Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipur . Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipu, GHAZIPUR-Uttar Pradesh

Bharat Sanchar Nigam Limited-BSNL has published Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipur . Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipu. Submission Date for this Tender is 26-04-2021. Electromechanical Work Tenders in GHAZIPUR Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

27323870
Corrigendum : Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipur . Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipu
Open Tender
Indian
Uttar Pradesh
GHAZIPUR
26-04-2021

Tender Details

Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipur . Providing Various Electromechanical Infrastructure In Ola Location Under Nfs Project In Te Building Zamania Under Ssa Ghazipur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Apr-2021 Date extension Date 26-04-2021

Key Value

Document Fees
INR 590 /-
EMD
INR 7197.0 /-
Tender Value
INR 3.59 Lakhs /-

BOQ Items

Name of Work: Providing various electromechanical infrastructure in OLA location under NFS project in TE building Zamania under SSA Ghazipur.. .
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Sub Head -I (Supply of Inverter Type Split AC Units)
2 1.01 Supply of 1.5 TR inverter type five star rating split AC unit having nominal cooling capacity of 4500 Kcal / hr (5.2 KW), minimum room air flow of 700 cub.mtr/hr and minimum Indian Seasonal Energy Efficient Ratio (ISEER) of 3.5 along with the copper pipe, 3x2.5 sqmm size of PVC insulated copper condr. Flexbile cable and PVC drain pipe up to the length of 5 mtrs. including transportation complete as per specifications, terms and conditions attached as required. ( Make: O-General / LG / Carrier /Daikin /Hitachi/Voltas) 4 Nos.
3 1.02 Note : 1) The length of refrigerant piping for liquid refrigerant , hot gas refrigerant and lenght of copper conductor cable for connection from indoor to outdoor unit shall be included upto 5 mtrs. Extra length of refrigerant piping and power cable shall be paid as per item no.1 & 2 of Part B. The drain pipe of good quality [ as recommended by the manufacturer ] upto 5 mtrs is also included in this item
4 2 Sub Head -II (ITC of Inverter Type Split AC Units & wiring)
5 2.01 Installation, Testing and Commissioning of 1.5 TR inverter type five star rating split AC unit having nominal cooling capacity of 4500 Kcal / hr (5.2 KW), minimum room air flow of 700 cub.mtr/hr and minimum Indian Seasonal Energy Efficient Ratio (ISEER) of 3.5 along with the copper pipe, suitable size of PVC insulated cord wire and PVC drain pipe up to the length of 5 mtrs. including transportation, gas charging, insulation, and making opening in wall and making good the damages etc., complete as per specifications, terms and conditions attached as required. ( For item no. 1 above) 4 Nos
6 2.02 Providing and fixing the following additional items suitable for the above AC units, over and above 5 mtrs length where ever required.
7 2.03 Copper pipes (hot gas and liquid line) including insulation etc., as required. (mtr) 8 Mtr
8 2.04 3x2.5 sqmm size of PVC insulated copper condr. Flexbile cable. (mtr) 15 Mtr
9 2.05 S/F of 20 mm dia PVC wire braided water drain pipe existing 1.5 TR Split AC units as required. 20 Mtrs.
10 2.06 S/F of 32 mm dia Hard heavy duty PVC pipe i/c all accessories elbow, socket etc as required. 20 Mtrs.
11 2.07 S/F of Heavy Duty Powder coated M.S. Stand for outdoor unit i/c fixing/grouting etc as reqd. 4 Nos
12 2.08 SITC of 4 KVA single phase 50 hz automatic voltage stabilizer having following features: Input voltage : 135-270 V A/C, Output Voltage : 230 + 5%, High/Low voltage cut off, Instant start button, Inbuilt time delay. 4 Nos.
13 2.09 Wiring for ckt/submain wiring a/w earth wire with the following size of FRPVC insulated copper conductor single core cable in surface/recessed in the steel conduit as required.
14 2.1 2 x4 Sq.mm + 1x4sqmm earth wire 20 Mtrs.
15 2.11 4 x4 Sq.mm + 2x4sqmm earth wire 20 Mtrs.
16 2.12 Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required. 4 Nos.
17 2.13 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
18 2.14 4way (4 + 12), Double door 1 No.
19 2.15 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
20 2.16 Single pole 12 Nos.
21 2.17 Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.\n
22 2.18 100 amps Four Pole 1 No.
23 2.19 Supplying & fixing of 18/19 watt batten type LED light fitting etc complete i/c connection with copper wire as reqd.(M/s Philips or S/S make) 15 Nos.
24 2.2 Supplying and fixing of following type fan suitable to operate on 240 volts 50 hz A/C supply having regulator for speed control i/c testing and commissioning etc as reqd. (Make : Bajaj/Havells or SS )
25 2.21 400 mm sweep wall mounted fan 2 Nos.
26 2.22 400 mm sweep, High flo, 1900 rpm, Pedastal fan 2 Nos.
27 2.23 Supplying and fixing of 25 watt, 230 V, LED type street light fitting with suitable size GI pipe bracket with base plate/clamps i/c connection with copper wire & necessary switch etc as required. (Make:Philips/Bajaj/Havells/C&S make) 4 Job
28 2.24 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
29 2.25 Upto 35 sq. mm (clamped with 1mm thick saddle) 30 Mtrs.
30 2.26 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
31 2.27 4 X 16 sq. mm (28mm) 2 Set
32 2.28 Providing and fixing 8 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. 30 Mtrs.
33 3 SH-III (SITC of AFD system)
34 3.01 S.I.T.C. of 4 Zone solid state microprocessor based Main A.F.D. panel suitable for working on 240 V AC supply/24 V DC supply and fabricated with16swg CRCA steel sheet with louvers for ventilation, in corporating audio visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities, provision of space for 2 Nos. suitable size battery, Battery charger trickle cum boost to take complete load of fire alarm i/c S/Fixing of 2 Nos. sealed maintenance free batteries 12 V, 7 AH etc as required. (M/s Agni or any BSNL approved Make) 1 Job
35 3.02 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. 100 Mtrs.
36 3.03 Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. 15 Nos.
37 3.04 Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. 3 Nos.
38 3.05 Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required. 8 Nos.
39 3.06 Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. 3 Nos.
40 3.07 Supplying and fixing of 4.5 Kg. CO2 type fire extinguisher with suitable hose pipe & horn etc complete as reqd.(M/s Minimax or SS make)(Note: Certificate of explosive deparment should be submiited.) 5 Nos
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail