Outsourcing Of Services For 11 Kv Ht Installations Of Ngarm , Qrsam And Sfdr Area And Repairs/Maintenance Of Ht/Lt Over Head Lines Ht/Lt Switch Gear Control Panel And Apfc Panels Installed At Various Locations Under Ge ( I ) Rnd Kanchanbagh , Hyderaba, Hyderabad-Telangana

Military Engineer Services-MES has published Outsourcing Of Services For 11 Kv Ht Installations Of Ngarm , Qrsam And Sfdr Area And Repairs/Maintenance Of Ht/Lt Over Head Lines Ht/Lt Switch Gear Control Panel And Apfc Panels Installed At Various Locations Under Ge ( I ) Rnd Kanchanbagh , Hyderaba. Submission Date for this Tender is 23-06-2021. Switch Gear Tenders in Hyderabad Telangana. Bidders can get complete Tender details and download the document.




Tender Notice

28009111
Corrigendum : Outsourcing Of Services For 11 Kv Ht Installations Of Ngarm , Qrsam And Sfdr Area And Repairs/Maintenance Of Ht/Lt Over Head Lines Ht/Lt Switch Gear Control Panel And Apfc Panels Installed At Various Locations Under Ge ( I ) Rnd Kanchanbagh , Hyderaba
National Competitive Bid
Indian
Telangana
Hyderabad
23-06-2021

Tender Details

Outsourcing Of Services For 11 Kv Ht Installations Of Ngarm , Qrsam And Sfdr Area And Repairs/Maintenance Of Ht/Lt Over Head Lines Ht/Lt Switch Gear Control Panel And Apfc Panels Installed At Various Locations Under Ge ( I ) Rnd Kanchanbagh , Hyderabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 15-Jun-2021 Amendment Technical Bid 16-06-2021
2 16-Jun-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 23-06-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 98000.0 /-
Tender Value
INR 49 Lakhs /-

BOQ Items

NAME OF WORK: OUTSOURCING OF SERVICES FOR 11 KV HT INSTALLATIONS OF NGARM, QRSAM AND SFDR AREA AND REPAIRS/MAINTENANCE OF HT/LT OVER HEAD LINES HT/LT SWITCH GEAR CONTROL PANEL AND APFC PANELS INSTALLED AT VARIOUS LOCATIONS UNDER GE (I) R&D KANCHANBAGH, HYDERABAD.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Out sourcing of services for Manning & Operation and Maintenance of Electric supply system in one shift for 8 hrs on all working days by employing the manpower as mentioned below for entire system comprising of HT and HT/LT lines, UG cables, transformers, 2/3/4/6 pole structures, LT panel boards, switch gears, street lights including maintenance of necessary records & documents, complete all as per directed in respect of NGARM/ SFDR/QRSAM Area\nNote :- \n(a) 1st Shift : 1400hrs to 2200 hrs \n01 Electrician (Semi Skilled) \n01 Helper (Un skilled)\n2nd Shift : 2200hrs to 0600 hrs \n01 Electrician (Semi Skilled) \n01 Helper (Un skilled)\n(b) Rate quoted shall be deemed to include for restoration of jumpers, HT fuses using existing resources during short circuit, wind / rain without any extra cost\n(c) Material like fuse wire shall be provided by the contractor and the same is deemed to be included in rate quoted.\n(d) During Break downs/ shut down of any type from TSSPDCL / DRDL sub stations shall be informed immediately to the department and necessary fault rectification to be done and the quoted rate is deemed to be included for same. 11 Per Month
2 1.01 Note for Item No 01 :- (i) In case of requirement, tradesmen provided per one area may be utilized in other areas at the discretion of the department without any extra cost to department as directed by Engineer-in-Charge. (ii) Rate quoted is deemed to be included for leave reserve/off of the staff employed. (iii) The rate quoted shall be deemed to include the cost of 02 pairs of uniform for tradesmen employed and the name of the contractor and the tradesman should be stitched on the front side of the shirt pocket. (iv) The rate quoted shall be deemed to including the Providing Log Books & Stationery for all above mentioned installations. (v) The necessary Tools & Plants shall be provided by the contractor. (vi) Group insurance, E.S.I & PF shall be provided to the operators by the contractor. Documents shall be submitted to the department. (vii) Wages to be paid to employee through individual bank account only and documents to be submitted to department. (viii) Minimum wages certificate along with attendance register and wage register shall be submitted for releasing of payment (ix) Minimum wages to the employees to be paid as per the norm published by the Min of Labour (wages as declared in particular specification ) and the same to be deemed to be included in the quoted rate.
3 1.02 (x) Each employee should be facilitated with adhoc bonus privilege as applicable in accordance with Govt Of India and the same to be deemed to be included in the quoted rate.(xi) In case of absence operator, double the rate quoted to be recovered. (xii) Departmental equipments of each building like fire fighting equipment, motors, pumps, Electric panels and its accessories copper brass materials etc., shall be under safe custody. In case of theft any item recovery shall be made from the contractor as per direction of Engr-in-Charge. (xiii) The Semi skilled tradesman should be qualified with minimum 05years of experience in handling the 11 KV installations/Switch gears, OH lines and UG cables (xiv) The skilled tradesmen should be ITI qualified and min 03years experience in working on 11KV distribution system . (xv) All people employed are responsible for cleaning and maintenance including restricting vegetation growth in his equipment surrounding area, upkeep of installations. \n(xvi) The contractor will adhere to pay monthly payment cycle to the employees irrespective of RAR/Funds availability with department to avoid embarassing situations to the principle employer.
4 2 S&F cable jointing kit for straight through joint (epoxy) for 1.1 KV grade XLPE, PVC insulated and sheathed aluminium conductor under ground cable including thimbles, nuts & bolts, washers etc and testing after jointing complete, all as directed for the following sizes.\nMake: M-seal/Raychem/Transeal/Denson
5 2.01 6 sqmm to 16 sqmm 4 core 8 Each
6 2.02 25 sqmm to 50 sqmm 3.5 core 8 Each
7 2.03 70 sqmm to 120 sqmm 3.5 core 6 Each
8 2.04 150 sqmm to 185 sqmm 3.5 core 5 Each
9 3 Supply & fix in repairs testing and comminisioning and programming of Numerical Protection Relay P642, Micom P642 in existing HT panel board.\nMake : Schneider 1 Job
10 4 Supply, install, test and commissioning LT Panel board, factory made cubical type, out door type made out of 3.15 mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof suitable for working 415 volts, 3 phase, 50 Hz having aluminium bus bars of capacity 600 Amps and half neutral duly colour coaded sleeves and supported with DMC/SMC insulators complete with Digital type multifunction meter V,A KVA, KVAR, PF, KWAH with class 1 accuracy including suitable range of CT's : ASS, VSS, set of three LED phase indicating lamps duly prewired with suitable size of copper conductor cables and shall be mounted in PCC foundation in PCC 1:2:4 type B1, with MS channels, nuts, bolts, washers etc the panel board shall be fabricated from the reputed CPRI approved firm as approved by GE and duly coated with red oxide primer and powder coated and the panel board shall be suitable to accommodate and including cost of the following switch gear items including removing unserviceable panel complete all as specified and directed :- 1 Job
11 4.01 (a) MCCB 400 Amps, 4 pole, 36 KA microprocessor release with LED display with neutral protection type with rotary handles, spreader links - 01 No. (I/C)\n(b) MCCB 320 Amps, 4 pole, 36 KA microprocessor release with LED display with neutral protection type with rotary handles, spreader links - 01 No. (out going)\n(c) MCCB 200 Amps, 4 pole, 25 KA Thermal magnetic, adjustable over load & short circuit currents, Icu=100% Ics - 02 Nos. (out going)\n(d) MCCB 100 Amps, 4 pole, 16 KA Thermal magnetic, adjustable over load & short circuit currents, Icu=100% Ics - 03 Nos. (out going)
12 5 Ditto all as per Item No: 4 above but out door type made out of 3.15 mm thick CRCA sheet with aluminium bus bar of capacity 600 Amps, including fixing of the following items :-\n(a) MCCB 400 Amps, 4 pole, 36 KA microprocessor release with LED display with neutral protection type with rotary handles, spreader links - 01 No. (I/C)\n(c) MCCB 160 Amps, 4 pole, 16 KA Thermal magnetic, adjustable over load & short circuit currents, Icu=100% Ics - 05 Nos. (out going)\n(d) MCCB 100 Amps, 4 pole, 16 KA Thermal magnetic, adjustable over load & short circuit currents, Icu=100% Ics - 02 Nos. (out going) 1 Job
13 6 S&F in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11/33 KV control panel including associated wiring, if reqd, complete all as specified and directed. 80 Each
14 7 M&L for Repairs/maintenance of 11KV HT VCB Panel including bus couplor of any type, size and capacity complete including the following :- \n(a) Taking out 11KV HT VCB of 400/630/800 Amps rating trolley from HT Panel after switching off electric supply, checking of mechanical system for proper functioning of upward/downward movement of HT VCB trolley including opening the VCB & checking the quality of insulating. Cleaning & servicing the fixed/moving contact & blowing out dust from bus bar chamber, spout gear mechanism and applying the proper lubrication/greasing and reassembling the VCB connection, testing, commissioning and putting on load complete all as directed. \nNote:- Spare parts which are required for replacement shall be measured and paid separetely under respective item of this Sch. 12 Each Job
15 8 Testing and re-setting of protection relay of 11 KV VCB, (indoor/outdoor) relays incoming and out going feeders with control panel and control cable differential relay once in a month through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Checking the condition of and taking corrective checking and oprating the switchgear and trip circuit of HT panel/breakers for its proper functioning complete all as specified and directed. 11 Job
16 9 Supply installing testing and commissioning in replacment the relay module Micom P111 making necessary cutting in the existing panel and necessary control wiring FRLS of size not less than 2.5Sqmm and providing Ferules for identification and necessary spares for fixing complete to the entire satisfaction of the Engr-in-Charge. 1 Each
17 10 Supply installing testing and commissioning in replacment the relay module Micom P127 making necessary cutting in the existing panel and necessary control wiring FRLS of size not less than 2.5Sqmm and providing Ferules for identification and necessary spares for fixing complete to the entire satisfaction of the Engr-in-Charge. 1 Each
18 11 Supply, lay, test and commissioning of XLPE insulated HT cable, screened PVC bedded, galvanised steel strip or wire armoured electric power cable of 6350 (UE) / 11000 (E) volts grade with multistranded aluminium conductor of cross sectional area 95 sqmm; 3 core including providing cable lugs and to be laid in trenches fixed along the poles bare or through pipes complete and removing the unserviceable cable all as specified and directed.\nNote : Excavation and earth work / san / cable covers will be measured and paid seperately. 180 RM
19 12 Material & Labour for GI tubing 100 mm dia light grade galvanised for cable protection including sealing both ends including removing old unserviceable item all as specified & directed. 10 RM
20 13 Excavation in trenches not exc.1.5 Mtr in width and not exceeding 1.5 Mtr in depth getting out in hard/dense soil 61 Cum
21 14 Removing excavated surplus soil material not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point all as specified. 19 Cum
22 15 Returning, filling, including spreading, levelling, watering and well ramming in layer not exceeding 25 cm thick. 42 Cum
23 16 Supply and filling Dry sand for cushioning in substatins / cables in trenches including spreading, levelling, hand punning complete all as specified and directed. 12.15 Cum
24 17 Supply and laying un reinforced precase concrete cable cover, class HV, type 1, flat size 300 x 180 x 40 mm for protection of HT cable including taking down unserviceable cable cover complete all as specified and directed. 833 Each
25 18 Material and Labour for cutting existing BT road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and directed 10 RM
26 19 Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paint over a coat of primer complete all as specified and directed.\n 6 Each Job
27 20 All as per Item No: 19 above but four pole structure\nMake of Paint for item No. 19 & 20 : Asian/Nerolac/Berger 10 Each Job
28 21 Labour for cutting the bushes and plants grown near the substation/ structures premises using necessary tools and plants and removing the plants from the root level at any depth and cleaning the premises completely and making good the site suitable for spreading the stone aggregate including disposing all the waste to a distance not exc 50M form the site all as directed. 1800 SQM
29 22 M&L 11KV grade pin type, composite polymeric insulator insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer conforming IS- 61109 including all galvanised steel disc fittings as required at site and removing of unserviceable insulators complete all as specified and directed. \nMake :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board 90 Each
30 23 M&L for LT line zig zag PVC spacer including replacing the broken u/s spacers and necessary ladder arrangement should be made by the contractor during replacing as required at site. 30 Each
31 24 M&L in replacement horn gap fuse assembly mounted on porcelan insulator and steel frame, D or Channel type for HT 11 KV, 400Amps rated current including base frame made with 'C' channel cross arms of suitable size shall be robust enough to sustain the various stresses encountered during all operational conditions of the cutout and necessary reconnecting all the wires/cables etc including removing the unserviceable drop out fuse assembly complete all as specified. Note: Fuse assembly for three phases will be considered as one Set. 2 Set of 3
32 25 M&L in replacement of Lightning arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp connecting to the earth strip including necessary fixing spares as required at site all as specified and directed. Note: A set of three lightening arresters will be considered as one set\n 2 Per Set
33 26 Repairs to AB switch (GOD) including replacement of male and female contacts, bolts & nuts and cleaning the carbon/ dust deposited on the switch contact surfaces and applying mineral jelly, oil grease to the moving/rotating parts etc after cleaning, removing carbon deposits including testing and commissioning the same for operation complete all as directed by Engr-in-charge. Note: The repairs to three poles of AB switch will be measured as on job.\n 20 Each Job
34 27 M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground ( earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip of 25x4mm (upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5, connected to earthing test point all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8 mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 40 mm dia GI light grade pipe for earth lead protection, 20 mm dia GI light grade pipe for watering , water funnel, testing point etc., including removing old earthing complete all as specified and testing on completion. 6 Each Job
35 28 Supply & Fix galvanised iron strip of 32 x 6mm on wall/trench including removing old strip as specified and directed.. 100 RM
36 29 S&F in repairs FRP V cross arms of 11000 volts grade conforming REC specifications pin insulator holes 22 mm dia at centre including necessary fixing spares like D/round MS clamps of thickness not less than 4mm as required at site and removing the old damaged cross arms all as directed . Make:Sintex/Rashtriya Electrical corp./Denson or as approved by the GE. 90 Each
37 30 Material and labour for locating UG cable fault through high voltage UG cable testing van through TSSPDCL or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-in-Charge. 3 Each Job
38 31 Material and labour for tracing the cable route using ultra sonic cable route locator of any HT/LT UG cables complete all as specified and directed. 200 RM
39 32 M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination cold shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed. 5 Nos
40 33 M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination cold shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed. 5 Nos
41 34 M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination cold shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed. 5 Nos
42 35 M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination cold shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed. 5 Nos
43 36 M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. 4 Each
44 37 M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm. 4 Each
45 38 Supply, fixing, testing and commissioning of automatic power corrector panel 100 KVAR in steps of (25KVAR- 2 No's (variable), 10 KVAR- 4 No's (variable) and 5 KVAR -2 No's. (fixed)) Indoor type fabricated with 2 mm thick CRCA sheet powder coated including cost of MCCB 250 Amps, 4 pole with rupturing capacity 35/36 KA-01 No. (incoming) and providing suitable contactors, relays, micro processed based 8 stage APFC relay auto/manual mode with backup TP/SP MCB's on each capacitor banks, Ammeter, Voltmeter , selector switch, CT's, duly internal wired with suitable size bus bar 3 Phase and neutral along with capacitor duty contactors, MPP capacitors, Capacitor panel shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels, nut, bolts, washers, etc and making connection with suitable size of XLPE LT cable and shall be powder coated including taking out old panel complete all as specified and directed.\nMake for Panel board: CPRI Approved manufacturer\nMake of MCCB/MCB :- Havells/L&T/Legrand/C&S/.\nMake of Capacitor :- Seimens/L&T/EPCOS.\nMake of Relays:- L&T/ABB/Seimens/EPCOS.\n 1 Each
46 39 Supply & Fix 25 KVAR power capacitor, type MPP, 415/440V,50HZ, 3ph including removing unserviceable power capacitor complete all as specified 4 Each
47 40 All as per Item No: 39 above but of capacity 20 KVAR 6 Each
48 41 All as per Item No: 39 above but of capacity 15 KVAR 6 Each
49 42 All as per Item No: 39 above but of capacity 10 KVAR 8 Each
50 43 Ditto as per Item No: 39 above but of capacity 05 KVAR \nMake for Item No: 39 to 43 : L&T/ Havells/Neptune 10 Each
51 44 Supply & Fix capacitor duty Contactors, 415 volts Suitable for 25 KVAR capacitor including removing the old unserviceable item all as specified and directed. 6 Each
52 45 All as per Item No 44 above but suitable to 20KVAR Capacitor 4 Each
53 46 All as per Item No 44 above but suitable to 15KVAR Capacitor 10 Each
54 47 All as per Item No 44 above but suitable to 10KVAR Capacitor 4 Each
55 48 All as per Item No 44 above but suitable to 05KVAR Capacitor 4 Each
56 49 Supply & Fix Control relay (Auxilary contactor), 4amps, 415 volts complete including removing unserviceable item all as specidied and directed. 4 Each
57 50 Supply & Fix Auxilary Contact bolck (1NO + 1NC) for contactor complete including removing unserviceable item all as speicified and directed. 4 Each
58 51 Supply & Fix HRC fuse Link 20 amps complete including removing unserviceable item all as speicified and directed. 20 Each
59 52 Supply & Fix in repairs Cylindrical fuse 415 volts 6 amps 10 Each
60 53 Supply & Fix APFC Relay 8 stage type complete with testing inlcuding removing the unserviceable item.\nMake : L&T/EPCOS/ Havells/ Neptune 6 Each
61 54 Supply & Fix Digital type Power factor meter 3Phase (multi function meter) suitable to existing size and modifications to existing panel complete with testing including removing the unserviceable item. \nMake : L&T/EPCOS/ Havells/ Neptune 4 Each
62 55 Supply & Fix current transformer 400/5A to 800/5A Class 1, VA 15 50Hz complete including removing unserviceable item all as specified and directed.\nMake : Kappa/L&T/C&S 6 Each
63 56 M&L Programming the existing APFC relay 8 stage and testing control wiring, capacitors, contactors, MCB complete capacitor bank panel all as specified and directed. 10 Job
64 57 M&L for repairs to LT Panel board, fabricating, brazing/welding , hinges, locking arrangenent supports, of any size as directed including nuts, bolts, washers welding, bending, cold or hot, drilling holes for bolts in any shape or size as directed. 10 Job
65 58 M&L for alteration of existing LT panel MCCB slots suitalbe for new MCCB as per site requirement complete all as specified and directed. 50 Job
66 59 Supply and fix inreplacement of MCB single pole 6-32 Amps working on 240 volts, 50 HZ AC, 10 KA 'C' curve all as specified and directed.\nMake: Legrand/C&S/L&T 10 Each
67 60 S&F in replacement of MCB SPN 32-40 Amps working on 240 volts, 50 HZ AC, 10 KA 'C' curve all as specified and directed. \nMake: Legrand/C&S/L&T 10 Each
68 61 S&F in replacement of MCB TP 40 Amps working on 415 volts, 50 HZ AC, 10 KA ,'C' curve all as specified and directed. \nMake: Legrand/C&S/L&T 50 Each
69 62 S&F in replacement of MCB TP 63 Amps working on 415 volts, 50 HZ AC, 10 KA ,'C' curve all as specified and directed. \nMake: Legrand/C&S/L&T 32 Each
70 63 M&L for testing APFC panel of capacity 100 KVAR to 400 KVAR of any make and model from the existing position, carrying out servicing, overhauling of the same, cleaning the unit thoroughly with carbon tetrachloride, checking of the contactors, relays, micro processed based 8 stage APFC relay auto/manual mode with backup TP/SP MCB's on each capacitor banks, Ammeter, Voltmeter , selector switch, CT's, duly internal wired and neutral entire components for proper function and circuit wiring complete reconnecting back and testing complete all as specified and directed. 20 JOB
71 64 Supply & Fix in repairs cable lugs of size 300 to 400 sqmm complete all as specified and directed. 90 Each
72 65 Supply & Fix in repairs cable lugs of size 185 to 240 sqmm complete all as specified and directed. 85 Each
73 66 Supply & Fix in repairs cable lugs of size 120 to 150 sqmm complete all as specified and directed. 80 Each
74 67 Supply & Fix in repairs cable lugs of size 70 to 90 sqmm complete all as specified and directed. 100 Each
75 68 Supply & Fix in repairs cable lugs of size 35 to 50 sqmm complete all as specified and directed. 75 Each
76 69 Supply & Fix in repairs cable lugs of size 16 to 25 sqmm complete all as specified and directed. 95 Each
77 70 Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paint complete all as specified and directed.\n 8 Each Job
78 71 All as per Item No: 70 above but four pole structure\nMake of Paint for item No. 70 & 71 : Asian/Nerolac/Berger 12 Each Job
79 72 S&F in repairs ISMC Cross arms for LT conductors, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending ,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as directed. 0.5 Per Qtl
80 73 S&F in repairs galvanised steel earth wire of 4mm dia on the over head LT pole with the help of aluminium tapes/craddles binding wire and necessary clamps for fixing the earth wire, providing the required sag for avoiding tension in earth wire complete all as directed. 400 RM
81 74 M&L for PCC 1:2:4, type B-1 (using 20 mm graded stone aggregate) as in coping of pole including form work for street light poles including demolition of old coping complete all as directed. 35 Cum
82 75 Supply and Fix colour coded PVC sleeves heat shrink (RYB) complete all as specified and directed. 20 RM
83 76 M&L in repairs stay assembly complete with accessories as shown in electrical plate no 1 including loop type isolator stay clamps stay strands excavation work and PCC work complete all as specified and directed. 4 Each