Improvement/Upgradation Of Lt Over Head Line With Under Ground Cable , Feeder Pillar Box Of Md Accn At Danapur Cantt, Danapur-Bihar

Military Engineer Services-MES has published Improvement/Upgradation Of Lt Over Head Line With Under Ground Cable , Feeder Pillar Box Of Md Accn At Danapur Cantt. Submission Date for this Tender is 29-03-2021. Feeder Pillar Tenders in Danapur Bihar. Bidders can get complete Tender details and download the document.




Tender Notice

27052082
Corrigendum : Improvement/Upgradation Of Lt Over Head Line With Under Ground Cable , Feeder Pillar Box Of Md Accn At Danapur Cantt
Open Tender
Indian
Bihar
Danapur
29-03-2021

Tender Details

Improvement/Upgradation Of Lt Over Head Line With Under Ground Cable , Feeder Pillar Box Of Md Accn At Danapur Cantt

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Mar-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 29-03-2021

Key Value

Document Fees
INR 1000 /-
EMD
INR 201000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: IMPROVEMENT/UPGRADATION OF LT OVER HEAD LINE WITH UNDER GROUND CABLE, FEEDER PILLAR BOX OF MD ACCN AT DANAPUR CANTT
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Dismantling of ACSR or AAC conductors service feeder or distributor span, of any size and removal from site complete all as specified and directed.\n 1 22 Quintal
2 2 Dismantling insulators any type, any size complete all as specified and directed. 2 460 Each
3 3 Dismantling and taking down cross arms of MS channel or angle sections, clamps, nut and bolt, washers, back plate of any size/shape complete and removal from site. completed all as specified and directed. 3 17 Quintal
4 4 Dismantling of old unserviceable earth wire / cradles of any size, service feeder or distributor span complete all as specified and directed.\n 4 2.6 Quintal
5 5 Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in any type of soil complete all as specified and directed.\n 5 2225 Cubic \nMetre
6 6 Returning, filling in, including spreading, levelling, and well ramming in layer not exceeding 25 cm thick in soft/loose soil complete all as specified and directed.\n 6 1265 Cubic \nMetre
7 7 Removing excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.\n 7 960 Cubic \nMetre
8 8 M&L laying well burnt old size bricks, sub class "B" bricks having crushing strength not less than 75 Kg / Sqcm, laid flat with width equal to length of brick , laid dry over electric cable for protection all as specified.\n 8 77 Per 1000 Nos
9 9 M&L for river sand, washed and screened dry for cushioning to under ground cable in layers of 23 cm thick (8 cm before laying the cable and 15 cm thick after laying the cable in trenches including spreading and levelling complete as specified and directed .\nNote :- Punned thickness shall only be considered for payment. 9 690 Cubic \nMetre
10 10 M&L Cement concret (1:3:6) Type C-2 using 40mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed. 10 3 Cubic \nMetre
11 11 Supplying, laying or fixing, jointing and testing LT under ground electric power cable Crossed linked polyethylene ( XLPE Cable) insulated, two or more core, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of following size / cross sectional area , laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. including necessary Clamps, nuts , bolts, washers and connecting accessories such as alluminium cable lugs, cable gland etc complete all as specified and directed. \nNote :- Excavation, earth work, sand cushioning, protection bricks and pipe shall be measured and paid separately under appropriate items \n 11
12 11.01 300 sqmm 3 ½ core 11.01 750 Running\nMetre
13 11.02 240 sqmm 3 ½ core 11.02 1150 Running\nMetre
14 11.03 185 sqmm 3 ½ core 11.03 780 Running\nMetre
15 11.04 150 sqmm 3 ½ core 11.04 850 Running\nMetre
16 11.05 95 sqmm 3 ½ core 11.05 400 Running\nMetre
17 11.06 50 sqmm 3 ½ core 11.06 950 Running\nMetre
18 11.07 35 sqmm 3 ½ core 11.07 1075 Running\nMetre
19 11.08 25 sqmm 3 ½ core 11.08 1800 Running\nMetre
20 11.09 16 sqmm 4 core 11.09 1650 Running\nMetre
21 11.1 10 sqmm 4 core 11.1 2800 Running\nMetre
22 11.11 10 sqmm 2 core 11.11 1585 Running\nMetre
23 12 M& L for earthing to FPB / Junction box complete with galvanized steel earth plate electrode 600x600x6.0mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less that 1.5 meters below normal ground level connected to galvanized iron strip 32 x 6 mm mm as earthing by means of bolts nuts and washers of galvanized iron including excavation and earth work and disposal of surplus soil including 40 mm GI tubing light grade and necessary fittings for protection of GI strip including laying of charcoal , dust and common slat , PCC 1:2: 4 type B 1 using 20 mm graded aggregate with earth pit with 40 X 40 X 6.0 mm MS angle iron frame RCC cover 40 mm thick (1:2: 4) type C1 using 20 mm graded stone aggregate reinforced with 8 mm dia round bar @ 75 mm C/C both way with plastering 15 mm thick CM ( 1: 6) internally and up to 150 mm below ground level externally . PGI funel with wire mesh ,20 mm dia medium grade GI pipe for watering complete all as shown on electrical plate No : 03 of SSR part - I 2009 and connected to earth test point including testing complete all specified and directed.\nNote:- Earth wire up to 7.5 meter connected to earth point shall be deemed to be included in unit rate. 12 50 Each Set
24 13 S&F Earth continuity conductor or main earthing lead beyond test point, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation 32x6 mm galvanised iron strip complete all as specified and directed. 13 30 Running\nMetre
25 14 M & L for Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer, complete all as directed 14 1.5 Quintal
26 15 S&F light grade Galvanised mild steel water tubing, 100mm nominal bore, complete with all fittings and laid in trenches under roads/ drains,fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers complete all as specified and directed. 15 60 Running\nMetre
27 16 S&F light grade Galvanised mild steel water tubing, 80mm nominal bore, complete with all fittings and laid in trenches under roads/ drains,fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers complete all as specified and directed. 16 30 Running\nMetre
28 17 S&F light grade Galvanised mild steel water tubing, 50mm nominal bore, complete with all fittings and laid in trenches under roads/ drains,fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers complete all as specified and directed. 17 70 Running\nMetre
29 18 S&F light grade Galvanised mild steel water tubing, 40mm nominal bore, complete with all fittings and laid in trenches under roads/ drains,fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers complete all as specified and directed. 18 120 Running\nMetre
30 19 Boring/Drilling ( horizontally) manually or mechanically by pneumatic tools under existing road ( maximum 10 M in width) suitable for passing GI tubing of 40 to 100 mm bore complete all as specified.\n 19 60 Running\nMetre
31 20 Supply and fix cable jointing kit for 1.1 KV grade cable for heat shrinkable type straight thorugh joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 185 to 240 Sqmm complete all as specified and directed. 20 3 Each
32 21 Supply and fix cable jointing kit for 1.1 KV grade cable for heat shrinkable type straight thorugh joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 70 to 150 Sqmm complete all as specified and directed. 21 3 Each
33 22 Supply and fix cable jointing kit for 1.1 KV grade cable for heat shrinkable type straight thorugh joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm complete all as specified and directed. 22 5 Each
34 23 Supply and fix cable jointing kit for 1.1 KV grade cable for heat shrinkable type straight thorugh joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 10 to 16 Sqmm complete all as specified and directed. 23 5 Each
35 24 Supply and fix cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 185 to 300 Sqmm complete all as specified and directed. 24 16 Each
36 25 Supply and fix cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 70 to 150 Sqmm complete all as specified and directed. 25 22 Each
37 26 Supply and fix cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm complete all as specified and directed. 26 25 Each
38 27 Supply and fix cable jointing kit for 1.1 KV grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core / 4 core XLPE armoured aluminium conductor cable of size 10 to 16 Sqmm complete all as specified and directed. 27 25 Each
39 28 S&F pole mounted SMC junction box/bus bar chamber for loop IN/OUT connection of street light cable of size 295x195x100 mm high heat distoration temperature, non-fusing , shockproff, rustproof, 100 % weatherproof, fire retardant- class FV-O as per IS 11731 Part-II and suitable locking arragement with three phase and neutral aluminium busbar of size 20X3 mm of length 170 mm wrapped with PVC sleeves with maintained the colour code and provision of making holes with GI nuts, bolts & washers for cable connections mounted on hydrograpic insulators with nuts & bolts at both ends of busbar complete all as specified and directed. \nMake: Sintex , Cat No: GSJB3020 or equivalent model of Hensel/Rittel as approved by the GE.\n 28 110 Each
40 29 S&F PVC Sheathed multi stranded unarmoured copper conductor cable LT 1100 volt grade Conforming to IS 7098 FRLS (inner sheet) of size 1.5 Sqmm 3 Core (Nominal Area) from pole junction box to light fitting with suitable size copper cable lugs and connector all complete as specified and directed. \nMake: Polycab/Havells/Plaza/Finolex. 29 627 Running\nMetre
41 30 Supply, fabrication, installation, commissioning and testing of LT factory made (CPRI approved) water and vermin proof protection pedestal type feeder pillar box of minimum size 1200mm x 600mm x 500mm (overalls), outdoor type made out of 3.00 mm thick CRCA sheet with frame and legs of mild steel angle iron of size 40 x 40 x 6 mm in all side with double door, front and back side openable and air ventilation arrangement including provision of cable looping box of size 600 x 450 x 400mm made out of 3 mm thick CRCA sheet with front side openable double door shutter hinged door and locking arrangement at back side complete painted with Powder Coated paint of approved shade and suitable for 3 phase 4 wire system 500 voltage grade complete wiring and all incoming connections with copper strip busbar of required size to MCCB input including PCC (1:3:6) type C-2 as in foundation of size 0.80m x 0.60m x 0.90m depth (30 cm below ground level & 60 cm above ground level) including necessary excavation and earth work complete all as specified and as directed alongwith comprising of the following accessories :- \n 30 11 Each Job
42 30.1 (a) Aluminium busbar 400 Amps capacity including insulator with nuts & bolts-04 Nos\n 30.1
43 30.2 (b) Copper busbar 200 Amps capacity including insulator with nuts & bolts-04 Nos\n 30.2
44 30.3 (c) MCCB,adjustable thermal magnetic release type of IP 66 protection,, 4 poles, 415 Volts, Lcu = 35/36 KA breaking capacity, rating 160 Amps including all fixing accessories with both ends spreader links-01 No. (Make- L&T/ Legrand/ Schneider)\n 30.3
45 30.4 (d) MCCB, adjustable thermal magnetic release type of IP 66 protection 4 pole, 415 volts, 25 KA breaking capacity rating 63 amps including all fixing accessories with both ends spreader links-04 Nos (Make- L&T/ Legrand/ Schneider).\n 30.4
46 30.5 (e) MCB SPN 40 Amps 240 volts 10 KA - 02 Nos (Make- L&T/ Legrand/ Schneider)\n 30.5
47 30.6 (f) Neon indicator lamp with holder (RYB) = 03 Nos. (Make- L&T/ Legrand/ Schneider)\n 30.6
48 30.7 (g) Digital Voltmeter of range (0-500) volt flush mounting type with selector switch = 01 No. (Make- L&T/ Legrand/ Schneider) 30.7
49 30.8 NOTE: (i) Rate of earthwork and PCC are deemed to be inclusive in this item.\n(ii) Any other items which are not mentioned above but are essential for smooth functioning shall also deemed to be included in the quoted rates. 30.8
50 31 Supply, fabrication, installation, commissioning and testing of LT factory made (CPRI approved) water and vermin proof protection pedestal type feeder pillar box of minimum size 1200mm x 600mm x 500mm (overalls), outdoor type made out of 3.00 mm thick CRCA sheet with frame and legs of mild steel angle iron of size 40 x 40 x 6 mm in all side with double door, front and back side openable and air ventilation arrangement including provision of cable looping box of size 600 x 450 x 400mm made out of 3 mm thick CRCA sheet with front side openable double door shutter hinged door and locking arrangement at back side complete painted with Powder Coated paint of approved shade and suitable for 3 phase 4 wire system 500 voltage grade complete wiring and all incoming connections with copper strip busbar of required size to MCCB input including PCC (1:3:6) type C-2 as in foundation of size 0.80m x 0.60m x 0.90m depth (30 cm below ground level & 60 cm above ground level) including necessary excavation and earth work complete all as specified and as directed alongwith comprising of the following accessories :- 31 4 Each Job
51 31.1 (a) Aluminium busbar 400 Amps capacity including insulator with nuts & bolts-04 Nos 31.1
52 31.2 (b) Copper busbar 200 Amps capacity including insulator with nuts & bolts-04 Nos 31.2
53 31.3 (c) MCCB,adjustable thermal magnetic release type of IP 66 protection,, 4 poles, 415 Volts, Lcu = 35/36 KA breaking capacity, rating 160 Amps including all fixing accessories with both ends spreader links-01 No. (Make- L&T/ Legrand/ Schneider) 31.3
54 31.4 (d) MCCB, adjustable thermal magnetic release type of IP 66 protection 4 pole, 415 volts, 25 KA breaking capacity rating 63 amps including all fixing accessories with both ends spreader links-01 Nos (Make- L&T/ Legrand/ Schneider). 31.4
55 31.5 (e) MCB SPN 40 Amps 240 volts 10 KA - 10 Nos (Make- L&T/ Legrand/ Schneider). 31.5
56 31.6 (f) Neon indicator lamp with holder (RYB) = 03 Nos (Make- L&T/ Legrand/ Schneider). 31.6
57 31.7 (g) Digital Voltmeter of range (0-500) volt flush mounting type with selector switch = 01 No (Make- L&T/ Legrand/ Schneider). 31.7
58 31.8 NOTE: (i) Rate of earthwork and PCC are deemed to be inclusive in this item.\n(ii) Any other items which are not mentioned above but are essential for smooth functioning shall also deemed to be included in the quoted rates. 31.8
59 32 Supply, fabrication, installation, commissioning and testing of LT out door type factory made CPRI Approved , junction box of size 900mmX600mmX400mm (over all dimension) made out of 3.00 mm thick CRCA sheet dully supported with mild steel angle iron of size 25X25X5mm vertical frame and legs with mild steel flat iron 25X5 mm in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of size 0.80m X 0.6m X 0.90m depth (0.30m below ground level and 0.60m above ground level ) and connections of all outgoing / incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables including the following fitment accessories all complete as specified and as directed.\n 32 12 Each Job
60 32.1 (a) Alluminium bus bar of size 50 mm X 6 mm X 400mm long wrapped with PVC sleeves with maintained the colour code and provision of making holes as required with nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends = 04 Nos.\n 32.1
61 32.2 (b) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No. 32.2
62 32.3 NOTE: (i) Rate of earthwork and PCC are deemed to be inclusive in this item.\n(ii) Any other items which are not mentioned above but are essential for smooth functioning shall also deemed to be included in the quoted rates. 32.3
63 33 Supply, fabrication, installation, commissioning and testing of LT wall mounting Panel board of size 1000 mm (height) x 1000 mm (breadth) x 300 mm (depth) factory made CPRI approved panel, weather, dust & vermin proof indoor, double door, front openable, including four compartment for fixing of four Nos single phase meter and MCB and providing glass view for reading of meter and providing rubber / PVC gasket of suitable size all sides of door, with copper busbar wrapped with PVC tape/ sleeves with maintained colour code and copper strip / wire busbar of suitable size to MCB input and MCCB/ MCB output of suitable length for connection of cable from main bus bar and copper strip of size 25x5mm, length 50cm as earth strip, made out of 2.0 mm thick mild steel CRCA sheet with suitable size angle iron supporting frame including applying two coats of powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 1.5 sqmm copper wire and connections of all outgoing / incomming LT cable of any size are as follows :-\n 33 9 Each Job
64 33.1 INCOMMING\nCopper strip busbar of size 25 x 5 mm wrapped with PVC sleeves with maintained the colour code and provision of making holes with copper nuts, bolts & washers for cable connections including hydrographic insualtors with nuts & bolts at both ends - 04 Nos\n 33.1
65 33.2 (b) MCCB IP 44 and IP 66/67 protection, 4 pole 415 volts, Lcu= 25 KA breaking capacity, rating 63 Amps adjustable thermal magnetic release including all fixing accessories with both ends spreader links - 01 Nos, Make- L&T/ Legrand/ Schneider. 33.2
66 33.3 (c) Digital voltmeter of range (0-100) volts, flush mounting type of size 100mm x 100 mm (4" x 4") square dia with selector switch - 01 No (Make- L&T/ AE/ Schneider)\n\n 33.3
67 33.4 (d) LED Neon indicator lamp (RYB) with holder 230/250 volts AC - 01 set (set of three) Make - (Make- L&T/ Legrand/ Schneider) 33.4
68 33.5 OUTGOING\n(a) MCB Single pole and neutral (SPN) 32 amps, 240 volts, 'C' curve 10 KA all complete as specified and directed. - 08 Nos (Make- L&T/ Legrand/ Schneider) 33.5
69 33.6 (b) Single Phase Electronic Energy Meter accuracy Class 1.0, 240V, with in-home display 5-30 A, 3 nos self locking meter seal, LCD diplay with optical port, anti temper features, LCD test ,serial no, Date, RTC,Cumulative Kwh, Last bill Kwh, Instanteous Load, Last bill MD, Instantaneous KW,Volts,PF,HZ, MD, total Tamper Count, Self Billing Code, Battery backup in absence of power for display active energy kwh, including all incoming and out goinig connections. = 04 Nos (Make- L&T, Cat No:WM101BC5DDH / Secure) 33.6
70 33.7 NOTE: Any other items which are not mentioned above but are essential for smooth functioning shall also deemed to be included in the quoted rates. 33.7
71 34 Supply, fabrication, installation, commissioning and testing of LT wall mounting Panel board of size 900 mm (height) x 700 mm (breadth) x 300 mm (depth) factory made CPRI approved panel, weather, dust & vermin proof indoor, double door, front openable, including two compartment for fixing of two Nos single phase meter and MCB and providing glass view for reading of meter and providing rubber / PVC gasket of suitable size all sides of door, with copper busbar wrapped with PVC tape/ sleeves with maintained colour code and copper strip / wire busbar of suitable size to MCB input and MCCB/ MCB output of suitable length for connection of cable from main bus bar and copper strip of size 25x5mm, length 50cm as earth strip, made out of 2.0 mm thick mild steel CRCA sheet with suitable size angle iron supporting frame including applying two coats of powder coated paint over a coat of red oxide zinc chrome primer over exposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 1.5 sqmm copper wire and connections of all outgoing / incomming LT cable of any size are as follows :-\n\n 34 12 Each Job
72 34.1 INCOMMING\nCopper strip busbar of size 25 x 5 mm wrapped with PVC sleeves with maintained the colour code and provision of making holes with copper nuts, bolts & washers for cable connections including hydrographic insualtors with nuts & bolts at both ends - 04 Nos\n 34.1
73 34.2 (b) MCCB IP 44 and IP 66/67 protection, 4 pole 415 volts, Lcu= 25 KA breaking capacity, rating 63 Amps adjustable thermal magnetic release including all fixing accessories with both ends spreader links - 01 Nos (Make- L&T/ Legrand/ Schneider) 34.2
74 34.3 (c) Digital voltmeter of range (0-100) volts, flush mounting type of size 100mm x 100 mm (4" x 4") square dia with selector switch - 01 No (Make- L&T/ AE/ Schneider)\n\n 34.3
75 34.4 (d) LED Neon indicator lamp (RYB) with holder 230/250 volts AC - 01 set (set of three) Make - (Make- L&T/ Legrand/ Schneider). 34.4
76 34.5 OUTGOING\n(a) MCB single pole 32 amps, 240 volts, 'C' curve 10 KA all complete as specified and directed. - 04 Nos (Make- L&T/ Legrand/ Schneider) 34.5
77 34.6 (b) Single Phase Electronic Energy Meter accuracy Class 1.0, 240V, with in-home display 5-30 A, 3 nos self locking meter seal, LCD diplay with optical port, anti temper features, LCD test ,serial no, Date, RTC,Cumulative Kwh, Last bill Kwh, Instanteous Load, Last bill MD, Instantaneous KW,Volts,PF,HZ, MD, total Tamper Count, Self Billing Code, Battery backup in absence of power for display active energy kwh, including all incoming and out goinig connections. = 02 Nos (Make- L&T, Cat No:WM101BC5DDH / Secure) 34.6
78 34.7 NOTE: Any other items which are not mentioned above but are essential for smooth functioning shall also deemed to be included in the quoted rates. 34.7