Military Engineer Services-MES has published Repair And Replacement Of Three Nos Transformer At Si Line Bhopal Under Ge Bhopal. Submission Date for this Tender is 10-02-2021. Transformer Supply Tenders in Bhopal Madhya Pradesh. Bidders can get complete Tender details and download the document.
Name of Work: REPAIR AND REPLACEMENT OF THREE NOS TRANSFORMER AT SI LINE BHOPAL UNDER GE BHOPAL | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Supplying, installing, connecting, testing & commissioning mineral oil immersed, natural air-cooled, outdoor type, double wound (copper) distribution transformer, three phase, 160 kVA rating, non sealed type, 50 Hz rated frequency, 11 kV high voltage and 415 V low voltage nominal system voltage, minimum 75 kVp basic insulation level, 11000 V/ 433-250 V no-load voltage ratio, connection (vector) symbol Dyn11, 30° positive phase displacement, off circuit tap changing arrangement for voltage variations of +2.5% to -5% in steps of 2.5% for variation of HV, energy efficiency level 1, 4.5% impedance, ONAN type cooling all as per IS-1180 (Part 1): 2014 complete with all fittings, accessories and item as specified and as directed. | 19166C | 2 | Each |
2 | 2 | Supplying, installing, connecting, testing & commissioning mineral oil immersed, natural air-cooled, outdoor type, double wound (copper) distribution transformer, three phase, 100 kVA rating, non sealed type, 50 Hz rated frequency, 11 kV high voltage and 415 V low voltage nominal system voltage, minimum 75 kVp basic insulation level, 11000 V/ 433-250 V no-load voltage ratio, connection (vector) symbol Dyn11, 30° positive phase displacement, off circuit tap changing arrangement for voltage variations of +2.5% to -5% in steps of 2.5% for variation of HV, energy efficiency level 1, 4.5% impedance, ONAN type cooling all as per IS-1180 (Part 1): 2014 complete with all fittings, accessories and item as specified and as directed. | 19165E | 1 | Each |
3 | 3 | M & L for earthing complete with copper plate earth electrode 600 mm X 600 mm X 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 20 mm X 3 mm copper strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. | 19474A | 12 | Each |
4 | 4 | S & F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 mm X 3 mm copper strip complete all as specified and as directed. | 19488A | 60 | Running Metre |
5 | 5 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed. | 03006A | 14 | Cum |
6 | 6 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. | 03009A | 3 | Cum |
7 | 7 | Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point | 03029A | 11 | Cum |
8 | 8 | M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. | 04025B | 4 | Cum |
9 | 9 | M & L for brick work with sub class 'B' bricks, non-modular sizes as per IS 1077: 1992, straight or curved on plan exceeding 6 m mean radius built in cement mortar 1:6 complete all as specified and as directed. | 05004H | 15 | Cum |
10 | 10 | Material and labour for plastering 10 mm thick on fair faces of brick work or concrete surfaces (on vertical surfaces) in cement mortar 1:6 finished even and fair complete all as specified and as directed. | 14001Q | 40 | Sqm |
11 | 11 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 95 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. | 19246C | 40 | Running Metre |