Repair , Replacement And Maintenance Of Unserviceable Lt Equipment/Control Gear , Lt Panel And Connectd Works For External Electric Supply In Domestic Area At Af Stn Gurgaon Under Ge P Af Gurgaon, GE (P) AF Gurgaon-Haryana

Military Engineer Services-MES has published Repair , Replacement And Maintenance Of Unserviceable Lt Equipment/Control Gear , Lt Panel And Connectd Works For External Electric Supply In Domestic Area At Af Stn Gurgaon Under Ge P Af Gurgaon. Submission Date for this Tender is 29-05-2021. Bolts Tenders in GE (P) AF Gurgaon Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

27797547
Corrigendum : Repair , Replacement And Maintenance Of Unserviceable Lt Equipment/Control Gear , Lt Panel And Connectd Works For External Electric Supply In Domestic Area At Af Stn Gurgaon Under Ge P Af Gurgaon
Open Tender
Indian
Haryana
GE (P) AF Gurgaon
29-05-2021

Tender Details

Repair , Replacement And Maintenance Of Unserviceable Lt Equipment / Control Gear , Lt Panel And Connectd Works For External Electric Supply In Domestic Area At Af Stn Gurgaon Under Ge P Af Gurgaon - 2 Taking Out Old Serviceable / Unserviceable Under Ground Cable Of Following Sizes From Trenches / Poles / Pipe / Floor 16 Sqmm 3.5 / 4 Core To 35 Sqmm 3.5 / 4 Core . 3 Taking Out Old Serviceable / Unserviceable Under Ground Cable Of Following Sizes From Trenches / Poles / Pipe / Floor 50 Sqmm 3.5 / 4 Core To 120 Sqmm 3.5 / 4 Core. 4 Taking Out Old Serviceable / Unserviceable Under Ground Cable Of Following Sizes From Trenches / Poles / Pipe / Floor 185 Sqmm 3.5 / 4 Core To 240 Sqmm 3.5 / 4 Core. 5 Supplying , Laying , Passing Through Pipe , Connecting And Testing Ug Cable Xlpe Insulated , Armoured Heavy Duty Electric Cable With Aluminium Conductor , 1100 Volts Grade Of Following Size ( Note:- Excavation & Earthwork Etc Shall Be Measured And Paid Sepretaly ) All As Specified And As Directed By Engr-In-Charge:- 6 Xlpe Cable Of Size 16 Sqmm, 4 Core . 7 Xlpe Cable Of Size 25 Sqmm, 3½ Core . 8 Xlpe Cable Of Size 35 Sqmm, 3½ Core . 9 Xlpe Cable Of Size 50 Sqmm, 3½ Core . 10 Xlpe Cable Of Size 70 Sqmm, 3½ Core . 11 Xlpe Cable Of Size 95 Sqmm, 3½ Core . 12 Xlpe Cable Of Size 120 Sqmm, 3½ Core . 13 Xlpe Cable Of Size 185 Sqmm, 3½ Core . 14 Xlpe Cable Of Size 240 Sqmm, 3½ Core . 15 Excavation In Trenches In Soft / Loose Soil , Not.Exc 1.5 Mtr Wide And Not.Exc 1.5 Mtr Deep And Getting Out In Soft / Loose Soil For Laying Of Cable / Foundation Of Pole And Stay Etc In Complete As Sepecified And Directed By Engr-In-Charge. 16 Removing Excavated Materials Not Exceeding 50 Mtr And Depositing Where Directed At A Level Not Exceeding 1.5 Mtr Above Ground Level From Starting Point Complete As Sepecified And Directed By Engr-In-Charge. 17 Returning Filling Including Spreading, Levelling, Watering And Well Ramming In Layers N.Exc 25 Cm Complete As Sepecified And Directed By Engr-In-Charge. 18 M&L For Sand Cushioning In Trenches For Protection Of Lt Under Ground Cable Including Punning And Consolidation Complete As Sepecified And Directed By Engr-In-Charge. 19 Supply And Laying Well Burnt Sub Class ‘B’ Bricks, Locally Available In Trenches For Protection Of Underground Cable Complete As Sepecified And Directed By Engr-In-Charge. 20 M&L For Drilling Hole Under Hard Standing / Road In Different Location As Per Site Requirement ( Between 03 Mtr To 12Mtr Maximum ) For Laying Of Pipe For Protection Of Cable Etc By Means Of Mannual Bookle And Without Disturbing The Top Surface And Making Good The Disturbed Surface If Any Complete As Sepecified And Directed By Engr-In-Charge. 21 Supply And Laying Gi Tube Medium Grade 80 Mm Bore, Isi Marked Complete As Sepecified And Directed By Engr-In-Charge. 22 All As Per Item No 11 Here-In-Before But 40 Mm Bore. 23 M&L In Repair For Heat Shrinkable Jointing Kit Including Suitable Size Of Connector Complete All As Per Directed By Engr-In-Charge. Note : Cost Of Necessary Excavation And Earth Work , Labour, Jointing Kit Complete, Fixing Charges & T&P Including Removing Of Grass / Shrubs Nearby The Fault Location Shall Be Deemed To Include In Quoted Rates ) For The Following Sizes :- 24 Xlpe Cable Of Size 25 Sqmm To 50 Sqmm X 3.5 / 4 Core. 25 Xlpe Cable Of Size 70 Sqmm To 120 Sqmm X 3.5 / 4 Core. 26 Xlpe Cable Of Size 180 Sqmm To 240 Sqmm X 3.5 / 4 Core. 27 Supply And Fixing Aluminium Thimble , Cable Gland And Lux After Disconnecting From Panel And Taking Down Burnt Cable From Panel Of Different Location And Cutting Out The Burnt Portion Of Cable And Extended The Cable From Cable Loop, Preparation Of Cable Including Necessary Connection And Testing Complete ( Note : ( I ) 01 Job Consisting Of 04 Nos Lugs / Thimble At One End Of Cable ( Ii ) Rate Of Necessary Earth Work For Opening Of Loop If Requried At Site Are Deemed To Be Included In The Quoted Rate. ) Of Following Sizes :- 28 16 Sqmm 4 Core 1100 Volt Grade. 29 25 Sqmm 3.5 Core 1100 Volt Grade. 30 35 Sqmm 3.5 Core 1100 Volt Grade. 31 50 Sqmm 3.5 Core 1100 Volt Grade. 32 120 Sqmm 3.5 Core 1100 Volt Grade. 33 180 Sqmm 3.5 Core 1100 Volt Grade. 34 240 Sqmm 3.5 Core 1100 Volt Grade. 35 M&L For Load Balancing Of Single / Three Phase System At Lt Panel Upto Distribution Box Of Any Size And Capacity Complete Including Disconnecting Of Existing Cables And Refixing The Same As Per Load Balance Requirement Including Replacement Of Burnt / Carbonized Aluminium Tube Terminal Of Any Size And Capacity All As Specified And As Directed By Engr-In-Charge.Note : ( I ) Necessary Eqpt And Safety Mesures Reqd For Load Balancing Arranged By The Contractor Without Any Extra Cost. ( Ii ) Cost Of New Aluminium Tube Terminal Of Any Size As Per Site Reqmt Change Under The Job Deemed To Be Included In The Quoted Rate ( Iii ) Contractor Shall Also Submit The Written Record Of Phase Wise Electric Load On Panels / Transformer Duly Signed By Contractor, Je & Age. 36 M&L For Lt Insulator Shackle Type Porceline , Vitreous, White , Brown Or Green Insulator Including One Galvanised Mild Steel Straps , Washers , Insulator Bolts For 1100 Volts 100 Mm Height , 115 Mm Dia Complete All As Specified And Directed By Engr-In-Charge. 37 M&L For Lt Pin Type Porceline , Vitreous, White , Brown Or Green Insulator Including One Galvanised Mild Steel Spindal , Washers , Two Galvanised Iron Washers And One Galvanised Iron Nut 100 Mm Height , 65 Mm Dia For 1100 Volts Complete All As Specified And Directed By Engr-In-Charge. 38 S&F In Replacement Lt Volt Meter ( 0-500 ) Digital Squire Flush Type Of Size 96X96 Mm Including Necessary Addition / Alternation Of Panel Including Cutting / Welding Of Front Side Of Panel Board / Feeder To Match The Existing Panel Board / Feeder Including Taking Out Of Unserviceable Volt Meter Complete As Sepecified And Directed By Engr-In-Charge. 39 S&F In Replacement 1100 Volts Grade Lt Ammeter ( 0 - 300 A ) Digital Squire Flush & Ct Type With Cts Including Necessary Addition / Alternation Of Panel Including Cutting / Welding Of Front Side Of Panel Board / Feeder To Match The Existing Panel Board / Feeder Taking Out Of Unserviceable Ammeter Complete As Sepecified And Directed By Engr-In-Charge. 40 S&F In Replacement 1100 Volts Grade Lt Ammeter ( 0 - 500 A ) Digital Squire Flush & Ct Type With Cts Including Necessary Addition / Alternation Of Panel Including Cutting / Welding Of Front Side Of Panel Board / Feeder To Match The Existing Panel Board / Feeder Taking Out Of Unserviceable Ammeter Complete As Sepecified And Directed By Engr-In-Charge. 41 M&L For Spray Painting To Lt Panel Board With Synthetic Enamel High Glow Paint Ist Grade Including Preparation / Cleaning Of Steel Surfaces. Complete As Sepecified And Directed By Engr-In-Charge. 42 S&F In Replacement Of Mccbs Thermal Meganitic Including Necessery Fixing Arrengement & Tasting Complete All As Sepecified And As Directed By Engr-In-Charge Of Following Sizes:- 43 ( A ) 100 Amps 4 Pole Breaking Capasity 35 / 36 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.420245 Or Equivalent Out Of Makes Specified In Ist Of Makes. 44 ( B ) 160 Amps 4 Pole Breaking Capasity 35 / 36 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.420247 Or Equivalent Out Of Makes Specified In Ist Of Makes. 45 ( C ) 200 Amps 4 Pole Breaking Capasity 35 / 36 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.420218 Or Equivalent Out Of Makes Specified In Ist Of Makes. 46 ( D ) 200 Amps 4 Pole Breaking Capasity 50 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.420278 Or Equivalent Out Of Makes Specified In Ist Of Makes. 47 ( E ) 250 Amps 4 Pole Breaking Capasity 50 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.420279 Or Equivalent Out Of Makes Specified In Ist Of Makes. 48 ( F ) 400 Amps 4 Pole Breaking Capasity 50 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.422021 Or Equivalent Out Of Makes Specified In Ist Of Makes. 49 ( G ) 630 Amps 4 Pole Breaking Capasity 50 Ka Complete All As Sepecified And As Directed By Engr-In-Charge. Make :Legrand Cat Part No.422023 Or Equivalent Out Of Makes Specified In Ist Of Makes. 50 M&L For Detecting Of Fault In 1100 Volt Cable Of Any Size Upto 400 Sqmm 3.5 Core Laid In Trenc Fault Locating Machine Comprising Of Surg Generator Pulse, Echo Fault Locator With High Frequency Distance Calculator Etc And Exposing The Cable Fault, Removal Of Deteriated Portion Of Cable , Treating Of Cable And Making The Same Ready For Jointing Work Complete All As Specified And Directed By Engr-In-Charge. 51 Taking Down Existing Old Lt Panel Board / Lt Feeder Pillar Box Comprising Of Mccb & Switch Fuse Unit Of Any Capacity And Size Including Bus Bar , Ammeters, Voltmeters Etc After Disconnecting All Cable Connection And Removing From Site Complete All As Directed. 52 Supply, Install, Commissioning And Testing Of Lt Panel Board Double Door Outdoor Type Floor Mounted Of Factory Made Powder Coated Made Out Of Outside Body Of 3.15Mm Thick Steel Sheet And Inside Body 14 Gauge Steel Sheet, Locking Arrangement, Front Side And Rear Side Opening Arrangement Of Suitable Size, Incl Mounted On Angle Iron Stand Of Size 50X50x6mm Having Minimum Height 1.5 Feet Duly Grouted Or Welded On Floor Including Pcc 1:2:4 Fdn Base Complete As Per Manufacturers Instruction, Aluminium Bus Bar Tpn Of 630A For Mccb To All Feeders Including Provn Of Following Items:- ( A )     Incoming Mccb 630 Amp 50 Ka 4Pole-01 No ( B )    Outgoing Mccb 200 Amp 35 / 36 Ka 4Pole -03 No ( C )    Outgoing Mccb 160 Amp 35 / 36 Ka 4Pole -02 No ( D ) Change Over Switch 400 Amp Tpn-01 No ( E )     Ryb Indication For Each Incoming & Outgoing Supplies-01 Set ( F )     Digital Voltmeter, Amp Meter, With Ct’S & Selector Switch-01 Set ( G )     Termination Of All Cables With Suitable Size Thimble And Glands-1 Job. ( H ) Pcc 1:2:4 Type B-1 300X300x500mm Fdn Block To Four Legs Incl Earth Work. 53 Supply, Install, Commissioning And Testing Of Lt Panel Board Double Door Outdoor Type Floor Mounted Of Factory Made Powder Coated Made Out Of Outside Body Of 3.15Mm Thick Steel Sheet And Inside Body 14 Gauge Steel Sheet, Locking Arrangement, Front Side And Rear Side Opening Arrangement Of Suitable Size, Incl Mounted On Angle Iron Stand Of Size 50X50x6mm Having Minimum Height 1.5 Feet Duly Grouted Or Welded On Floor Including Pcc 1:2:4 Fdn Base Complete As Per Manufacturers Instruction, Aluminium Bus Bar Tpn Of 400A For Mccb To All Feeders Including Provn Of Following Items:- ( A )     Incoming Mccb 200 Amp 35 / 36 Ka 4Pole-01 No ( B )    Outgoing Mccb 100 Amp 35 / 36 Ka 4Pole -02 No ( C )    Outgoing Mccb 63 Amp 35 / 36 Ka 4Pole -01 No ( D ) Change Over Switch 200 Amp Tpn-01 No ( E )     Ryb Indication For Each Incoming & Outgoing Supplies-01 Set ( F )     Digital Voltmeter, Amp Meter, With Ct’S & Selector Switch-01 Set ( G )     Termination Of All Cables With Suitable Size Thimble And Glands-1 Job. ( H ) Pcc 1:2:4 Type B-1 300X300x500mm Fdn Block To Four Legs Incl Earth Work. 54 Supply, Install, Commissioning And Testing Of Lt Panel Board Double Door Outdoor Type Floor Mounted Of Factory Made Powder Coated Made Out Of Outside Body Of 3.15Mm Thick Steel Sheet And Inside Body 14 Gauge Steel Sheet, Locking Arrangement, Front Side And Rear Side Opening Arrangement Of Suitable Size, Incl Mounted On Angle Iron Stand Of Size 50X50x6mm Having Minimum Height 1.5 Feet Duly Grouted Or Welded On Floor Including Pcc 1:2:4 Fdn Base Complete As Per Manufacturers Instruction, Aluminium Bus Bar Tpn Of 400A For Mccb To All Feeders Including Provn Of Following Items:- ( A )     Incoming Mccb 200 Amp 35 / 36 Ka 4Pole-01 No ( B )    Outgoing Mccb 100 Amp 35 / 36 Ka 4Pole -02 No ( C )    Outgoing Mccb 63 Amp 35 / 36 Ka 4Pole -02 No ( D ) Ryb Indication For Each Incoming & Outgoing Supplies-01 Set ( E )     Digital Voltmeter, Amp Meter, With Ct’S & Selector Switch-01 Set ( F )     Termination Of All Cables With Suitable Size Thimble And Glands-1 Job. ( G ) Pcc 1:2:4 Type B-1 300X300x500mm Fdn Block To Four Legs Incl Earth Work. 55 Earthing Complete With Galvanised Steel Earth Plate 600 X 600 X 6Mm Thick Buired Directly In Ground ( Earth Pit Not Less That 2.25Mtr Deep Below Ground Level ) With Top Edge Of The Plate Not Less Than 1.5Mr Below Normal Ground Level Connected To Galvanised Iron Strip Of Size 25 X 3Mm By Means Gi Welding After Tighten By Bolts, Nuts, Check Nuts And Washers From Earth Pit To Test Point With Protection Gi Pipe Of Size 40Mm Dia Light Grade And Providing Masonry Enclosure And Watering Pipe Of Dia 40Mm Including Wiremesh Steel Funnel, Including Watering Arrangement 200 Ltrs For Each Earth Pitcomplete As Specifed And Directed By Engr-In-Charge . Make Of Gi Pipe Is Prakash / Jindal ( Note : Gi Strip 7.5 Mtr Included In The Quoted Rate From Earth Pit To Test Point ) 56 Dismantling Of Old / Rusted Gi Wire / Strip Complete At Site From Shade / Building Upto 20Mtr Height Complete All As Specified And As Directed By Engr-In-Charge 57 M&L For Earth Continuity Conductor Or Main Earthing Lead Fixed To Wall On Batten Or Fixed On Wall Of The Building On Insulator Or Pvc Pipe Or Chases Or Buried In Ground Or Fixed To Poles Or Any Other Indicated Situation For Loop Earthing Etc As Required Of Size 20 X 3 Mm Copper Strip Complete All As Specified And Directed By Engr-In-Charge. 58 M&L For Repair Of Earthing Pit With Brick Work And Pcc 1:3:6 Including Rcc Pit Cover Of Size 300X300mmx50mm Thick With Provision Of Opening Handle Complete Including Necessary Watering, Ramming And Compact Of Soil Near The Earth Pit Complete All As Specified And As Directed By Engr-In-Charge. 59 Supplying And Fixing 1100 Volts Grade Heavy Duty Cable Pvc Insulated Aluminium Conductor , Served With Inner Sheathing Of Pvc Tape And Overall Pvc Sheathed In Service Connection Of Size 10 Sqmm 2 Core Including Taking Down Old Cable Complete All As Specified And As Directed By Engr-In-Charge. 60 M&L For Surface Dressing And Proper Laying Of Xlpe Electrical Cable Of Any Size And Capacity Nearby The Lt Panel After Disconnecting All Incoming And Outgoing Connection Complete Including Cleaning Of Grass Nearby The Lt Panel Upto 2Mtr All Around , Necessary Earthwork As Required All As Specified And As Directed By Engr-In-Charge. . ( Note : Rate Of Necessary Earthwork As Required At Site Are Deemed To Be Included In The Quoted Rate ) 61 Disposal Of Old Junk / Garbage Both Solid And Liquid Through Browser With Tactor With Minimum 3Cum Capacity And Disposal Out From Mod Land Maximum Distance 5 Km Complete All As Directed By Engr-In-Charge. 62 M&L In Repair For Prestressed Concrete Pole , 9 Mtr Long, 102 Mm X 172 Mm At Top And 12Mm X 279 Mm At Bottom Class 10 Complete Including Excavation & Earth Work, Pcc 1:4:8 Type-D-2 In Pole Fdn & Pcc 1:3:6 Type C-1 In Coping Of Pole Complete As Sepecified And Directed By Engr-In-Charge. 63 Supply Only Synthetic Insulating Mat Of Size 2Mx1mx10mm Thick Isi Marked Complete As Sepecified And Directed By Engr-In-Charge. 64 Supply Only Synthetic Insulating Mat Of Size 2Mx1mx12mm Thick Isi Marked Complete As Sepecified And Directed By Engr-In-Charge. 65 M&L For Re-Stringing Of Ascr Conductor Of Any Size / Dia By Removing Sag In Between The Line Including Disconnecting Acsr Conductor From Both Side To Overhead Line And Rejoining After Repair Work Complete All As Specified And Directed By Engr-In-Charge. 66 M&L For Providing Pvc Rigid Spacer For 4 / 5 Line Lt Overhead Line Complete All As Specified And Directed By Engr-In-Charge. 67 M&L For Chang Over Switch Of Capacity 250 Amps , 415 Volts , 4 Pole With Sheet Metal Inclosure Complete All As Specified And Directed By Engr-In-Charge. 68 M&L For Chang Over Switch Of Capacity 400 Amps , 415 Volts With Sheet Metal Inclosure Complete All As Specified And Directed By Engr-In-Charge. 69 M&L For Chang Over Switch Of Capacity 630 Amps , 415 Volts , 4 Pole With Sheet Metal Inclosure Complete All As Specified And Directed By Engr-In-Charge. 70 M&L For Chang Over Switch Of Capacity 100 Amps , 415 Volts, 4 Pole With Sheet Metal Inclosure Complete All As Specified And Directed By Engr-In-Charge. 71 M&L For Chang Over Switch Of Capacity 63 Amps , 415 Volts , 4 Pole With Sheet Metal Inclosure Complete All As Specified And Directed By Engr-In-Charge. 72 M&L For Side Handle Main Switch 3 Pole 415 Volt 200 Amp Complete All As Specified And Directed By Engr-In-Charge. Make - Havells / L&T / Abb. 73 M& L For Prunning Of Trees Over The Acsr Conductor And All E / M Installations Including Trimming Of Tree In The Radius Of 2.5 Mtr From Acsr Conductor And Its Disposal Complete All As Directed By The Engr-In-Charge In Consultation With Users. 74 Supply And Fixing In Replacement Of Stay Assembly Complete With 16Mm Dia Stay Rod Including Pcc 1:3:6 Type C-2 Complete All As Specified And As Directed By Engr-In-Charge. ( Excavation And Earth Work Measured And Paid Seperately ) . 75 S&F Danger Notice Plate Of 1.6 Mm Thick Mild Steel Sheet Vitreous Enamelled White With Letters, Figures And Conventional Skull And Bones In Signal Red Colour And Fixed With Ms Clamps, Bolts And Nuts Of Approved Siz, For Lt , 20X15 Cm Size Complete All As Specified And As Directed. 76 M&L For Preparation Of Old Painted Surface Of Electric Rcc Pole By Removing All Dirt, Dust Etc And Apply Approved Colour One Coat Of Syhnthetic Enemal Paint Upto 1.5 Mtr Height ( Five Layer 30 Cm Blue And 30 Cm White One Over Another ) And One Coat Of Synthetic Enamel Paint On Steel Surface Such As Cross Arm Including Writing Of Identification No , Etc Complete All As Specified And Directed.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-May-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 29-05-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 78000.0 /-
Tender Value
INR 39 Lakhs /-

BOQ Items

NAME OF WORK : REPAIR, REPLACEMENT AND MAINTENANCE OF UNSERVICEABLE LT EQUIPMENT/CONTROL GEAR, LT PANEL AND CONNECTD WORKS FOR EXTERNAL ELECTRIC SUPPLY IN DOMESTIC AREA AT AF STN GURGAON UNDER GE (P) AF GURGAON
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Schedule of Works
2 1.01 Taking out old serviceable /unserviceable under ground cable of following sizes from trenches/poles /pipe/floor 16 Sqmm 3.5/4 core to 35 Sqmm 3.5/4 core . BI01010001010000000000000515BI0100001115 370 RM
3 2 Taking out old serviceable /unserviceable under ground cable of following sizes from trenches/poles /pipe/floor 50 Sqmm 3.5/4 core to 120 sqmm 3.5/4 core. BI01010001010000000000000515BI0100001116 790 RM
4 3 Taking out old serviceable /unserviceable under ground cable of following sizes from trenches/poles /pipe/floor 185 Sqmm 3.5/4 core to 240 sqmm 3.5/4 core. BI01010001010000000000000515BI0100001117 260 RM
5 4 Supplying , laying , passing through pipe , connecting and testing UG cable XLPE insulated ,armoured heavy duty electric cable with aluminium conductor ,1100 volts grade of Following size (Note:- Excavation & earthwork etc shall be measured and paid sepretaly) all as specified and as directed by Engr-in-charge:- BI01010001010000000000000515BI0100001118
6 4.01 XLPE Cable of size 16 Sqmm, 4 Core . BI01010001010000000000000515BI0100001119 100 RM
7 4.02 XLPE Cable of size 25 Sqmm, 3½ Core . BI01010001010000000000000515BI0100001120 130 RM
8 4.03 XLPE Cable of size 35 Sqmm, 3½ Core . BI01010001010000000000000515BI0100001121 140 RM
9 4.04 XLPE Cable of size 50 Sqmm, 3½ Core . 180 RM
10 4.05 XLPE Cable of size 70 Sqmm, 3½ Core . 350 RM
11 4.06 XLPE Cable of size 95 Sqmm, 3½ Core . 160 RM
12 4.07 XLPE Cable of size 120 Sqmm, 3½ Core . 100 RM
13 4.08 XLPE Cable of size 185 Sqmm, 3½ Core . 150 RM
14 4.09 XLPE Cable of size 240 Sqmm, 3½ Core . 110 RM
15 5 Excavation in trenches in soft/loose soil , not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc in complete as sepecified and directed by Engr-in-Charge. 300 CUM
16 6 Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point complete as sepecified and directed by Engr-in-Charge. 180 CUM
17 7 Returning filling including spreading, levelling, watering and well ramming in layers n.exc 25 cm complete as sepecified and directed by Engr-in-Charge. 120 CUM
18 8 M&L for sand cushioning in trenches for protection of LT under ground cable including punning and consolidation complete as sepecified and directed by Engr-in-Charge. 90 CUM
19 9 Supply and laying well burnt sub class ‘B’ bricks, locally available in trenches for protection of underground cable complete as sepecified and directed by Engr-in-Charge. 8 1000 Nos
20 10 M&L for drilling hole under hard standing /road in different location as per site requirement (between 03 mtr to 12mtr maximum) for laying of pipe for protection of cable etc by means of mannual bookle and without disturbing the top surface and making good the disturbed surface if any complete as sepecified and directed by Engr-in-Charge. 110 RM
21 11 Supply and laying GI tube medium grade 80 mm bore, ISI marked complete as sepecified and directed by Engr-in-Charge. 50 RM
22 12 All as per item No 11 here-in-before but 40 mm bore. 60 RM
23 13 M&L in repair for heat shrinkable jointing kit including suitable size of connector complete all as per directed by Engr-in-charge. Note : Cost of necessary excavation and earth work , labour, Jointing kit complete, fixing charges & T&P including removing of grass/shrubs nearby the fault location shall be deemed to include in quoted rates) for the following sizes :-
24 13.01 XLPE Cable of size 25 sqmm to 50 Sqmm x 3.5/4 core. 30 Each Job
25 13.02 XLPE Cable of size 70 sqmm to 120 Sqmm x 3.5/4 core. 25 Each Job
26 13.03 XLPE Cable of size 180 sqmm to 240 Sqmm x 3.5/4 core. 12 Each Job
27 14 Supply and fixing aluminium thimble , cable gland and lux after disconnecting from panel and taking down burnt cable from panel of different location and cutting out the burnt portion of cable and extended the cable from cable loop, preparation of cable including necessary connection and testing complete (Note : (i) 01 Job consisting of 04 Nos Lugs/thimble at one end of cable (ii) Rate of necessary earth work for opening of loop if requried at site are deemed to be included in the quoted rate.) of following sizes :-
28 14.01 16 Sqmm 4 core 1100 volt grade. 10 Each Job
29 14.02 25 Sqmm 3.5 core 1100 volt grade. 15 Each Job
30 14.03 35 Sqmm 3.5 core 1100 volt grade. 20 Each Job
31 14.04 50 Sqmm 3.5 core 1100 volt grade. 25 Each Job
32 14.05 120 Sqmm 3.5 core 1100 volt grade. 35 Each Job
33 14.06 180 Sqmm 3.5 core 1100 volt grade. 20 Each Job
34 14.07 240 Sqmm 3.5 core 1100 volt grade. 15 Each Job
35 15 M&L for load balancing of Single/three phase system at LT Panel upto Distribution box of any size and capacity complete including disconnecting of existing cables and refixing the same as per load balance requirement including replacement of burnt/carbonized aluminium tube terminal of any size and capacity all as specified and as directed by Engr-in-charge.Note : (i) Necessary eqpt and safety mesures reqd for load balancing arranged by the contractor without any extra cost. (ii) Cost of New aluminium tube terminal of any size as per site reqmt change under the job deemed to be included in the quoted rate (iii) Contractor shall also submit the written record of phase wise electric load on panels/transformer duly signed by contractor, JE & AGE. 12 Each Job
36 16 M&L for LT insulator shackle type porceline , vitreous, white , brown or green insulator including one galvanised mild steel straps , washers , insulator bolts for 1100 volts 100 mm height , 115 mm dia complete all as specified and directed by Engr-in-Charge. 8 Each
37 17 M&L for LT pin type porceline , vitreous, white , brown or green insulator including one galvanised mild steel spindal , washers , two galvanised iron washers and one galvanised iron nut 100 mm height , 65 mm dia for 1100 volts complete all as specified and directed by Engr-in-Charge. 12 Each
38 18 S&F in replacement LT volt meter (0-500) digital squire flush type of size 96x96 mm including necessary addition/ alternation of panel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder including taking out of unserviceable Volt meter complete as sepecified and directed by Engr-in-Charge. 4 Each
39 19 S&F in replacement 1100 Volts grade LT Ammeter (0 - 300 A) digital squire flush & CT type with CT's including necessary addition/ alternation of panel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder taking out of unserviceable Ammeter complete as sepecified and directed by Engr-in-Charge. 4 Each
40 20 S&F in replacement 1100 Volts grade LT Ammeter (0 - 500 A) digital squire flush & CT type with CT's including necessary addition/ alternation of panel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder taking out of unserviceable Ammeter complete as sepecified and directed by Engr-in-Charge. 2 Each
41 21 M&L for Spray painting to LT panel board with synthetic enamel high glow paint Ist grade including preparation/cleaning of steel surfaces. complete as sepecified and directed by Engr-in-Charge. 16 Each
42 22 S&F in replacement of MCCBs thermal meganitic including necessery fixing arrengement & tasting complete all as sepecified and as directed by Engr-in-Charge of following sizes:-
43 22.01 (a) 100 Amps 4 Pole breaking capasity 35/36 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.420245 or equivalent out of makes specified in ist of makes. 12 Each
44 22.02 (b) 160 Amps 4 Pole breaking capasity 35/36 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.420247 or equivalent out of makes specified in ist of makes. 15 Each
45 22.03 (c) 200 Amps 4 Pole breaking capasity 35/36 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.420218 or equivalent out of makes specified in ist of makes. 10 Each
46 22.04 (d) 200 Amps 4 Pole breaking capasity 50 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.420278 or equivalent out of makes specified in ist of makes. 8 Each
47 22.05 (e) 250 Amps 4 Pole breaking capasity 50 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.420279 or equivalent out of makes specified in ist of makes. 6 Each
48 22.06 (f) 400 Amps 4 Pole breaking capasity 50 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.422021 or equivalent out of makes specified in ist of makes. 6 Each
49 22.07 (g) 630 Amps 4 Pole breaking capasity 50 KA complete all as sepecified and as directed by Engr-in-Charge. Make :Legrand Cat Part No.422023 or equivalent out of makes specified in ist of makes. 3 Each
50 23 M&L for detecting of fault in 1100 Volt cable of any size upto 400 Sqmm 3.5 core laid in trenc fault locating machine comprising of surg generator pulse,ECHO fault locator with high frequency distance calculator etc and exposing the cable fault,removal of deteriated portion of cable , treating of cable and making the same ready for jointing work complete all as specified and directed by Engr-In-Charge. 32 Each job
51 24 Taking down existing old LT panel board/ LT feeder pillar box comprising of MCCB & switch fuse unit of any capacity and size including bus bar ,ammeters, voltmeters etc after disconnecting all cable connection and removing from site complete all as directed. 3 Each job
52 25 Supply, install, commissioning and testing of LT panel board double door outdoor type floor mounted of factory made powder coated made out of outside body of 3.15mm thick steel sheet and inside body 14 gauge steel sheet, locking arrangement, front side and rear side opening arrangement of suitable size, Incl mounted on Angle iron stand of size 50x50x6mm having minimum height 1.5 feet duly grouted or welded on floor including PCC 1:2:4 fdn base complete as per manufacturer's instruction, aluminium bus bar TPN of 630A for MCCB to all feeders including provn of following items:- (a)    Incoming MCCB 630 Amp 50 KA 4pole-01 No (b)   Outgoing MCCB 200 Amp 35/36 KA 4pole -03 No (c)   Outgoing MCCB 160 Amp 35/36 KA 4pole -02 No (d) Change over switch 400 Amp TPN-01 No (e)    RYB indication for each incoming & outgoing supplies-01 set (f)    Digital Voltmeter, amp meter, with CT’s & selector switch-01 set (g)    Termination of all cables with suitable size thimble and glands-1 Job. (h) PCC 1:2:4 type B-1 300x300x500mm fdn block to four legs incl earth work. 1 Each Set
53 26 Supply, install, commissioning and testing of LT panel board double door outdoor type floor mounted of factory made powder coated made out of outside body of 3.15mm thick steel sheet and inside body 14 gauge steel sheet, locking arrangement, front side and rear side opening arrangement of suitable size, Incl mounted on Angle iron stand of size 50x50x6mm having minimum height 1.5 feet duly grouted or welded on floor including PCC 1:2:4 fdn base complete as per manufacturer's instruction, aluminium bus bar TPN of 400A for MCCB to all feeders including provn of following items:- (a)    Incoming MCCB 200 Amp 35/36 KA 4pole-01 No (b)   Outgoing MCCB 100 Amp 35/36 KA 4pole -02 No (c)   Outgoing MCCB 63 Amp 35/36 KA 4pole -01 No (d) Change over switch 200 Amp TPN-01 No (e)    RYB indication for each incoming & outgoing supplies-01 set (f)    Digital Voltmeter, amp meter, with CT’s & selector switch-01 set (g)    Termination of all cables with suitable size thimble and glands-1 Job. (h) PCC 1:2:4 type B-1 300x300x500mm fdn block to four legs incl earth work. 1 Each Set
54 27 Supply, install, commissioning and testing of LT panel board double door outdoor type floor mounted of factory made powder coated made out of outside body of 3.15mm thick steel sheet and inside body 14 gauge steel sheet, locking arrangement, front side and rear side opening arrangement of suitable size, Incl mounted on Angle iron stand of size 50x50x6mm having minimum height 1.5 feet duly grouted or welded on floor including PCC 1:2:4 fdn base complete as per manufacturer's instruction, aluminium bus bar TPN of 400A for MCCB to all feeders including provn of following items:- (a)    Incoming MCCB 200 Amp 35/36 KA 4pole-01 No (b)   Outgoing MCCB 100 Amp 35/36 KA 4pole -02 No (c)   Outgoing MCCB 63 Amp 35/36 KA 4pole -02 No (d) RYB indication for each incoming & outgoing supplies-01 set (e)    Digital Voltmeter, amp meter, with CT’s & selector switch-01 set (f)    Termination of all cables with suitable size thimble and glands-1 Job. (g) PCC 1:2:4 type B-1 300x300x500mm fdn block to four legs incl earth work. 1 Each Set
55 28 Earthing complete with galvanised steel earth plate 600 x 600 x 6mm thick buired directly in ground (earth pit not less that 2.25mtr deep below ground level ) with top edge of the plate not less than 1.5mr below normal ground level connected to galvanised iron strip of size 25 x 3mm by means GI welding after tighten by bolts, nuts, check nuts and washers from earth pit to test point with protection GI pipe of size 40mm dia light grade and providing masonry enclosure and watering pipe of dia 40mm including wiremesh steel funnel, including watering arrangement 200 ltrs for each earth pitcomplete as specifed and directed by Engr-in-charge . Make of GI Pipe is Prakash/Jindal (Note : GI strip 7.5 mtr included in the quoted rate from earth pit to test point) 6 Each set
56 29 Dismantling of old/rusted GI wire/Strip complete at site from shade/building upto 20mtr height complete all as specified and as directed by Engr-in-charge 60 RM
57 30 M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or fixed on wall of the building on insulator or PVC pipe or chases or buried in ground or fixed to poles or any other indicated situation for loop earthing etc as required of size 20 x 3 mm copper strip complete all as specified and directed by Engr-In-charge. 60 RM
58 31 M&L for repair of earthing pit with brick work and PCC 1:3:6 including RCC pit cover of size 300x300mmx50mm thick with provision of opening handle complete including necessary watering, ramming and compact of soil near the earth pit complete all as specified and as directed by Engr-in-charge. 15 Each Job
59 32 Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor , served with inner sheathing of PVC tape and overall PVC sheathed in service connection of size 10 Sqmm 2 core including taking down old cable complete all as specified and as directed by Engr-in-charge. 250 RM
60 33 M&L for surface dressing and proper laying of XLPE electrical cable of any size and capacity nearby the LT Panel after disconnecting all incoming and outgoing connection complete including cleaning of grass nearby the LT Panel upto 2mtr all around , necessary earthwork as required all as specified and as directed by Engr-in-charge. . (Note : Rate of necessary earthwork as required at site are deemed to be included in the quoted rate) 10 Each Job
61 34 Disposal of old junk/garbage both solid and liquid through browser with Tactor with minimum 3cum capacity and disposal out from MOD land maximum distance 5 KM complete all as directed by Engr-in-charge. 8 Each Trip
62 35 M&L in repair for Prestressed concrete pole , 9 mtr long, 102 mm x 172 mm at top and 12mm x 279 mm at bottom class 10 complete including excavation & earth work, PCC 1:4:8 type-D-2 in pole fdn & PCC 1:3:6 type C-1 in coping of pole complete as sepecified and directed by Engr-in-Charge. 4 Each Job
63 36 Supply only Synthetic insulating mat of size 2Mx1Mx10mm thick ISI marked complete as sepecified and directed by Engr-in-Charge. 4 Each
64 37 Supply only Synthetic insulating mat of size 2Mx1Mx12mm thick ISI marked complete as sepecified and directed by Engr-in-Charge. 4 Each
65 38 M&L for re-stringing of ASCR conductor of any size/dia by removing sag in between the line including disconnecting ACSR conductor from both side to overhead line and rejoining after repair work complete all as specified and directed by Engr-in-Charge. 800 RM
66 39 M&L for providing PVC rigid spacer for 4/5 line LT overhead line complete all as specified and directed by Engr-in-charge. 80 Each
67 40 M&L for Chang over switch of capacity 250 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. 2 Each
68 41 M&L for Chang over switch of capacity 400 Amps , 415 Volts with sheet metal inclosure complete all as specified and directed by Engr-in-charge. 6 Each
69 42 M&L for Chang over switch of capacity 630 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. 1 Each
70 43 M&L for Chang over switch of capacity 100 Amps , 415 Volts, 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. 4 Each
71 44 M&L for Chang over switch of capacity 63 Amps , 415 Volts , 4 pole with sheet metal inclosure complete all as specified and directed by Engr-in-charge. 4 Each
72 45 M&L for side handle main switch 3 pole 415 volt 200 Amp complete all as specified and directed by Engr-in-charge. Make - Havells/L&T/ABB. 4 Each
73 46 M& L for prunning of trees over the ACSR Conductor and all E/M Installations including trimming of tree in the radius of 2.5 mtr from ACSR conductor and its disposal complete all as directed by the Engr-in-Charge in consultation with users. 22 Per Km line
74 47 Supply and fixing in replacement of stay assembly complete with 16mm dia stay Rod including PCC 1:3:6 type C-2 complete all as specified and as directed by Engr-in-charge. (Excavation and earth work measured and paid seperately). 8 Each Job
75 48 S&F danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved siz,for LT ,20X15 cm size complete all as specified and as directed. 30 Each
76 49 M&L for preparation of old painted surface of electric RCC pole by removing all dirt, dust etc and apply approved colour one coat of syhnthetic enemal paint upto 1.5 mtr height (Five layer 30 cm Blue and 30 cm White one over another) and one coat of synthetic enamel paint on steel surface such as cross arm including writing of identification No , etc complete all as specified and directed. 70 Each Job
77 50 All as per item No 49 herein before but one coat of aluminium paint on steel tubular pole. 50 Each Job
78 51 Notes:- (i) The amount of Rs. 117690/- against Schedule of Credit on Page No.116 shall be deducted from the total amount quoted against Sch 'A' while deriving the Contract Sum for Acceptance.
Disclaimer :