Special Repair/Replacement Of Manual Street Light Switch To Automated Sensor Based Street Light Switch And Connected Items In Saa , Apfc Panel/Capacitor Bank At Bihuguri And 155Bh And Replacement Of Old Unsv Ci Pipe Into Di Pipe From Zone 1 Pump House To, GE South Tezpur-Assam

Military Engineer Services-MES has published Special Repair/Replacement Of Manual Street Light Switch To Automated Sensor Based Street Light Switch And Connected Items In Saa , Apfc Panel/Capacitor Bank At Bihuguri And 155Bh And Replacement Of Old Unsv Ci Pipe Into Di Pipe From Zone 1 Pump House To. Submission Date for this Tender is 28-05-2021. Switch Supply Tenders in GE South Tezpur Assam. Bidders can get complete Tender details and download the document.




Tender Notice

27899891
Corrigendum : Special Repair/Replacement Of Manual Street Light Switch To Automated Sensor Based Street Light Switch And Connected Items In Saa , Apfc Panel/Capacitor Bank At Bihuguri And 155Bh And Replacement Of Old Unsv Ci Pipe Into Di Pipe From Zone 1 Pump House To
Open Tender
Indian
Assam
GE South Tezpur
28-05-2021

Tender Details

Special Repair / Replacement Of Manual Street Light Switch To Automated Sensor Based Street Light Switch And Connected Items In Saa , Apfc Panel / Capacitor Bank At Bihuguri And 155Bh And Replacement Of Old Unsv Ci Pipe Into Di Pipe From Zone 1 Pump House

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-May-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-05-2021
2 28-May-2021 Amdt Other 28-05-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 70480.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: SPL REPAIR/REPLACEMENT OF MANUAL STREET LIGHT SWITCH TO AUTOMATED SENSOR BASED STREET LIGHT SWITCH AND CONNECTED ITEMS IN SAA, APFC PANEL/CAPACITOR BANK AT BIHUGURI AND 155BH AND REPLACEMENT OF OLD UNSV CI PIPE INTO DI PIPE FROM ZONE 1 PUMP HOUSE TO ASSAM RIFLES B COY UNDER GE (S) TEZPUR (2ND CALL)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 M & L Earthing complete with GI earth plate electrode 60cmX60cmX6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connecting to galvanized earth strip 32 x 6 mm as earthing conductor by means of bolts, nuts, check nuts and washers of GI and all as shown in Electrical plate No.3 of SSR Part I and including testing on completion all as specified locations and as directed by the Engineer-in-Charge.\nNote: 1.The above quoted rate shall include cost of main earthing lead of 32 x 6mm GI earth strip, charcoal, salt, excavation and earth work in any type of soil CI cover, funnel with 20mm dia light grade GI water pipe including GI protection pipe 40mm dia light grade for earth strip etc. 2. The cost of earth pit is deemed to be included in the unit rate. 3. The cost of taking down old unsv earthing with all its accessories is deemed to be included in the unit price. 4 Each
2 2 S & F CPRI approved multi step Automatic Power Factor Correction (APFC) Panel indoor type by OEM for 3 Phase, double door, 415 V & 50 Hz system of capacity 80 KVAR (1x2KVAR+1x3KVAR+3x5KVAR + 2x 10 KVAR+2x20KVAR) with incoming MCCBs including Ammeter, voltmeter, phase indication lamps, PF Meter, necessary contactors, site selectable CT, Push button On/Off for separate capacitors, Auto/Manual Operation including taking down old unserviceable APFC panel including all its accessories complete all as specified and directed. The following are the items are to be included. Make- L&T/Havells . Note :- The cost of disconnection of existing cable and re-connecting with new panel if needed is deemed to be included in the unit price. 1 Each
3 3 S & F CPRI approved multi step Automatic Power Factor Correction (APFC) Panel indoor type by OEM for 3 Phase, double door, 415 V & 50 Hz system of capacity 30 KVAR (1x3KVAR +1x2KVAR + 3x5KVAR + 1x10KVAR), with incoming MCCBs including Ammeter, voltmeter, phase indication lamps, PF Meter, necessary contactors, site selectable CT, separate Push button On/Off for separate capacitors, Auto/Manual Operation including taking down old unserviceable APFC panel including all its accessories complete all as specified and directed. The following are the items are to be included. Make- L&T/Havells . Note :- The cost of disconnection of existing cable and re-connecting with new panel if needed is deemed to be included in the unit price. 2 Each
4 4 S & F CPRI approved multi step Automatic Power Factor Correction (APFC) Panel Outdoor type by OEM for 3 Phase, double door, 415 V & 50 Hz system of capacity 100 KVAR (1x2KVAR+1x3KVAR+3x5KVAR + 2x 10 KVAR+3x20KVAR) with incoming MCCBs including Ammeter, voltmeter, phase indication lamps, PF Meter, necessary contactors, site selectable CT, Push button On/Off for separate capacitors, Auto/Manual Operation including taking down old unserviceable APFC panel including all its accessories complete all as specified and directed. The following are the items are to be included. Make- L&T/Havells . Note :- The cost of disconnection of existing cable and re-connecting with new panel is deemed to be included in the unit price. 1 Each
5 5 M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, 3 core , cross-sectional area 50 sqmm laid in trenches complete all as specified and directed. 20 RM
6 6 Excavation in trenches n.exc 1.5 mtr wide and n exc 1.5 mtr in depth and getting out in soft/ loose soil for laying cables / GI pipe, foundation of pole, stay etc complete all as specified and as directed by Engr - in - Charge. 209.09 Cum
7 7 Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25 cm in soft/loose soil complete all as specified and as directed by Engr - in - Charge. 291.23 Cum
8 8 Removing surplus excavated soil n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed by Engr - in - Charge. 146.44 Cum
9 9 Material and labour sand filling in trenches with clean dry unwashed sand for cushioning of under ground cable complete all as specified and as directed by Engr - in - Charge.\nNote : Punned thickness of sand will be measured. 47.3 Cum
10 10 M&L for sub class 'B' brick for protection of UG cable in tranches of old size brick all as specified and directed by Engineer-in-charge. 5.079 Per 1000 Nos
11 11 Taking down unserviceable Main Switch/MCB of any capacity complete all as specified and directed 30 Each
12 12 Taking down unserviceable cable of any size and type complete all as specified and directed 620 RM
13 13 Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel striop or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 25 sq mm 3.5 core. 120 RM
14 14 All as per item no 13 above but 25 sqmm 2 core. 500 RM
15 15 Supply and fixing of Automatic street light control switch Panel complete with:\n(a) Infrared sensor based Nature Switch for automatic switching of street lights. Nature switch operation should be based on Natural light Lux level. Required illuminance level for switching ON is less or equal to 30 Lux and for switching OFF 10 Lux. The sensor should also have part night operation facility of minimum 4 hrs to maximum 12 hrs. - 01 No.\nMake Of Sensor: Kakatiya Energy System/Bajaj/Healer.\n(b) Power contactor single phase, 230 volts, 63 Amp capacity, confirming to IEC-60947-4-1. - 01 No.\nMake:- BCH/L&T/Schneider.\n(c) The sensor along with suitable power contactor and incoming outgoing MCBs should be enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof and FR grade Thermoplastic polycarbonate enclosure (with hinged lid) confirming to IP66 protection class 2 of swuitable size to accomodate all panel accessories. -01 Job.\nMake:- Hensel/Syntex \n(d) MCB SP 63 Amp, B Curve, Confirming to IEC-60898/IS8828. -02 Nos.\nMake: Hager/Schneider/L&T.\n(e) All control cable wiring inside the panel should be of copper conductor, multistranded, PVC insulated, FRLS, 1100 volts grade, of size 10 sq mm, single core, followed by colour coding and lugs/thimbles.\nMake: Finolex/Polycab/Plaza.\n(f) All equipments are mounted on suitable size insulators.\nMake Of Complete Panel: Healer Enterprises, Model No: Swadeep-66-8KW1P\n 25 Each
16 16 Supply and fixing of Automatic street light control switch Panel complete with:\n(a) Infrared sensor based Nature Switch for automatic switching of street lights. Nature switch operation should be based on Natural light Lux level. Required illuminance level for switching ON is less or equal to 30 Lux and for switching OFF 10 Lux. The sensor should also have part night operation facility of minimum 4 hrs to maximum 12 hrs. - 01 No.\nMake Of Sensor: Kakatiya Energy System/Bajaj/Healer.\n(b) Power contactor single phase, 230 volts, 40 Amp capacity, confirming to IEC-60947-4-1. - 03 No.\nMake:- BCH/L&T/Schneider.\n(c) The sensor along with suitable power contactor and incoming outgoing MCBs should be enclosed in a pole/ wall mountable rust proof, electric shock proof, termite proof and FR grade Thermoplastic polycarbonate enclosure (with hinged lid) confirming to IP66 protection class 2 of swuitable size to accomodate all panel accessories. -01 Job.\nMake:- Hensel/Syntex \n(d) MCB TPN 40 Amp, B Curve, Confirming to IEC-60898/IS8828. -02 Nos.\nMake: Hager/Schneider/L&T.\n(e) All control cable wiring inside the panel should be of copper conductor, multistranded, PVC insulated, FRLS, 1100 volts grade, of size 10 sq mm, single core, followed by colour coding and lugs/thimbles.\nMake: Finolex/Polycab/Plaza.\nf) All equipments are mounted on suitable size insulators.\nMake Of Complete Panel: Healer Enterprises, Model No: Swadeep-66-8KW3P.\n 5 Each
17 17 Dismantling and taking out from trenches the existing old u/s CI pipe with spigot and socketed ends and lead joints including burning out joints and recovering lead etc. including all fittings such as bends, elbow and Tees etc. of following sizes complete all as specified and directed. (Note: Excavation and earth work will be measured and paid for separately) (a) 150 mm Bore 250 RM
18 18 All as per item No-17 but 100 mm Bore 950 RM
19 19 Supply, laying, jointing and testing ductile iron pipes of 150 mm inner diameter with Spigot and Socket ends , Class K7 including rubber tyton gasket joints in any length, ISI Marked (IS 8329 : 2000) laid in trenches complete all as specified and directed. 250 RM
20 20 All asitem No-19 but 100 mm dia 950 RM
21 21 Boring under roads/paths suitable for passing the 150mm /100 mm /80 mm bore CI /DI pipe including making arrangement necessaru T&P as required,. 30 RM
22 22 Demolation of broken valve chamber of any size/type including PCC foundation and angle iron frame with cover complete all as spacified and as directed by Engr-in-Charge 9 Each Job
23 23 Material & labour for construction of brick missionary valve pit of size 1000x1000x900mm (internal dimension) with frame of angle iron and MS sheet cover 3 mm thick and locking arrangements duly painted with two coats of synthetic enamel paint over a coat of red oxide primer including dismantling and removal of existing broken MS frame and cover etc. complete all as specified and shown in drawing. 6 Each
24 24 Construction of brick masonary valve pit in replacement of size 90X90X90 CM ( internal size) type A for sluice valave complete all as specified and shown on drawings including MS cover 3 mm thick including locaking arrangement and 40x40x6 mm angle iron frame duly painted with two coats of sythetic enamel paint over a coat of red oxide primer including necessary earthwork , material and labour complete all as specified and shown in drawing. 4 Each
25 25 Construction of brick masonary valve pit in replacement of size 60X60X60 CM ( internal size) type A for gate valave 50/40/25 mm dia complete all as specified and shown on drawings including MS cover 3 mm thick including locaking arrangement and 40x40x6 mm angle iron frame duly painted with two coats of sythetic enamel paint over a coat of red oxide primer including necessary earthwork , material and labourcomplete all as specified and shown in drawing. 2 Each
26 26 M&L for flanged joint suitable for 150 mm dia CI pipe and fittings joints with rubber fiber board gasket complete all as specified. 10 Each
27 27 M&L for flanged joint suitable for 100 mm dia CI pipe and fittings joints with rubber fiber board gasket complete all as specified. 12 Each
28 28 M&L for run lead joint suitable for 150 mm dia CI pipe and fittings joints complete all as specified. 15 Each
29 29 M&L for run lead joint suitable for 100 mm dia CI pipe and fittings joints complete all as specified. 20 Each
30 30 100 mm thick PCC 1:3:6 type C-2 using 40 mm graded crused stone aggregate as in floor finishes including finishing the surface even and smooth without using extra cement complete all as specified and directed by Engr-in - charge 18 Sqm
31 31 Supply and fix, mild steel clamp suitable for DI pipe line 150 mm dia made out from mild steel flat 40 x 6 mm thick, bend to shape and drilling hole two nos for providing bolt of size not less than 20 mm dia complete all as specified and directed. 13 Each
32 32 Supply & fixed in repairs straight plain brass ferrules of 20 mm dia bore (or connecting screw) of following sizes, screwed both ends complete all as specified and directed. 15 Each
33 33 Supply & fix, Ductile cast iron bends in replacement ( of any size any radius and any angle) taper any type straight, bend increasing and decreasing or double socket etc, Tee pieces single branch piece, Y pieces double branch piece, cross piece tail , collers, caps ,plugs etc socketed or flanged conforming to IS 1538 laid in tenches or on surface( excavation earthwork , lead joints and flanged joints shall be measured and paid for separately) Fittings shall be of size upto 200 mm bore Make:Tata/Jindal/Electrosteel. 250 Kgs
34 34 Dismantling and taking out from trenches/wall the existing old u/s GI/PPR pipe including all fittings such as bends, elbow and Tees etc. of following sizes complete all as specified and directed. (a) 20 mm bore 100 RM
35 35 All as per item No-34 but 25 mm bore 70 RM
36 36 Provision of over flow pipe in exisiting OH building tank of supply, laying, jointing and testing GI Pipe medium grade inclusive of all fittings such as bends, Tee, union, elbow, reducer and Socketed etc. ISI marked of following sizes complete all as specified and directed. (Note: Excavation and earth work will be measured and paid for separately) (a) 20 mm bore 1000 RM
37 37 All as per item No-36 but 25 mm bore 90 RM
38 38 Material and labour for Dismantling of existing sluice valve of size 150mm dia and repair by in replacement including taking down old sluice valve CI body with Gun metal/Steel spindle with hand operated iron wheel both ends flanged and drilled including ring, nuts, bolts class PN 1.6 conforming to IS 14846-2000. ISI Marked of following sizes complete all as specified and directed. by Engr-in charge 5 Each Job
39 39 All as per item No-38 but for 100 mm dia. Note 1:-The contract sum shall be arrieved at after deducting amount of schedule of credit from the total quated amount. Note 2-Contractor's supervisor and main worker would wear shirt/T-shirt of colour sky blue/brown/yellow preferable embosed with contractor's firm name while carriying out any activities in defence area for better check of security purpose.\n 8 Each Job
Disclaimer :