Augmentation Of 132 By 33 Kv Grid Sub Station Arampora From 90 Mva To 120 Mva And Other Allied Electrical And Civil Works, ARAMPORA KUPWARA-Jammu And Kashmir

Jammu And Kashmir Power Development Department-PDDJK has published Augmentation Of 132 By 33 Kv Grid Sub Station Arampora From 90 Mva To 120 Mva And Other Allied Electrical And Civil Works. Submission Date for this Tender is 15-05-2021. Electrical Maintenance Tenders in ARAMPORA KUPWARA Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

27713552
Augmentation Of 132 By 33 Kv Grid Sub Station Arampora From 90 Mva To 120 Mva And Other Allied Electrical And Civil Works
Open Tender
Indian
Jammu And Kashmir
ARAMPORA KUPWARA
15-05-2021

Tender Details

Augmentation Of 132 By 33 Kv Grid Sub Station Arampora From 90 Mva To 120 Mva And Other Allied Electrical And Civil Works

Key Value

Document Fees
INR 5000 /-
EMD
Refer document
Tender Value
INR 4.32 Crore /-

BOQ Items

Name of Work: Augmentation of 132/33 KV Grid sub-station Arampora from 90 MVA to 120 MVA and other allied works.
S. No. Item Description Item Code / Make Quantity Units
1 1 (A) SUPPLY:- Design, Manufacture, Supply, Packaging & Forwarding, Transportation, Delivery at site of equipments and materials. BI01010001010000000000000515BI0100001115
2 2 Power Transformer BI01010001010000000000000515BI0100001116
3 3 Design, Engineering, Manufacture and Assembly of 3-Phase, 132/33 KV 50 MVA, Power Transformer Complete with all fittings and accessories required for efficient and trouble free operations of Transformer, Testing at Manufacture’s works and Customer’s Premises, Supply, Loading at Factory, Transportation and Delivery at site with OLTC, RTCC, SCADA Compatable, NIFPES, HV and LV Connectors and other required accessories and fittings including all the mandatory spares.(Complete Unit) BI01010001010000000000000515BI0100001117 1 No
4 4 Main Equipments BI01010001010000000000000515BI0100001118
5 5 Circuit breakers BI01010001010000000000000515BI0100001119
6 6 3 pole, 145 kV,1250 Amp of 3-Phase, 50c/s, 31.5 kA for 1 second, SF6 Circuit Breaker out door type with offered operating mechanism, all accessories,clamps, auxiliaries and marshalling boxes / kiosks etc. complete in all respects as specified in the technical specification BI01010001010000000000000515BI0100001120 1 No
7 7 3 pole, 36kV,1250Amp, 50c/s, 25kA, Vaccum Circuit Breakers out door type with offered operating mechanism, all accessories,clamps, auxiliaries and marshalling boxes / kiosks etc. complete in all respects as specified in the technical specification. BI01010001010000000000000515BI0100001121 1 No
8 8 3 pole, 36kV,1250Amp, 50c/s, 25kA, Vaccum Circuit Breakers out door type with offered operating mechanism, all accessories,clamps, auxiliaries and marshalling boxes / kiosks etc. complete in all respects as specified in the technical specification.( For Outgoing 33 KV Feeders after replacement of wornout/old one's) BI01010001010000000000000515BI0100001122 5 No
9 9 Isolators BI01010001010000000000000515BI0100001123
10 10 145 kV, 50 c/s, 2000 Amps, 31.5 kA for one second, AC Motor Operated horizontal double break, outdoor type 3 pole isolators with all accessories,clamps, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification without earthing blades. BI01010001010000000000000515BI0100001124 4 Sets
11 11 36 kV, 50 c/s, 2500 Amps,25kA for 3 Sec, horizontal double break, outdoor type manual operated 3 pole isolators with all accessories, auxiliaries,clamps, marshalling boxes, other essentials, complete in all respects as specified in the technical specification without earthing blades. BI01010001010000000000000515BI0100001125 2 Sets
12 12 Current Transformers BI01010001010000000000000515BI0100001126
13 13 Single phase, 50 c/s, 145kV 5-core Current Transformers (1200-800-400/1-1-1-1-1A 31.5A for 1 sec rated dynamic current 100kA(peak), class A insulation, Burden 20 VA including first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001127 3 No
14 14 Single phase, 50 c/s, 145kV 5-core Current Transformers (1200-800-400/1-1-1-1-1A 31.5A for 1 sec rated dynamic current 100kA(peak), class A insulation, Burden 20 VA ( for replacement of existing worn out old ones) including first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001128 3 No
15 15 Single phase, 50 c/s 36 kV Current Transformers (1200-600-300/1-1-1 A , 25kA for 1 sec, rated dynamic current 25kA(peak), class A insulation, Burden 20 VA ( for replacement of existing worn out old ones) inlcluding first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001129 9 No
16 16 Neutral Current Transformer with current rating 1200-800-400/1 A and 1200-600-300/1A and VA burden 15 VA including first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001130 2 No
17 17 Surge Arrestor BI01010001010000000000000515BI0100001131
18 18 Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, clamps, auxiliaries, complete in all respects as specified in the technical specification 120 KV(RMS) BI01010001010000000000000515BI0100001132 3 No
19 19 Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, clamps, auxiliaries, complete in all respects as specified in the technical specification 30 KV(RMS) BI01010001010000000000000515BI0100001133 3 No
20 20 Control and Relay panel BI01010001010000000000000515BI0100001134
21 21 Control & Relay panel for station auxillary completely wired including substation automation supporting IEDs/numerical relays.(As per site requirement and having 110V DC voltage ) BI01010001010000000000000515BI0100001135 1 No
22 22 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable for DC supply complete as per specification. BI01010001010000000000000515BI0100001136
23 23 2 core, 2.5 sq mm BI01010001010000000000000515BI0100001137 640 m
24 24 5 core, 2.5 sq mm BI01010001010000000000000515BI0100001138 4650 m
25 25 7 core, 2.5 sq mm BI01010001010000000000000515BI0100001139 465 m
26 26 8 core, 2.5 sq mm BI01010001010000000000000515BI0100001140 160 m
27 27 10 core, 2.5 sq mm BI01010001010000000000000515BI0100001141 1000 m
28 28 14 core, 2.5 sq mm BI01010001010000000000000515BI0100001142 275 m
29 29 16 core, 2.5 sq mm BI01010001010000000000000515BI0100001143 1010 m
30 30 19 core, 2.5 sq mm BI01010001010000000000000515BI0100001144 680 m
31 31 2 core, 6.00 sq mm BI01010001010000000000000515BI0100001145 185 m
32 32 4 core, 6.00 sq mm BI01010001010000000000000515BI0100001146 460 m
33 33 4 core, 16.00 sq mm BI01010001010000000000000515BI0100001147 135 m
34 34 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded aluminium conductor power cable for AC supply .3.5 core, 25 sq mm BI01010001010000000000000515BI0100001148 200 m
35 35 Cable Glands, ferrules & Lugs for all above cables etc. BI01010001010000000000000515BI0100001149 2 Lot
36 36 Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns. BI01010001010000000000000515BI0100001150 3 No.
37 37 CONDUCTOR AND HARDWARE FITTINGS BI01010001010000000000000515BI0100001151
38 38 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN BI01010001010000000000000515BI0100001152 1.75 Km
39 39 Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN. BI01010001010000000000000515BI0100001153 12 No.
40 40 Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm. BI01010001010000000000000515BI0100001154 12 No.
41 41 Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN. BI01010001010000000000000515BI0100001155 21 No.
42 42 Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm. BI01010001010000000000000515BI0100001156 18 No.
43 43 Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. BI01010001010000000000000515BI0100001157 120 No.
44 44 Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. BI01010001010000000000000515BI0100001158 110 No.
45 45 T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001159 24 No.
46 46 T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001160 30 No.
47 47 T Clamps Twin 500mm2 / single 500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001161 6 No
48 48 Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162 BI01010001010000000000000515BI0100001162 115 No.
49 49 (B) HANDLING, STORAGE, PRESERVATION, ERECTION / INSTALLATION, DEHYDRATION, TESTING AND COMMISSIONING OF EQUIPMENTS AND MATERIAL (EXCEPT CIVIL WORKS) BI01010001010000000000000515BI0100001163
50 50 Power Transformer BI01010001010000000000000515BI0100001164
51 51 Erection and Assembly of 3-Phase, 132/33 KV 50 MVA, Power Transformer Complete with all fittings and accessories required for efficient and trouble free operations of Transformer with OLTC, RTCC, SCADA Compatable, NIFPES, HV and LV Connectors and other required accessories and fittings including all the mandatory spares.(Complete Unit) BI01010001010000000000000515BI0100001165 1 No
52 52 Main Equipments BI01010001010000000000000515BI0100001166
53 53 Circuit breakers BI01010001010000000000000515BI0100001167
54 54 3 pole, 145 kV,1250 Amp of 3-Phase, 50c/s, 31.5 kA for 1 second, SF6 Circuit Breaker out door type with offered operating mechanism, all accessories,clamps, auxiliaries and marshalling boxes / kiosks etc. complete in all respects as specified in the technical specification ( with adjustments to the existing foundations if required) BI01010001010000000000000515BI0100001168 1 No
55 55 3 pole, 36kV,1250Amp, 50c/s, 25kA, Vaccum Circuit Breakers out door type with offered operating mechanism, all accessories,clamps, auxiliaries and marshalling boxes / kiosks etc. complete in all respects as specified in the technical specification.( with adjustments to the existing foundations if required) BI01010001010000000000000515BI0100001169 1 No
56 56 3 pole, 36kV,1250Amp, 50c/s, 25kA, Vaccum Circuit Breakers out door type with offered operating mechanism, all accessories,clamps, auxiliaries and marshalling boxes / kiosks etc. complete in all respects as specified in the technical specification.( For Outgoing 33 KV Feeders after replacement of wornout/old one's)( with adjustments to the existing foundations if required) BI01010001010000000000000515BI0100001170 5 No
57 57 Isolators BI01010001010000000000000515BI0100001171
58 58 145 kV, 50 c/s, 2000 Amps, 31.5 kA for one second, AC Motor Operated horizontal double break, outdoor type 3 pole isolators with all accessories,clamps, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification without earthing blades. BI01010001010000000000000515BI0100001172 4 Sets
59 59 36 kV, 50 c/s, 2500 Amps,25kA for 3 Sec, horizontal double break, outdoor type manual operated 3 pole isolators with all accessories, auxiliaries,clamps, marshalling boxes, other essentials, complete in all respects as specified in the technical specification without earthing blades. BI01010001010000000000000515BI0100001173 2 Sets
60 60 Current Transformers BI01010001010000000000000515BI0100001174
61 61 Single phase, 50 c/s, 145kV 5-core Current Transformers (1200-800-400/1-1-1-1-1A 31.5A for 1 sec rated dynamic current 100kA(peak), class A insulation, Burden 20 VA including first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001175 3 No
62 62 Single phase, 50 c/s, 145kV 5-core Current Transformers (1200-800-400/1-1-1-1-1A 31.5A for 1 sec rated dynamic current 100kA(peak), class A insulation, Burden 20 VA ( for replacement of existing worn out old ones) including first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001176 3 No
63 63 Single phase, 50 c/s 36 kV Current Transformers (1200-600-300/1-1-1 A , 25kA for 1 sec, rated dynamic current 25kA(peak), class A insulation, Burden 20 VA ( for replacement of existing worn out old ones) inlcluding first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001177 9 No
64 64 Neutral Current Transformer with current rating 1200-800-400/1 A and 1200-600-300/1A and VA burden 15 VA including first fill of transformer oil plus 10% etc and all accessories , auxiliaries etc complete in all respects. BI01010001010000000000000515BI0100001178 2 No
65 65 Surge Arrestor BI01010001010000000000000515BI0100001179
66 66 Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, clamps, auxiliaries, complete in all respects as specified in the technical specification 120 KV(RMS) BI01010001010000000000000515BI0100001180 3 No
67 67 Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, clamps, auxiliaries, complete in all respects as specified in the technical specification 30 KV(RMS) BI01010001010000000000000515BI0100001181 3 No
68 68 Control and Relay panel BI01010001010000000000000515BI0100001182
69 69 Control & Relay panel for station auxillary completely wired including substation automation supporting IEDs/numerical relays.(As per site requirement and having 110V DC voltage ) BI01010001010000000000000515BI0100001183 1 No
70 70 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable for DC supply complete as per specification. BI01010001010000000000000515BI0100001184
71 71 2 core, 2.5 sq mm BI01010001010000000000000515BI0100001185 640 m
72 72 5 core, 2.5 sq mm BI01010001010000000000000515BI0100001186 4650 m
73 73 7 core, 2.5 sq mm BI01010001010000000000000515BI0100001187 465 m
74 74 8 core, 2.5 sq mm BI01010001010000000000000515BI0100001188 160 m
75 75 10 core, 2.5 sq mm BI01010001010000000000000515BI0100001189 1000 m
76 76 14 core, 2.5 sq mm BI01010001010000000000000515BI0100001190 275 m
77 77 16 core, 2.5 sq mm BI01010001010000000000000515BI0100001191 1010 m
78 78 19 core, 2.5 sq mm BI01010001010000000000000515BI0100001192 680 m
79 79 2 core, 6.00 sq mm BI01010001010000000000000515BI0100001193 185 m
80 80 4 core, 6.00 sq mm BI01010001010000000000000515BI0100001194 460 m
81 81 4 core, 16.00 sq mm BI01010001010000000000000515BI0100001195 135 m
82 82 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded aluminium conductor power cable for AC supply .3.5 core, 25 sq mm BI01010001010000000000000515BI0100001196 200 m
83 83 Cable Glands, ferrules & Lugs for all above cables etc. BI01010001010000000000000515BI0100001197 2 Lot
84 84 Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns. BI01010001010000000000000515BI0100001198 3 No.
85 85 CONDUCTOR AND HARDWARE FITTINGS BI01010001010000000000000515BI0100001199
86 86 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN BI01010001010000000000000515BI0100001200 1.75 Km
87 87 Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN. BI01010001010000000000000515BI0100001201 12 No.
88 88 Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm. BI01010001010000000000000515BI0100001202 12 No.
89 89 Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN. BI01010001010000000000000515BI0100001203 21 No.
90 90 Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm. BI01010001010000000000000515BI0100001204 18 No.
91 91 Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. BI01010001010000000000000515BI0100001205 120 No.
92 92 Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. BI01010001010000000000000515BI0100001206 110 No.
93 93 T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001207 24 No.
94 94 T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001208 30 No.
95 95 T Clamps Twin 500mm2 / single 500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001209 6 No
96 96 Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162 BI01010001010000000000000515BI0100001210 115 No.
97 97 (C) TWINING OF 132 KV MAIN AND RESERVE BUS AT GSS ARAMPORA (COMPLETE JOB) BI01010001010000000000000515BI0100001211
98 98 Dismantling of existing 132kV Main bus bar and bringing down on to ground including opening of connectors, jumpers, droppers etc all for facilitation of replacement of conductor from 0.2ACSR Panther to 0.5ACSR MOOSE (single into twin) BI01010001010000000000000515BI0100001212 0.38 KM
99 99 For Twining of 132kV Main Bus bar:\nLaying & stringing of 0.5 ACSR, Moose conductor including installation of insulator strings, hardware fittings & other accessories complete in all respects \n BI01010001010000000000000515BI0100001213 0.75 KM
100 100 Dismantling of existing 132kV Reserve bus bar and bringing down on to ground including opening of connectors, jumpers, droppers etc all for facilitation of replacement of conductor from 0.2ACSR Panther to 0.5ACSR MOOSE (single into twin) BI01010001010000000000000515BI0100001214 0.38 KM
101 101 For reserve bus bar:\nLaying & stringing of 0.5 ACSR, Moose conductor including installation of insulator strings, hardware fittings & other accessories complete in all respects \n BI01010001010000000000000515BI0100001215 0.75 KM
102 102 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN BI01010001010000000000000515BI0100001216 1.5 KM
103 103 200mm2 ACSR Panther Conductor (a)Aluminium =30/3.00 mm (b) Steel= 7/3.00 mm overall diameter =21.00 mm Approx. Wt. =976 kg/km ultimate strength = 89.67 KN including 1.5% Sag and jumpering. BI01010001010000000000000515BI0100001217 0.25 KM
104 104 Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN. BI01010001010000000000000515BI0100001218 40 NO
105 105 Single Suspension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 50% ultimate strength of Bundle conductors with forged steel hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor . The ball and socket designation must be 20mm. BI01010001010000000000000515BI0100001219 15 NO
106 106 Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. BI01010001010000000000000515BI0100001220 100 NO
107 107 Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. BI01010001010000000000000515BI0100001221 50 NO
108 108 T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001222 28 NO
109 109 T Clamps Twin 500mm2 / single 500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) BI01010001010000000000000515BI0100001223 52 NO
110 110 Spacers For Twin 500mm2 must be one-piece construction of aluminum alloy of an approved type without any projection, cuts, abrasions etc. or chattering parts and shall conform to IS:10162 BI01010001010000000000000515BI0100001224 80 NO
111 111 (D) Civil Works including Design, Supply, Execution/Laying of various foundations and prepration of drawings. BI01010001010000000000000515BI0100001225
112 112 (I)Strenthening of existing 50 MVA Power Transformer Foundation BI01010001010000000000000515BI0100001226
113 113 Excavation in all type of soils including mixed soils (i.e. soils containing pebbles/boulders etc.) for any section including all labour, POL, hire charges of equipments and T&Ps etc. including sheeting & shoring, dewatering, lifting, handling and stock piling of excavated materials, back filling with excavated or borrowed earth and disposal of surplus excavated earth as directed for all leads & lifts complete as per specification, construction drawings and direction of Engineer-in-charge. BI01010001010000000000000515BI0100001227 25 cum
114 114 Plain cement concrete of specified grade and strength conforming to IS: 456 placed as sub-base under structural concrete or as shown in approved construction drawings at all levels including cost of all materials, labour, hire charges of equipments and T&P, POL, shuttering etc complete for handling, transportation, batching, mixing, placing, vibrating, compacting, leveling, curing etc. as per specification, construction drawings and direction of Engineer-in-charge. BI01010001010000000000000515BI0100001228
115 115 Concrete of M-10 grade having cube strength of 7.5 N / mm2 with 20 mm nominal size coarse aggregate. BI01010001010000000000000515BI0100001229 5 Cum
116 116 Concrete of M-15 grade having cube strength of 15 N / mm2 with 20 mm nominal size coarse aggregate. BI01010001010000000000000515BI0100001230 1 Cum
117 117 Structural cement concrete ( plain/ reinforced) of specified 28 days strength (nominal size of coarse aggregate 20 mm) at all levels, including cost of all materials, labour, hire charges of equipments and T&P, POL, shuttering, curing, etc complete for handling, transportation, batching, mixing, placing, vibrating, and rendering, cleaning and finishing the exposed over ground surfaces with cement mortar 1:3 (1 cement : 3 sand) to give smooth and even surface, stub setting, fixing of foundation bolts ( as applicable) but excluding the cost of reinforcement complete as per specification, construction drawings and direction of Engineer-in-charge. BI01010001010000000000000515BI0100001231
118 118 Concrete of M-20 grade having cube strength of 20 N / mm2 with 20 mm nominal size coarse aggregate. BI01010001010000000000000515BI0100001232 12 Cum
119 119 Brick work with common burnt clay F.P.S. Bricks of class designation 75 in foundation and plinth in cement mortar 1:6. BI01010001010000000000000515BI0100001233 1.8 Cum
120 120 Cement Plaster 15mm in 1:4 Mix BI01010001010000000000000515BI0100001234 11 SQM
121 121 High yield strength cold deformed steel reinforcement bars conforming to IS: 1786 for R.C.C. or any other work including the cost of all materials, binding wire, labour, hire charges of equipments and T&P, bending, binding, placing and tieing in position, POL etc. complete as per specification, construction drawings and direction of Engineer-in-charges. BI01010001010000000000000515BI0100001235 600 kg
122 122 Supply and installation of broad gauge rails MS Rail 90 LB including fixing on RCC pedestal for transformer foundation as per drawings/design approved. BI01010001010000000000000515BI0100001236 2.4 RM
123 123 (II) Renovation/repairing of control room building at 132/33 KV GSS Arampora BI01010001010000000000000515BI0100001237
124 124 Dismantalling roofing including ridges,hips,valleysetc and stacking the material GSS premises as per directions of incharge site engineer.(G S sheets) BI01010001010000000000000515BI0100001238 220 sqm
125 125 Dismantalling of existing False cieling and stacking the material within GSS premises as per directions of incharge site engineer.complete job\n BI01010001010000000000000515BI0100001239 1 Job
126 126 Providing and fixing of corrrugated G .S sheet ( colour coated) roofing including vertical /curved surfcaefixed with polymer coated J or L hoksbolts/screws and nuts 8mm dia with bitumen and G Ilimpet washers or with G I limpet washers fitted with white lead excluding the cost of purlins,rafters and trusses and including cutting to size and shape wherever required.(.50 mm thick with zinc coating).=2371sft=220sqm\n \n\n BI01010001010000000000000515BI0100001240 220 SQM
127 127 Providing wood work in frames of false ceiling, partitions etc. sawn and fixed in position (Budloo / Fir wood) BI01010001010000000000000515BI0100001241 0.3 Cum
128 128 Providing and fixing of false ceiling at all heights.P/F of 12mm thick flat pressed 3 layer medium density particle board or graded particle board (grade I) with CNC marked design and PVC coated,IS:3087 marked with necessary nails etc.1200sft=111.6sqm\n BI01010001010000000000000515BI0100001242 111.6 SQM
129 129 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Supply and fixing. BI01010001010000000000000515BI0100001243 360 MTR
130 130 Wiring for light circuit/ submain wiring alongwith earth wire with the FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. Supply and fixing. BI01010001010000000000000515BI0100001244 540 MTR
131 131 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 5 pin 5/6 & 20 A modular socket outlet and 32 A modular switch, connections etc. as required. BI01010001010000000000000515BI0100001245 14 NO
132 132 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. BI01010001010000000000000515BI0100001246 12 NO
133 133 Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required. BI01010001010000000000000515BI0100001247 14 NO
134 134 Supply and fixing of 240 Volt,single phase ceiling fan of approved quality along with S.P. 5/6 amps, one way modular switch, ISI marked and dimmer BI01010001010000000000000515BI0100001248 5 NO
135 135 Supply and fixing of 16amps. to 32 amps. ratings , TPN MCB, “C” curve, 10 KA breaking capacity. BI01010001010000000000000515BI0100001249 4 NO
136 136 Supply and fixing of 100A MCCB 2 pole of approved quality BI01010001010000000000000515BI0100001250 2 NO
137 137 Supply and fixing of 63A RCCB 2 pole of approved quality BI01010001010000000000000515BI0100001251 2 NO
138 138 Modular base & cover plate for 12 module switch BI01010001010000000000000515BI0100001252 3 NO
139 139 Modular base & cover plate for 8 module switch BI01010001010000000000000515BI0100001253 14 NO
140 140 Modular base & cover plate for 4 module switch BI01010001010000000000000515BI0100001254 6 NO
141 141 12 Watt,240 Volt surface LED Lights for illumination of control room BI01010001010000000000000515BI0100001255 38 NO
142 142 S.P. 5/6 amps, one way modular switch, ISI marked. BI01010001010000000000000515BI0100001256 38 NO
143 143 Supplying and fixing of surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of din bar for mounting MCBs (but without MCBs and incomer ) as required . BI01010001010000000000000515BI0100001257 1 NO
144 144 Removing dry or oil bound distemper, water proofing\ncement paint and the like by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.=6000 SFT=558.1 Sqm BI01010001010000000000000515BI0100001258 558.1 SQM
145 145 Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade on New work (two or more coats) over and including priming coat with water thinnable cement primer and Finishing walls with water proofing cement paint (Excel) of required shade (two or more coats applied @ 2.20 kg/10sqm) complete BI01010001010000000000000515BI0100001259 558.1 SQM
146 146 Applying priming coat with ready mixed pink or grey primer of approved brand and manufacture on wood work (hard and soft wood),doors and windows=2790sft=259.5 sqm BI01010001010000000000000515BI0100001260 259.5 SQM
147 147 Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade, two coats on old/new work. BI01010001010000000000000515BI0100001261 259.5 SQM
148 148 Providing and fixing 35 mm thick glazed shutters for doors, windows and clerestory windows using 4mm thick float glass panes including ISI marked M.S. pressed butt hinges bright finished,all neccessary hardware fiitings including ISI marked M.S latches,M.S handles etc. of required size with necessary screws as per direction of Engineer-in-charge First class kail wood. BI01010001010000000000000515BI0100001262 10.5 SQM
149 149 Providing and fixing 35 mm thick wire gauze shutters using galvanized M.S. wire gauze of average width for aperture 1.4 mm in both directions with wire of dia. 0.63 mm for doors, windows and clerestory windows with ISI marked M.S. pressed butt hinges bright finished all neccessary hardware fiitings including ISI marked M.S latches,M.S handles etc. of required size with necessary screws as per direction of Engineer-in-charge First class kail wood. BI01010001010000000000000515BI0100001263 6.5 SQM
150 150 Providing and laying Vitrified tiles in different sizes (thickness to be\nspecified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours and shades, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement and matching pigments etc. complete. for control room floor. Size of tile 600x600 mm= 1550 Sft=144.2 Sqm BI01010001010000000000000515BI0100001264 144.2 SQM
151 151 Providing and fixing of PVC wall pannels of approved quality ISI marked for control room wall pannelling,including cost of frame work ,pvc angles ,bends and all other necessary accessories as required for finished surface ,complete for control room walls as per direction of engineer in charge =3550sft=330.2sqm BI01010001010000000000000515BI0100001265 330.2 SQM
152 152 Providing of Sofa set (5 seater with glass top table) and furniture for control room BI01010001010000000000000515BI0100001266 1 JOB
153 153 Providing and fixing of water purifier of approved quality for control room. BI01010001010000000000000515BI0100001267 1 Job
154 154 (III) Renovation/repairing of Existing Bathroom in the Control room building at 132/33 KV GSS Arampora BI01010001010000000000000515BI0100001268
155 155 Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 meters lead. BI01010001010000000000000515BI0100001269 85 SQM
156 156 Replacement of damaged PVC outlet pipes with bends etc. (disposal System) by new ones of required dia incl. connecting them with the existing septic tank & soakage pits incl. removal of all waste material & bushes complete job BI01010001010000000000000515BI0100001270 2 JOB
157 157 Repairing of septic tank and soakage pit (walls and slab s required)incl. removal of all waste material & bushes complete job as per directions of site incharge BI01010001010000000000000515BI0100001271 1 JOB
158 158 Providing and fixing of Ceramic glazed floor tiles (thickness to be specified by the manufactures) of Ist quality conforming of IS:13755 of NITCO, ORIENT, SOMANY KAJARIA, or equivalent make in colour such as White, Ivory, Gray, Fume Red brown laid on 20 mm thick bed of cement Mortor 1:4 (1 cemnt:4 coarse sand) including pointing the joints with White cement and matching pigment etc complete. BI01010001010000000000000515BI0100001272 105 SQM
159 159 Providing and fixing water closet squatting pan (Indian type WC pan) with 100mm sand cast Iron P or S trap, 10 liter low level PVC flushing cistern including flush pipe ( of approved make) manually controlled device (handle lever) conforming to IS:7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required. Long pan pattern white vitreous china WC pan of size 580mm BI01010001010000000000000515BI0100001273 3 NO
160 160 Providing and fixing wash basin with C.I/M.S brackets 15mm C.P brass pillar taps 32mm C.P brass waste of standard pattern including painting of fittings and brackets, cutting and making good the walls where ever required. White Vitreous China Wash Basin size 630mmx450mm with a pair of C.P brass pillar taps BI01010001010000000000000515BI0100001274 4 NO
161 161 Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception ,, of pipes and fittings BI01010001010000000000000515BI0100001275 3 NO
162 162 Providing and fixing PVC waste pipe for wash basin including PVC waste fittings complete. Flexible pipe 32 mm dia BI01010001010000000000000515BI0100001276 8 NO
163 163 Providing and fixing Polyethylene- Aluminum- Polyethylene (PE-ALPE) Composite Pressure Pipes conforming to IS: 15450, U.V. stabilized with carbon black having thermal stability for hot and cold water supply, capable to withstand temperature upto 80ºC, including all special fittings of composite material (engineering plastic blend and brass inserts wherever required) e.g. Elbows, tees, reducers, couplers and connectors etc. This includes testing of joints complete as per direction of the Engineer-in-charge:Internal work concealed with clamps at 1.00 meter spacing\nincluding cutting the chases and making good the wall etc.\n19.1.2.1 1216 (16mm OD) pipe BI01010001010000000000000515BI0100001277 25 RM
164 164 Construction of brick masonry manhole in cement mortar 1:4(1 cement : 4coarse sand) RCC top slab with 1:2:4 foundation concrete 1:4:8 inside plastering 12mm thick in cement mortar 1:3 Mix Size of manhole 90x80x 45 cm inside BI01010001010000000000000515BI0100001278 6 NO
165 165 Providing and fixing water heater reputed make (venus, racold, etc) ISI mark including all necessary firrings including making good wall after installation all complete 50 litre capacity BI01010001010000000000000515BI0100001279 3 NO
166 166 Providing and fixing C.P bib cock (Parco Or Jaqvar) of approved quality 15mm nominal bore BI01010001010000000000000515BI0100001280 10 NO
167 167 Providing fixing C.P Stop cock/Angle valves (Parco Or Jaqvar) concealed of standard design and approved make conforming to IS 8931 15mm nominal bore BI01010001010000000000000515BI0100001281 16 NO
168 168 Providing & Fixing of CP Brass Wall Mixer of (Parco Or Jaqvar) 15 mm nominal bore BI01010001010000000000000515BI0100001282 3 NO
169 169 Providing & Fixing of CP Brass wash basin Mixer and sink mixer of (Parco Or Jaquar) 15 mm nominal bore BI01010001010000000000000515BI0100001283 4 NO
170 170 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with C.P brass screws with concealed fiting arrangement of approved quality and colour. 450 mm long towel rail with total length of 495mm, 78 mm wide and effective height of 88mm, weighing not less than 190 gms BI01010001010000000000000515BI0100001284 3 NO
171 171 Supply,Instalation & commissioning of Exhaust Fan of Standard quality BI01010001010000000000000515BI0100001285 4 NO
172 172 ( E ) DISMANTLING OF VARIOUS EQUIPMENTS INCLUDING SHIFTING OF THE SAME TO STOCKING PLACE AT DIVISIONAL STORES AT AMARGARH SOPORE. BI01010001010000000000000515BI0100001286
173 173 Shifting of 132/33 kV 3-phase 20 MVA power transformer including dismantling of associated conductor and other hardware fittings. BI01010001010000000000000515BI0100001287 1 Job
174 174 145KV SF6 Circuit Breaker. BI01010001010000000000000515BI0100001288 1 NO
175 175 36KV Vacuum Circuit Breaker. BI01010001010000000000000515BI0100001289 6 NO
176 176 145 KV three pole isolator BI01010001010000000000000515BI0100001290 4 Sets
177 177 36 KV three pole isolator BI01010001010000000000000515BI0100001291 2 Sets
178 178 145 KV Current Transformer BI01010001010000000000000515BI0100001292 6 NO
179 179 33 KV Current Transformer BI01010001010000000000000515BI0100001293 9 NO
180 180 Neutral Current Transformer BI01010001010000000000000515BI0100001294 1 NO
181 181 Surge Arrestor 120 KV and 30 KV RMS BI01010001010000000000000515BI0100001295 6 NO
182 182 Conductor and Hardware fittings. BI01010001010000000000000515BI0100001296 1 Job
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy