Military Engineer Services-MES has published Repair Replacement And Improvement Of Lt Distribution System By Replacement Of Unsv Lt Cables And Switch Gears At Mh Kirkee Under Ge Mh And Rh Kirkee. Submission Date for this Tender is 17-02-2021. Switch Gear Tenders in KIRKEE AND AUNDH Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 10-Feb-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 17-02-2021 |
NAME OF WORK :REPAIR, REPLACEMENT AND IMPROVEMENT OF LT DISTRIBUTION SYSTEM BY REPLACEMENT OF U/S LT CABLES & SWITCH GEARS AT MH KIRKEE UNDER GE ( MH&RH) KIRKEE | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Excavation in trenches for taking out/laying of cable and pipe line not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide in soft/loose soil. | 280 | Cum | |
2 | 2 | All as per item No 1 above but in Hard dense soil | 61 | Cum | |
3 | 3 | Returning filling including spreading leveling watering and well ramming in layers not exceeding 25 cm thick each layer of soft/loose/hard/dense soil complete and all as specified. | 195 | Cum | |
4 | 4 | Removing excavated material to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above starting point. Complete and all as specified. | 146 | Cum | |
5 | 5 | M&L for riddled earth for cushioning including spreading, leveling and hand punning to underground cable in trench all as specified and directed.\nNote : Punned thickness shall only be measured and paid. | 102 | Cum | |
6 | 6 | M&L for old size brick Class 'B' protection for Under ground cable all as specified and directed. | 10791 | Each | |
7 | 7 | Re-laying only brick or cable cover retrieved while taking out old cable vide item No 8 below all as specified. | 200 | Each | |
8 | 8 | Taking down unserviceable cable of any size up to 300 Sqmm carefully from trenches/poles/ducts/LT panels, OH conductors and relay at different locations all as specified and directed by Engr-in-Charge. | 1414 | RM | |
9 | 9 | Re-laying only the serviceable cable of any size and description obtained from Item No-07 above after joining etc all as directed.\n Note: \n(i) While re-laying cable, retrieved sand will be re-used without any extra cost. (ii) Retrieved Bricks / PCC cover shall be used and paid as laying only rate. (iii) Excavation, re-laying bricks, Returning & Refilling, Removal will be paid under relevant item of schedule. | 100 | RM | |
10 | 10 | Material and labor for fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, insulated, armored heavy duty electric cable with aluminum conductor, XLPE , 1100 volts grade, cross-sectional area of size 16 Sqmm 2 core with all as specified and directed. by Engr-in-charge | 100 | RM | |
11 | 11 | All as per item No. 10 here-in-before but 25sqmm 3.5 core complete all as specified | 100 | RM | |
12 | 12 | All as per item No. 10 here-in-before but35sqmm 3.5 core complete all as specified | 200 | RM | |
13 | 13 | All as per item No. 10 here-in-before but 50sqmm 3.5 core complete all as specified | 150 | RM | |
14 | 14 | All as per item No. 10 here-in-before but 70sqmm 3.5 core complete all as specified | 100 | RM | |
15 | 15 | All as per item No. 10 here-in-before but 95sqmm 3.5 core complete all as specified | 200 | RM | |
16 | 16 | All as per item No. 10 here-in-before but 120sqmm 3.5 core complete all as specified | 110 | RM | |
17 | 17 | All as per item No. 10 here-in-before but 185 Sqmm 3.5 core complete all as specified | 180 | RM | |
18 | 18 | All as per item No. 10 here-in-before but 240 Sqmm 3.5 core complete all as specified | 174 | RM | |
19 | 19 | Dismantling and taking down old/unsv cross arms, bracing, supports etc complete carrying to store for credit all as specified and directed. | 1 | Qtl | |
20 | 20 | Supply and fixing cross arms bracings supports clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminum paints complete all as specified and directed. | 1 | Qtl | |
21 | 21 | Dismantling and taking down old/unsv ACSR conductor any size complete to carrying to store for Credit all as specified and directed | 0.5 | Qtl | |
22 | 22 | S&F ACSR conductor incl jointing with existing conductor and stringing on LT pole and proper fastening to pin/shackle insulators with aluminum binding wires and required jumpering connection all as directed. | 0.5 | Qtl | |
23 | 23 | Dismantling and taking down old/unsv LT insulator of any type any size from pole/stay or carrying to store for credit complete all as specified and directed. | 10 | Each | |
24 | 24 | S&F pin type, porcelain, vitreous, brown, including one galvanized mild steel spindle, two galvanized iron washer and one galvanized iron nut, 100mm height and 65 mm dia for 1100 volts grade all as specified and directed.. | 5 | Each | |
25 | 25 | S&F shackle type, porcelain vitreous white, brown or green insulator including galvanized mild steel straps , washers, insulators bolts ,washer and nuts of size 100 mm height and 115 mm dia for 1100 Volts grade complete all as specified and directed. | 5 | Each | |
26 | 26 | Taking down unserviceable earthing and M&L for earthing with galvanized steel earth plate electrode 60cm x 60 cm x 6.3 mm buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate vertically to depth of not less than 1.5 mtr below ground level connected to and including GI strip of size 32 x 6 mm 7.5 mtr beyond the earth pit as earthing lead including GI protection pipe 40 mm bore (light grade) up to 7.5 mtr beyond the earth pit and connecting to equipments by means of earthing lead , GI bolts, nuts & washer etc with provision of char-coal and salt etc all as per electrical plate No 3 of SSR Part - I, 2009 including RCC cover and MS angle iron frame watering arrangements with GI pipe 20 mm dia (medium grade) & MS funnel, concrete pit including excavation and earthwork and testing on completion etc complete all as specified and directed by Engr-in-charge.\nNote : Rate of item is deemed to be included for excavation in hard rock, by compressor machine to achieve required depth. | 10 | Each | |
27 | 27 | Labor only for restringing of overhead ACSR conductor of any size of 4 wire on pole after disconnecting all jumper connection & binding of insulators and including rejoin ting all connections and insulators, jumper binding with aluminum conductor complete all as specified and directed .\nNote : Pole to pole distance will be measured as one job | 500 | RM | |
28 | 28 | M & L for jointing the LT cable with heat shrinkable straight through join, by disconnecting the cable ends, removing the damaged portions of cable, by suitable means, joining by ferrules etc and testing for LT 1100 V cable of size 3.5/4 core 10-25 Sqmm all as directed and specified. | 5 | Each | |
29 | 29 | All as Per item No 28 above but for LT 1100 V cable of size 3.5/4 core 35-70 Sqmm all as directed and specified. | 8 | Each | |
30 | 30 | All as Per item No 28 above but for LT 1100 V cable of size 3.5/4 core 95-185 Sqmm all as directed and specified. | 2 | Each | |
31 | 31 | All as Per item No 28 above but for LT 1100 V cable of size 3.5/4 core 240 Sqmm all as directed and specified. | 2 | Each | |
32 | 32 | All as Per item No 28 above but for LT 1100 V cable of size 3.5/4 core 300 Sqmm all as directed and specified. | 2 | Each | |
33 | 33 | supply replace and , test, commissioning of LT capacitor up to 5 KVAR of LTXL-Ultra Heavy duty capacitors of capacity 1 to 15 KVAr on existing APFC panel and necessary panel wiring for stud mounting cylindrical type having very good KVAr to volume ratio conform to IEC 60831-1 & 2 IS 13340 of range voltage range 220 V to 440Volt of Ultra Heavy duty for non-linear loads up to 440 V MPP type, all as directed and satisfied by Engr-in-Charge. Make L & T cat No:LTCCU315B2(For capacitor),Make L & T cat No: CS96127 (for capacitor duty conductor) or equivalent make of Legrand /Schneider | 5 | Each | |
34 | 34 | All as per item No 33 above but of LT capacitor upto 20 to 25 KVAR all as directed and satisfied by Engr-in-Charge Make L & T cat No:LTCCU312025B2 (For capacitor),Make L & T cat No: CS96322(For capacitor duty conductor) or equivalent make of Legrand/Schneider | 2 | Each | |
35 | 35 | Taking down old unserviceable CT coil and S & F CT coil up to -/5 A capacity all as directed by Engr-in-Charge. | 15 | Each | |
36 | 36 | Supply and fixing MCCB, 3 pole, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0, 250 amps, adjustable type, incl dismantling taking down unsv MCCB, cutting of existing panel for fixing MCCB on suitable fitting and making good the panel all as directed by Engr-in-charge. \nMake- Hager//Legrand/L & T | 1 | Each | |
37 | 37 | All as per item No.36 above but of capacity 200 amps all as directed by Engr-in-charge. \nMake- Hager//Legrand/L & T | 1 | Each | |
38 | 38 | All as per item No.36 above but of capacity 160 amps,all as directed by Engr-in-charge make- Hager//Legrand/\nL & T | 1 | Each | |
39 | 39 | All as per item No.36 above but of capacity 100 amps, all as directed by Engr-in-charge. make- Hager//Legrand/\nL & T | 1 | Each | |
40 | 40 | All as per item No.36 above but of capacity 63 amps, all as directed by Engr-in-charge. make- Hager//Legrand/\nL & T | 1 | Each | |
41 | 41 | Supply and fixing MCCB, 3 pole, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0, 125 amps, adjustable type, incl dismentling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting and make panel good and all as directed by Engr-in-charge. make- Hager//Legrand/L & T | 1 | Each | |
42 | 42 | Supply and fixing MCCB, 4 pole, 16 KA breaking capacity, with Thermal magnetic release, optium 2.0, 100 amps, adjustable type, incl dismantling taking down unsv one making cutting of existing panel for fixing MCCB on suitable fitting and make panel good and all as directed by Engr-in-charge, make- Hager//Legrand/L & T | 1 | Each | |
43 | 43 | All as per item No.42 above but of capacity 63 amps, all as directed by Engr-in-charge. make- Hager//Legrand/\nL& T | 1 | Each | |
44 | 44 | Supply and fixing MCCB, 4 pole, 36 KA breaking capacity, with Adjustable type, optium 2.0, 630 amps, adjustable type, incl dismantling taking down unsv one, making cutting of existing panel for fixing MCCB on suitable fitting , Including use required sheet metal and make panel good and all as directed by Engr-in-charge. make- Hager//Legrand/L & T | 1 | Each | |
45 | 45 | All as per item No.44 above but of capacity 125 amps, adjustable type, ill as directed by Engr-in-charge. make- Hager//Legrand/L & T | 1 | Each | |
46 | 46 | Supply only GI tubing light grade 40mm bore, ISI marked, for cable protection | 20 | RM | |
47 | 47 | Supply only GI tubing light grade 50mm bore, ISI marked, for cable protection | 40 | RM | |
48 | 48 | Supply and laying GI tubing light grade 80mm bore, ISI marked, for cable protection. | 40 | RM | |
49 | 49 | M/L for trimming of branches of trees touching LT electric over head line and making clear about 3 mtr in radius by climbing up tree or by providing ladder, at a height of 9 mtr and above and carrying and depositing where directed not exceeding 50 mtr.\nNote : (i) Necessary T & P items arrange by contractor. | 800 | RM | |
50 | 50 | M&L for road cutting and boring of road without damage surface and inserts GI pipe and cable without any damage complete all as directed by Enger -in- charge. | 100 | RM | |
51 | 51 | Decarbonizing of LT indoor/outdoor Panel/feeder pillar box any type removing unserviceable MCCBs, burnt busbars, unserviceable indicator lamps, unserviceable Ammeter, unserviceable Volt meter , replacing burnt, damaged bus bar of any size and fixing proper hanging front and rear openings, welding of hinges including welding of broken MS sheet using extra sheets replace burnt thimbles with new existing size thimbles replacing with new MCCB, including dismantling the existing connected cables and re-connecting the same cables complete all as specified and directed by Engr -in- charge. \nNote : (i)MCCBs,Bus bars, indicator lamps, multifunction meters, will be measured & paid separately . (ii) necessary MS sheet and welding, of panel including coated rate | 5 | Each Job | |
52 | 52 | Servicing of APFC panel cleaning, tightening of connections, setting programme, testing of CT including calibration of APFC panel replace unserviceable capacitors, capacitor contactor, breakers, power factor controller after servicing testing panel and achieve power factor of 1.000 all as directed and satisfied by Engr-in-Charge.\nNote: Capacitors, capacitor contactor, power factor controller measured and paid separately. | 2 | Each Job | |
53 | 53 | supply and fix power factor controllers 8 steps, with timer, 415 volt, AC, 50 HZ power supply and replacing old unserviceable controllers including suitable wiring all as directed and satisfied by Engr-in-Charge. Make: L &T Cat No ETACONM008R or equivalent make of Schneider, EPCOS | 1 | Each | |
54 | 54 | Supply and fix tinned copper aluminum Bus Bar with suitable holes and bus bar insulating cover as per Existing capacity at site / as per requirement all as directed by Engineer-in-Charge including removing unserviceable aluminum bus bar . | 15 | Kg | |
55 | 55 | Supply, fix of RYB indicator lamp LED type for incoming and outgoing supply by making suitable hole of sizes all as directed by Engineer-in-Charge. Make: L & T Cat No: SILR240VAC, SILB240VAC, SILB240VAC or equivalent make of Schneider | 15 | Each | |
56 | 56 | Supply and fix Multifunction meter three phase digital type with LED display with RS 485 Port CT secondary site selectable -/5A flush type as per existing size all as directed by Engineer-in-Charge.\nMake : L & T Cat NO: WL4410110000 or equivalent make of Schneider/L & T/Legrand | 5 | Each | |
57 | 57 | M&L for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small unequalities not exc 15 cm deep (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete at an interval of every 30 days for the various sub stations. | 50 | Sqm | |
58 | 58 | Taking down unserviceable LT panel and Supply, install, commissioning and testing of LT outdoor type feedar pillar box 415 V/440 Volts, confirming to IEC 61439 with IP-54 protection of suitable size made out of 3.15 mm thick CRCA sheet with both side openable door with locking arrangement and complete panel should be powder coated with having neoprene rubber gasket for sealing door, doors of the panel should be removable type, including 800 A current capacity Aluminium bus bar for 3 Nos phase, 1 No of neutral of suitable size horizontal and vertical mouniting on suitable capacity of insulators, Multifunction meters with suitable size of Current Transformers copper wounded, resin cast, indicators lamp etc with provision for 11 Nos of 4 Pole MCCBs 01 No Incoming as MCCB 500 Amps & 10 Nos outgoing MCCBs with Analog street light timer , copper panel control wiring as per IS direction, make internal compartment for mounting MCCBs/MCbs and bus bars using 2 mm thick CRCA sheet, the panel shall be mounting on 50 x 50 x 6 mm MS angle iron and 60 cm above the normal ground level & embedded 20 cm below ground level in PCC foundation (1:2:4) type B 1, connect new UG cable for Incoming from Transformer to panel and out going ten nos thorugh MCCB cable shall enter through cable glands for safety of cable where enter through panel complete all as specified and directed by Engr-in-charge. \nNote: (i) Multifunction meter Make L & T Cat No: WC4420510000.\n(ii) Current Transformer should be caliberated and tested on MSEDL certificate should produce by contractor. \n | 2 | Each | |
59 | 59 | Dismantling the existing outgoing MCCB of capacity 63 Amps to 200 Amps, cleaning and re-fixing the MCCB with the LT Panel all as specified and as directed. | 1 | Each job | |
60 | 60 | Dismantling the existing incoming MCCB of capacity 500 Amps, cleaning and re-fixing the MCCB with the LT Panel all as specified and as directed. | 1 | Each Job | |
61 | 61 | M & L for preparation and painting of steel surfaces with 2 coats of zinc chrome primer and one coat of synthetic enamel paint all as specified and directed. | 50 | SQ M | |
62 | 62 | Supply and fix sheet moulding compound (SMC) junction box of size 450 mm x 375 mm x 200 mm fixed on wall with 300 Amp with tinned copper bus bar for three phase neutral fixed with unsulated supports for termination of incoming and outgoing cable with provision of cable entry and exit, incl taking down old one. Make: Sintex/Siemens/L & T product code No GSJB-4030 | 6 | Each |