Maintenance Of Water Supply Sys Incl Repair To Pump Set Motor Control Panelstarter Pump Mains Digici Pipes Valves At Yph Empressgarden Maint Rene Rep Of Int Elect Incl All Int Accy Submain Wiringfangeyser Etcfor Mdotm Accn Of Jcoor At Tb2 Under Ageemi In , DIGHI PUNE-Maharashtra

Military Engineer Services-MES has published Maintenance Of Water Supply Sys Incl Repair To Pump Set Motor Control Panelstarter Pump Mains Digici Pipes Valves At Yph Empressgarden Maint Rene Rep Of Int Elect Incl All Int Accy Submain Wiringfangeyser Etcfor Mdotm Accn Of Jcoor At Tb2 Under Ageemi In . Submission Date for this Tender is 16-02-2021. Submersible Pump Tenders in DIGHI PUNE Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

26690162
Corrigendum : Maintenance Of Water Supply Sys Incl Repair To Pump Set Motor Control Panelstarter Pump Mains Digici Pipes Valves At Yph Empressgarden Maint Rene Rep Of Int Elect Incl All Int Accy Submain Wiringfangeyser Etcfor Mdotm Accn Of Jcoor At Tb2 Under Ageemi In
Open Tender
Indian
Maharashtra
DIGHI PUNE
16-02-2021

Tender Details

Maintenance Of Water Supply Sys Including Repair To Pump Set Motor Control Panelstarter Pump Mains Digici Pipes Valves At Yph Empressgarden Maint Rene Rep Of Int Elect Incl All Int Accy Submain Wiringfangeyser Etcfor Mdotm Accn Of Jcoor At Tb2 Under Ageemi In Geckke

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Feb-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-02-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 80180.0 /-
Tender Value
INR 40.09 Lakhs /-

BOQ Items

Name of Work : MAINT OF WATER SUPPLY SYSTEM INCL REPAIR TO PUMP SET, MOTOR, CONTROL PENELS/STARTER, PUMPING MAINS,DI/GI/CI PIPES VOLVES, PAINTING ETC AT TB-II, YPH & EMPRESS GARDEN AND MAINT, RENEWAL REPAIR OF INTERNAL ELECTRIFICATION INCL ALL INTERNAL ACESSORIES, SUBMAIN WIRING, FAN, GEYSER ETC FOR MD/OTM ACCN OF JCOs/OR AT TB-II UNDER AGE E/M-I IN GE (C) KIRKEE
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth for laying of pipes etc and getting out in soft / loose soil complete all as specified and directed. 200 Cum
2 2 Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth for lying of pipes etc and getting out in road cuttings/Hard dense soil complete all as specified and directed. 25 Cum
3 3 Removing surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and directed. 30 Cum
4 4 Returning filling in trenches including spreading, leveling, watering and well ramming in layers n . Exc 25 cm complete all as specified and directed. 195 Cum
5 5 Repairs,Renewal of pipie lines and Attending emergency water supply breakdown complaints within 6 hours on telephonic intimation/SMS by arranging JCB/Excavator for excavation,braking footpath paved with PCC blocks,PCC flooring,bituminus road etc up to 4 mtrs depth,dewatering with suitable dewatering pump,cutting and removing defective pipes,lowering the required size of pipes,valves and fittings with the help of crane and welding works if any,refilling the trench after repair with excavated soil,relaying of removed PCC blocks and matching with sorroundings etc complete including PCC work as directed at site. Note.1) Materials required for the repairs such as pipes,fittings,valves,Mechanical joints, PCC,PCC blocks etc will be measured and paid under respective items. 2) Items such as Rubber gaskets,Nuts,bolts and washers etc are to be included in the quoted rate.3) the contractor shall provide sufficiant barricades,caution tape,dander boards etc at work site to avoid any accidents at site. 4) If the contractor fails to start the work within 6 hours on receipt of telephonic intimation /SMS , Necessary recovery will be made twice the quoted rates of respective items.5) Compensation if any due to any accident at site to be borne by the contractor. 4 Job
6 6 M & L for taking up cast iron water mains (incl all fitting) 80mm bore dia of pipe with spigot and socket ends from trenches complete all as psecified and directed. 18 RM
7 7 All as item no.6 above but size of pipe 100 mm bore 36 RM
8 8 All as item no.6 above but size of pipe 150 mm bore 36 RM
9 9 All as item no.6 above but size of pipe 200 mm bore 24 RM
10 10 All as item no.6 above but size of pipe 250 mm bore 20 RM
11 11 All as item no.6 above but size of pipe 300 mm bore 20 RM
12 12 M & L for Cutting cast iron pipes in position for insertion of fittings, mechanical joints, replacement of pipes etc for bore of pipe 80mm 4 Each
13 13 All as item no.12 above but 100 bore pipes 4 Each
14 14 All as item no.12 above but 150 bore pipes 4 Each
15 15 All as item no.12 above but 200 bore pipes 4 Each
16 16 All as item no.12 above but 250 bore pipes 2 Each
17 17 All as item no.12 above but 300 bore pipes 2 Each
18 18 M & L for Laying only 80 mm bore CI pipes with spigot and socket ends laid in trenches including thorough cleaning of old CI pipe by descaling internally with steel brushes equal to bore of pipe, scraping washing properly complete all as specified and directed. (to be measured only found serviceable in all respect retrived from item No 6). 6 RM
19 19 All as item no.18 but bore of pipe 100 mm.( servicable pipe received against item no.7) 12 RM
20 20 All as item no.18 but bore of pipe 150 mm.( servicable pipe received against item no.8) 12 RM
21 21 All as item no.18 but bore of pipe 200 mm.( servicable pipe received against item no.9) 6 RM
22 22 All as item no.18 but bore of pipe 250 mm.( servicable pipe received against item no.10) 6 RM
23 23 All as item no.18 but bore of pipe 300 mm.( servicable pipe received against item no.11) 6 RM
24 24 M & L for Ductile iron fittings such as bends (any type, radius and angle), tapers any type (straight, bend, incresing, decreasing or double socket etc.), Tee piece, single branch 'Y'junction double branch, collar etc., caps and plugs etc. as per IS: 9523-2000 of class K-7, with internal cement mortor lining, and external zinc and black bitumen coated of dia upto 150 mm complete all as specified and directed 200 Kg
25 25 M & L for Ductile iron fittings such as bends (any type, radius and angle), tapers any type (straight, bend, incresing, decreasing or double socket etc.), Tee piece, single branch 'Y'junction double branch, collar etc., caps and plugs etc. as per IS: 9523-2000 of class K-7, with internal cement mortor lining, and external zinc and black bitumen coated of dia upto 200 to 300mm complete all as specified and directed 120 Kg
26 26 Supply, laying, jointing & testing DI-K7 class with spigot and socket, suitable for Push on rubber joint, with internal cement mortor lining, and external zinc and black bitumen coated pipes in any lengths conforming to IS:8329-2000 including Rubber Gasket & joints as per IS:9523-2000 laid in trenches/ Road/ Ducts/ Footpath/ on wall/ on floor locations for 80 mm bore dia pipe complete all as specified and directed. Make: Electro steel/Electro cast. 18 RM
27 27 All as item no.26 above but 100 mm bore pipes. 24 RM
28 28 All as item no.26 above but 150 mm bore pipes. 24 RM
29 29 All as item no.26 above but 200 mm bore pipes. 18 RM
30 30 All as item no.26 above but 250 mm bore pipes. 14 RM
31 31 All as item no.26 above but 300 mm bore pipes. 14 RM
32 32 M&L for Laying,jointing and testing MS Pipe 450 mm to 500 mm bore, 7mm thick externally coated with anti corrosive paint with welded joints laid in trenches in short lengths as required at site up to 4 met in depth including taking out defective pipes all as directed at site. 24 RM
33 33 M&L for taking up worn out GI steel tubing incl all fitings fron trenches of 15 mm bore complete all as specified and directed. 80 RM
34 34 All as item no.33 above but 20 mm bore pipes. 150 RM
35 35 All as item no.33 above but 25 mm bore pipes. 200 RM
36 36 All as item no.33 above but 40 mm to 50 mm bore pipes. 250 RM
37 37 All as item no.33 above but 80 mm bore pipes. 36 RM
38 38 All as item no.33 above but 100 mm bore pipes. 24 RM
39 39 All as item no.33 above but 150 mm bore pipes. 12 RM
40 40 M&L for Laying in trenches/fixed to wall galvanised steel water tubing 15 mm bore, medium grade with and including all medium grade fittings complete all as specified. Make:Tata/Jindal. 80 RM
41 41 All as item no.40 above but 20 mm bore pipes. 150 RM
42 42 All as item no.40 above but 25 mm bore pipes. 200 RM
43 43 All as item no.40 above but 40 mm bore pipes. 150 RM
44 44 All as item no.40 above but 50 mm bore pipes. 100 RM
45 45 All as item no.40 above but 80 mm bore pipes. 36 RM
46 46 All as item no.40 above but 100 mm bore pipes. 24 RM
47 47 All as item no.40 above but 150 mm bore pipes. 12 RM
48 48 M&L for taking appart and reassembling stuffing box of sluice valve S.S. Spindle in position suitable for existing sluice valve including replacement of gland packing. Note: (i) Nuts, bolts & washers wherever required new shall be measured and paid separately as supply only. 12 Each
49 49 S&F in repairs CI body non raising SS spindle sluice valve with cast iron wheel, of size 80 mm bore, class PN-1.6 with SS spindle with brass nut, both ends flanged confirming to IS-14846 with standard bolts hole, fixing with nuts, bolts, washers, rubber gasket etc complete in position of pipe line all as specified and directed. \nNote for item no.49 to 54: (i) Nuts, bolts & washers wherever required new shall be measured and paid separately under respective item. (ii) Rubber gasket shall be inclusive of the quoted rate. 2 Each
50 50 All as item no.49 above but 100 mm bore 1 Each
51 51 All as item no.49 above but 150 mm bore 2 Each
52 52 All as item no.49 above but 200 mm bore 2 Each
53 53 All as item no.49 above but 250 mm bore 1 Each
54 54 All as item no.49 above but 300 mm bore 1 Each
55 55 All as item no.49 above but 450 mm bore 1 Each
56 56 S&F in repairs cast iron air release valves with air outlet,100 mm dia flanged including fittings as required at site, making necessary modification/ arrangements and on CI/MS/DI pipeline of bore up to 450 mm 2 Each
57 57 M &L for dismentling & taking out carefully sluice valve head with gate, spindle and stuffing box of size 80 mm to 450 mm bore in position, replacement of worn out SS/GM spindle & GM nut with new SS/GM spindle or GM nut for sluice valve class PN 1.6/ 1.0, and refixing gate, spindle, nut, valve head with stuffing box incl necessary PTFE gland packing, nuts, bolts, washers, gland bolts, rubbers gaskets etc complete all as specified and as directed. \nNote: (i) SS/GM spindle, GM/SS nuts shall be measured and paid separately under respective items. (ii) Nuts, bolts & washers wherever required new shall be measured and paid separately under respective item. (iii) PTFE gland packing and Rubber gasket shall be inclusive of the quoted rate of this item. 8 Each
58 58 Supply and fix SS spindle for sluice valve class PN 1.6/ 1.0, 80 mm to 150 mm bore 4 Each
59 59 Supply and fix SS spindle for sluice valve class PN 1.6/ 1.0, 200 mm to 300 mm bore 3 Each
60 60 Supply and fix SS spindle for sluice valve class PN 1.6/ 1.0, 450 mm bore 1 Each
61 61 Supply and fix SS nut suitably threaded internally as per spindle thread and to the size of wedge of valve gate for sluice valve 80 mm to 150 mm bore class PN 1.6/ 1.0 complete all as directed. 4 Each
62 62 All as item no.61 above but 200 mm to 300 mm sluice valve 3 Each
63 63 All as item no.61 above but 450 mm sluice valve 1 Each
64 64 S&F in repair gun metal gate valve with iron wheel head, screwed both ends for iron pipes 15mm bore complete all as specified and directed.Make Zoloto/Equivalent. 4 Each
65 65 All as item no.64 above but 20 mm bore 6 Each
66 66 All as item no.64 above but 25 mm bore 6 Each
67 67 All as item no.64 above but 40 mm bore 4 Each
68 68 All as item no.64 above but 50 mm bore 3 Each
69 69 Supply & fixing in repairs cast Iron swing check non return valve confirming to IS : 5312 (Part I) of 1969, both end flanged with rubber gasket & Nuts, bolts & washersof sizes 150 mm bore. \n(Note:- Nuts, bolts & washers wherever required new shall be measured in appropriate item as supply only ) 1 Each
70 70 All as item no.69 above but 80 mm bore. 1 Each
71 71 Supply & fixing in repairs cast Iron foot valve confirming to IS : 4038 flanged end with rubber gasket, Nuts, bolts & washers of sizes 150 mm bore. \n(Note:- Nuts, bolts & washers wherever required new shall be measured in appropriate item as supply only ) 3 Each
72 72 All as item no.71 above but 100 mm bore 1 Each
73 73 All as item no.71 above but 80 mm bore 1 Each
74 74 Supply and fix Mild steel screw bolts (machine made) with hexagonal heads at one end and screwed the other, each screwed end to be fitted with washers and one hexagonal nut, n exc 10 cm long , 10 to 20 mm dia of neck. 50 Kg
75 75 S&F MS mechanical joint with rubber washer, mild steel screw bolts (machine made) with screwed both ends of dia as per flange hole and required length each screwed end to be fitted with washers and one hexagonal nut suitable for bore of pipe 80mm complete all as specified. 4 Each
76 76 All as item no.75 above but 100 mm size. 4 Each
77 77 All as item no.75 above but 150 mm size. 6 Each
78 78 All as item no.75 above but 200 mm size. 6 Each
79 79 All as item no.75 above but 250 mm size. 4 Each
80 80 All as item no.75 above but 300 mm size. 4 Each
81 81 M&L for M & L for PCC (1:5:8) type C5 block masonry over 10 cm in width built in cement mortar (1:6) complete all as specified incl Demolition of unsv precast concrete block walling built in cement morter all as specified and directed. 4 Cum
82 82 M&L for cement plaster 10mm thick in CM1:4 on fair faces of brick work or concrete surfaces finished even and fair incl taking down plaster any description, racking out joints, hacking for key, scrubbing down with water complete all as specified. 80 Sqm
83 83 M&L for PCC 1:3:6 type-C2 (using 40mm graded stone aggregate) as in foundation, filling and mass concrete incl necessary form work werever required and incl demolition of Cement Concrete (un-reinforced) of any description and in any position not otherwise specifically provided for, all as specified and directed at site. 2 Cum
84 84 M&L for mild steel framed work with ends of bars souldered, welded or reveted or forced into spikes, framed guard bars, ladders, framed balusters, walk ways, railings, gates, frame work of water tank, valvepit and similar work confirming to Fe.290.Gde-E-165 incl painting with one coat of red oxide primer and one coats of anticorrosive black bituminous paint incl dismantling mild steel work of any description not otherwise specially provided for all as specified and directed. 120 Kg
85 85 M&L for one coat of synthetic enamel paint to old steel surfaces of any description, incl preparation of surfaces, for area over 10cm in width or girth,not otherwise described as per specified colour code all as specified and directed. 100 Sqm
86 86 M&L for preparation of plastered or unplastered surfaces of wall and applying one coat of cement based paint of approved tint complete all as specified and directed. 60 Sqm
87 87 M&L for preparation of plastered or unplastered surfaces of wall and applying two coats of cement based paint of approved tint complete all as specified and directed. 80 Sqm
88 88 M&L Cement concrete type B-2,1:2;4 ( 40 mm graded stone aggregate ) in sub base 75 mm thick 60 sqm
89 89 S&F 80 mm thick machine pressed precast concrete rubber moulded coloured interlocking paver block with coloured cement and pigment any shape and size confirming to IS-15658-2006 M-40 grade laid over 50 mm thick sand cushionining all as directed. 60 sqm
90 90 Supply and fix Hot Dipped Galvanized Chain Link Fencing with Zinc Coating, nominal height-2400mm, Pitch-50mm and wire dia 3.15 mm. (approx weight-2.55 Kg /Sqm) 120 Kg
91 91 M&L for mild steel work of angle fixed independently for fencing post and others confirming to Gde Fe 410-A incl cutting to dead end length where required, notching, drilling, fitting and/or welding or connecting with bolts and nuts incl dismentling taking down unsv one complete all as specified and directed. 180 Kg
92 92 M&L for TMT bars 10mm dia and over cut to length, bent to shape required, including cranking, bending spirally for hooping for columns hooking ends or as in horizontal bar for fixing in fencing and binding with and including mild steel wire (anealed) not less than 0.9mm dia or securingwith clips complete for support of chain link fencing incl dismentling taking down unsv one all as specified and directed. 60 Kg
93 93 Dismantling,transporting to service centre of water meter 450mm dia 300 to 450 cum /Hr flow for calibration and servicing including replacement of defective parts,complete set to work and re installing at site all as directed. 1 Each
94 94 Dismantling taking out complete pump of any type, capacity 90 HP to 100 HP from foundation including dismentling suction and delivery pipe connection from pump , carrying to wksp & back and repair/overhauling complete and reassemble and fixing to original position after repair/overhauling with nuts, bolts, washers, pipe connection complete including testing, commissioning all as specified and directed. ( Note-1.spares required for the repairs will be measured and paid under respective items . 2. Small items such as gaskets, Nuts,bolts and washers,screws, consumable like grease etc will be inclusive of quoted rates.) 2 Job
95 95 Ball Bearing, (DE). 2 Each
96 96 Ball Bearing (NDE). 2 Each
97 97 Impeller. 2 Each
98 98 Pump Shaft. 1 Each
99 99 Lantern Ring. 2 Each
100 100 Mechanical Seal. 2 Each
101 101 Water Deflector. 2 Each
102 102 Sleeve. 1 Each
103 103 Key Impeller. 1 Each
104 104 Gland Packing. 2 Each
105 105 Dismantling taking out complete pump of any type, capacity 15 HP to 30 HP of different models from foundation including dismentling suction and delivery pipe connection from pump , carrying to wksp & back and repair/overhauling complete and reassemble and fixing to original position after repair/overhauling with nuts, bolts, washers, pipe connection complete including testing, commissioning all as specified and directed.( Note-1.spares required for the repairs will be measured and paid under respective items . 2. Small items such as gaskets, Nuts,bolts and washers,screws, consumable like grease etc will be inclusive of quoted rates.) 1 Job
106 106 Ball Bearing, (DE). 1 Each
107 107 Ball Bearing (NDE). 1 Each
108 108 Impeller. 1 Each
109 109 Pump Shaft. 1 Each
110 110 Lantern Ring. 1 Each
111 111 Mechanical Seal. 1 Each
112 112 Water Deflector. 1 Each
113 113 Sleeve. 1 Each
114 114 Key Impeller. 1 Each
115 115 Gland Packing. 1 Each
116 116 Dismantling taking out Induction motor 90 Hp to 100 Hp from foundation by removing electric connection, coupling carefully and carrying to wksp & back for repair complete and reassemble and fixing to original position after repair/overhauling with nuts, bolts, washers, pipe connection and cable connection complete including testing, commissioning, proper alignment all as specified and directed. 2 Job
117 117 Dismantling taking out Induction motor 15 Hp to 30 Hp from foundation by removing electric connection, coupling carefully and carrying to wksp & back for repair complete and reassemble and fixing to original position after repair/overhauling with nuts, bolts, washers, pipe connection and cable connection complete including testing, commissioning, proper alignment all as specified and directed. 1 Job
118 118 M&L for complete rewinding of motor any type after cutting, taking out old damaged winding from stator core, cleaning of slots, providing proper insulating materials/lock strip in the slots, rewinding with existing size of super enamelled coper wire, required binding, bonding, insulation, varnishing and drying and proper testing after rewinding for motor capacity 90 HP to 100 HP 2 Job
119 119 M&L for complete rewinding of motor any type after cutting, taking out old damaged winding from stator core, cleaning of slots, providing proper insulating materials/lock strip in the slots, rewinding with existing size of super enamelled coper wire, required binding, bonding, insulation, varnishing and drying and proper testing after rewinding for the following sizes of motor capacity 15 HP to 30 HP 1 Job
120 120 Repair/maintenance/overhauling in situ of Pump starter panel by dismantling taking out old damaged panel wiring, replacement of Contactor, relays, Timer, Push buttion, single phase preventor, voltmeter, ammeter, LED indicator and other miscellenious items as required and testing complete after completion of work. Note: spares required for the repairs will be measured and paid under respective items. 3 Job
121 121 M&L for AC Contactor, 3 pole, 3 ph, 415V, AC, 50Hz, Type- ML-2 to ML-5 , Make- L&T, or equivelent of equivelent of Schneider/ABB/C&S 3 Each
122 122 M&L for AC side mounting add on aux contact block for contactor Make- L&T, or equivelent of Schneider/ABB/C&S 3 Each
123 123 M&L forAC front add on aux contact block Make- L&T, or equivelent of Schneider/ABB/C&S 3 Each
124 124 M&L forThermal overload relays, relay range 9 amp to 15 amps as applicable, Make-L&T or equivelent of Schneider/ABB/Crompton/C&S 3 Each
125 125 M&L for Electronic Timer, 3 - 30 Sec 415V Make- L&T, or equivelent of Schneider/C&S/Minilac 4 Each
126 126 M&L for Motor protection relay, O/L range 1.2 amps, Make-L&T or equivelent of Schneider/ABB/Crompton/C&S 4 Each
127 127 M&L for Single phase preventor relay, Make- L&T or equivelent of Schneider/ABB/C&S /Minilac 4 Each
128 128 M&L for LED indication Lamp as per existing size( R-Y-B) 9 Each
129 129 M&L for Starter Push button as per existing size ( Red/green) 9 Each
130 130 Supply and replacement of submerisible flat copper cable conductor 3 core 10 Sqmm 1100 volts grade complete all as sppecified and directed by Engineer in charge. 25 RM
131 131 Repair/Maint of unserviceble submersible pump of 15 HP capacity by lifting from UG sump and dismantling and strip opening of 3 phase 415volts,AC submersible pump set,transporting the pumping set to workshop for repair including replacement of unserviceable parts of pump such as GM impeller, neckring, bowl assebly, bushes , coupling, lock, sand cap , CI intermediate bowl, S/S pump shaft etc including testing at site on full load complete all as sepecified and directed by Engr in charge. NOTE :- I. The defective parts such as pump shaft, impellor, neckring, coupling, lock ,gun metal bushes, sand cap etc will be measured and paid separately under respective items. II. Rates for repair,servicing,complete checking, machine work what ever is reqd cutting,grinding,polishing and transportation from site to workshop and back are deemed to be included in the quoted rates.. 1 Each Job
132 132 Supply and fix Pump shaft stainless steel sleev suitable size 15HP submersibale pump 1 Each
133 133 Supply and fix Impeller bronze/gun metal of suitable for 15HP submersible pumps. 3 Each
134 134 Supply and fix Neck ring gun metal of suitable size for 15HP 4 Each
135 135 Supply and fix Gun metal bowl bushes suitable for submersible pump of 15 HP. 3 Each
136 136 Supply and fix Cast iron suction /discharge case bowl of suitable size for 15HP 2 Each
137 137 Supply and fix Sand cap of suitable size from 15HP 1 Each
138 138 Supply and fix Cast iron inter mediate bowl of suitable size from 15HP. 2 Each
139 139 Repair/servicing of unserviceble submersible motor of 15HP, 3 phase 415volts by lifting from UG sump,transporting to workshop,dismantling and strip opening re-winding with PVC insulated supperior quality water proof copper winding wire of suitable size/gauge and nos of turns including replacement of insulating materials incl new submersible cable of suitable size for connection from motor to outside upto a length of 1.5 mtrs and reassembling including testing at site on full load complete all as sepecified and directed by Engr in charge. NOTE :- I. The defective parts such as Thrust plate/bearing/sleev/pad/bush end etc will be measured and paid separately under relevant items as. II. Rates for repair,servicing,complete checking, machine work what ever is reqd cutting,grinding etc complete and transportation from site to workshop and backs are deemed to be included in the quoted rate. 1 Each Job
140 140 Supply and replacement of thrust plate suitable for submersible motor 15 HP 1 Each
141 141 Supply and replacement of thrust pad suitable for submersible motor 15 HP 1 Each
142 142 Supply and replacement of bearing suitable for submersible motor 15 HP 1 Each
143 143 Supply and replacement of bush suitable for submersible motor 15 HP 1 Each
144 144 Fabrication ,supply,install Installation boards( Sign Boards ) of size 3.50 met X1.00X0.50 met with angle iron frame duly welded of size30X30X3.00 mm thick pasted with flex board duly printed letters in white colour on dark blue background pre wired with LED Lighting,connecting cable weather proof 4.00 sq mm 2 core from switch board including taking out perished sign boards as per samples at Pump House all as directed. 4 Each
145 145 Chemical testing of water sample at month interval at PMC or at any govt recognised water testing lab for the following parameters: Turbidity, pH, Total Hardness, Alkalinity, Chloride, Nitrate, TDS, Iron, Flourides, calcium, Magnesium, Aluminium, Sulphide, Lead, Arsenic, Manganese, Copper, Mercury, residual chlorine. (Note: (i) Sample of water to be collected from each pump house at Dunkirk Line in sterilised bottle provided by the lab (ii) Sample of water to be deposited to lab and report to be collected duly signed by authorised person of Lab, (iii) Cost of transportation of water sample and collection of report shall be inclusive of quoted rate, (iv) Cost of Testing as specified shall be paid to Lab directly by the Contractor and the cost shall be inclusive of quoted rate, (v) Test shall be carried out in scheduled time, otherwise recovery shall be effected thrice the quoted rate, (vi) Complete parameter testing shall be considered as one job) 12 Each Job
146 146 M & L for surface point wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn in and including PVC casing caping of required size with all fittings and accessories alongwith one single core green colour PVC insulated 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dolly for one light point or one fan point or one call bell point controlled by one, one way switch including PVC switch board of required size or 3mm thick hylam sheet screwed with 04 nos cadmium coated screws & cup washer on existing MS concealled box for mounting of switch, regulators or bell push and casing caping terminal box for mounting ceiling rose/ holders etc incl dismentling taking down old unserviceable point wiring and making good to disturbed surfaces all as specified and directed. 650 Point
147 147 M & L for surface point wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn in and including PVC casing caping of required size with all fittings and accessories alongwith one single core green colour PVC insulated 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dolly for one 5 amps socket point independent including PVC switch board of required size or 3mm thick hylam sheet screwed with 04 nos cadmium coated screws & cup washer on existing MS concealled box for mounting of switch, socket incl dismentling taking down old unserviceable point wiring and making good to disturbed surfaces all as specified and directed. 120 Point
148 148 M & L for surface point wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn in and including PVC casing caping of required size with all fittings and accessories alongwith one single core green colour PVC insulated 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dolly for one 5 amps socket point on same board with other switches incl dismentling taking down old unserviceable point wiring and making good to disturbed surfaces all as specified and directed. 120 Point
149 149 M & L for surface point wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn in and including PVC casing caping of required size with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dolly for one two way light point controlled by two, two way switch including PVC switch board of required size or 3mm thick hylam sheet screwed with 04 nos cadmium coated screws & cup washer on existing MS concealled box for mounting of switch etc incl dismentling taking down old unserviceable point wiring and making good to disturbed surfaces all as specified and directed. 8 Point
150 150 M & L for surface point wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 2.5 sqmm (Nominal area) drawn in and including PVC casing caping of required size with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 2.5 sqmm as earth lead and connected to earth dolly for one 16amps socket (Power) point independent including PVC switch board of required size or 3mm thick hylam sheet screwed with 04 nos cadmium coated screws & cup washer on existing MS concealled box for mounting of switch, socket all as specified and directed. 80 Point
151 151 M & L for surface submain wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm (Nominal area) drawn through in and including PVC casing caping/PVC conduit size with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 1.5 sqmm as earth lead and connected to earth dolly incl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. NOTE: (a) Two run of cable with one run of earth wire and one run of casing capping/conduit will be measured as one length. 80 RM
152 152 M & L for surface submain wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 4.0 sqmm (Nominal area) drawn through in and including PVC casing caping/PVC conduit size with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 4 sqmm as earth lead and connected to earth dolly incl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. NOTE: (a) Two run of cable with one run of earth wire and one run of casing capping/conduit will be measured as one length. 60 RM
153 153 M & L for surface sub main wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 6.0 sqmm (Nominal area) drawn through in and including PVC casing caping/PVC conduit size with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 6.0 sqmm as earth lead and connected to earth dolly incl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. \nNOTE: (a)Two run of cable with one run of earth wire and one run of casing capping/conduit will be measured as one length. 250 RM
154 154 M & L for surface sub main wiring with two single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 10.0 sqmm (Nominal area) drawn through in and including PVC casing caping/PVC conduit size with all fittings and accessories alongwith one single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 10.0 sqmm as earth lead and connected to earth dolly incl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. \nNOTE: (a)Two run of cable with one run of earth wire and one run of casing capping/conduit will be measured as one length. 50 RM
155 155 M & L for surface sub main wiring with four single core PVC insulated unsheathed 1100 volt grade multi stranded FRLSHCopper conductor cable of size 10.0 sqmm (Nominal area) drawn through in and including PVC casing caping/PVC conduit size with all fittings and accessories alongwith two single core green colour PVC insulated unsheathed 1100 volt grade multi stranded FRLSH Copper conductor cable of size 10.0 sqmm as earth leads and connected to earth dolly incl dismentling taking down old unserviceable wiring and making good to disturbed surfaces all as specified and directed. \nNOTE: (a)Four run of cable with two run of earth wire and one run of casing capping/conduit will be measured as one length. 60 RM
156 156 S&F 5 Amp switch piano type single pole one way incl dismentling taking down unsv one all as specified and as directed. 850 Each
157 157 S&F 5 Amp switch piano type two way incl dismentling taking down unsv one all as specified and as directed. 20 Each
158 158 S&F bell push piano type one way 240 volt incl dismentling taking down unsv one . all as specified and as directed. 30 Each
159 159 S&F socket flush type 6 amps, 5 pin, 230v incl dismentling taking down unsv one all as specified and as directed. 200 Each
160 160 S&F switch socket combination multipurpose 2-in-1, 5 pin 6 amps, 230v incl dismentling taking down unsv one all as specified and as directed. 200 Each
161 161 S&F switch socket combination multipurpose 2-in-1,3 pin 16 amps and 3 pin 6 amps, 230v incl dismentling taking down unsv one all as specified and as directed. 150 Each
162 162 S&F lamp Holder insulated body with back plate for batten fitting incl dismentling taking down unsv one all as specified and as directed. 130 Each
163 163 S&F in repairs LED lamp 12 watt, CDL, B-22 cap, (Pin type), 230V, PF-0.95 (min) incl dismentling taking out unsv CFL. 130 Each
164 164 S&F ceiling rose surface Bakelite three terminal incl dismentling taking down unsv one all as specified and as directed. 480 Each
165 165 S&F call bell electric, ding dong, AC 240 volt, 50 HZ. incl dismentling taking down unsv one all as specified and as directed. 40 Each
166 166 S&F Electronic fan regulator with 5 step type,100 W, AC 240 Volts, 50 Hz incl dismentling taking down unsv one all as specified and as directed. 150 Each
167 167 S&F MCB, Single Pole, 6 to 32 amps, 240 Volts, 10 KA breaking cap, ‘’C” curve incl dismentling taking down unsv one all as specified and directed. 180 Each
168 168 S&F MCB, Double Pole, 6 to 32 amps, 415 Volts, 10 KA breaking cap, ‘’C” curve incl dismentling taking down unsv one all as specified and directed. 50 Each
169 169 S&F MCB, Four Pole, 40 to 63 amps, 415 Volts incl dismentling taking down unsv one all as specified and directed. 20 Each
170 170 S&F Sheet metal enclosure two way with 20 amps DP MCB-1 No incl dismentling taking down unsv one all as specified and directed. 5 Each
171 171 S&F MCB distribution board,Double door, metal enclosure, SPN, 230 Volts, 4 way incl dismentling taking down unsv one all as specified and directed. 5 Each
172 172 S&F MCB distribution board, Double door, metal enclosure, SPN, 230 Volts, 8 way incl dismentling taking down unsv one all as specified and directed. 30 Each
173 173 S&F MCB distribution board, Double door, metal enclosure, SPN, 230 Volts,12 way incl dismentling taking down unsv one all as specified and directed. 2 Each
174 174 S&F MCB distribution board, Double door, metal enclosure, TPN, 415 Volts, 4 way incl dismentling taking down unsv one all as specified and directed. 5 Each
175 175 S&F Vertical MCB distribution board, as MCB incomer, Double door, metal enclosure, TPN, 415 Volts, 4 way incl dismentling taking down unsv one all as specified and directed. 5 Each
176 176 S&F Vertical MCB distribution board, as MCCB incomer, IP 43 protection, Double door, metal enclosure, TPN, 415 Volts, 4 way incl dismentling taking down unsv one all as specified and directed. 2 Each
177 177 S&F Metal plug and socket board with MCB SP 20 amp, 16 KA incl dismentling taking down unsv one all as specified and directed. 15 Each
178 178 S&F PVC rectangular switch board of size 300mmx 250mm x50mm incl necessary cutting slots for mounting switch sockets etc incl dismentling taking down unsv one all as specified and directed. 40 Each
179 179 S&F PVC rectangular switch board of size 200mmx 150mm x50mm incl necessary cutting slots for mounting switch sockets etc incl dismentling taking down unsv one all as specified and directed. 60 Each
180 180 S&F PVC rectangular switch board of size 175mmx 100mm x50mm incl necessary cutting slots for mounting switch sockets etc incl dismentling taking down unsv one all as specified and directed. 80 Each
181 181 S&F PVC rectangular switch board of size 100mmx 100mm x50mm incl necessary cutting slots for mounting switch sockets etc incl dismentling taking down unsv one all as specified and directed. 100 Each
182 182 S&F Hylam Sheet 3mm thick on existing concealled MS/CI ractangular or Squar or round box with 04 nos cadmium coated screws and cup washer incl cutting slots for mounting switch/socket/fan regulator/ batten holder etc incl dismentling taking down unsv one 1 Sqm
183 183 S&F Round shaped surface/ recess mounted LED Flat panel,PDC Aluminium housing and PMMA difuser 12 watt suitable for surface/ POP celing complete with all fixing accessories and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable incl dismentling taking down unsv fitting any type all as specified and directed. 10 Each
184 184 S&F square shaped surface/ recess mounted LED Flat panel,PDC Aluminium housing and PMMA difuser 12 watt suitable for surface/ POP celing complete with all fixing accessories and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable incl dismentling taking down unsv fitting any type all as specified and directed. 10 Each
185 185 S&F LED tube 20 watt retro LED T8 ( PC ) to existing fluorescent FTL fitting surface mounted after dismentling electronic ballast, internal wiring and complete rewiring with 0.5 sqmm copper flexible conductor FRLSHom connector block to one end of Bipi holder and including connecting up to ceiling rose with 0.5 sqmm two core flexible copper conductor cable all as specified and directed. 250 Each
186 186 S&F LED batten tube type, 2'long, 09 watt,CDL 230 Volts , complete with all accssories internally pre wired and including connecting up to ceiling rose with 0.5 sqmm two core copper flexible conductor cable with mounting casing box 2 nos incl dismentling taking down unsv fitting any type all as specified and directed. 70 Each
187 187 S&F LED Tube light fitting, 36 watt, CDL, integrated LED batten, 230 Volts, 4 feet long , complete with all accssories internally pre wired and including connecting up to ceiling rose with 0.5 sqmm twin core copper flexible conductor cable incl LED lamp and mounting casing box 2 nos incl dismentling taking down unsv fitting any type all as specified and directed. 50 Each
188 188 S&F LED Tube light fitting, 18 watt, CDL, durable LED batten with decorative end caps, 230 Volts, 4 feet long , complete with all accssories internally pre wired and including connecting up to ceiling rose with 0.5 sqmm twin core copper flexible conductor cable incl LED lamp and mounting casing box 2 nos incl dismentling taking down unsv fitting any type all as specified and directed. 350 Each
189 189 S&F LED building security light 25 watt, 230V complete with all accessories and including connecting up to ceiling rose with 0.5 sqmm three core copper flexible conductor cable, One GI medium grade 25/32 mm dia bracket of total length 60 cm and fixed to wall with 2 Nos MS Clamp and fastener incl dismentling taking down unsv fitting any type all as specified and directed. 45 Each
190 190 REPAIR TO CEILING FANS WITH FOLLOWING ITEMS OF WORK :-\nM&L for Rewinding of Ceiling fan 1200/1400 mm sweep after dismenting complete motor assy, bearings, bushings, removal of burnt copper wire, cleaning of core, inserting proper insulating paper in slots, winding with and as per existing size/turn of super enamelled copper wire, heating, vernishing, replacement of unsv bearings / bushings, assemble of rotor and stator unit with capacitor, connecting wire, down rod, blades and testing complete. \nNote: 1. Contractor will collect fans from the complaint cells of specified area and bring back to complaint cell after repair. Cost of transportation will be inclusive of quoted rate. 2. Spares require for replacement such as bearing, Bushing, capacitor shall be measured and paid separately as supply & Fixing only. 3. Cost of Connector bock and capacitor holder shall be inclusive of the quoted rate. 300 Each
191 191 All as per item No- 45 here-in-above but for Exhaust fan 250/300 mm sweep industrial type. 5 Each
192 192 All as per item No- 45 here-in-above but for Exhaust fan 450 mm sweep industrial type. 5 Each
193 193 All as per item No- 45 here-in-above but for Air circulator fan 450 mm sweep. 40 Each
194 194 S&F ball bearing No 6201/6202/6203/6204 of SKF/Tata/NBC. 400 Each
195 195 S&F G.M. Bush bearing for ceiling fan as per existing pattern. 400 Each
196 196 S&F capacitor AC for 230 volts 50 Hz of capacity 1.8 Mfd. 400 Each
197 197 S&F capacitor AC for 230 volts 50 Hz of capacity 2.0/2.25/2.5 Mfd. 90 Each
198 198 S&F capacitor AC for 230 volts 50 Hz of capacity 3.15 Mfd. 10 Each
199 199 S&F capacitor AC for 230 volts 50 Hz of capacity 4.0 Mfd. 10 Each
200 200 Painting of ceiling fan 1200/1400 mm including scrapping, cleaning and removing dust from the blade an body and applying two coat of enamel paint over & one coat of primer all as directed by engr-in-chage 300 Each
201 201 S& F in repair of exhaust fan225 mm PVC body with louvres, 230 volt incl dismentling taking down unsv fan any type all as specified and directed. 12 Each
202 202 S& F in repair of exhaust fand 300 mm PVC body, 230 vol incl dismentling taking down unsv fitting any type all as specified and directed. 8 Each
203 203 S&F PVC insulated PVC sheathed copper flexiable wire multistrand 4sqmm 3 core, ISI marked 50 RM
204 204 S&F in repair thermostat ISI marked suitable for geysers 25 Ltrs to 50 Ltrs Capacity. 5 Each
205 205 S&F in repair fusible plug marked suitable for 25 and 50 ltrs capacity Geysers all as specified and directed. 5 Each
206 206 S&F in repair heating elementMarked round/triangular bas, push type or thread type including rubber washers for 1.5/2.0 KW all as specified and directed. 5 Each
207 207 S&F in repair innner water container made of SS, vertical or horizontal type for 25/50 ltr capacity gyser all as specified and directed. 3 Each
208 208 S&F in repair of aparatus plate suitable for vertical/horizintal type Geyser 25 or 50 ltr cap all as specified and directed. 5 Each
209 209 S&F in repair heavy duty copper connections pipe with brass hexagonal adopters at both side 15mm dia and 450mm long for hot water all as specified and directed. 5 Each
210 210 S&F in repair heavy duty PVC connections pipe with brass hexagonal adoptersat both side 15mm dia and 450mm long for hot /cold water all as specified and directed. 5 Each
211 211 Serving/Repair and maintenance of solar water heator 100/200 ltrs capacity including flushing out solar tank and pipes with chemicals installed at roof top of bldg up to 15 met height 15 Job
212 212 S&F in repair EDPM hose pipe including kit suitable for 100/200 Ltrs solar water heator 15 set
213 213 S&F in repair solar water heator element 3.00 Kw round base as per existing size and shape for 100/200 Ltrs solar water heator 15 Each
214 214 S&F in repair Pvc flexible copper conductor cable multi stranded of size 6.00 sq mm for 100/200 Ltrs solar water heator 300 Rm
215 215 S&F in repair Thermostat 40 -100 degree range as per existing size and shape for 100/200 Ltrs solar water heator 15 Each
216 216 M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 6 mtr long buried directly and vertically in ground with top edge at ground level after making bore hole of size not less than 300 mm dia and 6.0 Mtr long using suitable mechanical drilling rig (for drilling near the specified location), connected with galvanised earthing lead of 4 mm dia all as shown in Plate No-2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2with pit cover, funnel, wiremesh, 15 mm dia light grade GI tubing for protection of GI earthing lead 4mm, charcoal and salt in alternate 150mm thick layers around GI earth pipe, including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion. 20 Each Set