable cooling / freezing units with control panel and all other accessories complete for temperature (+) 4o C for 5 TR capacity details as under :- (a) Ambient Temp. (45o C) (b) Material to be stored (F&V Products) (c) Product Incoming Rate (1000 Kgs/Day) (d) Product Entry Temp. (20-22o C) (e) Pull down time ( 24 hours) (f) Insulation (i) Walls and Ceilling (60 mm PUF with Prepainted CRCA sheet as external finish and as intrnal finish) (ii) Floor (60 mm PUF Panels) (g) Sliding Door size (0.9 x 1.9 Meter) (h) Refrigeration unit (R-134A 60,000 BTUH (5 TR.)) 3 Each
446 446 Supplying, instalation , testing and commissioning of pre fabricated cold storage plant electrically driven with suitable cooling / freezing units with control panel and all other accessories complete for temperature range 2o C to 4o C for 4 body mortury cabinet details as under :- (a) Dimension (mm) (2110x2400x1785 high) (b) Interior finish (0.55 pre painted GI sheet) (c) Exterior finish (0.55 pre painted GI sheet) (d) Front finish & trims ( 0.50 Stainless steel) (e) Door & Door Frame - (FRP Door (45mm thick PUF) (f) Foamed Panel (i) Insulation thickness 80 (mm) (ii) Insulation material (Rigid Polyurethane foam (CFC free), Denisity 40 Kg/m3) (iii) Locking machanism (Cam-Locks embedded in foam) (g) Standard Accessories (i) Lamp (Vapor proof incandescent lamp, 40 W) (ii) Temperature indicator cum controller (Electronic with Digital display) 1 Each
447 447 (iii) Carriage assembly (Three piece, telescopic action, GI powder coated) (iv) Mortuary Tray (One piece stain less steel tray with tubular edge and handles). (h) Refrigerating system (Roof Top Mounting Unitary) (i) Capacity (BTU/H) (6000) (ii) Power supply (230 V/1 HP/50 HZ) (iii) Compressor Power (KW) (1.25) (iv) Total Unit Power Consumptions (KW) (1.75) (v) Operating conditions (4 Deg C Room Temperature @ 35 Deg C Ambient) (vi)Over all Dimensions (mm) of Ref. Unit (1140 (L x 900 (W)x415 (H)) Note : Cables for electric connections to the equipments mentioned above shall be measured under respective items of Sch 'A' Part-XII.
448 448 Supply, installation, testing and commissioning of LT panel board for effluent treatment plant, out door type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6 mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :- 1 Each
449 449 (a) Bus bar chamber 3 phase, 4 wire, 440 volts, 50c/s consisting of copper bus bar of capacity 100 Amps (all the four bus bar to be of the same size including neutral) for incoming/outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 Set.
450 450 (b) MCCB, 4 pole, 63 Amp, 415 volts, 25 KA (Ics) - 01 No. (incoming).
451 451 (c) MCCB, 4 pole, 25 Amp, 415 volts, 10 KA (Ics) - 01 No. (outgoing).
452 452 (d) MCB DP 25 Amps, 230 volts, 10 KA (Ics) - 03 Nos.
453 453 (e) MCB DP 16 Amps, 230 volts, 10 KA (Ics) - 03 Nos.
454 454 (f) DOL starter for upto 3 HP motor - 04 Nos.
455 455 (g) Ampere meter 0-100 Amps, square mounted, 96 mm square, with CTS 100/5 Amp rating with selector switch electronic type - 01 No.
456 456 (h) Voltmeter 0-500 volts square mounted, 96mm square with selector switch electronic type - 01 No.
457 457 (j) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job.
458 458 (k) Indicator lamp LED type in RBY colour set of 3 - 01 Set.
459 459 Supply, installation, testing and commissioning of LT panel board for sewage treatment plant, out door type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6 mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :- 1 Each
460 460 (a) Bus bar chamber 3 phase, 4 wire, 440 volts, 50c/s consisting of copper bus bar of capacity 250 Amps (all the four bus bar to be of the same size including neutral) for incoming/outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 Set.
461 461 (b) MCCB, 4 pole, 200 Amp, 415 volts, 25 KA (Ics) - 01 No. (incoming).
462 462 (c) MCCB, 4 pole, 40 Amp, 415 volts, 10 KA (Ics) - 03 No. (outgoing).
463 463 (d) MCCB, 4 pole, 63 Amp, 415 volts, 10 KA (Ics) - 02 No. (outgoing).
464 464 (e) MCB DP 25 Amps, 230 volts, 10 KA (Ics) - 04 Nos.
465 465 (f) DOL starter for upto 6 HP motor - 04 Nos.
466 466 (g) Star Delta starter for 12.5 HP motor - 02 Nos.
467 467 (h) Ampere meter 0-100 Amps, square mounted, 96 mm square, with CTS 100/5 Amp rating with selector switch electronic type - 01 No.
468 468 (j) Voltmeter 0-500 volts square mounted, 96mm square with selector switch electronic type - 01 No.
469 469 (k) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job.
470 470 (l) Indicator lamp LED type in RBY colour set of 3 - 01 Set.
471 471 Sch 'A' PART-XVIII : INCINERATOR \nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
472 472 Supply, Installation, commissioning and testing oil fired incinerator of suitable capacity for hospital waste / bio-medical waste 60Kg/hr. confirming to design and emission parameters mentioned in the Gazette and Guidelines of August 2003 of Central/State polution control board. The incinerator system shall comprise of following accessories/fitments:- 1 Set
473 473 (a) Main Incinerator with.\ni). Refractory lined Primary and Secondary Chamber.\nii). Refractory lined main charging door and ash cleaning door.
474 474 (b) (i). 1 No. fully automatic oil burner for primary chamber. \n(ii). 1 No. fully automatic oil burner for secondary chamber.
475 475 (c) Centrifugal forced draft combustion air fan with motor.
476 476 (d) Auto-loading device in the form Double Flap Damper Valve (DFDV) mechanism with outer gate manual and inner damper motorized.
477 477 (e) Suitable flow measurement device on the Primary & Secondary air ducting.
478 478 (f) Emergency stack / vent.
479 479 (g) High pressure venturi scrubber of Stainless Steel \n(SS316 L).
480 480 (h) Cyclonic type droplet separator cum recirculation tank with built in caustic solution tank in MSRL construction.
481 481 (i) I.D. Fan with MSRL casing & SS 316 L impeller with motor.
482 482 (j) Recirculation Pump (SS 316) with Motor along with piping & valves.
483 483 (k) Overhead HDPE Water tank of suitable capacity along with water piping between tank and scrubber.
484 484 (l) Interconnecting ducting within the battery limits.
485 485 (m) Instruments, valves, dampers and fittings within battery limits.
486 486 (n) PLC based Control Panel with necessary instruments.
487 487 (o) Data recording device in the form of a Printer.
488 488 (p) Oil tank along with oil piping, valves & strainers between tank & burner.
489 489 (q) Operating tools & tackles like rake, hoe, shovel, two teeth scrapper.
490 490 (r) Portable stack monitoring device for CO, CO2 & O2.
491 491 (s) Self supported Mild steel rubber lined chimney of 200 mm top dia and 30m height.
492 492 Supply, installation, testing and commissioning of LT panel board of sewage treatment plant, indoor type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :- 1 Set
493 493 (a) Bus bar chanber 3 phase, 4 wire, 440 volts, 50 c/s consisting of copper bus bar of capacity 150 amps (all the four bus bar to be of the same size including neutral) for incoming / outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 set.
494 494 (b) MCCB, 4 pole, 100 Amp, 415 volts, 25 KA (Ics) - 01 No. (incoming).
495 495 (c) MCCB, 4 pole, 40 Amp, 415 volts, 10 KA (Ics) - 02 Nos (outgoing).
496 496 (d) MCB DP 30 Amps, 230 volts, 10 KA (Ics) - 02 Nos.
497 497 (e) Ampere meter 0-100 Amps, square mounted, 96mm square, with CTS 100/5 Amp rating with selector switch electronic type -01 No.
498 498 (f) Voltmeter 0-500 volts square mounted, 96 mm square with selector switch electronic type - 01 No.
499 499 (g) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job.
500 500 (h) Indicator lamp LED type in RBY colour set of 3-01 set.
501 501 Sch 'A' PART-XIX : MECHANICAL LAUNDRY \nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
502 502 SUPPLY, INSTALLATION AND COMMISSIONING OF IRONER \nSIZE 800 Dia, 3000mm, 1 Roll\nSimple chain drive mechanism with single motor - Heating roll made of high quality stainless steel - Large contact area of 300 degree to maximize heat exchange - Patented automatic belt tensioning systme eliminates manual adjustment - Variable speed frequency inverter control - Gradual speed increment between rolls to improve ironing quality by stretching effect - Heat isolation panel on feeding side - simple control with ON/OFF button and speed adjustment - Heating roll and guide shaft drive simultaneously - Float type steam trap reduces steam consumption Maximum Ironing Width - 3000 mm Diameter of Roll - 800 mm Ironing Speed - 1-10 m /min Steam Pressure - 0.3 - 0.55 Mpa Main Motor - 1.1 Kw Frequency Inverter - 1.5 kw 1 Each
503 503 SUPPLY, INSTALLATION AND COMMISSIONING OF AIR COMPRESSOR (7.5 HP ) Double Stage Tank Cap 220 liter 8 Kg/ cm² . All Performance parameters are as per JIS standards - Duplex compressor mounted on base frame - Low noise and vibration levels - Easy installation - Continuous and heavy duty operation - cost of efficiency.\n 1 Each
504 504 SUPPLY, INSTALLATION AND COMMISSIONING OF STEAM BOILER(2 X 400 KGS) \n
505 505 (a) STEAM GENERATION PLANT\nHSD Fired Coil type Steam Boilers Reverse flame type capable of generating 400 kg/hr of steam from and at 100 deg celcius with max. safety valve set off pressure of 10.54 Kg/Sqcm including all accessories/Safeties, SIBR Kind 3 Each
506 506 (b) BOILER ROOM AUXILLARIES Day Tanks of (i) 2000 lits feedwater tank fabricated out of 6mm thick MS sheet with all fittings and gauge glass 1 Each
507 507 (b) BOILER ROOM AUXILLARIES Day Tanks of (i) 990 lits Fuel Oil tanks fabricated out of 5 mm thick MS sheet with all fittings like level gauge glass 1 Each
508 508 (c) (i) FLUE GAS DUCTING Flue duct ( Bare Size)fabricated out of 5mm thick MS Sheet, for 200 mm dia 4 RM
509 509 (c) (ii) FLUE GAS DUCTING Flue duct ( Bare Size)fabricated out of 5mm thick MS Sheet, for 250 mm dia 8 RM
510 510 (v) Water pump suitable for above softening plantwater @ 50liter per meter @ 30 m head 3 Each
511 511 (e) Steam Pressure reducing station complete with valves,gauges,safety valve,bypass valves & flanking valves,IBR, as under :-
512 512 (i) Steam piping from Boilers to Individual headers (IBR) 1 Each
513 513 (ii) One set of Fuel oil piping from the Oil tank to both boilers inclusive of Valves/NRV 1 Each
514 514 (iii) All boiler drain/Blow down piping to the pit 1 Each
515 515 (f) ELECTRICAL PANEL\n(i) Supply, installation, testing and commissioning of LT panel board for sewage treatment plant, indoor type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :- \n(a) Bus bar chanber 3 phase, 4 wire, 440 volts, 50 c/s consisting of copper bus bar of capacity 300 Amps (all the four bus bar to be of the same size including neutral) for incoming/outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 set. \n(b) MCCB, 4 pole, 250 Amp, 415 volts, 35 KA (Ics) - 01 No. (Incoming). (c) MCCB, 4 pole, 100 Amp, 415 volts, 25 KA (Ics) - 02 Nos (Outgoing). \n(d) MCCB, 4 pole, 63 Amp, 415 volts, 10 KA (Ics) - 02 Nos (Outgoing). (e) MCB DP 30 Amps, 230 volts, 10 KA (Ics) - 03 Nos. (f) Ampere meter 0-100 Amps, square mounted, 96 mm square, with CTS 100/5 Amp rating with selector switch electronic type - 01 No. (g) Voltmeter 0-500 volts square mounted, 96mm square with selector switch electronic type - 01 No. (h) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job. (j) Indicator lamp LED type in RBY colour set of 3 - 01 set. 1 Set
516 516 (g) INSULATION:- Hot insulation to all equipment complete with 50 mm thick 100/Cum insulation & aluminium cladding of 24 gauge, for
517 517 (i) Steam piping 1 Set
518 518 (ii) Steam Headers 1 Set
519 519 (iii) Flue gas Ducting within Boiler house 1 Set
520 520 (h) MISCELLANEOUS
521 521 (i) Structural steel work for making platform pipe supports, hanger and blow down chamber including cutting,bending,welding of structural steel with I Beams, TEE beams,Channels, Angles & Painting with one coat primers and two coats of approved paint 1 Set
522 522 (ii) Structural steel work for soft water tank 1 Set
523 523 (iii) Structural steel work for Day Oil tank 1 Set
524 524 Note : Cost of IBR approval along with initial steam drawings, obtaining clearance and Hydro test , initial Approval and final steam test shall be deemed to include in the rate quoted.
525 525 Supply, Installation, Testing & Commissioning of steam, cold water, drainage pipeline including electric cabling, connection, electric panels, starters etc., all Inclusive to make the plant and machinery functional as per manufacture instructionsand design / drawings and standard engineering practice 1 Job
526 526 Cable Connection \nPVC insulated unsheathed copper conductor cable of size 25 sqmm, single core, 1100 volts fixed on walls/poles or laid in ducts/trenches or passed through pipes complete all as specified. 80 RM
527 527 All as per Srl Item No 19.05 but of size 22.0500 sqm single core. 150 RM
528 528 Gay supported Main Chimney complete with base, cylindrical top sections, base plate, cowl on top of 525 mm dia 30 m height 1 Each
529 529 Polishing softener of 1600 liter per hour with brine tank, frontal piping and control valves 1 Each
530 530 Steam header High Pressure header (IBR) comprising of following:-(i) 250 mm dia & 3000 mm long seamless tube (ii) 2 Nos lintel flange nozzles. (iii) 1 No outlet flange (iv) Drain flange nozzles (v) Flanged ends and Blind flanged. (vi) Set of Bellow seal valves on steam line 1 Set
531 531 Steam Pressure reducing station complete with valves gauges saftey valve, bypass valves & flanking valves IBR, as under:- PR Station PRS-2 for steam press @ 4bar for 300 kg 1 Each
532 532 SCH 'A' PART-XX : NURSE CALL AND PUBLIC ADDRESS SYSTEM FOR FIRE FIGHTING (System should confirm to UL 1069 (Under Writers Laboratories), CSA (Canadian Standards Association), NEC(National Electrical Code)\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
533 533 LCD Consoles:- LCD console shall comprise of followings:- (a)  The console shall be a small self-contained unit, which shall not occupy more than 87 square inches of desk space. The console shall include an easy-to-read 4-line / 80-character backlit LCD display. \n(b) The console shall provide function selector buttons and a telephone-style 12-button dial pad. Selector buttons may be used to access user-configured 24-function menu. (c) The console may display up to three incoming calls each with an individual elapsed timer indicating how long the call has been pending. Ability to scroll to see additional pending calls. (d) While idle, the console shall display the time of day. Time may be displayed in 12 or 24-hour format. Time display shall be consistent system wide. (e) Console shall include capabilities for both open voice (speaker / microphone) and telephone style handset. Audio direction (talk / listen) for speaker / microphone and handset may be accomplished via automatic voice switching (VOX) or manually via a Push-to-Talk button . 14 Each
534 534 (f) The highest priority (or longest pending) call may be answered automatically by lifting the handset or by pressing the Push-to-Talk button. Calls may be answered out of sequence using line selector buttons or by dialing the desired room number. (g) Console shall provide independent volume controls for day/night call-in tones. A Mute button shall be provided to temporarily suppress tones for pending calls. (h) The console may be desk or wall mounted. (i) The console shall employ a modular quick-disconnect connector. It shall be possible to remove and / or replace the console without removing power from the system.
535 535 CORRIDOR LAMP/ROOM CONTROLLERS/ZONE LAMPS Corridor Lamps (2-lamp style) shall be provided as indicated on the plans and drawings. (a) Corridor Lamps shall utilize LED's for high visibility, long life and low maintenance. CorridorLamps utilizing incandescent lamps shall not be acceptable. (b) The corridor lamp shall make use of multiple colors and programmable flash rates and patterns to indicate pending calls, service requirements and staff presence. (c). Corridor Lamps shall serve as the hub for all room wiring. All field wire connections shall be accomplished using modular connectors. (d) Any Corridor Lamp shall be able to function as a Zone Lamp that shall visually annunciate calls from assigned room/stations without the use of a Zone Lampcontroller such as a duty station. (e) The Corridor Lamp shall be equipped with a heart-beat LED (visible to service personnel) to indicate that the unit is functioning properly. (f) The Corridor Lamp shall accommodate a paper label to indicate the room number. 110 Each
536 536 ROOM STATION : Room stations non audio shall be equipped with followings as shown on drawings:- (i) DIN style receptacle(s) for call cord.\n(ii) Reset Button to cancel pending calls. Reset button shall be able to cancel calls from other stations in the room if desired (iii) Red LED(s) to indicate call placement from one or both of the call points.(iv) Removing a call cord shall place a Cord Out call. (iv) Removing a call cord shall place a Cord Out call. (v) Cord Out calls may be cancelled locally using the cancel Button. No Dummy Plugs shall be required. (vi) Room stations shall employ modular connectors. It shall be possible to service Room Stations without removing power from the system. 364 Each
537 537 Pull Cord Station for WC:- Pull cord sub-stations shall be water resistant with a PVC (poly-vinyl chloride) pull-cord, membrance resetbutton and coveredcall assurance LED. Unit may utilize remote cancel button for ease of nurse cancel when pull cord station I mounted in inaccessiblelocation (e.g. ceiling). 137 Each
538 538 CALL CORD:-Standard Call Cords shall be pendant type with a single easy to activate call button, DIN style, male plug and sheet clip. Cable shall be minimum of10'/300cm. One standard call cord shall be provided for each bed with an additional 10% provided as spares. 364 Each
539 539 Public Address System for Fire Fighting\nSupplying, installing, testing and commissioning of Public Address (PA) System for the entire hospital consisting of the following :-\nMake : BOSCH/AHUJA or equivalent of make as approved by Accepting Officer.
540 540 (a) Mounting rack for amplifiers and monitors (shall be like table top ) 1 Set
541 541 (b) Monitoring Unit with monitoring LS, Volume control, Monitoring Amplifier selector switch with Digital display, Normal/ Stand by Amplifier selector switch. 1 Set
542 542 (c) Priority modules having Announcement from console-I level Digital Voice recorder - II level, Music - Least level Music Programme selector module.With Pre and Line Amps. 1 Set
543 543 (d) Amplifier with 480W RMS output 4 Set
544 544 (e) Single CD Player, with dual cassette deck, AM/FM Tuner. 1 Set
545 545 (f) Digital Announcing Console with Page Microphone for Selecting 12 zones expandable upto 15 zones having Keypad for zone selection, LED display 1 Set
546 546 (g) 6W Ceiling Ring Speakers complete with built in LMT, grill, mounting clamps etc 455 Set
547 547 (h) 6W Wall mounted box type speakers with built-in LMT, grill, mounting clamps etc. for Basement 16 Set
548 548 (j) 6Watt cone type speakers for outdoor application with built in LMT. 20 Set
549 549 (k) Car Calling console with Microphone Desk mounted. 2 Set
550 550 FRLS PVC insulated flexible copper conductor, single core 3 x 1.5 sqmm cable, drawing in existing surface/recessed PVC/steel conduit complete all as specified. 50 RM
551 551 All as per Srl item 20.07 above but of size 3 x 2.5 sqmm. 50 RM
552 552 Copper flexible cable 2 core 24/0.20mm with terminations, and connectors complete in all respect. 13424 RM
553 553 Supply, fixing, laying testing and commissioning of PVC insulated copper conductor CAT 6 cable suitable for nurse call sysytem. Make : Rauland Borg 6700 RM
554 554 Supply,Fixing, testing and commissioning of dome less ontroller-100(DCV100) Make: Rauland Borg. 16 Each
555 555 Supply,Fixing, testing and commissioning of dome less ontroller-116(DCV116) Make: Rauland Borg. 21 Each
556 556 Supply,Fixing, testing and commissioning of network interface Module (R4KNIM), make: Rauland Borg. 5 Each
557 557 Supply,Fixing, testing and commissioning of Terminal Board (R4KTMB), make: Rauland Borg. 9 Each
558 558 Supply,Fixing, testing and commissioning of power Supply (R4KK400) Make: Rauland Borg. 9 Each
559 559 SCH 'A' PART-XXI : MEDICAL GAS PIPE LINE SYSTEM\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
560 560 Supplying, installing, testing and commissioning of medical gases supply control station for the entire hospital consisting and providing the following all as specified.
561 561 (A) Oxygen System
562 562 (a) Oxygen Gas Oultet point 553 Set
563 563 (b) Oxygen Flow meters with humdiifer bottle 524 Set
564 564 (B) NITROS OXIDE SYSTEM
565 565 (a) Gas Outlets Point for N2O 21 Each
566 566 (C) COMPRESSED AIR SYSTEM
567 567 (a) Gas Oultet point for Air 4 Bar 147 Each
568 568 (b) Gas Outlet point for Air 7 Bar 14 Each
569 569 (D) Vaccum system
570 570 (a) Gas Outlet point for Vaccum 526 Each
571 571 (E) VACCUM ACCESSORIES
572 572 (a) ward vaccum unit with one regulator one collection bottle complete all as specified. 497 Each
573 573 (b) Theatre vaccum unit mounted on the trolley with 1 vaccum regulator & 2 collection bottles ( 2 units for each major and minor OT) 14 Each
574 574 (F) ALARM SYSTEM
575 575 (a) For 5 services ( o2, N2O, M. Air(4) S. Air ( 7) Vac) 7 Each
576 576 (b) For 4 services ( O2, N2O, C.Air(4), Vac) 3 Each
577 577 (c) For 3 services ( o2, C. air ( 4) Vac) 13 Each
578 578 (d) For 2 services ( O2, Vac) 24 Each
579 579 Central Main Alarm in the Plant Room 1 Each
580 580 Slave Main Alarm with computerized cabling 1 Each
581 581 Horizontal Bed Head Panel Length -1.8 mtr, made of extruded aluminium having twin horizontal rail to mount accessoires & having provision for gas outlets (as per the outlet list) and separate segregated channel for high voltage 6 no. Electrical Sockets and a channel for low voltage-Nurse Call / Monitor cabling/ telephone cable etc. and other items as per detailed specifications. 33 Each
582 582 Vertical Bed Head Panel - (for Triagex 3 beds & 12 Beded ICU) V. Length - 2.5 mtr made , made of extruded aluminium having twin vertical rail to mount accessories & having provision for gas outlets (as per the outlet list) and separate segregated channel for high voltage 12 no. Electrical Sockets and a channel for low voltage-Nurse Call / Monitor cabling/ telephone cabling etc. and other items as per detailed specifications. 4 Each
583 583 Matching Probes for Outlets
584 584 (a) O2 553 Each
585 585 (b) Nitrous Oxide 22 Each
586 586 (c) M. Air - 4 bar 147 Each
587 587 (d) S. Air - 7 bar 14 Each
588 588 (e) Vacuum 526 Each
589 589 Copper Piping (with third party inspection certificate) of following sizes:-
590 590 (a) 108mm OD x 2.0 mm thick 55 RM
591 591 (b) 76.1mm OD x 1.5 mm thick 118 RM
592 592 (c) 42mm OD x 1.2 mm thick 208 RM
593 593 (d) 28mm OD x 0.9 mm thick 380 RM
594 594 (e) 22mm OD x 0.9 mm thick 1645 RM
595 595 (f) 15mm OD x 0.9 mm thick 3684 RM
596 596 (g) 12mm OD x 0.7 mm thick 1277 RM
597 597 Valave Box
598 598 (a) 2 Gas 5 Each
599 599 (b) 3 Gas 6 Each
600 600 (c) 4 Gas 4 Each
601 601 (d) 5 Gas 7 Each
602 602 Rigid Retractable ceiling mount type pendant for OT provision for - 2xO2, 1x N2O, 1x Air (4), 1x Air (7) and 2 x Vac, 1x AGSS outlets, 6 x electrical sockets 7 Each
603 603 Multi Movement and Multiarm (800+1000mm arm with 330º movement) ceiling mount type pendant for major OT, and provision for the lifting of the Anaesthesia machine and head with provision for 3xO2, 1x N2O, 1x Air (4), 1x Air (7) and 3 x Vac, 10 x electrical sockets, monitor jacks, grounds and one tray and another tray (bottom) with drawer. 5 Each
604 604 H.P. Antistatic Rubber tube (100 mtrs, for O2- white, 50mtr N2O-Blue, 150 mtr Air - Black and 200 mtr for Vacuum - Yellow. 500 RM
605 605 Electrical Control Panel (input panel ) for both Vacuum Pumps and Compressors for the Manifold Room and cabling for all alarms 1 Set
606 606 Liquid Tank Capacity 5000 Ltr with foundation work & copper piping for liquid tank & other accessories 1 Set
607 607 PART- XXII : LIST OF WORKS AND PRICES FOR LIGHTNING PROTECTION SYSTEM\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
608 608 Supply, installation, testing and commissioning of Advance Lightning Protection complete with the lightning Air Terminal- Configured as a Spheroid consisting and comprising of separate electrically isolated 4 panels surrounding an Earthed Central Finial. The Insulation material used to electrically isolate the panels shall comprise of a base polymer which provides high Ozone & UV resistance with di-electric strenght of 24-38 KV/mm tested as per NFC 17-102 & IEC 60-1:1989. The ESE terminal shall not contain any electronic circuits or any moving parts for its operation. The ESE terminal shall be tested & certified by CPRI (Central Power Research Institute, Govt of India) for the impluse current of 45 KA (8/20 micro sec) with 5 positive & 5 negative impulse. The ESE terminal shall be approved by DGMS (Director General of a protection radius of 79m with the Level 1 (High) protection & to be mounted as per design and shall be provided with following accessories/fitments.\nMake : LPI - Australia (Allied Power Solutions) / Foudretech-France (Global Power System)\n\n
609 609 (a) Model: Stormaster 60 - 79m (Protection radius 79m with Level 1 / High protection) 2 Each
610 610 (b) Upper Termination Kit 2 Each
611 611 (c) Lower Termination Kit 2 Each
612 612 (d) FRP Mast (2m) 2 Each
613 613 (e) Inline coupling 2 Each
614 614 (f) Guy wire kit 2 Each
615 615 (g) GI Mast (3m) 2 Each
616 616 Supply only advance maintenance free chemical gel single pole earthing system of 1 number of "J K CHEMRODE" - 10 feet length, 50mm dia, 1.5mm thick electrolytic grade Copper tube duly filled with conducting natural minerals with the permanent sealings at both ends with the lead terminal at the top along with 1 set of Part (5Kgs) + 2 set (5 Kgs) LPI GRIP (Ground Resistance improvement Powder) - Part 1 (mixture of calcium carbonate & sodium sulphate) + Part 2 (Copper sulphate) along with heavy duty polyplastic Chember. \nMake : LPI(Australia) / Foudretech (France) 4 Each
617 617 Supply and fixing of specially designed lightning current High Voltage Sheilded Cable (HVSC) 7 layer cable consisting of Inner Core, Concentric Conductor (copper), Inner binding tape, Insulation material, Metallic screen, Outer binding tape, Outer sheath with the nominal cross sectional area of 50 sq.mm & overall diameter of 37mm with the insulation resistance of 1830 M Ohm-km, tested for 200 KV as per termination & connected to the earth pit with the lower terminal kit to safely route the lightning current.\nMake : LPI(Australia) / Foudretech (France) 120 RM
618 618 Supply only Test Link joint Kit in IP55 weather proof enclosure of suitable dimension. 2 Each
619 619 PART- XXIII : LIST OF WORKS AND PRICES FOR UPS AND DESK COMPUTER\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
620 620 Supplying, installation, testing and commissioning of SU20K3/3X 20KVA SmartOnline 3-Phase Intelligent, True Online UPS System has been redesigned to save valuable space and simplify runtime scalability. Power and battery components are combined into a single, small-footprint module (the smallest in its class). A robust internal battery runtime capability can be easily extended by installing additional modular internal battery packs through the convenient front panel access door.\nSU20K3/3X SmartOnline 3-Phase Intelligent, True On-Line UPS System provides mission-critical equipment with the highest level of power protection available. Large capacity 20,000 VA/16,000 watt power module continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. SmartOnline models provide some of the highest levels of isolation from THD (total harmonic distortion)—<3%—allowing equipment to perform at its peak. A 3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands.\n 13 Each
621 621 Extremely efficient operation (up to 97% efficient in Economy Mode) saves money by lowering electricity consumption. Hardwire input and output connections support a variety of permanent or PDU style power connections. SU20K3/3X features user-selectable 3-phase 220/380 or 230/400 or 240/415V AC input and output. Wide input voltage correction range (156-280V AC/270-485V AC)\n Frequency is 50 or 60 Hz (auto-selectable). SU20K3/3 includes internal power and battery components in a single small-footprint tower module. \nBattery support can be extended with additional internal battery modules and optional modular external battery frames. A manual bypass switch as well as an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power when the power module requires maintenance. Three built-in communication ports (RS-232, contact closure and AS-400) work with included PowerAlert Software to simultaneously provide shutdown commands and reporting on multiple servers without the need for costly accessories\n
622 622 An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a variety of UPS operational modes and conditions
623 623 Supplying, installation, testing and commissioning of SU30K33INT 30KVA SmartOnline 3-Phase Intelligent, True Online UPS System has been redesigned to save valuable space and simplify runtime scalability. Power and battery components are combined into a single, small-footprint module (the smallest in its class). A robust internal battery runtime capability can be easily extended by installing additional modular internal battery packs through the convenient front panel access door.\nSU30K33INT SmartOnline 3-Phase Intelligent, True On-Line UPS System provides mission-critical equipment with the highest level of power protection available. Large capacity 30,000 VA/24,000 watt power module continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. SmartOnline models provide some of the highest levels of isolation from THD (total harmonic distortion)—<3%—allowing equipment to perform at its peak. A 3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands. 9 Each
624 624 Extremely efficient operation (up to 97% efficient in Economy Mode) saves money by lowering electricity consumption. Hardwire input and output connections support a variety of permanent or PDU style power connections. SU30K33INT features user-selectable 3-phase 220/380 or 230/400 or 240/415V AC input and output. Wide input voltage correction range (156-280V AC/270-485V AC). Frequency is 50 or 60 Hz (auto-selectable). SU20K3/3 includes internal power and battery components in a single small-footprint tower module \nBattery support can be extended with additional internal battery modules and optional modular external battery frames. A manual bypass switch as well as an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power when the power module requires maintenance. Three built-in communication ports (RS-232, contact closure and AS-400) work with included PowerAlert Software to simultaneously provide shutdown commands and reporting on multiple servers without the need for costly accessories.
625 625 An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a variety of UPS operational modes and conditions.
626 626 Supplying, installing, testing and commissioning of desk computer completewith processor,UPS, Monitor & Printer etc. preloaded with latest window operating system as under:- \n\n
627 627 (a) Desk Computer\n Dual Core 2.6 GHz\n Intel G31 Chip set mother Board\n 1 GB DDR-II RAM\n 320 GB Hard Disk\n DVD RW\n Key Board, Optical Mouse\n 18.5" LCD with internal speakers\n 12 Each
628 628 (b) UPS-600 VA with internal battery\n 12 Each
629 629 (c) Printer -Laser Jet Printer\n 12 Each
630 630 PART- XXIV: LIST OF WORKS AND PRICES FOR FIRE FIGHTING WORK\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
631 631 A: FIRE HYDRANT SYSTEM:\nSupply, Erection and Commissioning of Diesel engine driven main fire hydrant pump horizontal mounted centrifugal pump located at ground floor level, capable of delivering 2280 liters of water / minute at an head of 70m and giving a jet pressure not less than 3,5 kg / sq.cm at the top most hydrant, suitable for automatic opeation, mounted on a common base frame inlcuding pressure gauge, pressure switch suitable diesel tank of required litres storage capacity and coupled to diesel engine of adequate HP. It shall be fitted on a common base frame wih antivibrating pads including all ohter auxillaries such as batteries, exhaust pipe necessary valves,. "Y" strainer for coolling water inlcuding cooling system and civil work etc. complete.\n 1 Each
632 632 Supply, Erection, Testing and Commissioning of electrical motor driven end suction back pullout centifugal/fire hydrant pump with bronze impellors, cast iron body, capable of delivering (2280 litres of water per minute at an head of 70m and giving a jet pressure not less than 3.5kg / sq.cm at the top most hydrant, and coupled to adequate HP electrical motor mounted on a common base frame with pressure gauge pressure switch etc as required including inter connecting wires, cables and civil work etc complete 3 Each
633 633 Supply, Erection, Testing and commissioning of jockey pump\n located at ground floorlevel capable of delivering 180 litres of\n water / minute at than 3.5 kg / sqem at the top most hydrant, \ncomplete with adequate HP. pressure not less Electircal driven\n monoblock type pump wtih squirrel cage motor with bronze\n impellors, pressure gauge, pressure switch and civil work etc.\n complete. 1 Each
634 634 Supply, Erection and commissioning of 'C' calss MS fire hydrant /\n wet iser system. The pipes shall be fitted on walls or suspended \n(as per IS 1239) for from ceiling with necessary specials, such as \nbends. Reducers, orifice plates, if any tees, flanges, CI Tapers\n etc. The rates shall include the cost of consumables for cutting\n and welding, painting with a coat of red oxide and two coats of\n post office red colour\n
635 635 (a) 300 mm dia\n\n 10 RM
636 636 (b) 200 mm dia\n\n\n 10 RM
637 637 (c) 1 50 mm dia 178 RM
638 638 (d) 1 00 mm dia 100 RM
639 639 (e) 80 mm dia 50 RM
640 640 Supply, Erection and commissioning of 'C' class MS pipes (as per IS 1239) for fire hydrant / wet riser system. The pipes shall be finex for underground with necessary specials, such as bends. Reducers, orifice plates, if any tees, flanges, CI Tapers etc. The rates shall include the cost of consumables for cutting and welding, with anticorrosive bitumastic paint and wrappping with polythene sheet based pipe kote of 4mm thickness for Under ground piping \n\n
641 641 (a) 150mm dia\n\n\n 1254.4 RM
642 642 (b) 100mm dia\n\n\n 50 RM
643 643 (c) 80 mm dia 20 RM
644 644 Supply, erection, testing and commissioning of 'FIRE HOSE \nCABINET" fhc) OF SIZE (APPROX) 750 mmX 600 mmX 450 \nmm with hinged door shutter and frame and fabricated out of \n14 SWG sheet steel fitted with 4mm thick toughned glass in the \nfront including finishing with powder coat/spray painting complete 21 Each
645 645 Supply, erection, testing and commissioning of 'FIRE HOSE CABINET" fhc) OF SIZE (APPROX) 1200 mm X 600 mm X 2100 mm with hinged door shutter and frame and fabricated out of 14 SWG sheet steel fitted with 4mm thick toughned glass in the front including finishing with powder coat/spray painting complete.\n\n\n\n\n\n\n\n\n 81 Each
646 646 (a) 63mm dia instantaneous pattern oblique single headed yard hydrant valve 21 Each
647 647 (b) 63mm dia instantaneous pattern oblique single headed internal \nhydrant valve. 81 Each
648 648 (c) 15 mtr 63mm dia controlled CP Hose with gun metal female \ninstantaneous coupling as required. 42 Each
649 649 (d) 15 mtr 63mm dia controlled RRL Hose with gun metal female \ninstantaneous coupling as required. 162 Each
650 650 (e) One branch pipe and nozzle with valve 102 Each
651 651 (f) 19mm dia bore reinforced rubber of length 36.5m fitted with \n6.35mm dia nozzle with a ball valve. The hose reel shall be \nrecessed swinging type with rell drum hose provided with \nnecessary couplings. 81 Each
652 652 (g) One no 25mm dia ball valve 81 Each
653 653 (h) Drawal out connection of gun metal with adequate pipe of MS 1 Each
654 654 (j) Cabinet of MS for the drawl out connection 1 Each
655 655 Supplying, erection, testing and commissioning of air release valve fitted on the top most point of the wet riser with riser with drain connection. The rate shall be inclusive of accessoires. 25mm dia ball valve and Air release valve.\n 20 Each
656 656 Supply, erection, testing and commissioning of fire brigade inlet connection of the system confiming to IS 5290, of\n\n
657 657 (a) 4 WAY 2 Each
658 658 (b) 2 WAY 8 Each
659 659 Fire Brigade Inlet Connection Cabinet of appropriate size as required of ms construction with 4 mm thick glass on front 10 Each
660 660 Supply, erection, testing and commissioning of sluice valves class PN-1, conforming to IS-14846, hand wheel operated, stainless steel stem with gunmetal parts, flanges drilled to IS-1538, non rising stem with body test pressure 15 Kg/cm² and seat test pressure 10 Kg/Cm2 complete, for following bore of pipes :\n\n
661 661 (a) 300mm dia.\n\n 2 Each
662 662 (b) 200 mm dia\n\n\n 2 Each
663 663 (c) 150mm dia 10 Each
664 664 (d) 100mm dia 9 Each
665 665 (e) 80mm dia 1 Each
666 666 Supply, erection, testing and commissioning of slim seal type Non Return valves with Cl body & cast steel disc and tested to 10kg/ sqcm including a set of suitable Gl washers, rubber gaskets etc complete), for\n\n\n\n\n\n
667 667 (a) 150mm dia 4 Each
668 668 (b) 100mm dia 2 Each
669 669 (c) 80 mm dia. 1 Each
670 670 Supply, erection testing & commissioning of pot strainer / Y strainer including rubber insertion, bolts, nuts, Gl flanges, etc complete for following bore of pipes:\n\n\n\n
671 671 (a) 150mm dia 3 Each
672 672 (b) 100mm dia 1 Each
673 673 Supply, erection testing and commissioniong of Air cushion tank of 200mm dia & 1000mm height with drain connection. The rate shall be inlcusive of accessoires. 25mm dia Air release valve and ball valve 18 Each
674 674 LT panel board, cubical type, indoor type, floor mounted, factory made fabricated with 2mm thick CRCA sheet and 40x40x6mm angle iron frame of suitable size to accommodate starter and controls of motor required for water supply pump, front openable with king arrangement, spray painted internally and externally and shall be consisting and comprising of following fitments/accessories:\n(a) Star delta starter fully automatic of suitable capacity for pumping set-02 Nos,60 HP.\n(b) Single phase preventer suitable for electric motor of pumping set 03 Nos. \n(c) Digital Amp meter of suitable capacity with cut outs and switches square mouthed 144mm square 03 Nos.\n(d) MCB 3 pole, 415 Volts, 50 cycle, 10 KA. 40 Amp 01 Nos.\n(e) MCCB 4 pole, 415 Volts, 50 cycle/second, 25KA 100Amp 2 Nos. \n(f) MCCB 250 Amp, 4 pole 415 Volts, 50cycle/second 35KA, 01 Nos (incoming)\n(g) Bus bar of copper 300Amp cap 03 Nos and 150 Amp cap 01 Nos. (h) Digital volt meter 0 to 500 Volts, square mouthed 144 mm square 01 Nos \n(j) Indicating lamp on all three phases with selector switches 01 set of three. (k) Wiring with PVC insulated cable with copper counductor of suitable size including copper lugs tapping size in floor/walls as required for connection of panel board.\n(1) Push button type DOL starter of suitable size for electric motor 5HP 1No.\n 1 Each
675 675 Autostart panel for the Diesel engine complete auto / manual switch, indication lamps protective fuses with battery charges, suitable of working on 230 C, AC single phase, enclosure being vermin & dust proof suitable for auto-operation of diesel engine main fire hydrant pump centrifugal type capable to deliver 2850 Lpm at 70m head.\n\n\n\n 1 Each
676 676 MS brackets fabricated out of angle / flats of required size with \n6mm / 8mm GI U clamps with Gl washers and nuts etc for \nsupporting GI / MS fire hydrant pipes running in fire dud pipes \n& ground floor ceiling level. The work shall also include making\n hole grouting the same in RCC slabs / masonry walls concrete\n and making good the same cement 1186 Each
677 677 12mm/15mm dia full threaded GI rods with necessary washers and nuts etc. for supporting GI MS fire hydrant pipes running in fire duct / terrace ground / basement floor ceiling level\n\n\n\n 1592 Each
678 678 12mm/15mm dia anchor fasteners for suspending Gl rods / brackets etc 1592 Each
679 679 1100V Grade Cables, PVC insulated armoured, copper/aluminium conductor, 1100V grade power cables, laid in trenches/ducts or passed through pipes etc, of following sizes :\n
680 680 (a) 4 core x 16 sq. mm Aluminium\n\n\n\n\n\n 50 RM
681 681 (b) 4 core x 10 sqmm Aluminium\n\n\n\n\n\n 20 RM
682 682 (c) 12 core x 1.5sq. mm copper 60 RM
683 683 (d) 2 core x 1.5 sqmm Armoured copper 400 RM
684 684 Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, with following sizes of conductor:\n\n\n
685 685 (a) 25 x 3 mm Gl strip\n 120 Each
686 686 (b) 50 x 6mm Gl Strip. 120 Each
687 687 Gunmental / Cl foot valve spring operated type, tested to 2 kg / sq.cm, of following sizes :\n\n\n\n\n
688 688 (a) 200 mm 3 Each
689 689 (b) 100 mm 1 Each
690 690 Pressure Switch for Auto operation of fire pumps of approved make with fittings.\n\n 5 Each
691 691 Pressure gauage of approved make 0-10 kgs, 4" dial with fittings complete 66 Each
692 692 Earthing complete with galvanised steel earth plate 600mmx600mmx6mm thick burried directly in ground (earth plate not less than electrode 2.25m deep below normal ground level)with top edge of the plate not less than 1.5m below normal ground level connected to and including Gl earth strip 32x6mm by means of steel bolts, nuts, check nuts and washers, PCC 1:2:4 type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia MS fabricated handle, light grade Gl watering pipe 20 mm bore with funnel, wire mesh, and connecting to test point, salt, charcoal, etc. including excavation and earth work in any type of soil, removal of surplus spoil to a distance not exc. 50m complete all as shown in electrical plate No. 3 of MES Schedule 2009 (Pt-I) and connected to main control board all as specified including testing on completion.\n 10 Each
693 693 100 mm dia exhaust pipe from engine to ground floor level with flexible joint, silencer & fittings etc and insulating the exhaust pipe with 50 mm thick rock wool insulation and cladded with 22 gauge Aluminium sheet in an approved manner.\n\n 5 RM
694 694 B: SPRINKLER SYSTEM\nSupply, erection, jointing, testing & commissioning of 'C' Class MS pipes (as per IS 1239). The pipes being suspended from beams, RCC roof slabs with necessary specials such as tees, bends, flanges redcuers etc., complete.Rate quoted shall also include for painting of pipe with one coat of primer & two coats of synthetic ename paint of approved colour & make, of size :\n\n\n
695 695 (a) 150 mm dia\n\n\n\n\n\n\n\n\n\n\n\n\n 299.45 RM
696 696 (b) 100 mm dia\n\n\n\n\n\n\n\n\n\n\n\n\n 143.95 RM
697 697 (c) 80 mm dia 372.57 RM
698 698 (d) 65 mm dia\n 1684.92 RM
699 699 (e) 50 mm dia 1552.45 RM
700 700 (f) 40 mm dia\n 1855.62 RM
701 701 (g) 32 mm dia\n 3191.62 RM
702 702 (h) 25 mm dia\n 9734.81 RM
703 703 Supply, erection, testing and commissioning of slim seal type butterfly valves with Shperoidal graphite iron disc (SG iron), with nitrile rubber seal and tested to 10kg/sq.cm including a set of suitable GI flange, as per BS 10 Table - 1, bolts, nuts Gl washer, neoperene rubber gaskets etc., complete. (intervalve make), of\nsize\n\n\n\n
704 704 (a) 150 mm dia 65 Each
705 705 (b) 200 mm dia 5 Each
706 706 Supply.erection, testing and commissioning of 15mm dia nominal bore quartzoid bulb type sprinklers with temperature rating of 68 deg C conventional type the shall also include suspending arrangement with ceiling, wall arrangement with ceiling, wall beam clamps, fasteners ceiling rosette (incase of false ceiling) etc.,complete, of \n\n\n\n\n\n\n\n\n
707 707 (a) Concealed type 6009 Each
708 708 (b) Upright type\n 4751 Each
709 709 (c) Sidewall type 50 Each
710 710 (d) Pendant type\n 344 Each
711 711 Supply, Erection, testing & comissioning of SS Flexible Pipe of suitable dia and length required for connecting. 4760 Each
712 712 Supply erection, testing and commissioning of hydraulically operated sprinkler alarm unit connected to sprinkler system (150 mm dia) floor comprising of alarm valve, water motor with alarm gong, pressure gauge, drain cock, check valve and pressure reducing valve. The quoted rate shall also including the necessary accessories, the location of the unit shall be as per the detailed drawing. \n 5 Each
713 713 Providing and fixing of 12mm / 15mm dia anchor fasteners for suspending Gl rods / brackets etc 1500 Each
714 714 Flow switch installed on the sprinkler main distribution line connected to the main sprinkler annunciation panel located in the ground floor suitable for 100mm bore pipe. 61 Each
715 715 Cast iron double flanged horrizontal type with gun metal seat non-return valve conforming to class 1 of IS-5312 incl nuts, bolts, gasket etc complete for 150mm dia pipe.\n 2 Each
716 716 FIRE BUCKETS & STAND :\n\n\n\n\n\n\n\n
717 717 (a) Fire Bucket 9 Itrs with round bottom & Stand (Steel Stand with provision of 2 bucket fixing)\n\n\n\n\n\n\n 10 Each
718 718 (b) Fire Bucket 9 Its. With round bottom & stand (Steel stand with provision of 4 buckets fixing) 5 Each
719 719 (c) Fire beater\n 5 Each
720 720 (d) Ceiling hook\n 5 Each
721 721 (e) Fire gong 5 Each
722 722 HFC 227 EA/HCFC Blend A Modular 10 kg capacity\n\n\n 50 Each
723 723 Aerosole 50 Each
724 724 FIRE DOOR \n\n\n\n\n\n\n
725 725 (a) One hr rating\n\n\n\n\n\n 210 SQM
726 726 (b) Two hr rating\n\n\n\n\n\n 140 SQM
727 727 D: FIRE ALARM SYSTEM\nSupply,installation, testing and commissioning of following:\n
728 728 (a) Intelligent addressable Micro processor based fire alarm control panel with02 loop capacity Networkable and expandable, with dual stage alarm facilities like hooter, fire / fault indicators, audio-visual signals, auto learn features, flexibility in shared zone mode or stand alone system, PC networking connectivity as RS232/RS485, communication facility, suitable for connect other systems. shall be interfaced to Graphic Software, having inbuilt power supply.\n 1 Each
729 729 (b) Graphic Display Software with PC for the same shall be atleast of PIV capacity and of specified make only 1 Each
730 730 Supply, installation, testing and commissioning of following Detectors & devices \n\n
731 731 (a) Intelligent addressable Optical Based smoke and heat detector with facility of numbering in the base( UL Listed)\n 2021 Each
732 732 Intelligent addressable Manual Pull Station and shall be resettable type.( UL Listed) 90 Each
733 733 Duct detector( UL Listed)\n 120 Each
734 734 Fault isolation module similar.\n\n\n\n\n\n\n\n\n\n\n 220 Each
735 735 Intelligent addressable Control Module with following application. 195 Each
736 736 Intelligent addressable input/monitor Module\n 50 Each
737 737 Response Indicator\n 1920 Each
738 738 ELECTRONIC HOOTER 85 Each
739 739 Power Supply unit with 12 V 7 Ah battery and with charger circuit for sounders. 12 Each
740 740 2 Core X 1.5 Sq.mm multistrand armoured copper cable with all accessories and 2 complete in all aspects, the cable shall be having cable pointers at every 1 Meter. These cables shall be used for the wiring of detectors and devices.\n 19050 RM
741 741 Stove enamelled back steel conduit having wall thickness not less than 1.6mm, concealed type, ind of all fittings such as elbows, tees, bends, reducers etc. as required, of 25mm dia.\n 6500 RM
742 742 LED lit laser etched fire exit sign complete with maintenance free battery of atleat1.5 hr duration with chrome finish, of\n\n\n\n\n
743 743 (a) Single side 90 Each
744 744 (b) Double side 95 Each
745 745 Gas Detector sensitron 8 Each
746 746 Gas Detector Panel\n 2 Each
747 747 Supply,installation, testing and commissioning of following:\n\n
748 748 (a) Intelligent addressable Micro processor based fire alarm control panel with02 loop capacity Networkable and expandable, with dual stage alarm facilities like hooter, fire / fault indicators, audio-visual signals, auto learn features, flexibility in shared zone mode or stand alone system, PC networking connectivity as RS232/RS485, communication facility, suitable for connect other systems. shall be interfaced to Graphic Software, having inbuilt power supply.\n 11 Each
749 749 (b) Graphic Display Software with PC for the same shall be atleast of PIV capacity and of specified make only 1 Each
750 750 Material and labour for Brick work using sub class B bricks in cement mortar 1:6\n 38.64 Cum
751 751 Material and labour for PCC work 1:5:10 using 40mm graded agregates type E2 33.6 RM
752 752 Supply and fix bronze ball valve 50mm dia\n 122 Each
753 753 Supply and fix CI sight glass 50mm dia\n 61 Each
754 754 Supply , Errection, Testing and commissioning of slim seal type Non return valves with CI body and cast steel disc and tested to 10kg/sqcm including a set of suitable GI washers , rubber gasket etc complete of size 300 mm dia 1 Each
755 755 SCH 'A' PART- XXV : AIR CONDITIONING WORK\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
756 756 Water Chilling Unit\nSupplying, fixing, testing and commissioning hermatically sealed water cooled centrifugal chilling unit 750 TR capacity complete with open/hermatically sealed compressor with motor condenser, chiller, controls, microprocessor based control panel, VFD panel with ACB, digital voltmeter & ammeter for incoming supply & load interconnecting refrigerant piping, base frame, concerete base for mounting the unit complete all as per specified with following features.\nChilled water in : 12.2O C\nChilled water out : 6.6O C\nChiller F.F. : 0.0005\n750 TR (Actual) 3 Each
757 757 Pump Set\nSupplying, fixing, testing and commissioning horizontal split casing type water circulating pump sets complete with motor, base plate foundation etc. complete all as specified with following features/fixtures :-
758 758 (a) Chilled water pump, horizontal split casing type, 1800 USGPM at 40m. head (one standby). 3 Each
759 759 (b) Condenser water pumps, horizontal split casing type, 2850 USGPM at 27m. head (one standby). 3 Each
760 760 Secondary Chilled Water Pumps & Variable Speed Pumping SystemSupplying, fixing, testing and commissioning of secondary variable speed pumping system consisting of 2 Nos. secondary pumps, 1 No. dedicated microprocessor based pump controller with parallel pumping software duly downloaded, 2 Nos. adjustable frequency drives and multiple differential pressure sensor/ transmitters as necessary complete all as specified.\nSecondary chilled water pumps 3600USGPM at 30m. head. (one standby)\nNote:\nThe entire system alongwith secondary pumps must be sourced from single manufacturer only for unit responsibility. \nThe system shall be complete in all respects and suitable for rating described hereinafter and as per specification. 2 Each
761 761 Cooling Tower\nSupplying, fixing, testing and commissioning FRP induced draft type cooling tower complete with FRP basin, FRP body, fan, distribution pipes, overflow pipe, ladder including foundation etc. complete all as specified suitable for 750 TR. 3 Each
762 762 Airhandling Unit\nSupplying, fixing, testing and commissioning of horizontal double skin floor mounted type airhandling units complete with fan, fan motor, drive, cooling coil, prefilters, microvee filter & HEPA filters, heaters, humidifier, mixing box, strip heaters, HRW canvass connection, fresh air damper with louvers & bird screen, including foundation, vibration isolator pads complete all as specified, of :-\n
763 763 (a) 20,000 cfm, 8 row coil 1 Each
764 764 (b) 6,500 cfm, 8 row coil 1 Each
765 765 (c) 6,000 cfm, 8 row coil 1 RM
766 766 (d) 4,500 cfm, 8 row coil 2 RM
767 767 (e) 4,000 cfm, 8 row coil 1 RM
768 768 (f) 3,500 cfm, 8 row coil 2 RM
769 769 (g) 2,500 cfm, 8 row coil 1 RM
770 770 Airhandling Unit\nSupplying, fixing, testing and commissioning of horizontal double skin floor mounted type airhandling unit complete with fan, fan motor, drive cooling coil prefilters, microvee filter fresh air damper with louvers & bird screen, including foundation, vibration isolator pads complete all as specified, of :-\n
771 771 (a) 20,000 cfm, 6 row coil \n 5 Each
772 772 (b) 18,000 cfm, 6 row coil \n 4 Each
773 773 (c) 16,000 cfm, 6 row coil \n 1 Each
774 774 (d) 15,000 cfm, 6 row coil \n 3 Each
775 775 (e) 13,000 cfm, 6 row coil \n 2 Each
776 776 (f) 10,000 cfm, 6 row coil \n 12 Each
777 777 (g) 9,000 cfm, 6 row coil \n 9 Each
778 778 (h) 8,000 cfm, 6 row coil \n 4 Each
779 779 Unitary Airhandling Units\nSupplying, fixing, testing and commissioning of double skin ceiling mounted unitary type airhandling unit complete with fan, fan motor drive, cooling coil, filters, canvass connections, 2 way throttling valve with snap acting thermostat etc. complete all as specified, of :-
780 780 (a) 6,000 cfm, 6 row coil cooling 3 Each
781 781 (b) 5,000 cfm, 6 row coil cooling 2 Each
782 782 (c) 4,000 cfm, 4 row coil cooling 3 Each
783 783 (d) 3,000 cfm, 4 row coil cooling 4 Each
784 784 (e) 2,000 cfm, 4 row coil cooling 2 Each
785 785 Fan Coil Unit\nSupplying, fixing, testing and commissioning of horizontal hide away type fan coil units complete with fan, fan motor, cooling coil, filters, 2 way modulating valve with snap acting thermostat, ball valve with & without strainer at inlet & outlet, including control panel with cabling and earthing complete all as specified, of :- \n1.5 Tons (600 cfm) 2 Each
786 786 Air Purifier\nSupplying, fixing, testing and commissioning of Photo hydro ionization cell based on advanced oxidation technology with broad spectrum UV tube duly enclosed in hydrated catalytic matrix cell with the capability to produce friendly oxidizers like hydro peroxides, super oxide ions, ozonide ions & hydroxide ions, duly encased in poly tube to prevent glass or mercury leakage into the atmosphere, the cell will have built in fiber optic device as remote indication of this operation complete all as specified, of :-
787 787 (a) 20,000 cfm 1 Each
788 788 (b) 6,500 cfm 1 Each
789 789 (c) 6,000 cfm 1 Each
790 790 (d) 4,500 cfm 2 Each
791 791 (e) 4,000 cfm 1 Each
792 792 (f) 3,500 cfm 2 Each
793 793 (g) 2,500 cfm 1 Each
794 794 Packaged Type Airwasher\nSupplying, fixing, testing and commissioning packaged type airwashers of G.I. construction fabricated from 16 gauge G.I. sheet body, blower housing, centrifugal forward curved blower with motor, drive set, acetate paper cooling pad of 90% effeciency with stainless steel sump and body, pump, water connection, Aluminum filters, canvas connection, mounting base of angle iron/chennel etc. blower & motor mounted on common rail using cushy foot mounting and M.S. frame for supports etc. complete all as specified, of :-
795 795 (a) 40,000 cfm, 50 mm static pressure 1 Each
796 796 (b) 30,000 cfm, 50 mm static pressure 1 Each
797 797 Axial Flow Fan\nSupplying, fixing, testing and commissioning axial flow type exhaust fan complete with fan and motor, drive set, mounting frame, mounting accessories canvass connection, gravity damper of G.I. at fan outlet and electric control panel with cabling and earthing complete all as specified (Fan to be suspended from ceiling/ installed on wall with M.S. supports of and mounting accessories etc. and Fan should be interlocked with fire panel of 3,000 cfm, 20 mmwg S.P. each 14 Each
798 798 Propeller Type Fan\nSupplying, fixing, testing and commissioning of propeller type fan for fresh air supply and exhaust complete all as specified of 5000 cfm, 610 mm dia each 5 Each
799 799 Exhaust Scrubber\nSupplying, fixing, testing and commissioning of centrifugal exhaust scrubber of 18 gauge sheet steel duly powder coated inner & outer construction with fan and motor and drive (both fan and motor shall be mounted on a common frame using cushy foot mounting) with side suction and front discharge including vibration isolator, water tank with float valve, pump, distributor, nozzels, eleminator, piping & valve from tank to pump to distributor, and M.S. frame for supports etc. complete all as specified for 50,000 cfm, 65 mmwg static pressure 1 Each
800 800 Air Curtain\nSupplying, fixing, testing and commissioning of air curtains with decorative casing, fan, motor, remote etc. complete all as specified of 1500 mm length each 17 Each
801 801 Inline Fans\nSupplying and fixing inline fans of G.I. construction complete with centrifugal fan with motor, canvass connection at inlet and outlet complete with electric panel with MCB and relays, cabling and earthing complete all as specified, of :-
802 802 (a) 1600 cfm, 20 mm S.P. 2 Each
803 803 (b) 1000 cfm, 20 mm S.P. 6 Each
804 804 (c) 800 cfm, 20 mm S.P. 4 Each
805 805 Hot Water Boiler\nSupplying, fixing, testing and commissioning of Horizontal fire tube boiler operative. All accessories, including automatic burner pre heaters interconnecting H.P. flexible/ copper piping. Fuel pumping and blower with damper & auto electric sequance control/ operational panel complete all as specified of 10,00,000 Kcal / Hr (1176 Kw) Each 3 Each
806 806 Heat Exchanger\nSupplying, fixing, testing and commissioning of plate type heat exchanger of 600000 kcal capacity with stainless steel plates of variable surface with nitril rubber gasket, carbon steel frame, etc. complete in all respect and all as specified. 3 Each
807 807 Condenser Water Piping\nSupplying, fixing, testing and commissioning `C' class mild steel - black steel pipes in condensor water piping system with all necessary fittings incl bends, tees, reducers, flanges, supports etc. complete all as specified, for
808 808 (a) 600 mm dia 100 RM
809 809 (b) 300 mm dia 100 RM
810 810 Butterfly Valves class 1, PN-1.6 conforming to IS-13095 of 1991 complete with flanges, bolts, nuts, gasket etc. As per specifications, hydroulically tested to 20 kg/cm2 complete in all respects, suitable for
811 811 (a) 600 mm dia pipe 3 Each
812 812 (b) 300 mm dia pipe 18 Each
813 813 Cast iron balancing Valves confirmation to IS, class 1 incl nuts, bolts, gasket etfc complete suitable for 300 mm dia pipe 3 Each
814 814 Cast iron double flanged horrizontal type with gun metal seat Non Return Valves confirming to class 1 of IS-5312 incl nuts, bolts, gasket etc complete suitable for 300 mm dia pipe 3 Each
815 815 Pot Strainers incl rubber insertion, bolts, nuts, G.I. Flanges etc complete, suitable for following bore of pipes :-
816 816 (a) 600 mm dia 2 Each
817 817 (b) 300 mm dia 1 Each
818 818 Water flow switch (incl for chilled water supply) 4 Each
819 819 Pressure gauge (incl for chilled water supply) 30 Each
820 820 Thermometer (incl for chilled water supply) 30 Each
821 821 Flexible Pipe Connection of suitable length for 300 mm bore pipe complete 18 Each
822 822 Chilled Water Piping\nSupplying, fixing, testing and commissioning `C' class mild steel black steel pipes with all necessary fittings, supports & insulation etc. complete all as specified, of
823 823 (a) 350 mm dia 2500 RM
824 824 (b) 250 mm dia 150 RM
825 825 (c) 200 mm dia 110 RM
826 826 (d) 125 mm dia 90 RM
827 827 (e) 150 mm dia 250 RM
828 828 (f) 100 mm dia 300 RM
829 829 (g) 65 mm dia 250 RM
830 830 (h) 80 mm dia 350 RM
831 831 (j) 50 mm dia 1050 RM
832 832 (k) 40 mm dia 350 RM
833 833 (l) 32 mm dia 100 RM
834 834 (m) 25 mm dia 50 RM
835 835 Butterfly Valves Class 1, PN-1.6 conforming to IS-13095 of 1991 complete with flanges, bolts, nuts, gasket etc. As per specifications, hydroulically tested to 20 kg/cm2 complete in all respects, suitable for
836 836 (a) 350 mm dia pipe 6 Each
837 837 (b) 250 mm dia pipe 18 Each
838 838 (c) 200 mm dia pipe 6 Each
839 839 (d) 150 mm dia pipe 4 Each
840 840 (e) 65 mm dia pipe 18 Each
841 841 (f) 50 mm dia pipe 64 Each
842 842 Ball Valves suitable for pipes of dia
843 843 (a) 40 mm with strainer 10 Each
844 844 (b) 40 mm without strainer 10 Each
845 845 (c) 32 mm with strainer 6 Each
846 846 (d) 32 mm without strainer 6 Each
847 847 (e) 25 mm with strainer 2 Each
848 848 (f) 25 mm without strainer 2 Each
849 849 Cast iron balancing Valves confirming to IS, clas 1 incl nuts, bolts, gasket etc complete, suitable for following dia pipes:-
850 850 (a) 350 mm 1 Each
851 851 (b) 250 mm 6 Each
852 852 (c) 200 mm 3 Each
853 853 (d) 150 mm 2 Each
854 854 (e) 65 mm 9 Each
855 855 (f) 50 mm 32 Each
856 856 Cast iron doubleflangged horrizontal type with gun metal seat non-return valve conforming to class 1 of IS-5312 incl nuts, bolts, gasket etc complete, suitable for following dia pipes :-
857 857 (a) 350 mm 2 Each
858 858 (b) 400 mm 2 Each
859 859 (c) 250 mm 3 Each
860 860 Pot Strainer, of size
861 861 (a) 350 mm 2 Each
862 862 (b) 250 mm 3 Each
863 863 Air purge valve (15 mm) 80 Each
864 864 Flexible Pipe for Connection of suitbale and required length of following bores :-
865 865 (a) 350 mm 4 Each
866 866 (b) 250 mm 18 Each
867 867 Expansion Tank \nSupplying, fixing, testing and commissioning expansion tank fabricated from 3 mm thick M.S. sheet having 50 mm thick polyurethen foam insulation covered with 26 gauge Aluminium sheet with main hole cover drain, over flow, quick fill, normal water supply connections complete in all respect and all as specified of 4000 litres capacity. 1 Each
868 868 Drain Piping\nSupplying, fixing, testing and commissioning G.I. drain piping complete with fittings, supports valves and 15 mm thick polyurethen foam insulation complete all as specified, for following dia :-
869 869 (a) 50 mm 110 RM
870 870 (b) 40 mm 100 RM
871 871 (c) 32 mm 200 RM
872 872 (d) 25 mm 300 RM
873 873 Ducting\nSupplying, fixing, testing and commissioning steel metal ducting complete with supports, dampers, etc. all as specified.\n\n(i) G.I. Sheet Metal Ducting (Rectangular), fabricated with
874 874 (a) 0.63 mm (24 Gauge) 8000 Sqm
875 875 (b) 0.80 mm (22 Gauge) 4125 Sqm
876 876 (c) 1.00 mm (20 Gauge) 1100 Sqm
877 877 (d) 1.25 mm (18 Gauge) 270 Sqm
878 878 (ii) Aluminium Ducting (Rectangular), fabricated with
879 879 (a) 0.80 mm (22 Gauge) 5000 Sqm
880 880 (b) 1.00 mm (20 Gauge) 1500 Sqm
881 881 Insulation\nSupplying and fixing of glass wool insulation on ducts complete all as specified of 25 mm thickness. 18000 Sqm
882 882 Supplying and fixing of UV/fire/water, thermal protective, canvas coating on duct insulation by wrapping canvas cloth dipped in star bond 30-36, complete all as specified. 18000 Sqm
883 883 Duct Acoustic Lining\nSupplying and fixing of duct acoustic lining with bonded glass insulation of density 32 kg/m3 covered with 26 gauge perforated aluminium sheet with nuts and bolts complete all as specified of 25 mm thickness. 2000 Sqm
884 884 Grills\nSupplying, fixing, testing and commissioning Aluminium powder coated supply and return air grilles/diffusers complete all as specified, for
885 885 (a) Aluminium supply air diffuser with damper. 104 Sqm
886 886 (b) Aluminium return air diffuser without damper. 104 Sqm
887 887 (c) Aluminium return air grilles without damper. 6 Sqm
888 888 Fresh/Return Air Grilles
889 889 (a) Fresh/Exhaust air damper with louvers, bird screen and damper. 22 Sqm
890 890 (b) Double louvered fresh air grill with damper \n(for airwasher). 8 Sqm
891 891 Fire Damper\nSupplying and fixing galvanised sheet fire dampers complete with damper electric actuator, smoke/heat detector, interlocking arrangement with blower motor complete all as specified. (Opening of fire damper in wall/ partition to be cut and later made good to a fire rating of similar capacity as of damper without any extra cost to Govt), for
892 892 (a) Fire dampers 45 Sqm
893 893 (b) Actuator assembly 200 Set
894 894 Volume Control Damper\nSupplying and fixing G.I. volume control damper with blades, adjustable lever, frame etc. complete all as specified. 150 Sqm
895 895 Electrical Panel Board (Airconditioning)\nSupply, installing, testing and commissioning of factory made LT panel board suitable for 415 volts, 3 phase 4 wire, 50 Hz AC supply fabricated out of CRCA sheet 2.0 mm thick, powder coated internally and externally painted, compartmentalized design fitted with ACB's & MCCB's on common bus bar in tier formation, indoor type, providing and comprising of the following all as specified :-\n(A) Incoming : 02 Nos 2000 Amps capacity triple pole metal clad incoming feeder control panel extensible pattern each provided with under mentioned equipments :-\n(i) Electrolytic copper bus bar 2000 Amps for phases and 1250 Amps for neutral - 01 Set.\n(ii) ACB 1600 Amps trip free withdrawable thype manual operated with mechanical ON/OFF indicator, auxiliary switches and safety features - 01 No. \n(iii) CT's of ratio 1600/05 Amps of suitable VA burden and accuracy for protection and metering - 01 Set.\n(iv) Static trip devices for over current and earth fault - 01 Set\n(v) Under voltage release - 01 No. \n(vi) Red and Green indicating lamps to indicate ON/OFF position - 01 Set\n(vii) Flush pattern voltmeter 0-500 volts, square dial with selector swich to measure voltage between phases and between phase and neutral - 01 No.\n(viii) Flush pattern Amp meter 0-2000 Amps, square dial with selector switch to measure current in any phase - 01 No.\n(ix) Cable boxes/side frame - 01 Set 1 Each
896 896 (B) Bus Coupler : 01 No. 2000 Amp capacity triple pole metal clad bus coupler panel extensible panel provided with under mentioned equipments:-\n(i) Electrolytic copper bus bar 2000 Amps for phases and 1250 Amps for neutral - 01 Set\n(ii) ACB 1600 Amps trip free withdrawable type manual operated with mechanical ON/OFF indicator, auxiliary switches and safety features - 01 No. \n(iii) Red and Green indicating lamps to indicate ON/OFF position - 01 Set\n(iv) Electricial/ Mechanical inter lock - 01 Set.\n(v) Cable boxes/side frame - 01 Set.\n(C) Out Going\n1(a) 02 Nos 1250 Amps capacity triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :-\n\n(i) Electrolytic copper bus bar 2000 Amps for phases and 1250 Amps for neutral - 01 Set\n(ii) ACB 1250 Amps trip free withdrawable type manual operated with mechanical ON/OFF indicator, auxiliary switches and safety features - 01 No.\n(iii) CT's of ratio 1250/05 Amps of suitable VA burden and accuracy for protection and metering - 01 Set.\n(iv) Static trip devices for over current and earth fault - 01 Set.\n(v) Under voltage release - 01 No.\n(vi) Red and Green indicating lamps to indicate ON/OFF position - 01 Set
897 897 (vii) Flush pattern Amp meter 0-1250 Amps, square dial with selector switch to measure current in any phase - 01 No.\n(viii) Cable boxes/ side frame - 01 Set.\n1(b) Triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :-\n(i) MCCB TPN 200 Amps with rupturing capacity 35 KA (Ics) complete with thermal magnetic release - 01 No.\n(ii) CT's of ratio 200/5 Amps of suitable VA burden and accuracy - 01 Set each.\n(iii) Red and Green indicating lamps to indicate ON/OFF position - 01 Set each.\n(iv) Flush pattern Amp meter 0-400 Amps, square dial with selector switch to measure current in phase - 01 No. each\n(v) Side frame - 01 Set each.\n1(c) Triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :-\n(i) MCCB TPN 100 Amps with rupturing capacity 35 KA (Ics) complete with thermal magnetic release - 01 No.\n(ii) CT's of ratio 100/5 Amps of suitable VA burden and accuracy - 01 Set.\n(iii) Red and Green indicating lamps to indicate ON/OFF position - 01 Set.\n(iv) Flush pattern Amp meter 0-200 Amps, square dial with selector switch to measure current in phase - 01 No. \n(v) Side frame - 01 Set.
898 898 2(a) 02 Nos 1250 Amps capacity triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :-\n\n(i) Electrolytic copper bus bar 2000 Amps for phases and 1250 Amps for neutral - 01 Set\n(ii) ACB 1250 Amps trip free withdrawable type manual operated with mechanical ON/OFF indicator, auxiliary switches and safety features - 01 No.\n(iii) CT's of ratio 1250/05 Amps of suitable VA burden and accuracy for protection and metering - 01 Set.\n(iv) Static trip devices for over current and earth fault - 01 Set.\n(v) Under voltage release - 01 No.\n(vi) Red and Green indicating lamps to indicate ON/OFF position - 01 Set \n(vii) Flush pattern Amp meter 0-1250 Amps, square dial with selector switch to measure current in any phase - 01 No.\n(viii) Cable boxes/ side frame - 01 Set.\n2(b) Triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :-\n(i) MCCB TPN 250 Amps with rupturing capacity 25 KA (Ics) complete with thermal magnetic release - 01 No.\n(ii) CT's of ratio 250/5 Amps of suitable VA burden and accuracy - 01 Set \n(iii) Red and Green indicating lamps to indicate ON/OFF position - 01 Set \n(iv) Flush pattern Amp meter 0-300 Amps, square dial with selector switch to measure current in phase - 01 No. \n(v) Side frame - 01 Set \n
899 899 2(c) Triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :-\n(i) MCCB TPN 100 Amps with rupturing capacity 25 KA (Ics) complete with thermal magnetic release - 01 No.\n(ii) CT's of ratio 100/5 Amps of suitable VA burden and accuracy - 01 Set.\n(iii) Red and Green indicating lamps to indicate ON/OFF position - 01 Set.\n(iv) Flush pattern Amp meter 0-200 Amps, square dial with selector switch to measure current in phase - 01 No. \n(v) Side frame - 01 Set.\n2(d) Change over switch on load type TPN 415 volts, 1600 Amps - 01 No.
900 900 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming / outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For Pump etc.) \n(i) 1 No. 1600 Amps ACB incoming.\n(ii) 1 set 1600 Amps ACB TPN and neutral conductor bus bars duly sleeved.\n(iii) 6 Nos. 200 Amps MCCB outgoing along with 6 Nos. star delta starter for 79/75 kw chilled water & condenser water pump motor. (one standby)\n(iv) 2 Nos. 400 Amps MCCB outgoing. \n(v) 6 Nos 32 Amps MCB outgoing along with 3 Nos. star delta starter for 9.5 kw motor. 1 Each
901 901 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming /outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For OT AHU)\n(i) 1 No. 250 Amps MCCB incoming.\n(ii) 1 Set 250 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved. \n(iii) 1 No. 200 Amps TPN MCB outgoing for 5x15 kw strip heater.\n(iv) 1 No. 16 Amps TPN MCB outgoing for humidifire.\n(v) 1 No. 63 Amps MCB outgoing along with 1 No. DOL starter for 22.0 kw motor. 1 Each
902 902 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For OT AHU). \n(i) 1 No. 100 Amps MCCB incoming.\n(ii) 1 Set 100 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved. \n(iii) 1 No. 100 Amps TPN MCCB outgoing for 40/35/25/20 kw strip heater.\n(iv) 1 No. 32 Amps TPN MCCB outgoing alongwith 1 No. star delta starter for 11.0/7.5/5.5 kw motor.\n(v) 1 No. 16 Amps MCB outgoing along with for humidifire.\n 8 Each
903 903 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For F.M. AHU's).\n(i) 1 No. 32 Amps MCCB incoming.\n(ii) 1 No. 32 Amps MCCB outgoing along with 1 No. star delta starter for 11.5/7.5/5.5 kw motor. 40 Each
904 904 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For C.S. AHU's).\n(i) 1 No. 16 Amps MCB incoming. \n(ii) 1 No. 16 Amps MCB outgoing along with 1 No. DOL starter for 3.7/2.2/1.1 kw motor. 14 Each
905 905 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming / outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For scrubber). \n(i) 1 No. 100 Amps MCCB incoming.\n(ii) 1 Set 100 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved. \n(iii) 1 No. 100 Amps TPN MCCB outgoing along with 1 No. star deta starter for 30 kw motor.\n(iv) 1 No. 16 Amps MCB outgoing along with 1 No. DOL starter for 1.0 kw pump. 1 Each
906 906 Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming / outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For Airwasher) \n(i) 1 No. 63 Amps MCCB incoming. \n(ii) 1 Set 63 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved. \n(iii) 1 No. 63 Amps TPN MCCB outgoing along with 1 No. star delta starter for 18.5/15.0 kw motor.\n(iv) 1 No. 16 Amps TPN MCB outgoing along with 1 No. DOL starter for 1.0 kw pump. 1 Each
907 907 Power Cabling\nSupplying and fixing PVC sheathed Aluminium cables with for various equipments through walls/ceiling/cable tray with appropriate clamps & fixing arrangements including M.S. perforated cable tray complete all as specified of
908 908 (a) 31/2 C - 400 sqmm 200 RM
909 909 (b) 31/2 C - 240 sqmm 400 RM
910 910 (c) 4 C - 6 sqmm 430 RM
911 911 (d) 4 C - 4 sqmm 600 RM
912 912 Control Consol\nSupplying, fixing, testing and commissioning desk type control consol floor mounted paneled type fabricated from 2.0 mm CRCA sheet with indication lamp, ON/OFF/FAULT lamps alarm relays and internal wiring. 1 Each
913 913 Control Cabling\nSupplying, fixing and terminations of multicore PVC control cabling of copper 1.5 sqmm upto control consol panel board through walls/ceiling/cable tray with appropriate clamps and fixing arrangements complete all as specified. 1 Job
914 914 Earthing Conductor\nDouble earthing continuity conductors of G.I. between panel boards and equipments as required of size.
915 915 (a) 32 x 6 mm (Strip) 1400 RM
916 916 (b) 8 SWG (wire) 1600 RM
917 917 (c) 10 SWG (wire) 1600 RM
918 918 Supply and fixing rotational moulded polyethylene water storage tank (cylintrical vertical with closed top), hoisted and fixed in position all as specified in SSR Part-I for 1000 litre capacity incl and providing brass float valve of suitable dia of inlet pipe with polythene float and fly nut complete screwed for iron pipe complete all as specified.\nNote : Tank to be hoisted on roof of existing pump house building and all inlet, outlet, washout and over flow pipes shall be measured under respective parts of Sch 'A'. 1 Each
919 919 Supplying, fixing, testing and commissioning underground 'C' class mild steel black steel pipes with necessary fittings and insulation (expandable polystyrens thermcol) etc complete all as specified.
920 920 (a) 400 mm dia 182.9 RM
921 921 (b) 350 mm dia 35.8 RM
922 922 (c) 250 mm dia 90.6 RM
923 923 (d) 200 mm dia 79.7 RM
924 924 (e) 150 mm dia 25.7 RM
925 925 (f) 125 mm dia 117 RM
926 926 (g) 100 mm dia 343.18 RM
927 927 (h) 80 mm dia 159.08 RM
928 928 (j) 65 mm dia 47 RM
929 929 (k) 50 mm dia 9.15 RM
930 930 (l) 40 mm dia 61 RM
931 931 (m) 32 mm dia 5 RM
932 932 M&L for brick work using sub class B bricks in cement mortar 1:6 for brick pillar of UG chiller pipe line 54 Cum
933 933 M&L for PCC work 1:5:10 using 40 mm graded aggregate type E2 for brick pillar of UG chiller pipe line 46 Cum
934 934 M&L for Ball valve of 15 mm dia for drain pipe 65 Each
935 935 M&L for Ball valve of 32 mm dia for drain pipe 7 Each
936 936 M&L for 2 way motorised Ball valve of 200 mm dia 1 Each
937 937 M&L for 2 way motorised Ball valve of 100 mm dia 1 Each
938 938 M&L for 2 way motorised Ball valve of 80 mm dia 11 Each
939 939 M&L for 2 way motorised Ball valve of 65 mm dia 32 Each
940 940 M&L for 2 way motorised Ball valve of 50 mm dia 13 Each
941 941 M&L for 2 way motorised Ball valve of 40 mm dia 6 Each
942 942 M&L for 2 way motorised Ball valve of 32 mm dia 2 Each
943 943 M&L for strainer of size 100 mm dia made of cast iron flanged type 1 Each
944 944 M&L for strainer of size 100 mm dia made of cast iron flanged type 11 Each
945 945 M&L for strainer of size 100 mm dia made of cast iron flanged type 32 Each
946 946 M&L for strainer of size 100 mm dia made of cast iron flanged type 13 Each
947 947 M&L for strainer of size 100 mm dia made of cast iron flanged type 6 Each
948 948 M&L for strainer of size 100 mm dia made of cast iron flanged type 2 Each
949 949 M&L for strainer of size 100 mm dia made of cast iron flanged type 113 Each
950 950 M&L for additional accessories to hot water boiler for air conditioning work
951 951 Supply, fixing, testing and commissioning day tanks of 990 liters fuel oil tanks fabricated out of 5mm thick MS sheet with all fittings like level gauge glass 1 Each
952 952 Supply, fixing, testing and commissioning of fuel duct (bare size) fabricated out of 5mm thick MS sheet for 250 mm dia 8 Each
953 953 Supply, fixing, testing of Gay supported chimney of top dia 675mm, 30 meter height made out of MS sheet. 1 Each
954 954 Supply, fixing of softner of 1200 liters per hour for Hot water boiler 1 Each
955 955 Supply, fixing, testing and commissioning of water pump suitable for softening plant of cap 1200 liters per Hr @ 50 liters per minute @ 30 m head. 1 Each
956 956 Air Handling Unit\nSupplying, fixing, testing and commissioning of horizontal double skin floor mounted type air handling unit complete with fan, fan motor drive, cooling coil, prefilters, microvee filter fresh air damper with louvers & bird screen, including foundation, vibration isolator pads complete all as specified of :-\n(a) 24000 cfm, 6 row coil 1 Each
957 957 Unitary Air Handling Unit\nSupplying, fixing, testing and commissioning of double skin ciling mounted unitary type air handling unit complete with fan, fan motor, drive, cooling coil, filters, canvas connections, 2 way throttling valve with snap acting thermostat etc. complete all as specified of :-\n(a) 7000 cfm, 6 row coil 1 Each
958 958 Butterfly valves class 1, PN-1.6, gear operated, conforming to IS-13095 of 1991 complete with flangs, bolts, nuts, gasket wtc, as per specifications, hydraulically tested to 20 Kg/Sqcm complete in all respects, suitable for\n(a) 400 mm dia 7 Each
959 959 Butterfly valves class 1, PN-1.6, gear operated, conforming to IS-13095 of 1991 complete with flangs, bolts, nuts, gasket wtc, as per specifications, hydraulically tested to 20 Kg/cmm2 complete in all respects, suitable for\n
960 960 (a) 100 mm dia 2 Each
961 961 (b) 80 mm dia 22 Each
962 962 (c) 40 mm dia 6 Each
963 963 Cast iron balancing valves conforming to IS, class 1 incl nuts, bolts, gasket etc complete suitable for following dia pipes :-
964 964 (a) 100 mm dia 1 Each
965 965 (b) 80 mm dia 11 Each
966 966 Pot Stariner of size :- 400 mm 2 Each
967 967 Air Pulge Valve (25mm) 7 Each
968 968 Providing and fixing rubber expension bellows with control rods/ spacers in pipe connection to equipment of size :- 400 mm 4 Each
969 969 SCH 'A' PART- XXVI : COMMUNICATION SYSTEM \nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
970 970 Rigid galvanised steel conduit, consealed type, welded, exclusive of junction & terminal boxes, but inclusive of all fittings such as tees bends elbows, reducers, bell mouth tube ends and all fixing accessories such as couplers lock nuts, saddles pipe, hook, etc., of 20mm dia bore for Intercom, musical system, TV Cable system, PA system & Computer system. 17450 RM
971 971 All as per item ser No 29.10 above but of 25mm dia bore. 700 RM
972 972 Junction box with cover any number or types of outlets, as ordered for rigid galvanised steel conduit of size 20mm dia. 1050 Each
973 973 All as per item ser No 29.3 above but for 25mm dia steel conduit. 40 Each
974 974 Perforated type GI trays for holding galvanised steel conduit of following sizes fabricated from perforated 2mm thick Mild Steel galvanised CRCA Sheet with expansion coupler, GI plates with bolts,nuts & washers,knock out hole, supporting fish platesand accessories, down rods-fasterners complete all as required at site.
975 975 (a) 150mm widex40mmx40mm 68.6 RM
976 976 (b) 300mm widex40mmx40mm 117.2 RM
977 977 SCH 'A' PART- XXVII : SIGNAGES WORKS
978 978 Composite Signage Ceiling hung : \nComposite signage, false ceiling suspended type, having 2 or 3 assorted pictograms/ text about department/ clinic/ ward type along with direction arrows on either side of the floor depiction in figure as well words, on either face readable from both sides, made up of 0.8mm thick standard modular aluminium graphic arc double surface panels. The Aluminium panel shall be secured with five Abs supporting strips (Polka Model PL-317) in size, for 1500mm over all length, two of which shall be at the end. A pair of Arc hidden aluminium extruded cum slotted rails fixed to a double sided aluminium extruded fixing rail to full length of panel shall be clipped on to the Abs Supporting strip at two designed points having built in clipping device. The ends of the united pair of Arc hidden rails shall be plugged with Arc double surface end cover on either end Text letters/ pictograms duly electonic plotter cut in coloured vinyl shall be pasted on to the powder coated surface of the aluminium panel. The signage unit shall be suspended from ceiling with custom designed stainless steel suspension rods as per fixing detail. The Composite Signage Ceiling hung shall have different depiction in accordance to their situation at each floor as per distribution as under :- \n (a) Basement Floor - 05 Nos. (b) Ground Floor - 07 Nos. (c) First Floor - 07 Nos. (d) Second Floor - 07 Nos (e) Third Floor - 06 Nos (f) Fourth Floor - 06 Nos 38 Each
979 979 Department Sign Ceiling.\nDepartment Sign close to ceiling level either mounted on wall above door height or suspended from false ceiling, having requisite Department/ Clinic/ Ward's Inscription. The DSC shall of standard Aluminium profile (Illusion modle C-150) of size 600mm x150mm with Abs side cap on either end. The DSC unit shall either be screwed to wall surface or suspended from false ceiling. The exposed surface of the profile shall have removable 0.6mm thick polycarbonate film covering to enable the user to insert the requisite Department/ linic/ Ward's inscription. The distribution of DSC shall be as under :-\n(a) Basement Floor - 06 Nos.\n(b) Ground Floor - 35 Nos.\n(c) First Floor - 21 Nos.\n(d) Second Floor - 13 Nos.\n(e) Third Floor - 09 Nos.\n(f) Fourth Floor - 08 Nos. 92 Each
980 980 Wall Bracket Sign. \nWall Bracket Sign shall be made of 0.8mm thick standard modular aluminium graphic arc double surface panels 200mm wide, secured with two Abs Supporting strips (Polka model PL-253) in size. A pair of Arc hidden aluminium extruded cum slotted rails anchored to a double sided aluminium extruded fixing rail to full width of panel shall be clipped to the Abs Supporting strip at two designed points having self built in clipping device. The ends of the united pair of Arc hidden shall be plugged with Arc double surface end cover on exposed end, supported to standard extruded aluminium wall rail to form the bracket. The wall rail shall be fixed to wall surface with aluminium screws and rawl plugs. Text letters/ Pictograms duly electronic plotter cut in coloured vinyl shall be pasted on the powder coated surface of the aluminium panel on either face. Wall Bracket Sign shall be of following type :- 445 Each
981 981 (a) Air Handling Unit - 41 Nos.
982 982 (b) Dining - 41 Nos.
983 983 (c) Dirty Utility - 35 Nos.
984 984 (e) Electric Room - 26 Nos.
985 985 (f) Female Toilet - 31 Nos
986 986 (g) His - 05 Nos.
987 987 (h) Janitor Closet - 10 Nos
988 988 (j) Male Toilet - 30 Nos
989 989 (k) Officer's Toilet - 11 Nos
990 990 (l) Pantry - 32 Nos.
991 991 (m) Wet Riser - 05 Nos
992 992 (n) Stairs - 35 Nos
993 993 (o) Stores - 56 Nos
994 994 (p) Soiled Linen - 29 Nos
995 995 (q) Sluice Room - 06 Nos
996 996 (r) Toilet - 44 Nos.
997 997 (s) UPS - 08 Nos
998 998 Floor Polka Sign.\nFloor Polka Sign suspended from ceiling made up of 0.8mm thick standard modular aluminium graphic arc double surface panels secured with two Abs supporting stips (Polka Model PL-317) in size at either end of its 300mm lengths. A pair of Arc hidden aluminium extruded cum slotted rails anchored to a double sided aluminium extruded fixing rail to full length of panel shall be clipped to the Abs supporting strip at two designed points having self built in clipping device. The ends of the united pair of Arc hidden rails shall be plugged with Arc double surface end cover on either end. Floor reference duly electronic plotter cut in coloured vinyl shall be paster on to the powder coated surface of the aluminium panel. FPS Shall be 2 on each floor in the Lifts Lobby along side Hospital street. 12 Each
999 999 Floor Directory Sign.\nFloor directory Signage unit on wall surface. The unit shall comprise of flat sign series of Aluminium anodised extruded top flat panel 124mm wide & subsequent number of flat panels 62mm wide on required basis (model 2124 and 2062 respectively), edge progile (model 2303) on either side. The unit shall measure 600x124 mm +62mm x number of panels required on each floor. Number of flat panels shall be 13 at Ground Floor, and 5 at basement floor. Each of the flat panel shall be provided with 4 numbers 31mm low height plastic holders (model 2502) for sliding in edge profile. The edge profile shall be provided with plastic pole cap on top and bottom end (model 2559 for left side and 2560 for the right side). The unit thus formed shall be fixed on 12mm thick MDF board duco painted of shape as per drawing, which in turn shall be fixed to wall surface using wood screws and rawl plugs. 13 Each
1000 1000 Door Plate Sign.\nDoor Plate Sign shall be laser cut 3 mm thick ACP pasted over 3mm thick coloured acrylic measuring 120x180mm. The ACP shall have CNC router cut pictogram/ words as per facility use. The Plate shall be fixed on door shutter with 4-12mm dia black powder coated steel studs. In case of DPS/B, DPS/Ba, DPS/W&DPS/Wa the size of plate shall be 120x120mm. Door Plate Sign shall be of following type :- 931 Each
1001 1001 (a) Air Handling Unit - 40 Nos
1002 1002 (b) Bath - 43 Nos.
1003 1003 (c) Bath Assist - 26 Nos.
1004 1004 (d) Change/ Dress - 10 Nos.
1005 1005 (e) Dining - 42 Nos.
1006 1006 (f) Dirty utility - 35 Nos.
1007 1007 (g) Electric Room - 24 Nos.
1008 1008 (h) Female Toilet - 31 Nos.
1009 1009 (j) His - 05 Nos.
1010 1010 (k) Janitor Closet - 35 Nos.
1011 1011 (l) Male Toilet - 30 Nos.
1012 1012 (m) Officer's Toilet - 11 Nos.
1013 1013 (n) Pantry 49 Nos.
1014 1014 (o) Wet Riser - 05 Nos.
1015 1015 (p) Stairs - 05 Nos.
1016 1016 (q) Stores - 56 Nos.
1017 1017 (r) Shaft - 05 Nos.
1018 1018 (s) Soiled Linen - 29 Nos.
1019 1019 (t) Sluice Room - 05 Nos.
1020 1020 (u) Under ground sump - 05 Nos.
1021 1021 (v) Toilet - 244 Nos.
1022 1022 (w) Telephone - 03 Nos.
1023 1023 (x) Wet Riser - 05 Nos.
1024 1024 (y) UPS - 08 Nos.
1025 1025 (z) Water Closet - 141 Nos.
1026 1026 (aa) Water Closet Assist - 39 Nos.
1027 1027 Wall Plate Sign.\nWall plate signage shall be laser cut 3mm thick ACP pasted over 3mm thick coloured acrylic measuring 120x180mm. The ACP shall have CNC router cut pictogram/ words as per facility use. The plate shall be fixed on wall with 4-12mm dia black powder coated steel studs with screws and rawl plugs. Wall plate sign shall be of following type :- \n(a) Drinking Water (Cooler) - 28 Nos.\n(b) Reception - 27 Nos. (c) Receipt / Issue - 02 Nos. (d) Shops - 05 Nos. (e) Trollery Bay - 39 Nos. (f) Waiting - 58 Nos. 159 Each
1028 1028 Room Use Plate.\nRoom use plate of size 250x60mm of aluminium extruded profile with Abs side caps, "ILLUSION" Model C-060 having removable 0.6mm thick polycarbonate film cover. The sign plate shall be screwed on to wall surface by the side of rooms door. 949 Each
1029 1029 Room Number Plate.\nRoom Number Plate of size 120x80mm of aluminium extruded profile with Abs side caps, "ILLUSION" model C-060 having removable 0.6mm thick poly carbonate film cover. The sign plate shall be screwed on to wall surface by the side of door and over BUP 1297 Each
1030 1030 Fire Safety Signs.\nSelf Contained Rechargeable Emergency Exit/Egress Light Sign (Surface mounted). The signage shall conform to IS-9583-1981 and to meet the technical conditions such as Battery duration+/-10%, Red LED "ON" indicates charging, Equipped with push Test Switch, 22 SWG CRCA white powder coated housing, and input-230v, 50 Hz. The signage shall be maintainable for 3 hours with backup of 1x11 CFL. SLA Rechargeable Battery 10 to 12 hours. \nSelf contained Rechargeable Emergency LED Exit/Egress Edgelit Lights Signage. 190 Each
1031 1031 Parking Warning Signs.\nWarning sign measuring 200x200mm shall be of CNC router cut 3mm Aluminium anodised sheet duly powder coated with vinyl cut pictogram of three types on one side. The sign shall be fixed on wall surface in the basement parking areas. 18 Each
1032 1032 Indoor signs for evacuation / fire / lift / stairs / ramps.\nVinyalized SAFETY GRADE - VG - Q1++1 mm aluminium based Hi - grade luminescent glow in the dark signs to be installed in the interiors with more than 10 hours glow capacity duly cut to size and individually printed as per the different govt, standards with specific text / graphics / language colour combinations size and code as directed by GE, duly installed with mirror screws and supporting powder coated aluminium / PVC based signs hangers as required at site for fixing double sided signs of different height and width as under :-
1033 1033 (a) 8 inch height and 20 inch width, size / code : EV-01 820. 146 Each
1034 1034 (b) 6 inch height and 12 inch width, size / code : EVST-02 612. 464 Each
1035 1035 (c) 8 inch height and 8 inch width, size / code : LT-03 88. 38 Each
1036 1036 (d) 6 inch height and 8 inch width, size / code : FF-04 68. 393 Each
1037 1037 (e) 6 inch height and 6 inch width, size / code : FL-05 66. 134 Each
1038 1038 (f) 4 inch height and 11 inch width, size / code : BG-06 411. 75 Each
1039 1039 (g) 6 inch height and 16 inch width, size / code : EVSTS-07 616. 242 Each
1040 1040 (h) 6 inch height and 16 inch width, size / code : EVSTD-08 616. 105 Each
1041 1041 PART- XXVIII : LIST OF WORKS AND PRICES FOR OT WORKS\nNote : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
1042 1042 Twin plate X-ray viewing screen designed to provide a high level of control luminance without flicker, size 1000mm x 700mm x 95mm deep, indigenous, complete all as specified.\nMake : MPS / APEX ENG / MANJOT 8 Each
1043 1043 Writing Board with magneting system of size 1000mm x 700mm x 60mm deep made of G.P sheet flushed with the wall system complete all as specified (Indegenous).\nMake : MPS / APEX ENG / MANJOT 8 Each
1044 1044 Storage unit size 1666mm x 865mm x 350mm having two shelves, made of zinc passivated steel with 5mm thick glass door & mounted flush with the theatre wall (Indegenous).\nMake : MPS / APEX ENG / MANJOT. 16 Each
1045 1045 Recess mounted bottom opening, clear room luminaire (peripheral light) with dimming, each having 2x36W CFL, Electronic ballast (size 2'x1') complete all as specified (Indegenous).\nMake : MPS / APEX ENG / MANJOT. 64 Each
1046 1046 Schedule of Credit (for demolished buildings)\n\nDeduct Schedule of credit worth Rs. 411801.17 (Minus) as listed in Schedule 'a' Part - XXIX\nNote : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
1047 1047 Schedule of Credit for material lying at site\n\nDeduct Schedule of credit worth Rs. 171642756.90 (Minus) as listed in Schedule 'a' Part - XXX (Sec-A)\nNote : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
1048 1048 Schedule of Credit for material lying at site\n\nDeduct Schedule of credit worth Rs. 8353693.90 (Minus) as listed in Schedule 'a' Part - XXX (Sec-B)\nNote : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
1049 1049 Schedule of Credit for material lying at site\n\nDeduct Schedule of credit worth Rs. 0.00 (Minus) as listed in Schedule 'a' Part - XXX(Sec-C)\nNote : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
1050 1050 Total Amount of Sch 'A' Part - XXXI (DEVIATION ORDER FOR CERTAIN CHANGES IN ONE BLOCK OF 05 AND TWO BLOCKS OF 06 MD QTRS FOR ORS ACCN AGAINST SCH 'A' PART-I SI ITEM NOS 18 & 19 (DUE TO REDUCTION OF PLINTH AREA)\nNotes:- (i) Go ahead approvals/approvals in principle for the changes/works has bee accorded during currency of previous cancelled contract. These changes shall be measured and paid for seperately under this schedule. 1 Lump \nSum
1051 1051 Total Amount of Sch 'A' Part -XXXII (DEVIATION ORDER FOR CERTAIN CHANGES IN ONE BLOCK OF 06 MD QTRS FOR JCOs ACCN AGAINST SCH 'A' PART-I SI ITEM NO 17 (DUE TO REDUCTION OF PLINTH AREA)\nNotes:- (i) Go ahead approvals/approvals in principle for the changes/works has bee accorded during currency of previous cancelled contract. These changes shall be measured and paid for seperately under this schedule. 1 Lump \nSum
1052 1052 PROVISIONAL SUM FOR CERTAIN BUILDING WORK\nProvide Provisional Sum of Rs 825000.00 for construction of block for housing ETP, sewage cum Pump house and water softening pumps with accessories/fitments etc.\nNotes:- (i) The work of provisional sum shall be carried out by the contractor only after written order of GE. The work order shall be placed by the GE duly priced on SSR 2004 Part-II rates.\n(ii) Building work shall be executed as per the work order placed by GE based on the drawings provided during currency of work. Measurements for entire work executed under provisional sum shall be recorded in MB and shall be form basis for making payment.\n(iii) Internal/external services and earthwork shall be measured under respective items of Sch 'A' (BOQ). 1 Lump \nSum