}

Repair/Replacement And Maintenance Of E/M Installation Sub Station And Other Allied Work At Ins Chilka Under Ge Chilka, Garrison Engineer Chilka-Odisha

Military Engineer Services-MES has published Repair/Replacement And Maintenance Of E/M Installation Sub Station And Other Allied Work At Ins Chilka Under Ge Chilka. Submission Date for this Tender is 12-06-2021. Electromechanical Work Tenders in Garrison Engineer Chilka Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

27568555
Corrigendum : Repair/Replacement And Maintenance Of E/M Installation Sub Station And Other Allied Work At Ins Chilka Under Ge Chilka
Open Tender
Indian
Odisha
Garrison Engineer Chilka
12-06-2021

Tender Details

Repair/Replacement And Maintenance Of E/M Installation Sub Station And Other Allied Work At Ins Chilka Under Ge Chilka

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Apr-2021 Corrigendum No 1 BOQ 24-04-2021
2 24-Apr-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-05-2021
3 02-May-2021 Corrigendum No 2 Date 12-05-2021
4 13-May-2021 Corrigendum No 3 Date 22-05-2021
5 24-May-2021 Corrigedum No 4 Date 01-06-2021
6 05-Jun-2021 Corrigendum No 5 Date 12-06-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 26000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR/REPLACEMENT AND MAINTENANCE OF E/M INSTALLATION, SUB STATION AND OTHER ALLIED WORK AT INS CHILKA UNDER GE CHILKA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 M&L for checking electrical LT distribution panels boards for loose electrical connection, and securing properly, replacement of damaged/missing nuts, bolts, washers etc as required, or dressing incoming and outgoing cable for punctured/cracked sheath/insulation by taking out and refix in same position by provideing suitable size lugs, necessary cutting, welding, drilling and fixing of missing/damaged door hinges/locking handle/latch provided and including cleaning inside of the panel board complete to the satisfaction of Engineer-in-Charge complete all as specified and as directed. 60 Each Job
2 2 M&L for cutting of vegetation growth/grass etc in and around the structures/panel boards etc upto 3 meter radius from the structure/panel board in a presentable manner and removing the same from site and clear the road/path etc complete all as specified. 10 Each job
3 3 Supply and spray glycol chemical approved quality for prevention of weed growth grass in outdoor sub stations/structures complete all as specified and as directed. 50 Litre
4 4 M&L for galvanised iron chain link fabric fencing PVC coated (green colour or any other as approved) of required width , mesh size 50mmx50 mm including strengthening with 2 mm dia wire as required complete all as specified and as directed. 200 Sqm
5 5 M&L for mild steel work as in angle iron of required shape to support to fencing at a distance along the lengh of fence where required or as directed in an uniform manner , cut to required length and including drilling, bending,welding etc complete all as specified and as directed. 150 Kg
6 6 Excavating in post holes (or similar holes) , each n exc 0.5 cum, getting out, returning, filling in & removing surplus soil to a distance not exceeding 50 m in soft/oose soil complete all as specified and as directed. 22 Each
7 7 M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete complete all as specified and as directed. 0.6 Each
8 8 Supply, installation, testing and commissioning in replacement of check electronic energy meter, with optical port, temper proof three phase, 4 wire with LCD display operated on rated voltage of 415 volts, 5% frequency variation with rated current 10-60 Amps, class of accuracy 1.0, dust and moisture proof with poly carbonate case sealing provision for optical port with display type of five digits and one decimal LCD provided for tamper indication (reverse and earth) protection level IP 51 confirming to IS 13779 of IEC62052-11,IEC62053-21 etc. complete including sealing arrangement , arrangment for wire seal of suitable size for LT three phase KWH meter and disconnecting the existing main cables including provision of copper leads of suitable size for connecting the LT cable of any size to the meter and then from meter to the existing MCCB/MCBs etc complete all as specified and as directed.\nMake :- SECURE Cat Part No Sprint 350 or equivalent in L&T/HPL Note :-(i) The rate quoted under this item is inclusive of copper lugs and copper leads/wire as required.\n(ii) Old unserviceable energy meter shall be deposited in AGE E/M store yard.\n 4 Each
9 9 M&L for preparation of old surface of PCC/RCC pole of any type for street/security lights and applying one coat of approved water proof plastic emulsion paint on entire pole surface including coping over one coat of primer including the SMC junction boxes, painting zebra pattern of alternate yellow and black strips, two rows of each colour with each strip of minimum 6 cm height starting from pole copping, writing of pole number in black paint on yellow background of dia 100mm dia circle and one coat of aluminium paint on mild steel surface i.e bracket, clamps and mild steel cable termination junction box etc complete all as specified and as directed . \n 700 Each Job
10 10 M&L for preparation of old painted surface of steel tubular pole of any type for street/security lights and applying one coat of aluminum paint on entire exposed surface of pole including backets, clamps and mild steel cable termination junction box etc and painting zebra pattern of alternate yellow and black strip two rose of each colour with each strip of minimum 6 cm height, starting from ple copping, writing pole Number in black paint on yellow background of dia 100mm dia circle and applying one coat of waterproof cement base paint in white colour to coping complete all as specified and as directed . \n 200 Each Job
11 11 Supply, installation, testing and commissioning in replacement of check electronic energy meter, with optical port, temper proof single phase, 2 wire with LCD display operated on rated voltage of 240 volts, 5% frequency variation with rated current 10-60 Amps, class of accuracy 1.0, dust and moisture proof with poly carbonate case sealing provision of two sealing screws for meter , one screw for terminal cover and sealing provision for optical port with display type of five digits and one decimal LCD provided for tamper indication (reverse and earth) protection level IP 51 confirming to IS 13779 of 1999/IEC 1036 and CBIP 88 etc, arrangment for wire seal of suitable size for LT single phase KWH meter complete all as specified and as directed.\nMake :- SECURE Cat Part No I Credit 300 or equivalent in L&T/HPL \nNote :- (i) The rate quoted under this item is inclusive of copper lugs and copper leads/wire as required.\n(ii) Old unserviceable energy meter shall be deposited in AGE E/M store yard. 10 Each
12 12 Supply, Installation, Testing and Commissioning of maintenance free heavy duty earthing GI chemical electrode of 50 mm dia, wall thickness 16 gauge and 3 meter length with internal conductor of GI of size 30mmx6mm along with 60 Kg bag of back fill compound (highly conductive, non corrosive moisture retaining chemical) complete including necessary excavation and earth work with top 300 mm deep having one brick thick masonry chamber in cement mortar 1:4 with sub class B bricks of size 300mmx300mm as per standard Engineering Practice with RCC cover 50 mm htick in RCC 1:2:4 reinforce with 8 mm dia tor steel @150 mm C/C with earth resistance shall be as per IS 3043 complete all as specified and as directed. 2 Each Job
13 13 S&F in replacement of 250 Amp 4 pole MCCB, 25 KA, 415V, 50 Hz, AC supply adjustable type of thermal and megnatic setting including necessary cable lugs & wire etc complete all as specifeid and directed. \nMake :- Legrand / Seimens / ABB 3 Each
14 14 S&F in replacement 250 Amp 3 pole MCCB, 25 KA , 415V, 50 Hz, AC supply adjustable type of thermal and megnatic setting including necessary cable lugs & wire etc complete all as specified and directed.\nMake -: Legrand / Seimens / ABB 3 Each
15 15 S&F in replacement 200 Amp, 3 pole MCCB, 25 KA, 415V, 50 Hz, AC supply adjustable type of thermal setting including necessary cable lugs & wire etc complete all as specified and directed .\nMake :- Legrand / Seimens / ABB 3 Each
16 16 S&F in replacement 100 Amp 3 pole MCCB, 25KA , 415V, 50 Hz, AC supply including necessary cable lugs & wire etc complete all complete as specified and directed. \nMake :- Legrand / Seimens / ABB 4 Each
17 17 S&F in replacement 63 Amp TP MCCB, 25 KA, 415V, 50 Hz, AC supply including necessary cable lugs & wire etc complete. \nMake :- Legrand / Seimens / ABB 4 Each
18 18 S&F in replacement digital type Ammeter 96mmX96 mm square Flush mounted case of class 1.0 complete all as specified and as directed.\nMake : Elmeasure / AE / IMP / Meco/ MEI / HPL 20 Each
19 19 S&F in replacement of digital type Voltmeter 0-500V, 96mmX96 mm square Flush mounted case of class 1.0 complete all as specified and as directed.\n Make :- Elmeasure / AE / IMP / Meco/ MEI / HPL 20 Each
20 20 S&F in replacement CT 400 - / 5A for ammeter compete all as specified and as directed. \nMake :- AE / IMP / Meco / MEI / HPL 10 Each
21 21 S&F in replacement of Air Circuit breaker rated current = 630 Amp, 4 Pole, 415V, 50 Hz, AC supply, electrically driven automatic operation, Conforming to IEC 60947-2 with spring charging system, Accurate protection through microprocessor based trip unit, Integrated LCD display , Withdrawable design with Guide Frame, and making necessary arrangements as per site reuirement, to fix it including necessary cable lugs & wire etc complete all as specified and directed. \nMake :- Legrand / Seimens / ABB 2 Each
22 22 S&F in replacement 400 Amp, 4 Pole Change over switch, 50 KA, 415V, 50 Hz, AC supply, I - O - II operation, manual type, open construction or closed type construction as per site reuirement, adjustable type of thermal and megnatic setting, handel, including necessary cable lugs & wire etc complete all as specified and directed. \nMake :- Legrand / Seimens / ABB 2 Each
23 23 S&F in replacement VCB motorised spring charging ON/OFF mechanism, motor/manual operated, 220/230V AC/DC operated and including charging motor of 150 watt, single phase and trip/closing coil, charging spring etc complete all as specified and as directed.\nMake :- Legrand / Seimens / ABB 2 Each
24 24 Supply ,installation and testing air circulators of 450 mm sweep,220/230V, AC operated complete with and inclduing mounting arrangement as required at site inside installation for temperature control of HT/LT panels/motors or any other equipment so installed complete all as specified and as directed. \nMake :- Bajaj/Almonard/GE/Crompton\nNote:- Old unserviceable Air circulator meter shall be deposited in AGE E/M store yard. 4 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail