Power Development Department has published Supply , Installation , Testing And Commissioning Of Infrastructure For Creation Of 100 Kva Sub-Station Phe Along With Ht/Lt Network At Hayatpura In Block Manjakote District Rajouri Under Water Supply Scheme. Submission Date for this Tender is 30-01-2021. Substation Tenders in RAJOURI Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Name of Work: Creation of 1 x 100 kVA PHE S/Stn along with HT and LT Network at Hayatpura under WSS on Turnkey Basis for PHE Division Rajouri. (All the items should be as per latest specifications and drawing adopted/Approved by Department) | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Erection of 11 KV (HT) Line\n(Note: For detailed specifications please refer attached SBD which forms a part of the tender) | |||
2 | 1.01 | Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410, SP-15) with pit excavation. (As per recommended IS/REC Standard) | item1.01 | 11 | Nos |
3 | 1.02 | Supplying and erection of GI Channel “V’' cross-arm (75 x 40x6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole structure. \nNOTE: Please refer Pole drawings for details (As per recommended IS/REC Standard) | item1.02 | 200 | Kgs |
4 | 1.03 | Supplying and fixing of 11 kV Pin Insulators (polymer) with Pins ( 5 KN) (As per recommended IS/REC Standard) | item1.03 | 27 | Nos |
5 | 1.04 | Supplying and fixing of 11 kV Disc Insulators (polymer) Complete with fittings (45KN) depending upon conductor size. (As per recommended IS/REC Standard) | item1.04 | 12 | Nos |
6 | 1.05 | Supply and erection Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete for 11 KV Tension points. (As per recommended IS/REC Standard) | item1.05 | 3 | Nos |
7 | 1.06 | Supplying and fixing of Galvanized Nuts and Bolts of sizes. | item1.06 | 15 | Kgs |
8 | 1.07 | Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of conductor including joints with PG clamps of required size\n30 mm2 ACSR ( Weasel) (As per recommended IS/REC Standard) | item1.07 | 1.5 | Kms |
9 | 2 | Erection of 11/0.433 kV Distribution Transformer\n(Note: For detailed specifications please refer attached SBD which forms a part of the tender) | |||
10 | 2.01 | Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and installation of 100kVA, 11/0.433 kV Distribution Transformer, Energy Efficiency Level-II, Aluminium Wound, oil filled, with LT cable termination box with detachable Aluminium Gland Plate.(As per recommended IS/REC Standard) | item2.01 | 1 | Nos |
11 | 2.02 | Supply and installation of LT bi-metalic connectors for making connection from DT bush rod to aluminium cables (As per recommended IS/REC Standard) | item2.02 | 12 | Nos |
12 | 2.03 | Supplying and fixing of 11 kV Pin Insulators (polymer) with Pins ( 5 KN) (As per recommended IS/REC Standard) | item2.03 | 3 | Nos |
13 | 2.04 | Supply and installation of 11 kV Disc Insulators (polymer) Complete with fitting( 45 KN) (As per recommended IS/REC Standard) | item2.04 | 3 | Nos |
14 | 2.05 | Supply and installation of Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type (As per recommended IS/REC Standard) | item2.05 | 1 | Set |
15 | 2.06 | Supply and installation of 11 kV, G.O AB Switch , 3-phase, 200A (As per recommended IS/REC Standard) | item2.06 | 1 | Set |
16 | 2.07 | Supply and installation of 11 kV Horn, Gap Fuse Set, 3-phase, 100A (As per recommended IS/REC Standard) | item2.07 | 1 | Set |
17 | 2.08 | Supply and fixing of Un Armoured Single Core XPLE, FRLS Cable (185 mm2) (As per recommended IS/REC Standard) | item2.08 | 44 | Mtr |
18 | 2.09 | Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410 SP-15) with pit excavation\n(Note: The poles shall be provided by JKPDD) (As per recommended IS/REC Standard) | item2.09 | 2 | Nos |
19 | 2.1 | Supplying and erection of GI channel/angle cross arms including fixing GI channels ( 100x50x6mm) / (75x40x6 mm) / angles(50x50x6 mm) with 50X8 mm back clamps without drilling/punching holes in the poles. (As per recommended IS/REC Standard) | item2.10 | 300 | Kgs |
20 | 2.11 | Supply and erection Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nutbolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete for 11 KV Tension points as per REC standard. (As per recommended IS/REC Standard) | item2.11 | 2 | Set |
21 | 2.12 | Excavation of Earthing Pits of dia = 600 mm and depth= 3000 mm, Supplying and fixing of 3 No. sub station earthing by GI Pipe 40 mm or GI Rod 20mm, 2.5 mtr long through GI Strip of 50X6 mm 1 no for neutral earthing and 25X3 mm 2 nos (for 2 Nos transformer body earth, 2 Nos Pole earth, 1 no. LA Earth and 1 no. GO handle earth). (Note: For LA Earth 1 pipe shall be kept separate) GI Nuts, Bolts and Clamps, refilled with earth enhancement materials and earthing chamber made of brick masonary with RCC Slab Cover. (As per recommended IS/REC Standard) | item2.12 | 3 | Nos |
22 | 2.13 | Supplying and fixing of Galvanized Nuts and Bolts of sizes. | item2.13 | 15 | Kgs |
23 | 3 | Erection of of LT Line on Conductor, 3-Ph, 4-wire,\n(Note: For detailed specifications please refer attached SBD which forms a part of the tender) | |||
24 | 3.01 | Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410, SP-15) with pit excavation. (As per recommended IS/REC Standard) | item3.01 | 1 | Nos |
25 | 3.02 | Supply and fixing of Mukky clamps for LT Shackle insulators with GI back clamps to be fixed without drilling/punching of poles on ST poles. (As per recommended IS/REC Standard) | item3.02 | 4 | Nos |
26 | 3.03 | Supplying and fixing of Shackle Insulators (polymer) ( 16 KN) (As per recommended IS/REC Standard) | item3.03 | 4 | Nos |
27 | 3.04 | Supplying and fixing of Galvanized Nuts and Bolts of sizes. | item3.04 | 4 | Kgs |
28 | 3.05 | Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of conductor including joints with PG clamps of required size\n30 mm2 ACSR (Weasel) (As per recommended IS/REC Standard) | item3.05 | 0.1 | Kms |