Military Engineer Services-MES has published Repair /Maintenance Of Dg Sets, Lt Panels, Mccbs , Old U/S Cable And Earth Pits, Led Street Light Fitting , Pcc Poles , Solar Street Light Fittings And Connected Works In Tech Area And Officer Mess At Mcc Air Force Station Basant Nagar Under Ge (Af) F. Submission Date for this Tender is 01-02-2021. Diesel Generators Tenders in MCC BASANTNAGAR Haryana. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 25-Jan-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 01-02-2021 |
Name of Work: REPAIR /MAINTENANCE OF DG SETS, LT PANELS, MCCBS , OLD U/S CABLE AND EARTH PITS, LED STREET LIGHT FITTING , PCC POLES , SOLAR STREET LIGHT FITTINGS AND CONNECTED WORKS IN TECH AREA AND OFFICER MESS AT MCC AIR FORCE STATION BASANT NAGAR UNDER GE (AF) FARIDABAD | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Maintenance/repair to 320 KVA Gen set installed at sub station by replacement of lubricant oil filter fuel oil filter bye pass filter, “O’ ring, fuel filter water separator assembly, draining out un serviceable engine oil, cleaning of pump, checking & tightening of mounting nut & bolts, crank case, cleaning of valves, battery terminals, checking of radiator, PH value of coolant, topping with premixed coolant and inhibitor corrosion testing the engine on load and checking for any leakage of oil/fuel/coolant all as required and directed by Engineer-in-Charge.\nNote :-(i) Parts required for replacement will be measured and paid separately under Schedule ‘A’ item as suply only. The labour element involved is deemed to be included in quoted rate against this item.\n(ii) The contractor will be responsible for attending any complaint/defect occurs to DG set at odd hours during operation. If the defects are not attended within 4-6 hrs recovery of Rs. 300/- per day will be effected \n\n | 2 | Each Job | |
2 | 1.01 | SPARE PARTS FOR DG SET (Ref item No 1 above)\nSupply only Element lub oil filter Cartrige . Kirloskar cat part No KV0.043.03.0.00 complete all as specified and directed by Eng-in -charge. | 4 | Each | |
3 | 1.02 | Supply only fuel filtter Cartage Kirloskar cat part No KV0.110.01.0.00 complete all as specified and directed by Eng-in -charge. | 4 | Each | |
4 | 1.03 | Supply only Pre Filter Assembly Kirlosker part No KV2.506.20.0.00 complete all as specified and directed by Eng-in -charge. | 4 | Each | |
5 | 1.04 | Supply only seal 'O' ring Make- Kirloskar complete all as specified and directed by Eng-in -charge. | 4 | Each | |
6 | 1.05 | Supply only KOEL Care genuine oil Kirloskar Part No 82.050.10.0.20 complete all as specified and directed by Eng-in -charge. | 105 | Ltrs | |
7 | 1.06 | Supply only K-COOL super plus Coolent Kirloskar part No - 82.020.35.1.05 complete all as specified and directed by Eng-in -charge. | 40 | Ltrs | |
8 | 1.07 | Supply only Air Filter for 320 KVA DG Set . Make :-Kirloskar complete all as specified and directed by Eng-in -charge. | 4 | Each | |
9 | 1.08 | Supply only distilled water. complete all as specified and directed by Eng-in -charge. | 10 | Ltrs | |
10 | 1.09 | Supply only Battery terminals. complete all as specified and directed by Eng-in -charge. | 8 | Each | |
11 | 2 | Maintenance/repair to 75 KVA Gen set " Greevs" installed at sub station in Basant Nagar Officer's Mess by replacement of lubricant oil filter fuel oil filter bye pass filter, “O’ ring, fuel filter water separator assembly, draining out un serviceable engine oil, cleaning of pump, checking & tightening of mounting nut & bolts, crank case, cleaning of valves, battery terminals, checking of radiator, PH value of coolant, topping with premixed coolant and inhibitor corrosion testing the engine on load and checking for any leakage of oil/fuel/coolant complete all as specified and directed by Engr-In-Charge. \nNote :- (i) Parts required for replacement will be measured and paid separately under Schedule ‘A’ item as supply only. The labour element involved shall be deemed to be included in the unit rate quoted against this item.\n(ii) The contractor will be responsible for attending any complaint/defect occurs to DG set at odd hours during operation. If the defects are not attended within 4-6 hrs recovery of Rs. 300/- per day will be effected \n | 1 | Each Job | |
12 | 2.01 | SPARE PARTS FOR DG SET (Ref item No 2 above)\nSupply only Element lub oil filter Cartrige complete all as specified and directed by Eng-in -charge. | 2 | Each | |
13 | 2.02 | Supply only fuel filtter Cartage complete all as specified and directed by Eng-in -charge. | 2 | Each | |
14 | 2.03 | Supply only Pre Filter Assembly complete all as specified and directed by Eng-in -charge. | 2 | Each | |
15 | 2.04 | Supply only seal 'O' ring Make- Kirloskar complete all as specified and directed by Eng-in -charge. | 2 | Each | |
16 | 2.05 | Supply only genuine Engine oil Make- Servo/Castrole complete all as specified and directed by Eng-in -charge. | 30 | Ltrs | |
17 | 2.06 | Supply only Coolent complete all as specified and directed by Eng-in -charge. | 20 | Ltrs | |
18 | 2.07 | Supply only Air Filter for 75 KVA DG Set complete all as specified and directed by Eng-in -charge. | 2 | Each | |
19 | 2.08 | Supply only distilled water.complete all as specified and directed by Eng-in -charge. | 10 | Ltrs | |
20 | 3 | M&L for repair of PCB suitable for 320 KVA DG set AMF panel complete all as specified and directed by Engr-In-Charge. . | 3 | Each | |
21 | 4 | M&L for repair of AVR Unit of 320 KVA DG Set complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
22 | 5 | M&L for Repair/replacement of Self starter of 320 KVA DG Set complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
23 | 6 | M&L for replacement of fuel pipe of DG set connecting from inlet of the tank to dg set complete all as specified and directed by Engr-In-Charge. | 10 | RM | |
24 | 7 | S&F in replacement of Digital maltifunctional power meter for AMF panel complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
25 | 8 | Supply and replacement of V belt for radiator fan suitable for 320 KVA DG set as per sample complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
26 | 9 | M&L for repair/replacement of battery 12 volts, 180 amh complete all as specified and directed by Engr-In-Charge.Make :Exide/Amron/SF. | 2 | Each Job | |
27 | 10 | Supply, installing testing and commissioning in replacement of factory made and tested (Including CPRI test cetified) indoor type floor mounted LT panel board, cubical type suitable for 415 Volts 3 phase, 4 wire 50Hz, Ac supply system having busbar chember with insulated AL busbar of rating 1000 A for phase installed on porcelin/SMC insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 2.00 mm thick CRCA MS sheet and angle iron frame 40x 40x 6mm thick frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coat of red oxide primer, front and back opening type with aproaches for cable entry with double door shutter and locking arrangements including internal wiring with PVC insulated stranded copper conductor cable FRLS IS 694 sheathed 1100V grade of appropriate size The panel shall be comprising of following complete all as specified and directed by Engr-In-Charge.:-\nINCOMING-\n(i) Mains MCCB 4 pole 630 Amps with adjustable setting, 415 Volts with breaking capacity 50 KA. -01 No.\n(ii) Onload changover 630 amp 4 pole,415 volt - 01 No\n(iii) Aluminium Bus bar three phase 4 wire 1000 amps 1100 volts -01 Set.\n(iv) Digital type voltmeter 0-500 volts and with selector switch-01 No.\n(v) Indication lamp RYB-01 Set.\n(v) Digital Amp meter with CTs & built in selector switch-01 No.\nOUTGOING-\n(i) MCCB 3 pole 250 Amps,, 415 Volts with breaking capacity 35 KA.-05 No.\n(ii) MCCB 3 pole 400 Amps, 415 Volts with breaking capacity 35 KA.-01 No. | 1 | Each Job | |
28 | 11 | Supply, installing testing and commissioning in replacement of factory made and tested (Including CPRI test cetified) indoor type floor mounted LT panel board, cubical type suitable for 415 Volts 3 phase, 4 wire 50Hz, Ac supply system having busbar chember with insulated AL busbar of rating 1200 A for phase installed on porcelin/SMC insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 2.0 mm thick CRCA MS sheet and angle iron frame 40x 40x 6mm thick frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coat of red oxide primer, front and back opening type with aproaches for cable entry with double door shutter and locking arrangements including internal wiring with PVC insulated stranded copper conductor cable FRLS IS 694 sheathed 1100V grade of appropriate size The panel shall be comprising of following:-\nINCOMING - Mains\n(i) Air circuit Breaker 4 pole 800 Amps, 415 Volts with breaking capacity 65 KA. -01 No.\n(ii) Aluminium Bus bar three phase 4 wire 1200 amps 1100 volts copper-01 Set.\n(iii) Digital type voltmeter 0-500 volts and with selector switch-01 No.\n(iv) Digital Amp meter with CTs & built in selector switch-01 No.\n(v) Indication lamp RYB-01 Set.\nOUTGOING-\n(i) MCCB 3 pole 250 Amps, 415 Volts with breaking capacity 25 KA.-04 No.\n(ii) MCCB 3 pole 400 Amps, 415 Volts with breaking capacity 35 KA.-01 No.\n(III) MCCB 3 pole 160 Amps, 415 Volts with breaking capacity 25 KA.-01 No. | 1 | Each | |
29 | 12 | M&L for Design, development, supply commissioning and testing EHCC certified ground tubular effective chemical earthing system (CPRI tested for 15 KA current capacity for LT Iine) highly anticorrosive long life electrode with and including adequate protective coating to withstand servere weather conditions in the earth pit of the standard size comprising of 40mm x 3m Long Copper rod as primary conductor and hollow copper tube of 80mm x 3m long as secondary conductor to install with suitable connecting terminal confirming of IS 3043 : 1987 specification, highly conductive packing material to be filled in earth pits for providing uniform, low resistivity anticorrosive, hygroscopic medium around the earth system for improving the efficiency of current dissipation with crystalline conductive mixture (CCM) 20 Kg per bag (3 bag per kit) minimum or sufficient quanitities required as per site complete including RCC earthing pit cover , material and labour complete all as specified and as directed by Engr in Charge. | 2 | Each | |
30 | 13 | M & L for GI pipe light grade for cable protection in tenches of size 50mm dia complete all as specified and directed by Engr-In-Charge. | 10 | RM | |
31 | 14 | M&L for Earthing with galvanised steel plate electrode 60cmx60cmx6 mm thick buried directly in ground (Earth pit not less than 2.25 mtr deep from ground level) surrounded from all directions with charcoal dust, salt and edge of earth plate not less than 1.5 mtr below ground level connected to galvanized iron strip 32 mmx6mm earth lead by means of nuts, bolts and washers incl excavation and earth work PCC chamber and RCC cover of PCC 1:2:4 type B-1 using XPM weighing not less than 4Kg/Sqmm using 20mm graded stone aggregate for coping/under covers, 20mm size GI pipe light grade for watering funnel wire mesh etc, complete all as specified and shown in electrical plate No 5 of SSR Part I. | 4 | Each Job | |
32 | 15 | Dewatering the existing U/G sump of 20000 Ltrs capacity and cleaning the internal surface of sump for removing scales, funges, mud and other foreign material ,scrubbing with water using wire brush and watering the surfaces with mixture of bleaching powder and water ,finally washing with fresh water and treating with one coat of lime wash to internal wall and bottom surfaces etc complete for one time,writing in enamel paint note in block capital letter as cleaned on (date) and due date etc,height not less than 5 cm complete all as specified and directed by Engr-In-Charge. | 2 | Each Job | |
33 | 16 | Supply and fixing in replacement of chlorine dozing pump with flow rate 0 to 10 LPH ,suction tubing 6 mm ,dosing pressure 4.5 Kg/cm 2 ,230 volt 50 Hz ,single phase and diaphragm made from pure solid PTFE ,compatibility with most chemicals complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
34 | 17 | M&L for repair of centrifugal pump of capacity 5 hp ,3 phase shifting to workshop Complete opening for rewinding with super enamled copper wire of existing size & repair/replacement of worn out parts such as shaft,Ball bearing, bush, impellers, coupling ,mechanical seal,jet assembly etc including re-assembling and refixing in position complete all as specified and directed by Engr-In-Charge. | 1 | Each job | |
35 | 18 | M&L for disconnecting the main supply & taking out the submersible pump capacity 10 HP , 3 phase from the borewell with the help of Chain pulley arrangement and shifting to the workshop and back after rewinding and repair/replacement of wornout parts including refixing with complete electric and water pipe connections & testing after installing complete all as specified and directed by Engr-In-Charge. | 2 | Each Job | |
36 | 19 | Taking up or down following sizes steel tubing and connections, including cleaning for refixing or removal to store complete all as specified and directed by Engr-In-Charge. \n25 mm bore | 100 | RM | |
37 | 20 | 20 mm bore | 150 | RM | |
38 | 21 | 15 mm bore | 100 | RM | |
39 | 22 | Supply, laying and fixing GI water tubing medium grade with all fittings and fixed complete to all walls,ceiling,laid in floors,roof etc with following sizes complete all as specified and directed by Engr-In-Charge. \n25 mm bore | 100 | RM | |
40 | 23 | 20 mm bore | 150 | RM | |
41 | 24 | 15 mm bore | 100 | RM | |
42 | 25 | Supply and fix in replacement Onload changover 630 Amps ,4 Pole ,50 Hz ,415 Volt in sheet steel enclosure complete all as specified and directed by Engr-In-Charge. . Make :-Havells/Indoasian /L&T | 1 | Each | |
43 | 26 | Supply and fix in repair Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and directed by Engr-In-Charge. | 4 | RM | |
44 | 27 | Supply and fix in repair Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed by Engr-In-Charge. | 50 | Each | |
45 | 28 | Supply and fix in repair Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed by Engr-In-Charge. | 4 | Each | |
46 | 29 | S&F in repair wall mounted TPN busbar chamber factory made with busbar of current rating 400 Amp, 415, 4 way complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
47 | 30 | Supply and fixed in repair,MCCB 250 Amp ,3 pole, microprocessor based thermal magnetic type ,36 KA including under voltage/over voltage relay complete all as specified and directed by Engr-In-Charge. .Make : -HPL TABBASIX2200C3P/Havells/indoasian) | 2 | Each | |
48 | 31 | Taking out old rusted solar water heater tank of capacity 100-150 ltr and Supply and fix new solar water heater tank of same capacity incluted connection of water inlet and outlet and including heating element of 2 kW complete all as specified and directed by Engr-In-Charge. | 3 | Each | |
49 | 32 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ XLPE, armoured, Al conductor cable of size 16 to 35 sqmm,Outdoor type complete all as specified and directed by Engr-In-Charge. | 4 | Each | |
50 | 33 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ XLPE, armoured, Al conductor cable of size 70 to 95 sqmm,Outdoor type complete all as specified and directed by Engr-In-Charge. | 4 | Each | |
51 | 34 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ XLPE, armoured, Al conductor cable of size 150 to 185 sqmm,Outdoor type complete all as specified and directed by Engr-In-Charge. | 4 | Each | |
52 | 35 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ XLPE, armoured, Al conductor cable of size 300 to 400 sqmm,Outdoor type complete all as specified and directed by Engr-In-Charge. | 2 | Each | |
53 | 36 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. | 80 | RM | |
54 | 37 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. | 30 | RM | |
55 | 38 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed by Engr-In-Charge. | 25 | RM | |
56 | 39 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 corecomplete all as specified and directed by Engr-In-Charge. | 25 | RM | |
57 | 40 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3.5 core complete all as specified and directed by Engr-In-Charge. | 25 | RM | |
58 | 41 | Excavation in trenches not exceeding 1.5 m wide and and not exceeding 1.5 m depth in loose/soft soil and getting out complete all as specified and directed by Engr-In-Charge. | 14 | Cum | |
59 | 42 | Returning, filling in, with excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm, complete all as specified and directed by Engr-In-Charge. | 10.8 | Cum | |
60 | 43 | Removal of surplus soil to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by Engr-In-Charge. | 2.7 | Cum | |
61 | 44 | M & L for brick protection with sub class 'B' bricks laid dry flat over electric cable in trenches all as specified and directed by Engineer-in Charge. | 400 | Each | |
62 | 45 | M & Labour for sand cushioning with a layer of sand 80mm thick consolidated before laying of cable and 150mm thick consolidated after laying of cable in trenches ducts for electric cable protection including consolidation complete all as specified and directed by Engr-In-Charge. | 4.5 | Cum |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail